Buderus AM10 Installation and User Manual

Taper
Installation and User Manual
for the user
Read carefully before
installation and use
pour l'utilisateur
Lire attentivement avant
l'installation ou
l'utilisaton
para el usuario
Read carefully before
installation and use
Installation and user manual
Guide d'installation et d'utilisation
Instrucciones de montaje y servicio
Controller
Commande
Controller
mode
°F
888
modulating outdoor reset control AM10
commande modulante extérieure de
réinitialisation AM10
modulating outdoor reset control AM10
7218 6100 (05/2007) US/CA/MX
contents / table des matières / índice de contenido
AM102
Contents 3
1 Installation manual 3
1.1 Description of Module 3
1.2 Outdoor reset 4
1.3 Mounting of the AM10 4
1.4 Single Boiler Control 7
1.5 Multiple Boiler Control 8
1.6 Domestic Hot Water 9
2 User Manual 10
2.1 Introduction 10
2.2 Heating characteristic 10
2.3 Operation 10
2.4 Description of the settings 11
2.5 Faults 13
Table des matières 14
1 Guide d'installation 14
1.1 Description du module 14
1.2 Réinitialisation extérieure 15
1.3 Montage de l'AM10 16
1.4 Commande de chaudière simple 18
1.5 Commande pour chaudières
multiples 20
1.6 Eau chaude domestique 21
2 Guide d'utilisation 22
2.1 Introduction 22
2.2 Caractéristique de chauffage 22
2.3 Fonctionnement 22
2.4 Description des réglages 23
2.5 Défaillances 25
Índice de contenido 26
1 Instrucciones de montaje 26
1.1 Description of Module 26
1.2 Outdoor reset 27
1.3 Mounting of the AM10 27
1.4 Single Boiler Control 30
1.5 Multiple Boiler Control 31
1.6 Domestic Hot Water 32
2 User Manual 33
2.1 Introduction 33
2.2 Heating characteristic 33
2.3 Operation 33
2.4 Description of the settings 34
2.5 Faults 36
AM10 - We reserve the right to make any changes due to technical modifications! 3
Installation manual 1
Contents
1 Installation manual
1.1 Description of Module
Product description
The AM10 is a modulating control for Buderus
boilers equipped with the EMS bus. It sets the
supply water temperature based on outdoor
temperature. The boiler fires, runs and modu-
lates based on the information received from
the AM10, and the delta temperature between
supply and return.
An ON/OFF signal from third party room ther-
mostats or zone controllers is used to commu-
nicate a heat demand.
The AM10 offers warm weather shutdown
(WWSD) when the outdoor temperature rises
above a custom settable temperature.
To control and stage two boilers, combine the
AM10 with a CM10 module (see page 8).
Fig. 1 Set includes
2 x
2 x
2 x
4 x
3 x
mode
°F
Installation manual
AM10 - We reserve the right to make any changes due to technical modifications!4
1
1.2 Outdoor reset
Outdoor reset is a smart way to economically
control space heating based on outdoor tem-
perature. It functions based on the fact that the
colder the weather the greater the heat loss of
a structure, and the higher the supply water
temperature needed to heat the house. On a
warmer day with smaller losses a lower water
temperature will be able to heat the house.
Outdoor reset is the preferred control when
using multiple zones, as the boiler supply
water temperature is not dictated by a master
or largest zone, but solely based on the heat
loss of the structure.
Heating curve
The AM10 has a built in linear heating curve
that sets the supply water temperature in rela-
tion to the outdoor temperature.
The maximum supply water temperature set
on the boiler dial works as a high limit. The
boiler will follow the heating curve in the AM10
up to the high limit.
1.3 Mounting of the AM10
The AM10 module should be mounted inside
a GB142 boiler above the controls.
Outside
temperature
design day
Supply
temperature
Default 14 °F 167 °F
Example 1 F 170 °F
Example 2 -10 °F 175 °F
Example 3 -20 °F 180 °F
Fig. 2 Installation
AM10 - We reserve the right to make any changes due to technical modifications! 5
Installation manual 1
EMS-Bus
Thermostat
Outdoor sensor
Fig. 3 EMS-Bus
Fig. 4 Thermostat
On/Off
mode
°F
L
L 100 ft.
R 100 Ω
Ø = 18 AWG
Ø
Fig. 5 Outdoor sensor
mode
°F
L
L 100 ft.
R 100 Ω
Ø = 18 AWG
Ø
Installation manual
AM10 - We reserve the right to make any changes due to technical modifications!6
1
Positioning of the outdoor sensor
For best performance the outdoor sensor is to
be positioned where the sun can never reach
it. Mount only on a North facing wall of the
building out of the sunlight, with at least 1 foot
above snow line. Keep the sensor away from
heat sources like dryer, water heater, or boiler
vents, windows, etc.
[°F] [kΩ] F] [kΩ] [°F] [kΩ] [°F] [kΩ]
-40 336.5 5 72.9 50 19.9 95 6.5
-31 242.6 14 55.3 59 15.7 104 5.3
-22 177.0 23 42.3 68 12.5 113 4.4
-13 130.4 32 32.7 77 10.0 122 3.6
-497.14125.486 8.1
Table 1 Sensor resistance table
Fig. 6 Sensor location
AM10 - We reserve the right to make any changes due to technical modifications! 7
Installation manual 1
1.4 Single Boiler Control
To equip a single GB142 boiler with outdoor reset control:
Required items:
ON/OFF thermostat for every heating zone with individual zone pump or zone valve
Pump relay
Wiring
If there are multiple zones, wire all thermostats in parallel for calls for heat from any thermostat
to produce a heat demand.
Fig. 7 Wiring detail
Outdoor
sensor
N
Pump Relay
H C1 C2 X X
T T
Dedicated
120 Vac
15 Amp Circuit
Neutral
Zone
valve
Line
120 Vac
Field wiring
Low Voltage
Field wiring
AM10 Module
EV
1
2
FW
1 21 2
WA
1 2
FA
1 2
RC
DHW Tank
Sensor
Factory
Installed
Jumper
RC 10/20
Outdoor
sensor
T T
Connection
DHW
Sensor
Safety
Limit
Orange Blue Lt Green Lt Gray Red
GB142 wire terminal strip
Terminals FA and WA
not used in this
application
1
2
1
2
On / Off
1 2
Do not install RC10 module when
using this configuration.
Installation manual
AM10 - We reserve the right to make any changes due to technical modifications!8
1
1.5 Multiple Boiler Control
For every two boilers install one AM10 with a
CM10 cascade module. Connect a system
supply sensor to the CM10.
The CM10 will determine if one or both boilers
need to fire and at what modulation. The
CM10 also rotates the boilers for equal run
time. For details on the CM10 module, consult
the CM10 manual.
Fig. 8 Plumbing details
1. outdoor sensor
2. pump relay
3. supply sensor
4. supply
5. return
1
2
4
3
5
Do not install RC10 module when
using this configuration.
AM10 - We reserve the right to make any changes due to technical modifications! 9
Installation manual 1
1.6 Domestic Hot Water
1 boiler 1 tank:
Use tappings on the boiler manifold, and con-
nect the tank sensor to the boiler's control
panel.
2 boilers w/ 1 tank on boiler 1
Use tappings on the boiler manifold, and con-
nect the tank sensor to the boiler's control
panel.
2 boilers w/ 2 tanks, 1 each
Use tappings on the boiler manifold, and con-
nect the tank sensor to each boiler's control
panel.
User Manual
AM10 - We reserve the right to make any changes due to technical modifications!10
2
2 User Manual
2.1 Introduction
The "AM10" is an outdoor temperature-depen-
dent controller with a linear heating character-
istic. The heating is switched on and off using
the on/off input.
2.2 Heating characteristic
The heating characteristic indicates the rela-
tionship between the outdoor temperature
and the flow temperature. This concerns a
straight line which can be described by two
points (A and B). Point A is the flow tempera-
ture in the case of an outdoor temperature of
14 °F and point B is the flow temperature in
the case of an outdoor temperature of 68 °F.
C is the high limit flow temperature set on the
boiler. See fig. 9.
The flow temperature requested by the
"AM10" can never be higher than the high limit
flow temperature of the boiler. That is why you
are recommended to set the flow temperature
on the boiler (line C) to the maximum value,
unless you deliberately want to compensate
the heating characteristic, for example by a
floor heating system.
2.3 Operation
Use the "Mode" key (fig. 10, pos. 1) to go
through the various menu items
" "; a line (fig. 10, pos. 2) on
the display indicates the active menu item.
The value of a menu item which can be set will
flash. The value can then be changed using
the plus "+" and minus "" (fig. 10, pos. 3)
keys. The settings will not be lost if there is a
power outage.
Fig. 9 Heating characteristic
1. Flow temperature
2. Outdoor temperature [°F]
B
+68 +14 -40
C
A
1
2
Fig. 10 Display view
°F
mode
1 2
3
AM10 - We reserve the right to make any changes due to technical modifications! 11
User Manual 2
If the display receives no user's input for
10 seconds, it will automatically switch over to
its idle display (outdoor temperature). The dis-
play code is shown (flashing) when the appli-
ance is locked. Otherwise the following
symbols are implemented:
2.4 Description of the settings
Idle display
The current outdoor temperature is shown
(64 °F); the corresponding symbol " " is
marked. A heat request " " has been regis-
tered on the "AM10"; the appliance is in heat-
ing mode " ".
Flow temperature setpoint
The "Mode" key was used to select the
second menu item: the flow temperature set-
point " ".
Range: 32 - 194 °F.
Symbol Meaning
Flame
Appliance in heating
mode
Switch contact
Heating on input
"AM10"
Engineer's
wrench .
Appliance locked
Fig. 11 Idle display (1st menu item)
°F
Fig. 12 The flow temperature on the boiler,
requested by the "AM10"
8154
°F
User Manual
AM10 - We reserve the right to make any changes due to technical modifications!12
2
Target point of heating characteristics
The "Mode" key was used to select the " "
symbol. This concerns the target point of the
heating characteristic corresponding with an
outdoor temperature of 14 °F. The value will
flash and can be changed using the plus "
+"
and minus "" keys.
Adjustment range: 68 - 194 °F.
Factory setting: 167 °F.
Base point of heating characteristics
The "Mode" key was used to select the " "
symbol. This concerns the base point of the
heating characteristic corresponding with an
outdoor temperature of 68 °F. The value will
flash and can be changed using the plus "
+"
and minus "
" keys.
Adjustment range: 68 - 194 °F.
Factory setting: 86 °F.
Warm weather shut down (WWSD)
The "Mode" key was used to select the
WWSD temperature " ". This concerns
the maximum outdoor temperature at which
the heating is still operational.
The value will flash and can be changed using
the plus "
+" and minus "" keys.
Adjustment range: 32 - 86 °F.
Factory setting: 70 °F.
Fig. 13 Display of third menu item
8163
°F
Fig. 14 Display of fourth menu item
100
°F
Fig. 15 Display of fifth menu item
868
°F
AM10 - We reserve the right to make any changes due to technical modifications! 13
User Manual 2
2.5 Faults
The appliance is locked. When the appliance
is in idle mode, a flashing appliance display
code is shown instead of the outdoor temper-
ature and the key symbol " " is displayed.
The parameters can then be set by selecting
the relevant parameter using the "Mode" key.
However, the appliance will be in idle mode
and the display code will show for as long as
the system detects a fault.
The meanings of the various codes and the
relevant troubleshooting procedures are
detailed in the boiler's installation instructions.
Fault code 5H
This is a communication fault. Check the con-
nection to the boiler.
Sensor fault/emergency operation
If no sensor is detected on the "AM10",
dashes are shown in the numerical field
instead of the outdoor temperature.
If there is a heat request (the display will show
), the "AM10" will request 122 °F, if this is
permitted by the high limit.
Fig. 16 Fault indication
84E
°C
Fig. 17 Sensor fault display
°F
Guide d'installation
AM10 - Nous réservons le droit d’effectuer tous changements dus à des modifications techniques !14
1
Table des matières
1 Guide d'installation
1.1 Description du module
Description du produit
L'AM10 est une commande modulante pour
les chaudières Buderus équipées d'un bus
EMS. Elle règle la température de l'eau d'ali-
mentation en fonction de la température exté-
rieure. La chaudière s'allume, fonctionne et
est modulée en fonction de l'information reçue
de l'AM10 et du delta de température entre
l'alimentation et le retour.
Un signal ON/OFF de tierce partie d'un ther-
mostat de pièce ou d'une commande de zone
sert à communiquer la demande de chaleur.
L'AM10 offre une fonction de mise hors ser-
vice par temps chaud (MHSTC) si la tempéra-
ture extérieure monte au-dessus d'une
température programmable. Pour commander
et monter deux chaudières, combiner l'AM10
et un module CM10 (voir page 20).
Fig. 1 Contenu de l'ensemble
2 x
2 x
2 x
4 x
3 x
mode
°F
AM10 - Nous réservons le droit d’effectuer tous changements dus à des modifications techniques ! 15
Guide d'installation 1
1.2 Réinitialisation extérieure
La réinitialisation extérieure est une manière
intelligente de commander économiquement
le chauffage individuel en fonction de la tem-
pérature extérieure. Ses fonctions sont
basées sur le principe que plus le climat est
froid, plus la perte de chaleur d'une structure
est grande et plus la température de l'eau
d'alimentation doit être élevée pour chauffer la
maison. Par temps plus chaud avec des per-
tes plus faibles, de l'eau à température plus
basse pourra chauffer la maison.
La réinitialisation extérieure est la méthode de
commande préférée si l'on utilise des zones
multiples, étant donné que la température de
l'eau dans la chaudière ne sera pas dictée par
une zone principale ou la plus grande zone,
mais uniquement par la perte de chaleur de la
structure.
Courbe de chaleur
L'AM10 comporte une courbe de chaleur
linéaire intégrée qui détermine la température
de l'alimentation d'eau en fonction de la tem-
pérature extérieure.
La température maximale de l'alimentation
d'eau réglée sur la commande de la chaudière
fonctionne en limite supérieure. La chaudière
suivra la courbe de chaleur dans l'AM10
jusqu'à la limite supérieure.
Température
extérieure de
journée
standard
Tempéra-
ture d'ali-
mentation
Défaut 14 °F 167 °F
Exemple 1 F 170 °F
Exemple 2 -10 °F 175 °F
Exemple 3 -20 °F 180 °F
Guide d'installation
AM10 - Nous réservons le droit d’effectuer tous changements dus à des modifications techniques !16
1
1.3 Montage de l'AM10
Le module AM10 devrait être monté à l'inté-
rieur d'une chaudière GB142 au-dessus des
commandes.
Bus EMS
Thermostat
Fig. 2 Installation
Fig. 3 Bus EMS
Fig. 4 Thermostat
On/Off
mode
°F
L
L 100 pi.
R 100 Ω
Ø = Cal. 18
Ø
AM10 - Nous réservons le droit d’effectuer tous changements dus à des modifications techniques ! 17
Guide d'installation 1
Capteur extérieur
Emplacement du capteur extérieur
Pour obtenir les meilleures performances, le
capteur extérieur doit être placé dans un
endroit où le soleil ne l'atteindra jamais.
Le monter uniquement sur un mur orienté vers
le nord hors de portée du soleil et au moins
30 cm (1 pi) au-dessus de la hauteur maxi-
male de la neige. Garder le capteur à l'écart
de sources de chaleur telles qu'un évent de
sécheuse, de chauffe-eau ou de chaudière,
une fenêtre, etc.
Fig. 5 Capteur extérieur
mode
°F
L
L 100 pi.
R 100 Ω
Ø = Cal. 18
Ø
[°F] [kΩ] [°F] [kΩ] [°F] [kΩ] [°F] [kΩ]
-40 336.5 5 72.9 50 19.9 95 6.5
-31 242.6 14 55.3 59 15.7 104 5.3
-22 177.0 23 42.3 68 12.5 113 4.4
-13 130.4 32 32.7 77 10.0 122 3.6
-4 97.1 41 25.4 86 8.1
Tableau 1 Table de résistance du capteur
Guide d'installation
AM10 - Nous réservons le droit d’effectuer tous changements dus à des modifications techniques !18
1
1.4 Commande de chaudière
simple
Pour équiper une chaudière GB142 simple
d'une commande de réinitialisation
extérieure :
Articles nécessaires :
Thermostat ON/OFF pour chaque zone de
chauffage avec vannes et pompes de
zones individuelles
Relais de pompe
Câblage.
Fig. 6 Emplacement du capteur
AM10 - Nous réservons le droit d’effectuer tous changements dus à des modifications techniques ! 19
Guide d'installation 1
S'il y a plusieurs zones, câbler tous les ther-
mostats en parallèle pour permettre à l'appel
de chaleur de n'importe quel thermostat de
produire une demande de chaleur.
Fig. 7 Détail du câblage
N
Relais de pompe
H C1 C2 X X
T T
Neutre
Vanne
par zone
Ligne
Câblage à
basse tension
Module AM10
EV
1
2
FW
1 21 2
WA
1 2
FA
1 2
RC
Capteur de
réservoir
d’ECD
Cavalier
installé
en usine
RC10/20
Capteur
extérieur
T T
Connexion
Orange Bleu Vert pâle Gris pâle
Rouge
Barrette GB142
Les bornes FA et WA
ne servent pas dans
cette application
1
2
1
2
Marche / Arrêt
1 2
Capteur
d’ECD
Limite de
sûreté
Câblage secteur
de 120 V CA
Circuit 120 V CA
dédié de 15 A
Capteur
extérieur
Ne pas installer de module RC10 si
cette configuration est employée.
Guide d'installation
AM10 - Nous réservons le droit d’effectuer tous changements dus à des modifications techniques !20
1
1.5 Commande pour chaudières multiples
Pour chaque paire de chaudières installées, il
faut un module AM10 et un module de cas-
cade CM10. Brancher un capteur d'alimenta-
tion de système au CM10.
Le CM10 détermine si une seule ou les deux
chaudières doivent s'allumer et à quel degré
de modulation. Le CM10 fait également la
rotation des chaudières pour équilibrer le
temps de fonctionnement. Pour connaître les
détails du module CM10, consulter le manuel
du CM10.
Fig. 8 Détails de la plomberie
1. capteur extérieur
2. relais de pompe
3. capteur d'alimentation
4. alimentation
5. retour
1
2
4
3
5
Ne pas installer de module RC10 si
cette configuration est employée.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

Buderus AM10 Installation and User Manual

Taper
Installation and User Manual

dans d''autres langues