SPECIFICATIONS
Dim Control Max Load: 30 mA Source/Sink
Radio Frequency: 2.4 GHz (IEEE 802.15.4)
RF Transmission Output Power: +20dBM
Operating Temperature: -40 to +85 C
Operating Humidity: 10 to 90%, non-condensing
Drivers: Limited to 4 LED Drivers
Wire Size: 18 AWG, 8” Wires, UL1316, 600V
Dimensions: 2.25” L x 2.0” W x .3” H
(57 x 50.8 x 7.6 mm)
CAUTION
DIM10-087-06-FW controllers must be installed in
accordance with national, state, and local electrical
codes and requirements.
DESIGN CONSIDERATIONS
Below are some recommendations for successful
dimming using the DIM10-087-06-FW. The dimming
control wires are referenced as Dim+ and Dim-. The
dimming signals have a Maximum voltage of 10V DC.
Do not ground the DIM- wire to chassis ground;
this is a return signal and is critical for proper
dimming.
Route dimming wires away from AC lines if
possible.
Maximum of 4 LED Drivers per controller, consult
Synapse Support if a greater ratio is needed.
Do not mount to a heatsink or to a LED driver.
When installing the DIM10-087-06-FW into an
enclosure, consideration of the internal antenna
position and interference is required in order to
provide the most optimum wireless signal
strength. Prior to permanently mounting it, make
sure the antenna is free of any metal objects
within 12 in. of the antenna.
NEEDED MATERIAL
Mounting Hardware: (1) #4 and M3 screws and
standoff recommended
INSTALLATION INSTRUCTIONS
WARNING: TO AVOID FIRE, SHOCK, OR
DEATH: TURN OFF POWER AT CIRCUIT
BREAKER OR FUSE AND VERIFY THAT POWER IS
OFF BEFORE WIRING!
MOUNTING
1. Place the controller in desired location and secure
it using #4 sized screw and standoff using the
mounting hole located in the center of the board.
WIRING THE DIM10-087-06-FW
CONTROLLER
Note: Unless specified, the connections to a
standard Dim to Off LED driver and the DALI 2
LED driver are the same.
2. Connect the POWER (BROWN) wire of the DIM10-
087-06-FW to the 5-24V DC Aux output from the
LED driver.
3. Connect the DIM- and DALI- (GRAY/WHITE
STRIPE) wires of the DIM10-087-06-FW to the
COMMON/DALI- or COMMON/DIM- based on the
LED driver you have.
CONNECTING SENSORS
Note: Steps 4-7 are for adding sensors to the
DIM10-087-06-FW controller; if you are not
connecting sensors skip this section.
There are two sensor inputs on the DIM10-087-06-FW
designed for low powered (24V DC) type sensors.
The SENSOR A (YELLOW) wire is used to
connect sensor A.
The SENSOR B (ORANGE) wire is used to
connect sensor B.
4. Connect the sensor power wire to the AUX out on
the LED driver (the LED driver powers the sensor).
5. Connect the sensor Common to the
COMMON/DALI- or COMMON/DIM- based on the
LED driver you have.
6. Connect the SENSOR A (YELLOW) wire or the
SENSOR B (ORANGE) wire of the DIM10-87-06-FW
controller to the sensor CTRL/Control wire.
7. If you are using more than one sensor then
duplicate the installation as described above.
(See Figures 1 AND 2)
CONNECTING THE DIMMING CIRCUIT
Note: Steps 8-10 are for connecting up to a
Standard Dim to Off LED driver; if you are using a
DALI 2 LED driver skip to steps 11-13.
8. Connect the DIM+ (PURPLE) wire from the DIM10-
087-06-FW to the DIM+ wire on the LED driver.
9. Connect the DIM- (GRAY/WHITE STRIPE) wire
from the DIM10-087-06-FW to the COMMON/DIM-
wire on the LED driver.
10. Cap the unused DALI+ (PURPLE/WHITE STRIPE)
wire.
(See Figure 1)
DIM10-087-06-FW Controller
Load Ratings: 700mW @ 5 to 24V DC
Operating Temperature: -40 to +85 C / Operating Humidity: 10 to 90%, non-condensing
WARNING AND CAUTIONS:
TO AVOID FIRE, SHOCK, OR DEATH: TURN OFF POWER AT CIRCUIT BREAKER
OR FUSE AND TEST THAT POWER IS OFF BEFORE INSTALLING!
PROPER GROUNDING REQUIRED TO AVOID STATIC DISCHARGE WHICH
CAN DAMAGE CONTROLLERS DURING INSTALLATION.
INSTALLATION GUIDE
WARNING AND CAUTIONS:
If you are unsure about any part of these instructions, consult an electrician; all
work should be performed by qualified personnel.
Disconnect power at circuit breaker or fuse when servicing, installing or removing
fixture or changing lamps.
DOC-1000546-A-3
Note: Steps 11-12 are for connecting up to a DALI
2 LED driver.
11. Connect the DALI+ (PURPLE/WHITE STRIPE) wire
from the DIM10-087-06-FW to the LED driver
DALI+.
12. Cap the unused DIM+ (PURPLE) wire.
(See Figure 2)
POWERING UP THE FIXTURE AND
CONTROLLER
After connecting the Controller to the LED Driver and
any sensors, make sure to cap any unused wires.
Switch power on to the fixture. The light should turn
on.
STATUS LED
Note: When the controller is powered the
following colors indicate the current status.
Red = No Network Found (Communication Lost) 
Blinking Green = Network Found, Controller Not
Configured (Device not yet added to SimplySNAP) 
Green = Network Found, Controller Configured
(Normal Operation)
Refer to the SimplySNAP User’s Manual for information
on provisioning the DIM10-087-06-FW.
Figure 1 - DIM to OFF Wiring Diagram
Figure 2 - DALI-2 Wiring Diagram
STATUS LED
WARNING:
· If a single Synapse controller is used to drive the
DIM+ input of multiple LED drivers, then all of the
DIM- lines from all drivers MUST be directly
tied/shorted together to provide a common
return/ground to the controller.
· Synapse will not warranty or be liable for designs
with any other electronic means of coupling DIM-
lines from multiple drivers.
DOC-1000546-A-3
REGULATORY INFORMATION AND
CERTIFICATIONS
RF Exposure Statement: This equipment complies
with FCC radiation exposure limits set forth for an
uncontrolled environment. This equipment should be
installed and operated with minimum distance of 20cm
between the radiator and your body. This transmitter
must not be co-located or operating in conjunction with
any other antenna or transmitter.
Industry Canada (IC) certifications: This digital
apparatus does not exceed the Class B limits for radio
noise emissions from digital apparatus set out in the
Radio Interference Regulations of the Canadian
Department of Communications.
Le present appareil numerique n’emet pas de bruits
radioelectriques depassant les limites applicable aux
appareils numeriques de la class B prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada.
FCC certifications and regulatory information
(USA only)
FCC Part 15 Class B: This device complies with part
15 of the FCC rules. Operation is subject to the
following two conditions: (1) These devices may not
cause harmful interference, and (2) These devices
must accept any interference received, including
interference that may cause harmful operation.
RADIO FREQUENCY INTERFERENCE (RFI) (FCC
15.105): This equipment has been tested and found to
comply with the limits for a Class B digital device,
pursuant to Part 15 of the FCC rules. These limits are
designed to provide reasonable protection against
harmful interference in a residential installation. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful
interference to radio communications. However, there
is no guarantee that interference will not occur in a
particular installation. If this equipment does cause
harmful interference to radio or television reception,
which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
(1) Re-orient or relocate the receiving antenna; (2)
Increase the separation between the equipment and
the receiver; (3) Connect the equipment into an outlet
on a circuit different from that to which the receiver is
connected; (4) Consult the dealer or an experienced
radio/TV technician for help.
Declaration of Conformity (FCC 96-208 & 95-19):
Synapse Wireless, Inc. declares that the product name
“DIM10-087-06-FW” to which this declaration relates,
meet the requirements specified by the Federal
Communications Commission as detailed in the
following specifications:
• Part 15, Subpart B, for Class B equipment
• FCC 96-208 as it applies to Class B personal
computers and peripherals
• This product has been tested at an External Test
Laboratory certified per FCC rules and has been found
to meet the FCC, Part 15, Emission Limits.
Documentation is on file and available from Synapse
Wireless, Inc.
If the FCC ID for the module inside this product
enclosure is not visible when installed inside another
device, then the outside of the device into which this
product is installed must also display a label referring
to the enclosed module FCC ID. Modifications (FCC
15.21): Changes or modifications to this equipment not
expressly approved by Synapse Wireless, Inc., may
void the user’s authority to operate this equipment.
CERTIFICATIONS
Model : DIM10-087-06-FW
Contains FCC ID : U9O-SM220
Contains IC : 7084A-SM220
UL File No : E346690
DALI-2 Certified Application Controller
Contact Synapse for Support- (877) 982-7888