Astria Fireplaces Rhapsody Mode d'emploi

Catégorie
Cheminées
Taper
Mode d'emploi
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use
any phone in your building.
Leave the building immediately.
Immediately call your gas supplier from a neigh-
bor’s phone. Follow the gas supplier’s instruc-
tions.
If you cannot reach your gas supplier, call the
fire department.
- Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury, death, or property damage.
AVERTISSEMENT:
RISQUED’INDENDIE OU D’EXPLOSION
Le non-respect Des avertissements de sécurité
pourrait d’entraîner des blessures graves, la mort
ou des dommages matériels.
- Ne pas entreposer ni utilizer d’essence ni d’autres
vapeurs ou liquides inflammables dans le voisinage
de cet appareil ou de tout autre appareil.
- QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucan interrupteur. Ne pas vous servir
des téléphones se trouvant dans le bâtiment où
vous trouvez.
Sortez immédiatement de bâtiment.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions du
fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz,
appelez le service des incindies.
- L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié
ou par le fournisseur de gaz.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future
reference.
Installateur : Laissez cette notice avec l’appareil.
Consommateur : Conservez cette notice pour
consultation ultérieure.
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only)
or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit
is used.
Cet appareil peut installé dans une maison préfabriquée (mobile) déjà installée à demeure, si les réglements
locaux le permettent. Ce appareil doit être utilisé uniquement avec le type de gaz indiqué sure la plaque
signalétique. Cet appareil ne peut être converti à d’autres gaz, sauf si une trousse de conversion est utilsée.
Installation and Operation Instructions
Models
PFS
®
USC
Report No. F14-108
Ce manuel est disponible en francais, simplement
en faire la demande. Numéro de la pièce 900077-03.
P/N 900077-02 Rev. F 12/2018
Rhapsody42TEN Rhapsody54TEN
Rhapsody® Direct-Vent Gas Fireplaces
Featuring Infini-FlameTM Technology
P900077-02
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
2
DANGER
HOT GLASS WILL
CAUSE BURNS.
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot viewing glass is pro-
vided with this appliance and shall be installed for the protection of children and
other at-risk individuals.
DANGER
PELIGRO
VITRE CHAUDE
RISQUE DE BRÛLURES.
NE TOUCHEZ PAS UNE VITRE
NON REFROIDIE.
NE LAISSEZ JAMAIS UN ENFANT
DE TOUCHER LA VITRE.
EL VIDRIO CALIENTE
CAUSARÁ QUEMADURAS.
USTED NUNCA DEBE
TOCAR EL VIDRIO CALIENTE.
LOS NIÑOS NUNCA DEBE
TOCAR EL VIDRIO.
L’écran pare-étincelles fourni avec ce foyer réduit le risque de brûlure en cas de
contact accidentel avec la vitre chaude et doit être installé pour la protection Des
enfants et Des personnes à risques.
Una barrera diseñada para reducir el riesgo de quemaduras desde la mirilla (vidrio)
caliente es proveida con este aparato y deberá instalarse para la protección de los
niños y otros individuos en riesgo.
Vea el volante adjunto para la representación de color adecuado
See attached color flyer for proper color representation
Voir ci-joint tract pour une bonne représentation de la couleur
SAFETY AND YOUR FIREPLACE
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
3
Afin d’éviter les brûlures
graves ou les blessures,
ne pas retirer l’écran de
protection de la foyer qui
empêche tout contact
direct avec la vitre.
Suivez les instructions de sécurité
ci-dessous et veillez à ce que tous
les membres de votre famille soient
conscients du danger de brûlure
encouru :
Les surfaces de votre foyer deviennent
EXTRÊMEMENT CHAUDES !
La vitre située à l'avant du foyer atteint
des températures EXTRÊMEMENT
ÉLEVÉES et peut causer de graves
blessures en cas de contact.
Tenez les enfants à l'écart du foyer
lorsqu'il fonctionne. Surveillez
attentivement les enfants dans les
pièces où un foyer est utilisé afin
d'éviter qu'ils ne soient en contact avec
la vitre.
Tenez tous les vêtements, les meubles,
l'essence et tout autre liquide
inflammable à l'écart du foyer.
Même après fermeture du gaz, les
surfaces du foyer restent extrêmement
chaudes.
Veillez à coller les Étiquettes de mise
en garde relatives à la sécurité
d'utilisation à l'endroit où vous
utilisez le foyer, pour rappeler à tous
les utilisateurs les dangers liés aux
températures élevées
(Pages 47)
.
Lisez L’information de sûreté
importante (Page 5)
.
Para evitar quemaduras y lesiones
graves, no quite el protector de malla
o guardia de seguridad que evita el
contacto directo con el vidrio.
Siga las instrucciones de seguridad
a continuación y asegúrese de que
todos en su hogar sepan acerca de este
peligro de quemadura:
¡Las superficies de la chimenea
estarán EXTREMADAMANTE
CALIENTES!!
El vidrio delante de la
chimenea alcanza temperaturas
EXTREMADAMENTE ALTAS y puede
causar quemaduras graves si se toca.
Mantenga a los niños alejados de
la chimenea en funcionamiento.
Supervise en forma cercana a los niños
en cualquier cuarto donde haya una
chimenea funcionando para impedir el
contacto con el vidrio.
Mantenga la ropa, mobiliario, gasolina
y otros líquidos inflamables alejados
de la chimenea.
Aún después de haber apagado el
gas, las superficies de la chimenea
permanecen extremadamente
calientes.
Asegúrese de colocar las Etiquetas de
advertencia de seguridad de operación
en el lugar donde enciende la chimenea,
para que todos recuerden los peligros
asociados con las altas temperaturas
(Página 47)
.
Lea Información importante de
seguridad (Página 5).
Seguridad y su
chimenea
La sécurité et
votre foyer
[FRENCH][ENGLISH] [SPANISH]
Safety and Your
Fireplace
To prevent severe burns
and injuries, do Not
remove the barrier on the
appliance which prevents
direct contact with the
glass.
Follow the safety instructions below
and be sure everyone in your household
understands this burn hazard:
The surfaces on your fireplace get
EXTREMELY HOT!
The glass on the front of the
fireplace reaches EXTREMELY HIGH
temperatures and can cause severe
burns if touched.
Keep children away from an operating
fireplace. Closely supervise children
in any room where a fireplace is
operating to prevent contact with glass.
Keep clothing, furniture, gasoline, and
other flammable liquids away from the
fireplace.
Even after the gas is turned off,
fireplace surfaces remain extremely
hot.
Be sure to attach the enclosed Safety-
in-Operation Warnings where you
turn on your fireplace, to help remind
everyone of the dangers associated with
high temperatures
(Pages 47)
.
Read Important Safety Information
(Page 5)
.
All parts of your
IHP fireplace get
EXTREMELY HOT!
Toutes les parties de votre
foyer IHP deviennent
EXTRÊMEMENT CHAUDES !
¡Todas las partes de la
chimenea IHP se ponen
MUY CALIENTES!
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
4
Important Safety Informa-
tion
1. WARNING: Do not operate appliance
with the glass front removed, cracked,
or broken.
2. Do not use this appliance if any part
has been under water. Immediately
call a qualified service technician to
inspect the appliance and to replace
any part of the control system and
any gas control which has been under
water.
3. Due to high temperatures, the appli-
ance should be located out of traffic
and away from furniture and draperies.
4. Children and adults should be alerted
to the hazards of high surface tem-
perature and should stay away to avoid
burns or clothing ignition.
5. Clothing or other flammable material
should not be placed on or near the
appliance.
6. Young children should be carefully
supervised when they are in the same
room as the appliance. Toddlers,
young children, and others may be sus-
ceptible to accidental contact burns.
A physical barrier is recommended
if there are at-risk individuals in the
house. To restrict access to a fireplace
or stove, install an adjustable safety
gate to keep toddlers, young children,
and other at-risk individuals out of the
room and away from hot surfaces.
7. Any safety screen, guard or barrier
removed for servicing an appliance
must be replaced prior to operating
the appliance.
8. Installation and repair should be done
by a qualified service person. The ap-
pliance should be inspected before use
and at least annually by a professional
service person. More frequent clean-
ing may be required due to excessive
lint from carpeting, bedding material,
et cetera. It is imperative that control
compartments, burners, and circulat-
ing air passageways of the appliance
be kept clean. See maintenance in-
structions on Page 61.
L’information de sûreté
importante
1. AVERTISSEMENT. Ne pas utiliser l’appareil
si le panneau frontal en verre n’est pas en
place, est craqué ou brisé.
2. Ne pas se servir de cet appareil s’il a été
plongé dans l’eau, même partiellement.
Faire inspecter l'appareil par un technicien
qualifié et remplacer toute partie du systéme
de contrôle et toute commande qui ont été
plongées dans l'eau.
3. En raison des températures élevées,
l’appareil devrait être installé dans un en-
droit où il y a peu de circulation et loin du
mobilier et des tentures.
4. Les enfants et les adultes devraient être
informés des dangers que posent les tem-
pératures de surface élevées et se tenir à
distance afin d’éviter des brûlures ou que
leurs vêtements ne s’enflamment.
5. On ne devrait pas placer de vêtements
ni d’autres matières inflammables sur
l’appareil ni à proximité.
6. Les jeunes enfants devraient être surveillés
étroitement lorsqu’ils se trouvent dans la
même pièce que l’appareil. Les tout petits,
les jeunes enfants ou les adultes peuvent
subir des brûlures s’ils viennent en contact
avec la surface chaude. Il est recommandé
d’installer une barrière physique si des
personnes à risques habitent la maison.
Pour empêcher l’accès à un foyer ou à un
poêle, installez une barrière de sécurité ;
cette mesure empêchera les tout petits, les
jeunes enfants et toute autre personne à ris-
que d’avoir accès à la pièce et aux surfaces
chaudes.
7. Tout écran ou protecteur retiré pour per-
mettre l’entretien de l’appareil doit être
remis en place avant de mettre l’appareil
en marche.
8. L’installation et la réparation devrait être
confiées à un technicien qualifié. L’appareil
devrait faire l’objet d’une inspection par un
technicien professionnel avant d’être utilisé
et au moins une fois l’an par la suite. Des
nettoyages plus fréquents peuvent être
nécessaires si les tapis, la literie, et cetera
produisent une quantité importante de pous-
sière. Il est essentiel que les compartiments
abritant les commandes, les brûleurs et les
conduits de circulation d’air de l’appareil
soient tenus propres. Voyez les instructions
d’entretien à la page 61.
Información importante de
seguridad
1. ADVERTENCIA: No opere el artefacto con el
frente de vidrio quitado, agrietado o roto.
2. No use este artefacto si alguna de sus partes
ha estado bajo agua. Llame de inmediato
a un técnico de servicio calificado para
que inspeccione el artefacto y reemplace
cualquier parte del sistema de control y
cualquier control de gas que haya estado
bajo agua.
3. Debido a las altas temperaturas, el artefacto
debe situarse fuera de las áreas de tráfico y
lejos del mobiliario y cortinas.
4. Se debe alertar a los niños y adultos sobre
los peligros de las altas temperaturas en la
superficie y que se mantengan alejados para
evitar quemaduras o ignición de la ropa.
5. No debe colocarse ropa u otros materiales
inflamables sobre y cerca del artefacto.
6. Se debe supervisar de cerca a los niños
cuando estén en el mismo cuarto que el
artefacto. Los niños pequeños, los jóvenes
y otras personas pueden ser susceptibles
a quemaduras por contacto accidental. Se
recomienda instalar una barrera física si hay
personas en riesgo en la casa. Para restringir
el acceso a una chimenea o estufa, instale
una puerta de seguridad ajustable para
mantener a los niños pequeños, jóvenes y
otras personas en riesgo fuera del cuarto y
lejos de las superficies calientes.
7. Cualquier malla o resguardo de seguridad
quitado para dar servicio a un artefacto, debe
reinstalarse antes de operar el artefacto.
8. Una persona de servicio competente debe
realizar la instalación y reparación. Una
persona de servicio profesional debe
inspeccionar el artefacto antes de usar al
menos una vez por año. Se puede requerir
limpieza más frecuente debido a la pelusa
excesiva del alfombrado, del material de
cobijas, etc. Es imprescindible mantener
limpios los compartimientos de control, los
quemadores y los pasajes de circulación del
aire del artefacto. Ver las instrucciones de
mantenimiento en la página 61.
IMPORTANT SAFETY INFORMATION
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
5
THANK YOU FOR YOUR PURCHASE. WE APPRECIATE YOUR BUSINESS!
Please carefully read and follow all instructions in this manual. Pay special attention to all warnings and safety
information. Following these safety, care, and operation instructions will help ensure many years of dependable and
enjoyable service from your fireplace.
Please read and understand these instructions before installing,
operating, or servicing this product. We recommend that our
gas hearth products be
installed and serviced by
professionals who are
certied in the U.S. by the
National Fireplace Institute®
(NFI) as NFI Gas Specialists.
General Information
Safety and Your Fireplace ..................................................................2
Important Safety Information ............................................................4
Fireplace Installation, Operation, and Maintenance Notices ............... 6
Packaging List ...................................................................................8
Introduction ....................................................................................... 8
Gas Pressure .....................................................................................9
Requirements for the Commonwealth of Massachusetts ................11
Cold Climate Insulation ....................................................................11
Manufactured Home Requirements .................................................12
Location ...........................................................................................12
Vent Termination Clearances ...........................................................13
Minimum Clearances to Combustibles ............................................15
Wall Finishes / Surrounds / Mantels ................................................16
Installation Preparation ....................................................................16
Installation
Installation Sequence ......................................................................17
Construct the Fireplace Framing ......................................................18
Route the Gas Supply Line into the Fireplace ..................................20
Vent System Preparation ................................................................21
Install the Vent System .................................................................... 25
Complete the Field Wiring ................................................................36
Optional: Wire and Install the Power Vent .......................................38
Optional: Route Backlighting Wiring ................................................ 38
Connect the Gas Line .......................................................................38
Optional: Install the Modesty Panel .................................................39
Install the Wall Switch Receiver .......................................................39
Verify Proper Fireplace Operation ....................................................39
Optional: Install the Backlighting Reflector ......................................40
Install the Firebox Liners .................................................................40
Optional: Install the Backlighting Light Assemblies .........................40
Install the Glass Media ....................................................................40
Install the Baffle ............................................................................... 40
Install the Glass Door ......................................................................40
Adjust the Air Shutter to Ensure Proper Flame Appearance ............. 40
Install the Finishing Materials ..........................................................42
Optional: Install the Bezel and Barrier .............................................. 42
Initialize the Remote Control System ............................................... 46
Attach the Safety-in-Operation Warnings.........................................46
Installation Accessories ................................................................... 48
Gas Conversion Kits ........................................................................50
Operation
Operation ......................................................................................... 53
Maintenance ....................................................................................61
Required Accessory Components ....................................................64
Optional Accessory Components .....................................................65
Lighting Instructions .......................................................................66
Troubleshooting ...............................................................................68
Replacement Parts ..........................................................................69
Warranty .......................................................................................... 71
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
6
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
APPLIANCE INSTALLATION, SERVICE, AND MAINTENANCE NOTICES
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause injury or
property damage. Refer to this manual. For assistance or additional information consult a
qualified installer, service agency or the gas supplier.
AVERTISSEMENT
Une installation, un réglage,une modification, une réparation ou un entretien mal effectué
peut causer des dommages matériels ou des blessures. Voir la notice de l’utilisateur qui
accompagne l’appareil. Pour de l’aide ou des renseignements supplémentaires, consultez
un installateur, un technicien agréé ou le fournisseur de gaz.
Only trim kit(s) supplied by the manufacturer shall be used in the installation of this appliance.
Seules des portes certifiées pour cet appareil doivent être utilisées.
These appliances must not be connected to a chimney or flue serving a separate solid fuel
burning appliance.
Any change to this appliance and/or its operating controls is dangerous. Improper installation
or use of this appliance can cause serious injury or death from fire, burns, explosion or carbon
monoxide poisoning.
CARBON MONOXIDE POISONING: Early signs of carbon monoxide poisoning are similar to the flu
with headaches, dizziness and/or nausea. If you have these signs, obtain fresh air immediately.
Turn off the gas supply to the appliance and have it serviced by a qualified professional, as
it may not be operating correctly. Some people are more affected by carbon monoxide than
others, including pregnant women, people with heart or lung disease or anemia, those under
the influence of alcohol, and those at high altitudes.
Turn off gas and electrical power to the appliance and allow it to cool before cleaning or
servicing the appliance.
If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier
for this appliance.
Si l’écran est endommagé, il doit être remplacé par celui fournit par le fabricant de cet
appareil.
For use with barrier(s) Part No(s). J7427 (42” Models) and J7426 (54” Models). Follow
installation instructions.
Reinstall any barrier removed before operating the appliance. The barrier is designed to reduce
the risk of burns from hot glass. Do not operate the appliance without the barrier installed.
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
7
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
APPLIANCE OPERATION NOTICES
WARRANTY INFORMATION
IMPORTANT SAFETY AND WARNING INFORMATION
CAUTION
Hot while in operation. Do not touch. Severe Burns may result. Keep children, clothing furniture,
gasoline and other liquids having flammable vapors away.
ATTENTION
L’appareil est chaud lorsqu’il fonctionne. Ne pas toucher l’appareil. Risque de brûlures graves.
Surveiller les enfants. Garder les vêtements, les meubles, l’essence ou autres liquides produisant
des vapeur inflammables loin de l’appareil.
These fireplaces are vented gas appliances. Do not burn wood or other material in these
appliances.
These appliances are designed to operate on natural gas or propane gas only. The use of
other fuels or combinations of fuels will degrade the performance of this system and may be
dangerous.
Provide adequate clearances around air openings and adequate accessibility clearance for
service and proper operation. Never obstruct the front openings of the appliance.
These appliances are designed as supplemental heaters. Therefore, it is advisable to have an
alternate primary heat source when installed in a dwelling.
Your gas appliance is covered by a limited lifetime warranty. You will find a copy of the warranty
accompanying this manual. Please read the warranty to be familiar with its coverage.
Retain this manual. File it with your other documents for future reference.
Failure to comply with the installation and operating instructions provided will result in an
improperly installed and operating appliance, voiding its warranty.
Do not attempt to alter or modify the construction of the appliance or its components. Any
modification or alteration may void the warranty, certification, and listings of this unit.
WARNING
This product can expose you to chemicals including Carbon Black, which is known to the State of California to
cause cancer, and Carbon Monoxide, which is known to the State of California to cause birth defects or other
reproductive harm. For more information go to www.P65Warnings.ca.gov
AVERTISSEMENT
Ce produit peut vous exposer à des produits chimiques, y compris du carbone noir qui est reconnu par
l'État de Californie comme un produit cancérigène, et du monoxyde de carbone, qui est reconnu par
l'État de Californie comme pouvant causer des déformations fœtales ou perturber la fonction reproduc-
tive. Pour plus d’information, aller sur www.P65Warnings.ca.gov
Installation
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
8
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
INSTALLATION
PACKAGING
All models include
The assembled vented gas fireplace heater is packaged with:
Literature Kit (Installation and Operation Instructions (this manual), Hot Glass Safety Flyer, and
Safety-In-Operation Warning Labels)
Vent restrictor assembly
Baffle (shipped on fireplace floor)
Heat shield and insulation (shipped inside the fireplace)
Six (6) Non-combustible fiberboards
Three (3) AAA batteries
Handheld remote control (transmitter)
Remote control receiver (wall switch) assembly with four (4) AA batteries
• Barrier
Required accessories
Firebox liner kit
Floor kit
Glass media kit (required with DESIGNER style floor kits only)
NOTE: Ensure all required accessory kits are available before installing the fireplace.
Optional accessories
Surround kit
Bezel kit
Panel backlighting kit (Required when illusion panels are used)
Power vent kit (Requires Rhapsody power vent adaptor kit)
Gas conversion kit
Glass Media Kits - Reflective Blue, Platinum, Goldfinger, and Copper
INTRODUCTION
These vented gas fireplace heaters are sealed combustion, air-circulating gas fireplaces designed for residential,
manufactured home, and commercial applications. Direct-vent appliances operate with the combustion chamber
isolated from the indoor environment. All air for combustion is brought in from the outside, and exhaust gases are
vented through the same direct-vent, coaxial (intake/exhaust) vent system.
These appliances are designed to operate on natural or propane gas only. The use of other fuels or fuel combinations
will degrade the performance of this system, may be dangerous, and may void the warranty.
Electronic fireplaces are designed with an electronic intermittent pilot ignition system. External electrical power is
required to operate these units. In the event of a power outage, four (4) AA batteries (in battery holder) provide
backup power for fireplace operation.
Batteries will operate the gas valve OPEN/CLOSE and pilot ON/OFF functions only. Electrical power (120V AC line
voltage) is required to operate the following components:
• Blower
Power vent system
Panel backlighting kit
A remote control system is included with all models and provides remote operation of several fireplace functions
(manual adjustment of the gas valve settings is not possible).
NOTE: Installation and repair should be done by a qualified service person. The appliance should be inspected
before use and at least annually by a professional service person. More frequent cleaning might be required due to
excessive lint from carpeting, bedding material, et cetera. It is imperative that control compartments, burners, and
circulating air passageways of the appliance be kept clean.
Remarqué : L’installation et la réparation devrait être confiées à un technicien qualifié. L’appareil devrait faire
l’objet d’une inspection par un technicien professionnel avant d’être utilisé et au moins une fois l’an par la suite.
Des nettoyages plus fréquents peuvent être nécessaires si les tapis, la literie, et cetera produisent une quantité
importante de pous-sière. Il est essentiel que les compartiments abritant les commandes, les brûleurs et les
conduits de circulation d’air de l’appareil soient tenus propres.
NOTE: Diagrams and illustrations are not necessarily shown to scale.
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
9
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Approved Vent Components
These fireplaces are designed, tested and listed for operation and installation with the following vent components
only:
Secure Vent® Direct-Vent System Components,
Secure Flex® Flexible Vent Components, and
• Z-FLEX® Model GA Venting Systems listed to UL1777 and ULCS635 manufactured by Flexmaster Canada
Limited.
Use only the correct size venting (4-1/2” inner and 7-1/2” outer).
These approved vent system components are labeled for identification. DO NOT use any other manufacturer’s vent
components with these fireplaces.
Codes and Standards
These fireplaces comply with National Safety Standards and are tested and listed by PFS (Report No. 14-108) to
ANSI Z21.88 (in Canada, CSA-2.33), and CAN/CGA-2.17-M91 (CSA P4.1) in both USA and Canada, as vented gas
fireplace heaters.
These appliances comply with CSA P.4.1-2015 “Testing Method for Measuring Annual Fireplace Efficiency. P4
(EnerGuide) is a measurement of the Canadian Office of Energy Efficiency.
These fireplaces are listed for installation in bedrooms, aftermarket mobile homes, and manufactured homes.
The installation must conform to local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54—latest edition, or the Natural Gas and Propane Installation Code, CSA B149.1.
The fireplace, when installed, must be electrically grounded and wired in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70—latest edition, or the Canadian Electrical
Code, CSA C22.1—latest edition.
BTU Input
Table 1 - Input Rate, Gas Valves
Models Input Rate (BTU/HR)
Natural Gas Propane (field converted)
42” Low 19,500 19,500
High 27,000 25,000
54” Low 26,000 27,000
High 37,000 34,000
Table 2 - Thermal Efficiency (%)
Model Natural Gas Propane (field converted)
AFUE * P4 ** AFUE * P4 **
42” 67 61 68.5 66
54” 70.2 66.9 69.8 71.8
* AFUE is a measurement of the US Department of Energy
** P4 (EnerGuide) is a measurement of the Canadian Office of Energy Efficiency.
Gas Pressure
Table 3 - Inlet Gas Supply Pressure
Fuel Minimum Maximum
Natural Gas 5” WC / (1.25 kPa) 10.5” WC / (2.61 kPa)
Propane 11.0” WC / (2.74 kPa) 13.0” WC / (3.23 kPa)
Table 4 - Manifold Gas Supply Pressure
Fuel Low High
Natural Gas 1.6” WC / (0.4 kPa) 3.5” WC / (0.87 kPa)
Propane 6.3” WC / (1.57 kPa) 10.0” WC / (2.49 kPa)
The control valves have a 3/8” (10 mm) NPT thread inlet and outlet side of the valve (Figure 1).
Based on CSA P. 4.1-2015
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
10
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 1 - Electronic Gas Valve
Orange Wire
(from DFC Wire
Harness)
Pressure Regulator
Tower
Main Gas Inlet
3/8" NPT
Green Wire
(from DFC Wire Harness)
Inlet (IN) Test Port
Manifold (OUT)
Test Port
Connect GTMS
wire harness
Yellow Ground Wire
(from DFC Wire Harness)
Test gauge connections are provided on the front of the electronic gas control valve (identified IN for the inlet and
OUT for the manifold side). To access the pressure taps on the valve, remove the four (4) screws in the access plate
below the burner. A set of external 1/8” NPT test ports is also provided just below the glass door, to the right of center
(Figure 2). If installed, remove the optional bezel and surround to access the ports.
Figure 2 - Electronic Gas Valve Test Ports
Inlet (IN) Manifold (OUT)
Air shutter
adjustment lever
Lower right corner
of fireplace
NOTE: Before accessing the test ports, the fireplace must be OFF and COLD. Turn OFF the main gas supply before
connecting to the pressure taps.
Propane tanks are at pressures that will cause damage to valve components. Verify that the tanks have step down
regulators to reduce the pressure to safe levels.
Using a propane tank smaller than 100 lbs may create pressure loss and insufficient fuel delivery, which can cause
sooting, severe delayed ignition, or other malfunctions (see NPFA 58).
Any damage as a result of insufficient tank size or other improper installation is NOT covered under the limited war-
ranty.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during
any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
11
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Orifice Sizes—Sea Level to High Altitude
These fireplaces are tested and approved for installation at elevations of 0–4500 ft (0–1372 m) above sea level
using the standard burner orifice sizes (Table 5). For elevations above 4500 ft, contact your gas supplier or qualified
service technician.
Model Natural Gas
drill size Propane
drill size
42” #40 (.098”)* #54 (.055”)*
54” #32 (.116”)* #51 (.067”)*
* Standard size installed at factory
Table 5 - Burner Orifice Sizes, Elevation 0–4500 ft ( 0–1372 m)
Deration
At elevations above 4500 ft, the amount of BTU fuel value delivered must be reduced by either:
Using gas that has been derated by the gas company.
Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the
(USA) National Fuel Gas Code NFPA 54/ANSI Z223.1—latest edition or, in Canada, the CAN/CGA-B149.1 codes—
latest edition.
NOTE: Flame breadth, height and width will diminish 4% for every 1,000 ft of altitude.
IN CANADA—CAN/CGA-2.17-M91 (HIGH ALTITUDE):
THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE,
IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER, PROVINCIAL OR TERRITORIAL
AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN/
CGA-B149.1 OR CAN/CGA-B149.2 INSTALLATION CODES.
REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
These appliances are approved for installation in the U.S. state of Massachusetts if the following additional
requirements are met:
Install this fireplace in accordance with Massachusetts Rules and Regulations 248 C.M.R. 4.00 through 8.00.
Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts.
The flexible gas line connector used shall not exceed 36” (914 mm) in length.
The individual manual shutoff must be a T-handle type valve.
Massachusetts Horizontal Vent Requirements
In the Commonwealth of Massachusetts, horizontal terminations installed less than seven (7) ft above the finished
grade must comply with the following additional requirements:
A hard wired carbon monoxide detector with an alarm and battery back-up must be installed on the floor level
where the gas fireplace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL
2034 listed and be ISA certified.
A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height
of eight (8) ft above grade and be directly in line with the horizontal termination. The sign must read, in print size no
less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.
COLD CLIMATE INSULATION
For cold climate installations, seal all cracks around your fireplace with noncombustible material and wherever cold
air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on
which fireplace rests, if floor is above ground level. Gas line holes and other openings should be caulked or stuffed
with unfaced fiberglass insulation. Caulk the firestop only where the pipe penetrates an outside wall, attic, or other
unconditioned space.
NOTE: Do not use loose, or blown-in insulation in the cavity surrounding the fireplace.
If the fireplace is being installed on a cement slab in cold climates, a sheet of plywood or other raised platform can
be placed underneath to prevent conduction of cold transferring to the fireplace and into the room. It also helps to
sheetrock inside surfaces and tape for maximum air tightness and caulk firestops.
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
12
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
MANUFACTURED HOME REQUIREMENTS
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile
home, where not prohibited by local codes.
Cet appareil peut être installé dans une maison préfabriquée (mobile) déjà installée à demeure si les règlements
locaux le permettent.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for
use with other gases, unless a certified kit is used.
Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique. Cet appareil ne
peut être converti à d’autres gaz, sauf si une trousse de conversion est utilisée.
CAUTION
Ensure that the cross members are not cut or weakened during installation. The structural
integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.
CAUTION
This appliance must be grounded to the chassis of the manufactured home in accordance with
local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA
70—latest edition or the Canadian Electrical Code CSA C22.1—latest edition.
LOCATION
In selecting the location, the aesthetic and functional use of the fireplace are primary concerns. However, vent
system routing to the exterior and access to the fuel supply are also important. The fireplace may be located on or
near conventional construction materials. See Construct the Fireplace Framing on Page 18 for more information.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
En raison des températures élevées, l’appareil devrait être installé dans un endroit où il y a peu de
circulation et loin du mobilier et des tentures.
The location should also be free of electrical, plumbing or other heating/air conditioning ducting.
Be aware that this is a heat producing fireplace. Objects placed above the unit are exposed to elevated temperatures.
Do not insulate the space between the fireplace and the area above it.
Figure 3 - Typical Locations and Venting
HORIZONTAL VENT
(Rear Vent Application with a chase) HORIZONTAL VENT
(Top Vent Application)
VERTICAL VENT
(Top Vent Application)
(Rear Vent Application)
VERTICAL VENT (Rear Vent Application without a chase)
HORIZONTAL VENT
Horizontal Vent
(Top Vent)
Vertical Vent
(Top Vent)
HORIZONTAL VENT
(Rear Vent Application with a chase) HORIZONTAL VENT
(Top Vent Application)
VERTICAL VENT
(Top Vent Application)
(Rear Vent Application)
VERTICAL VENT (Rear Vent Application without a chase)
HORIZONTAL VENT
Top Vent
Top Vent
Top Vent
Top Vent Top Vent
Top Vent
Recessed
Installation
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
13
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Figure 5 - Horizontal Vent Termination Clearances
NOTE: See Figure 26 on
Page 32 for exterior wall
recess allowances for
horizontal termination.
Combustible projection
2-1/2” or less in length
Combustible projection
greater than 2-1/2” in length
Ventilated
soffit Unventilated
soffit
18”
(457 mm) 12”
(305 mm)
6
(152)
Termination kit
Termination kit
6”
VENT TERMINATION CLEARANCES
The following vent termination figures and charts should be used. Any installation must conform with local codes or,
in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane
Installation Code, CAN/CGA-B149.1.
Vertical Vent Termination Clearances
Terminate multiple vent terminations according to the installation codes listed above and Figure 4.
Figure 4 - Multiple Terminations
12”
(305 mm)
minimum
Terminate single vent caps relative to building components according to Table 6 and Figure 4.
Table 6 - Termination Heights for Vents above Flat or Sloped Roofs (NFPA 54 / ANSI Z223.1)—Gas Vent Rule
Roof Pitch Termination Height *
Flat to 6/12 1.0 ft (0.3 m)
6/12 to 7/12 1.25 ft (0.38 m)
7/12 to 8/12 1.5 ft (0.46 m)
8/12 to 9/12 2.0 ft (0.61 m)
9/12 to 10/12 2.5 ft (0.76 m)
10/12 to 11/12 3.25 ft (0.99 m)
11/12 to 12/12 4.0 ft (1.22 m)
12/12 to 14/12 5.0 ft (1.52 m)
14/12 to 16/12 6.0 ft (1.83 m)
16/12 to 18/12 7.0 ft (2.13 m)
18/12 to 20/12 7.5 ft (2.29 m)
20/12 to 21/12 8.0 ft (2.44 m)
12
X
Roof Pitch is X/12
2 FT
MIN.
2 FT MIN.
Lowest
Discharge
Opening
H*
*H = MINIMUM HEIGHT FROM ROOF TO
LOWEST DISCHARGE OPENING OF VENT
TERMINATION HEIGHTS FOR VENTS ABOVE
FLAT OR SLOPED ROOFS
Horizontal Overhang
Vertical
Wall
Vent
Termination
Storm Collar
Concentric
Vent Pipe
Flashing
1” (26 mm) Minimum
Clearance to Combustibles
Horizontal Vent Termination Clearances
The horizontal vent termination must have a minimum of 6” (152 mm) clearance to any overhead combustible
projection of 2-1/2” (64 mm) or less (Figure 5). For projections exceeding 2-1/2” (64 mm) (Figure 5). For additional
vent location restrictions refer to Table 7.
All horizontal terminations may be located as close as 6” (152mm) to any (non-combustible and combustible)
exterior sidewall. This distance may be decreased to 2” (51mm) for noncombustible exterior sidewalls with all
approved terminations (Table 21).
26mm
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table 7 - Horizontal vent termination clearances for buildings with combustible and noncombustible exteriors
Fixed
Closed Openable Fixed
Closed
V
V
VV
V
V
X
X
VX
G
G
J
F
B
B
K
H
I
A
E
L
D
B
M
C
B
V
V
A
G
G
B
TERMINATION CAP AIR SUPPLY INLET GAS METER RESTRICTED AREA
(TERMINATION PROHIBITED)
Openable
See Table 6
V
V
Inside Corner
VV
Outside Corner Recessed Location
Balcony with No Side
Wall
V
Balcony with Perpendicular Side Wall
G
F
M
M
NPO
Q
U.S. Installation ** Canadian Installation *
AClearance above grade, veranda, porch, desk, or balcony 12” (300 mm) ** 12” (300 mm) *
BClearance to window or door that may be opened 6” (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
9” (230 mm)
for fireplaces > 10,000 Btu/h (3 kW), and < 50,000 Btu/h (15
kW),
12” (300 mm)
for fireplaces > 50,000 Btu/h (15 kW) **
6” (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
12” (300 mm)
for fireplaces > 10,000 Btu/h (3 kW)
CClearance to permanently closed window 9” (229 mm)
recommended to prevent window condensation 12” (305 mm)
recommended to prevent window
condensation
DVertical clearance to ventilated soffit located above the
termination within a horizontal distance of 18” (458 mm) 18” (458 mm) 18” (458 mm)
EClearance to unventilated soffit 12” (305 mm)
30” (760 mm) to vinyl soffit 12” (305 mm)
30” (760 mm) to vinyl soffit
FClearance to outside corner 5” (127 mm)
minimum 5” (127 mm)
minimum
GClearance to inside corner 2” (51 mm) minimum 2” (51 mm) minimum
HClearance to each inside of center line extended above
meter / regulator assembly 36” (910 mm)
within a height of 15 ft above the meter / regulator assembly ** 36” (910 mm)
within a height of 15 ft above the meter /
regulator assembly *
IClearance to service regulator vent outlet 36” (910 mm)** 36” (910 mm)*
JClearance to nonmechanical air supply inlet to building or
the combustion air inlet to any other fireplace 6” (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
9” (230 mm)
for fireplaces > 10,000 Btu/h (3 kW) and < 50,000 Btu/h (15 kW),
12” (300 mm)
for fireplaces > 50,000 Btu/h (15 kW)**
6” (150 mm)
for fireplaces < 10,000 Btu/h (3 kW),
12” (300 mm)
for fireplaces > 10,000 Btu/h (3 kW)
KClearance to a mechanical air supply inlet 36” (910 mm) above if within 10 ft (3 m) horizontally ** 72” (1830 mm) *
LClearance above paved sidewalk or paved driveway located
on public property 84” (2130 mm) ‡ 84” (2130 mm) ‡
MClearance under veranda, porch, deck or balcony 12” (300 mm) *‡ 12” (300 mm) *‡
NDepth of alcove (maximum) 72” (1830 mm) ** 72” (1830 mm) *
OClearance to termination (alcove) 6” (15.2 mm) ** 6” (15.2 mm)*
PWidth of alcove (minimum) 36” (910 mm) ** 36” (910 mm) *
QClearance to combustible above (alcove) 18” (457 mm) ** 18” (457 mm) *
*
**
*‡
In accordance with the current CAN/CGA-B149.1 National Gas And Propane Installation Code
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
Only permitted if veranda, porch, deck, or balcony is fully-open on a minimum two sides beneath the floor
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
15
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
MINIMUM CLEARANCES TO COMBUSTIBLES
Fireplace And Vent Clearances
The fireplace is approved with zero clearance to combustible materials on all sides (Table 8), with the following
exceptions:
When unit is recessed, the side walls surrounding the unit must not extend beyond unit front edge (allowance
made for mantel legs / side trim in Figure 6).
When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend
beyond the front edge of the unit (Figure 6).
Table 8 - Minimum Clearances *
Back 1/2” (13 mm) to wrapper
0” (0 mm) to Spacers
Sides 1/2” (13 mm) to wrapper
0” (0 mm) to Spacers **
Top Spacers 0” (0 mm)
Floor 0” (0 mm)
From Bottom of Unit to Ceiling 65” (1651 mm)
Vent 3” (77 mm)—Top *
1” (26 mm)—Sides and Bottom
Front Service Clearance—
clearance immediately in front of viewing area(s) 36” (914 mm)
* 3” (77 mm) above any horizontal/inclined vent component.
** See Page 19 for clearance requirements to the nailing flange located at each side of the unit and any screw heads adjacent to it.
Hearth Extension
A hearth extension is not required with this fireplace. Any hearth extension used is for appearance only and does not
have to conform to standard hearth extension installation requirements.
Shelf Height
The venting attached to the top vent should be routed in a way to minimize obstructions to the space above the
fireplace. Do not insulate the space between the fireplace and the area above it (Table 9). The minimum height from
the base of the fireplace to the underside of combustible materials used to construct a utility shelf in this fashion is
shown in Table 9.
NOTE: This is a heat-producing appliance. Objects placed above the unit are exposed to elevated temperatures.
Table 9 - Combustible Shelf Height—Top Vent
Model
Top Vent with one 90° Elbow
Secure Vent®
(using rigid elbow) Secure Flex®
(using flex elbow)
42” * 57-1/2” (1450 mm) 59” (1500 mm)
54” * 61” (1550 mm) 62-3/4” (1594 mm)
Shelf Height
(see table)
No combustibles
or insulation
in the shaded
area between
the appliance
and the shelf
above it.
1’ Vertical section is
required below elbow
General Information
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
16
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
NOTICE: All Rhapsody model fireplaces
include a barrier to reduce the risk of burns
from hot viewing glass. This barrier in the
fireplace is a screen shown to the right.
42” Barrier J7427
54” Barrier J7426
Wall Finishes / Surrounds / Mantels
Clearances to combustible mantels vary according to mantel depth (Figure 6).
Mantels constructed of non-combustible material may be installed at any height above the appliance opening; however, do
NOT allow anything to hang below the top edge of the fireplace door.
Minimum clearance requirements include any projections such as shelves, window sills, mantels, etc. above the
fireplace.
NOTE: To avoid heat-related finish damage, we recommend the use of high temperature paint (rated 175°F or higher) on
the underside of the mantel.
NOTE: The factory-supplied non-combustible fiberboard MUST be installed around the fireplace opening.
Figure 6 - Combustible Side Clearances Figure 7 - Mantel Height
12
(305) 10
(254)
8
(203) 6
(152)
4
(102)
2
(51)
in. (mm)
18 (457)
20 (508)
22 (559)
24 (610)
26 (660)
28 (711)
Fireplace
Mantel depth
INSTALLATION PREPARATION
The fireplace is shipped with all gas controls and components installed and pre-wired. Before installing the fireplace,
follow these steps:
1. Remove and retain the shipping carton.
2. Confirm receipt of required items listed in Packaging on Page 8.
3. Retrieve the (6) pieces of non-combustible fiberboard from behind the fireplace, and set aside in a safe location
for later installation.
4. If not already done, remove the barrier.
5. Remove the glass door (Page 59), and set aside in a secure location for later reinstallation.
NOTE: Place the glass door on the shipping carton to protect its surface.
6. Remove baffle and other items shipped inside firebox. Set aside in a secure location for later installation.
5(127)
8-1/4
(209)
14
(356)
12 (305)
17 (431)
Top View of
Fireplace
45o
8-1/4”
(209 mm)
Combustible materials
allowed in shaded area
“Safe Zone”.
Combustible walls
shown in dark gray
Combustible mantel
legs may project
beyond either side of
the fireplace opening
as long as they are kept
within the shaded area
illustrated here.
At 8-1/4” side
wall clearance, a
combustible wall
can project 12”
5” (127
mm)
At 14” minimum
side wall
clearance, a
combustible wall
can project to
any length.
12” (305
mm)
17” (431
mm)
14” (356
mm)
Installation
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
17
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
INSTALLATION SEQUENCE
The typical sequence of installation is outlined below; however, each installation is unique and may result in
variations to the steps described.
See the pages referenced in the following steps for detailed instructions.
Check local codes for more restrictive installation. The more restrictive installation for clearances must be used.
Framing
1. Construct the Fireplace Framing (Page 18).
2. Prepare the Fireplace Top Spacers (Page 20).
3. Route the Gas Supply Line into the Fireplace (Page 20).
4. Rough in the Electrical Supply, if Needed (Page 21).
5. Place the Fireplace in the Framing, Secure, and install Heat Shield (Page 21).
Venting
6. Select a Horizontal or Vertical Vent System (Page 21).
7. Install the Vent Restrictor (if necessary) (Page 21).
8. Install the Vent System (Page 25).
Electrical Connection
9. Complete the Field Wiring (Page 36).
10. Optional: Wire and Install the Power Vent (Page 38).
11. Optional: Route Backlighting Wiring (Page 38).
Gas Connection
12. Connect the Gas Line (Page 38).
13. Optional: Install the Modesty Panel (Page 39).
14. Install the Wall Switch Receiver (Page 39).
15. Initialize the Remote Control System (Page 39).
16. Verify Proper Fireplace Operation (Page 39).
Finishing
17. Optional: Install the Backlighting Reflector (Page 40).
18. Install the Firebox Liners (Page 40).
19. Optional: Install the Backlighting Light Assemblies (Page 40).
20. Install the Glass Media (Page 40).
21. Install the Baffle (Page 40).
22. Install the Glass Door (Page 40).
23. Adjust the Air Shutter to Ensure Proper Flame Appearance (Page 40).
24. Install the Finishing Materials (Page 42).
25. Install the Bezel, Barrier, and Optional Surround (Page 43).
26. Attach the Safety-in-Operation Warning Labels (Page 46-47).
Installation
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
18
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
1. Construct the Fireplace Framing
IMPORTANT! BEFORE YOU BEGIN FRAMING, DETERMINE WHETHER YOU WILL BE INSTALLING THE
FIREPLACE AS A CLEAN FACE UNIT OR USING A SURROUND AND BEZEL. SEE PAGES 43 AND 44. WE
STRONGLY RECOMMEND WHEN THE FIREPLACE IS FRAMED WITH A 1/2” NONCOMBUSTIBLE BOARD,
WE RECOMMEND USING A SECOND LAYER, LOCALLY SOURCED, NONCOMBUSTIBLE BOARD SIMILAR
TO DUROCK® OR HARDIBOARD®. IF A SECOND LAYER OF BOARD IS USED, THE FIREPLACE FRAMING
MUST BE OFFSET BACK SO THE TWO LAYER SURFACE WILL BE ON THE SAME PLANE AS THE WALLS
ON THE SIDES AND TOP OF THE FIREPLACE.
1. Frame the fireplace as illustrated in Table 10. All framing details must allow for a minimum clearance to combustible
framing members as shown in Table 8. Steel studs are strongly recommended where exposed to heat.
2. Mount the fireplace on a fully supported base extending the full width and depth of the unit. If installed on combustible
materials, such as carpeting, vinyl tile, or combustible material other than wood flooring, the appliance shall be
installed on a metal or wood panel extending the full width and depth of the fireplace.
NOTE: Headers may be in direct contact with the fireplace top standoff spacers when they are bent up vertically,
maintaining the 9-3/8” clearance to the fireplace top, but must not be supported by them or notched to fit around them.
All construction above the fireplace must be self-supporting. DO NOT use the fireplace for structural support.
Installation
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
19
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table 11 - Fireplace Framing Specifications—Corner Installation with Horizontal Termination
Model A B C D E
42” 53-3/4”
(1365 mm) 94-3/4”
(2407 mm) 67”
(1702 mm) 47-3/8”
(1203 mm) 25-1/8”
(638 mm)
54” 65-3/4”
(1670 mm) 106-3/4”
(2711 mm) 75-1/2”
(1917 mm) 53-3/8”
(1356 mm) 29-3/8”
(745mm)
NOTE: Back wall of chase/enclosure (including finishing materials) shown.
B
A
CD
E
7 (178)
Table 12 - Fireplace Dimensions
Model A B C D E
42” 26-7/8” (683 mm) 53-3/4” (1366 mm) 32-1/2” (826 mm) 44-1/8” (1121 mm) 15-11/16” (398 mm)
54” 32-1/2” (826 mm) 65-3/4” (1670 mm) 36-3/8” (924 mm) 56-1/8” (1426 mm) 19-5/8” (498 mm)
NOTE: Assemble top standoffs before installing fireplace.
Table 13 - Viewable Glass
42” models 40” W x 10-1/2” H
1016 mm x 267 mm
54” models 51” W x 14-3/4” H
1295 mm x 375 mm
Table 14 - Surround Dimensions
42” models 55” W x 23-3/4” H
1397 mm x 603 mm
54” models 67” W x 27-11/16” H
1702 mm x 704 mm
Table 15 - Vent Collar
All models 4-1/2” inner x 7-1/2” outer
B
7
(178)
5-1/8
(130)
12-1/8
(308)
10-1/2
(267)
F
D
C
E
inches
(millimeters)
CEILING
F
~
A1/2 of A
u
u
u
NOTE: Fireplace is designed for 1” thickness of non-combustible board on the face of the unit. If the finished surface is to match a thinner finish material the unit
must be recessed up to 1/2” to allow non-combustible to be flush with surrounding finish material (see * for dimensions).
Table 10 - Fireplace Framing Dimensions - Inches (millimeters)
Model A B* C D E** F
42” 57
(1448) 21
(533) 43-1/2*
(1105)* 50-3/8
(1280) 42-1/8
(1070) 65
(1651)
54” 69
(1753) 21
(533) 48-1/4*
(1226)* 54-1/4
(1378) 47-1/8
(1197) 65
(1651)
*with 1/2” recess for flush framing
** Top Jack Stud Header positioned horizontally (see Pages 43-44)
NOTE: Illustration provided for dimensions. Fireplace must be adequately
framed and supported with 2 x 4, or larger building materials.
a. Required frame opening width (1/2 of a = horizontal centerline of
fireplace and vent framing opening)
b. Required frame opening depth with 1/2” (13mm) thick wall
finish material (for other wall finish thicknesses, adjust frame
opening depth and nailing flanges accordingly)
c. Minimum frame opening height (from base of appliance to header)
d. Minimum height from appliance base to vertical centerline of horizontal
termination vent pipe is 12” [42” models and 54” models] straight vent
section and 90° elbow off appliance vent collar)
NOTE: The vertical centerline of the horizontal termination vent pipe is NOT
the same as the vertical centerline of the vent frame opening because of
firestop/spacer offset.
e. Minimum frame opening height from base of appliance to jack stud
header.
f. Minimum height from appliance base front to ceiling
NOTE: Mount on a fully supported platform extending full width and depth
of unit.
u Cripple (jack) Stud, Recessed
1/2” Back (both sides and top)
v Mounting platform
v
Installation
900077-02F, 12/2018
Innovative Hearth Products
Rhapsody® Linear Direct-Vent Gas Fireplaces
20
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
2. Prepare the Fireplace Top Spacers
1. The two (2) 9-3/8” standoff spacers on top of the fireplace cabinet are shipped flat (Figure 8).
2. Bend the standoffs as shown (Figure 8).
3. Align the holes in the standoff with the holes in the fireplace top, and secure with the supplied screws (Figure 8).
Figure 8 - Standoffs Figure 9 - Routing the gas line through the framing
Positioned flat as
shipped from the
factory
Assembled
standoff
Left side front corner of
fireplace framing shown.
Gas line may also enter on
the right side or bottom.
Pipe coupling
(recommended)
15-3/4”
(400 mm)
1-5/8”
(43 mm)
3. Route the Gas Supply Line into the Fireplace
1. Route a 1/2” (13 mm) gas line to the left side of the fireplace (Figure 9).
2. Route the gas line through the gas supply line access opening (Figure 11).
NOTE: The gas supply line should not be connected to the appliance until step 11. Connect the Gas Line (Page 38).
NOTE: Gas lines must be routed, assembled, and made of materials that are in strict accordance with local codes and
regulations. Never use galvanized or plastic pipe.
NOTE: See Page 55 for more information on Accessing the Control Compartment.
NOTE: All codes require a shutoff valve mounted in the supply line. Figure 33 (Page 39) illustrates the method
for connecting the gas supply. The flex-line method is acceptable in the U.S., however, Canadian requirements
vary depending on locality. Installation must be in compliance with local codes. The provided gas-line shutoff
valve (located in the control compartment) is intended as a service shutoff. National and local codes may require
installation of a second gas-line shutoff valve (not provided) in a readily accessible location. Consult local codes. It
is the responsibility of the plumber to provide an accessible shutoff.
Figure 10 - Front access panel Figure 11 - Routing the gas line into the fireplace
Access
Panel
Remove front access panel by removing
the three (3) screws indicated by arrows.
A forth screw underneath the base of the
unit holds the door in place.
Gas line shutoff valve
(disconnected from flex line)
Gas flex line
Left side
gas supply line
access opening
(Left side recommended)
Door Removal Instructions
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Astria Fireplaces Rhapsody Mode d'emploi

Catégorie
Cheminées
Taper
Mode d'emploi

dans d''autres langues