Simplicity 076340-00 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur

Ce manuel convient également à

Generator Systems
Operator’s Manual
Liquid-Cooled
Generator System
This generator is rated in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian
Standards Association) standard C22.2 No. 100-4 (motors and generators).
80005444 Rev B
2 BRIGGSandSTRATTON.COM
Thank you for purchasing this quality-built Briggs & Stratton® generator. We’re pleased that you’ve placed your confidence in
the Briggs & Stratton brand. When operated and maintained according to the instructions in this manual, your generator will
provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with standby generators and
how to avoid them. Because we do not necessarily know all the applications this equipment could be used for, it is important
that you read and understand these instructions thoroughly before attempting to start or operate this equipment. This product
is only for use as an optional generator system which provides an alternate source of electric power and to serve loads such
as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause
discomfort or inconvenience.
Save these original instructions for future reference.
This generator requires professional installation before use. Refer to the separate installation manual for full information.
Your installer should follow the instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your generator. Consult your Yellow Pages. There
are thousands of Briggs & Stratton authorized service dealers worldwide who provide quality service. You can also contact
Technical Service by phone at 800732-2989, or click on Find a Dealer at BRIGGSandSTRATTON.COM, which provides a list of
authorized dealers.
Generator and engine model and serial numbers should be recorded in the installation manual.
Briggs & Stratton Power Products Group, LLC
P.O. Box 702
Milwaukee, WI 53201-0702
Copyright © 2015. All rights reserved. No part of this material
may be reproduced or transmitted in any form without the express
written permission of Briggs & Stratton Power Products Group, LLC.
3
Table of Contents
Important Safety Instructions........................4
Installation ....................................7
For the Installing Dealer/Contractor: ..............................7
Owner Orientation ............................................7
Fuel Factors .................................................8
Generator Location............................................8
Delivery Inspection............................................9
Controls ..................................... 10
System Control Panel.........................................12
Access Ports ...............................................13
Operation .................................... 14
Automatic Operation .........................................14
Setting Exercise Timer ........................................15
Maintenance .................................. 15
Fault Detection System .......................................15
Generator Maintenance .......................................17
Engine Maintenance..........................................18
Battery ....................................................21
Storage....................................................22
Maintenance Chart.............................. 23
Troubleshooting................................ 24
Warranty..................................... 25
Product Specifications ........................... 28
4 BRIGGSandSTRATTON.COM
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a degree
or level of hazard seriousness. A safety symbol may be used
to represent the type of hazard. The signal word NOTICE is
used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that
it is safe for you and others. You must also make sure that
the procedure, work method or operating technique that you
choose does not render the generator system unsafe.
Fire
Toxic Fumes
Explosive Pressure
Rotating Fan Blade
Lift Hazard Read Manual
Exploding BatteryRotating Belt/Pulley
Chemical BurnAuto Start
Hot SurfaceRotating Parts
Electrical ShockExplosion
WARNING The engine exhaust from this product
contains chemicals known to the State of California to
cause cancer, birth defects, or other reproductive harm.
WARNING Certain components in this product and
related accessories contain chemicals known to the State
of California to cause cancer, birth defects, or other
reproductive harm. Wash hands after handling.
WARNING Running engine gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide could result in death,
serious injury, headache, fatigue, dizziness,
vomiting, confusion, seizures, nausea or fainting.
Operate this product ONLY outdoors in an area that will
not accumulate deadly exhaust gas.
Keep exhaust gas away from any windows, doors,
ventailation intakes, soffit vents, crawl spaces, open
garage doors or other openings that can allow exhaust
gas to enter inside or be drawn into a potentially occupied
building or structure.
Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions/recommendations. Smoke alarms cannot
detect carbon monoxide gas.
WARNING Storage batteries give off explosive
hydrogen gas during recharging.
Slightest spark will ignite hydrogen
and cause explosion, resulting in
death or serious injury.
Battery electrolyte fluid contains
acid and is extremely caustic.
Contact with battery contents could cause severe
chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
DO NOT dispose of battery in a fire. Recycle battery.
DO NOT allow any open flame, spark, heat, or lit cigarette
during and for several minutes after charging a battery.
DO NOT open or mutilate the battery.
Wear protective goggles, rubber apron, rubber boots and
rubber gloves.
Remove watches, rings, or other metal objects.
Use tools having insulated handles.
5
WARNING Generator produces hazardous voltage.
Failure to properly ground generator could result
inelectrocution.
Failure to isolate generator from utility power could
result in death or serious injury to electric utility
workers due to backfeed of electrical energy.
DO NOT touch bare wires or bare receptacles.
DO NOT use generator with electrical cords which are
worn, frayed, bare or otherwise damaged.
DO NOT handle generator or electrical cords while
standing in water, while barefoot, or while hands or feet
are wet.
If you must work around a unit while it is operating,
stand on an insulated dry surface to reduce the risk of a
shock hazard.
DO NOT allow unqualified persons or children to operate
or service generator.
In case of an accident caused by electrical shock,
immediately shut down the source of electrical power and
contact the local authorities. Avoid direct contact with
the victim.
Despite the safe design of the generator, operating this
equipment imprudently, neglecting its maintenance or
being careless could cause possible injury or death.
Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
Before performing any maintenance on the generator,
disconnect the battery cable indicated by a NEGATIVE,
NEG or (-) first. When finished, reconnect that cable last.
After your system is installed, the generator may crank
and start without warning any time there is a power
failure. To prevent possible injury, always set the
generator’s system switch to OFF, remove the service
disconnect from the disconnect box AND remove the
15 Amp fuse BEFORE working on the equipment.
WARNING Hazardous Voltage - Contact with power
lines could cause electric shock or burns,
resulting in death or serious injury.
Lifting Hazard / Heavy Object - Could result
in serious injury.
If lifting or hoisting equipment is used, DO NOT contact
any power lines.
DO NOT lift or move generator without assistance.
DO NOT lift unit by roof as damage to generator
will occur.
WARNING Propane and Natural Gas are extremely
flammable and explosive, which could cause
burns, fire or explosion resulting in death or
serious injury.
Install the fuel supply system according to NFPA 37 and
other applicable fuel-gas codes.
Before placing the generator into service, the fuel system
lines must be properly purged and leak tested.
After the generator is installed, you should inspect the fuel
system periodically.
NO leakage is permitted.
DO NOT operate engine if smell of fuel is present or other
explosive conditions exist.
DO NOT smoke around the generator. Wipe up any oil
spills immediately. Ensure that no combustible materials
are left in the generator compartment. Keep the area near
the generator clean and free of debris.
WARNING Exhaust heat/gases could ignite
combustibles or structures resulting in
death or serious injury.
Contact with muffler area could cause
burns resulting in serious injury.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
Exhaust outlet side of weatherproof enclosure must
have at least 5 ft. (1.5m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
Standby generator weatherproof enclosure must be at
least 5 ft. (1.5m) from windows, doors, any wall opening,
shrubs or vegetation over 12 inches (30.5 cm) in height.
Standby generator weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang, or trees.
DO NOT place weatherproof enclosure under a deck or
other type of structure that may confine airflow.
Use only flexible fuel line provided. Connect provided fuel
line to generator. DO NOT use with or substitute any other
flexible fuel line.
Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
Keep at least minimum distances shown in General
Location Guidelines to insure for proper generator cooling
and maintenance clearances.
Replacement parts must be the same and installed in the
same position as the original parts.
6 BRIGGSandSTRATTON.COM
WARNING Moving parts could crush and cut.
Starter and other rotating parts could
entangle hands, hair, clothing, or
accessories resulting in serious injury.
NEVER operate generator without protective housings,
covers, or guards in place.
DO NOT wear loose clothing, jewelry or anything that
could be caught in the starter or other rotating parts.
Tie up long hair and remove jewelry.
Before servicing, remove 15 Amp fuse from control panel
and disconnect Negative (NEG or -) battery cable.
WARNING Hot pressurized coolant could cause serious
injury.
DO NOT open radiator cap when hot.
Before servicing, allow coolant to cool.
CAUTION Installing the 15A fuse could cause the
engine to start at any time without warning
resulting in minor or moderate injury.
Observe that the 15 Amp fuse has been removed from the
control panel for shipping.
DO NOT install this fuse until all plumbing and wiring has
been completed and inspected.
CAUTION Excessively high operating speeds could
result in minor injury and/or equipment damage.
Excessively low speeds impose a heavy load on generator.
DO NOT tamper with governed speed. Generator supplies
correct rated frequency and voltage when running at
governed speed.
DO NOT modify generator in any way.
NOTICE Improper treatment of generator could damage it
and shorten its life.
Use generator only for intended uses.
If you have questions about intended use, contact your
authorized dealer.
Operate generator only on level surfaces.
Adequate, unobstructed flow of cooling and ventilating air
is critical to correct generator operation.
The access panels/door must be installed whenever the
unit is running.
DO NOT expose generator to excessive moisture, dust,
dirt, or corrosive vapors.
Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
DO NOT start engine with air cleaner or air cleaner
cover removed.
DO NOT insert any objects through cooling slots.
DO NOT use the generator or any of its parts as a step.
Stepping on the unit could cause stress and break parts.
This may result in dangerous operating conditions from
leaking exhaust gases, fuel leakage, oil leakage, etc.
If connected devices overheat, turn them off and
disconnect them from generator.
Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
-unit makes unusual noises.
7
Installation
We sincerely appreciate your patronage. For this reason, we
have made every effort to provide for a safe, streamlined
and cost-effective installation. Because each installation is
unique, it is impossible to know of and advise the trade of all
conceivable procedures and methods by which installation
might be achieved. Neither could we know of possible
hazards and/or the results of each method or procedure.
For these reasons, only current licensed electrical and
plumbing professionals should attempt generator system
installations. Installations must strictly comply with all
applicable codes, industry standards andregulations.
Your generator is supplied with this “Operator’s Manual”
and a separate “Installation Manual”. These are important
documents and should be retained by the owner after the
installation has been completed.
This product is only for use as an optional generator system
which provides an alternate source of electric power and
to serve loads such as heating, refrigeration systems, and
communication systems that, when stopped during any power
outage, could cause discomfort or inconvenience.
NOTICE This product does NOT qualify for either an
emergency standby or legally required standby system as
defined by NFPA 70 (NEC).
Emergency generator systems are intended to
automatically supply illumination, power, or both, to
designated areas and equipment in the event of failure
of the normal supply. Emergency systems may also
provide power for such functions as ventilation where
essential to maintain life, where current interruption of
the normal supply would produce serious life safety or
health hazards.
Legally Required standby generator systems are
intended to automatically supply power to selected
loads in the event of failure of the normal source
which could create hazards or hamper rescue or fire-
fighting operations.
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the right
to change, alter, or otherwise improve the product and this
document at any time without prior notice.
Only current licensed electrical and plumbing professionals
should attempt generator system installations. Installations
must strictly comply with all applicable codes, industry
standards, laws and regulations.
For the Installing Dealer/Contractor:
For most applications, the Installation manual contains all
the information required to properly install and start the
generator. This operator’s manual describes routine operation
and owner maintenanceprocedures.
If you need more information in this matter, please call
800732-2989, between 8:00 AM and 5:00 PM CT.
Owner Orientation
This section provides generator owners with the information
necessary to achieve the most satisfactory and cost effective
installation possible.
The illustrations are for typical circumstances and are meant
to familiarize you with the installation options available
with your generator. A thorough understanding of these
options will provide fundamental control over the cost of
your installation, as well as ensure your final satisfaction
andsecurity.
Federal and local codes, appearance, noise levels, fuel types,
and distances are the factors that must be considered when
negotiating with an installation professional. Remember
that as the distance from the existing electrical service and
gaseous fuel supply increases, and the number of 90 degree
bends in the fuel supply increases, compensations in piping
and wiring materials must be made. This is necessary to
comply with local codes and overcome electrical voltage
drops and gaseous fuel pressure drops.
The factors mentioned above will have a direct affect on
the overall price of your generator installation.
In some areas you may need to acquire electrical permits
for installing the generator, building permits for installing
gas lines, and permits for noise allowances. Your installer
should check your local codes AND obtain the permits before
installing the system.
For the Owner:
To help you make informed choices and communicate
effectively with your installation contractor(s), read and
understand Owner Orientation in this manual before
contracting or starting your generatorinstallation.
To arrange for proper installation, contact the store at which
you purchased your generator, your dealer, a licensed
electrician or your utility power provider.
The generator warranty is VOID unless the system is
installed by licensed electrical and plumbingprofessionals.
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
The Emission Control System for this generator is warranted
for standards set by the U.S. Environmental Protection
Agency and by the California Air Resources Board (CARB).
8 BRIGGSandSTRATTON.COM
Fuel Factors
An important consideration affecting the entire installation
is the type of fuel used by your generator. The system was
factory tested and adjusted using either natural gas or liquid
propane (LP vapor). For proper engine function, factors
that are inherent to each of these fuels, your location and
the duration of possible utility interruptions are important
considerations in the following fuel guidelines:
Use clean, dry fuel, free of moisture or any
particulate material. Using fuels outside the following
recommended values may cause performanceproblems.
In engines set up to run on propane (LP), commercial
grade HD5 propane with a minimum fuel energy of 2500
BTUs/ft3 with maximum propylene content of 5% and
butane and heavier gas content of 2.5% and minimum
propane content of 90%.
Natural gas rating will depend on specific fuel but typical
derates are between 10 to 20% off the LP gas rating.
Power Decrease at High Altitude or High Temperature
Air density is less at high altitudes, resulting in less available
engine power. Specifically, engine power will decrease 3%
for each 1,000 feet (300 meters) above sea level and 1% for
each 10° F (5.6°C) above 77°F (25°C). Make sure you and
your installer consider these factors when determining total
generator load.
Delivery Inspection
Carefully inspect the generator for any damage that may have
occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss
or damage. If loss or damage is noted after delivery, separate
the damaged materials and contact the carrier and your
installer for claim procedures. Missing or damaged parts are
not warranted.
The generator is supplied with:
Fully-serviced coolant system
Fully-serviced oil/lubricating system
Flexible fuel hook-up hose
Installation and start-up manual
Operator’s manual
Spare access door keys
Spare 15A fuse
Touch up paint
To be supplied by installer:
Carbon monoxide detector(s)
Smoke detector(s)
Starting battery
Reinforced concrete mounting pad
Connecting wire and conduit
Fuel supply valves/plumbing
Various specialty tools/equipment
WARNING
Propane and Natural Gas are extremely
flammable and explosive, which could cause
burns, fire or explosion resulting in death or
serious injury.
The generator is equipped with an automatic safety gas
“fuel shut-off” valve.
DO NOT operate the equipment if the “fuel shut-off” valve
is missing or inoperative.
9
Generator Location
The actual physical location of your generator has a direct
affect on:
1. The amount of plumbing required to fuel your generator.
2. The amount of wiring required to control and connect
your generator.
Specific location guidelines are discussed in the installation
manual. Acquaint yourself with that information and confer
with your installer. Be sure to ask how your site might
affect installation costs and compliance with local codes
andstandards.
Install generator outdoors in an area that will not
accumulate deadly exhaust gas.
DO NOT install generator where exhaust gas could
accumulate and enter inside or be drawn into a
potentially occupied building or structure.
By law it is required in many states to have a Carbon
Monoxide (CO) detector in operating condition in your.
Carbon monoxide detector(s) (A) MUST be installed
and maintained indoors according to the manufacturer’s
instructions/recommendations. A CO monitor is an
electronic device that detects hazardous levels of CO.
When there is a buildup of CO, the monitor will alert the
occupants by flashing visual indicator light and alarm.
Smoke alarms cannot detect CO gas.
Ensure exhaust gas is kept away from any windows,
doors, ventilation intakes, soffit vents, crawl spaces,
open garage doors or other openings that can
allow exhaust gas to enter inside or be drawn into a
potentially occupied building or structure. Neighboring
structures may be exposed to the engine exhaust from
your standby generator and must be considered when
installing your standby generator.
Wind and air currents should be taken into
consideration when positioning generator.
See the installation manual for full details on safe generator
location.
WARNING Running engine gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide could result in death,
serious injury, headache, fatigue, dizziness,
vomiting, confusion, seizures, nausea or fainting.
Operate this product ONLY outdoors in an area that will
not accumulate deadly exhaust gas.
Keep exhaust gas away from any windows, doors,
ventilation intakes, soffit vents, crawl spaces, open garage
doors or other openings that can allow exhaust gas
to enter inside or be drawn into a potentially occupied
building or structure.
Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions/recommendations. Smoke alarms cannot
detect carbon monoxide gas.
WARNING Exhaust heat/gases could ignite
combustibles or structures resulting in death or serious
injury.
Exhaust outlet side of weatherproof enclosure must
have at least 5 ft. (1.5 m) minimum clearance from any
structure, shrubs, trees, or any kind of vegetation.
Standby generator weatherproof enclosure must be at
least 5 ft. (1.5 m) from windows, doors, any wall opening,
shrubs or vegetation over 12 in. (30.5 cm) in height.
Standby generator weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang or trees.
DO NOT place weatherproof enclosure under a deck or
other type of structure that may confine airflow.
USE ONLY flexible steel fuel line provided. Connect
provided fuel line to generator. DO NOT use with or
substitute any other flexible fuel line.
Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
DO NOT place weatherproof enclosure in manner other
than shown in illustrations.
A
10 BRIGGSandSTRATTON.COM
Controls
35 kW Generator
Read this operator’s manual and Important Safety Instructions before operating your generator.
Compare the illustrations of this model with your generator to familiarize yourself with the locations of various
controls and adjustments. Save this manual for future reference.
Generator is pictured with access doors removed for clarity
and screen guard open for clarity.
A - Exhaust Port — High-performance muffler lowers engine
sound level to comply with most residential codes.
B - Coolant Fill Door — Provides access for servicing engine
with coolant.
C - Air Cleaner — Protects engine by filtering dust and
debris out of intake air.
D - Battery Door opening — Provides access to starting
battery and air cleaner.
E - Engine Label — Identifies engine model and type.
F - Oil Dip Stick — Used to check the engine oil level.
G - Oil Fill Cap — Remove to service the engine with
recommended oil.
H - Screen Guard — Prevents fingers from touching radiator
fan and houses the coolant recovery bottle. Must stay
closed while generator is in use.
J - Coolant Recovery Bottle — Located on inside of screen
guard. Provides visual indicator of engine coolant level.
K - Oil Filter — Filters engine oil to prolong system life.
L - Fuel Inlet — Fuel supply is connected here.
M - Oil Drain Hose — Provided to facilitate oil changing.
N - ID Label (located on base) — Identifies unit by
serial number.
P - Circuit Breaker Enclosure — Equipped with removable
bottom to assist with conduit connection.
R - Control Panel Door opening — Provides access to
control panel, oil filter, etc.
S - Control Panel — Used for various test, operation and
maintenance functions. See System Control Panel.
A
B
C
D
A
E
F
G
H
J
K
L
M
N
P
R
S
11
Brief descriptions of the controls used during installation are:
A - Menu/Programming Navigation Buttons — See
Menu section for details
B - USB Port — Authorized Dealer Service Use Only
C - Generator Operation Control Buttons
•“AUTO” Normal operating position. Press and hold
button to put unit into Automatic mode. If a utility
power outage is sensed, the system will start the
generator. When utility power is restored, auto lets the
engine stabilize internal temperatures, shuts off the
generator, and waits for the next utility outage.
•“OFF” Turns off running generator, prevents unit from
starting, and resets any detected faults.
OFF must be pressed and held for more than 5
seconds in order to reset service codes.
•“MANUAL” Used to manually start the generator.
“AUTO” LED — LED will light when unit is placed
into Auto mode. LED will blink if exercise cycle is not
set or set to OFF.
D – 15 Amp Fuse — Protects the home generator DC
control circuits. If the fuse has ‘blown’ (melted open)
or was removed, the engine cannot crank or start.
Replace the fuse using only an identical ATO 15A
fuse. One spare fuse is supplied with the unit.
E - Cover — This protective cover must be opened to
access the fuse and the USB port.
F - Digital Display — Displays generator mode, menu
options, service codes, and service engine indicators
System Control Panel
Compare this control panel illustration with your generator to familiarize yourself with the location of these important controls:
A
B
C
F
E
D
12 BRIGGSandSTRATTON.COM
Access Ports
The generator is equipped with an enclosure that has
several access doors. The doors are named for a significant
component located behind them, as follows::
A - Fuel Inlet port (shown for reference)
B - Control Panel door
C - Exhaust opening (shown for reference)
D - Coolant Fill door
E - Battery door
F - Muffler door
The enclosure also includes muffler and radiator access
panels, used for cleaning those components. Those panels
should remain closed at all other times to assure proper
cooling, reduce noise, and for added safety.
Each generator is supplied with a set of identical keys. These
keys fit the locks that secure the access doors.
To open access door:
1. Insert key into lock of access door handle and turn key
one quarter turn counterclockwise.
2. Grasp door’s handle and turn one quarter turn
counterclockwise to open. Remove key.
3. Coolant Fill door is unlocked in the same manner. It can
be used for adding coolant or oil.
To close access door:
1. Close door and turn door’s handle one quarter
turnclockwise.
2. Insert key into lock of door handle and turn key one
quarter turn clockwise. Remove key.
WARNING Contact with muffler area could cause burns
resulting in serious injury.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
C
D
E
F
B
A
Operation
Important Owner’s Considerations
Engine Oil
This engine is shipped from the factory pre-run and filled
with non-synthetic oil (API SL 10W-30W). This allows
for system operation in a wide range of temperature and
climate conditions. Before starting the engine, check oil
level and ensure that engine is serviced as described in the
Maintenance section.
Coolant System
This engine is shipped from the factory filled with a
50-50 mix of automotive (ethylene glycol) anti-freeze and
water. This will provide optimum year round protection
against freezing, boiling and corrosion.
Battery
The installer must supply a valve-regulated, rechargeable
12 volt DC starting battery. See Battery in Final Installation
Considerations in the installation manual.
15 Amp Fuse
The generator’s 15 Amp fuse is critical to correct system
operation. The 15 Amp fuse was removed at the factory to
prevent the unit from starting during shipping. Your installer
will ensure the fuse is properly installed upon completion of
the installation.
NOTICE Any attempt to crank or start the engine before it
has been properly serviced with the recommended coolant
or oil will result in equipment failure.
Refer to the Maintenance section for coolant and oil fill
information.
Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
WARNING Battery posts, terminals and related
accessories contain lead and lead compounds - chemicals
known to the State of California to cause cancer and
reproductive harm. Wash hands after handling.
Automatic Operation
To select automatic operation, do the following:
1. Confirm 15 Amp fuse is installed in control panel.
2. Set the main distribution panel circuit breaker that
sends utility voltage to the transfer switch to ON.
3. Set the generator’s circuit breaker to its ON position.
4. Set the control panel system switch to AUTO.
Checking Automatic Operation
To check the system for proper automatic operation, proceed
as follows:
1. Turn OFF the service disconnect or main distribution
panel circuit breaker sending power to the automatic
transfer switch.
When utility voltage is lost and the sensor has timed
out, the engine will crank and start. Let the system go
through its entire automatic operation sequence.
2. With the generator output supplying its loads, turn ON
the service disconnect or main distribution panel circuit
breaker that supplies utility power to the automatic
transfer switch.
3. The automatic transfer switch will transfer loads back
to utility power after a 5 minute minimum run time and
utility power is available.
4. The generator will run for an additional one minute for
engine cool down, then shut down.
If utility power is restored and generator does not shut down
after 10 minutes, set system switch to OFF and contact your
installer or local service center.
This completes the test procedures for automatic operation.
The generator will now start automatically and will supply
power to the transfer switch when utility power islost.
CAUTION Installing the 15A fuse could cause the
engine to start at any time without warning
resulting in minor or moderate injury.
Observe that the 15 Amp fuse has been removed from the
control panel for shipping.
DO NOT install this fuse until all plumbing and wiring has
been completed and inspected.
14 BRIGGSandSTRATTON.COM
Setting Exercise Timer
The generator is equipped with an exercise timer. During the
exercise period, the unit runs for approximately 20 minutes
and then shuts down. Electrical load transfer DOES NOT occur
during the exercise cycle (unless an utility power outage
occurs).
The generator will only enter the exercise cycle if the unit is
in the AUTO mode and this exact procedure is followed.
To set the exercise timer:
NOTICE The generator is set with a default exercise cycle
setting of Tuesday at 2:00 P.M, Central Time. To change the
cycle setting, proceed to the following steps:
1. Choose the day and time you want your generator to
exercise.
2. Press and hold the left arrow and right arrow
simultaneously for 3 seconds to enter the General
Set-Up program mode. See General Set-Up flow chart
in Menu Section.
3. Verify and/or set the time and date on the unit.
4. Go to the SET EXERCISE prompt and hit the “OK”
button.
NOTICE Items will flash until they are selected.
SELECT DAY: Use the left or right arrow to toggle
through the days of the week, Once the day is
selected, hit the “OK” button.
SELECT HOUR: Use the left or right arrow to toggle
through between 1 and 12. Choose the hour of day
you want the generator to exercise then hit the “OK”
button.
SELECT MINUTE: Use the left of right arrow to toggle
between :00 and :59. Choose the minute of the day
you want the generator to exercise then hit the “OK”
button.
SELECT AM/PM: Use the left of right arrow to toggle
between AM and PM. Once chosen, hit the “OK”
button.
NOTICE During the weekly exercise cycle, the generator will
run for 20 minutes, but it will not supply power to the home.
During the exercise cycle, the in-home monitor will continue
blinking the GENERATOR READY green LED.
If you want to change the day and time the unit exercises,
simply perform the procedure again.
To turn off the generator exercise cycle, go to the OFF
selection within the day of the week menu and press OK. The
display will then scroll: EXERCISE CYCLE OFF.
Maintenance
The generator warranty does not cover items that have been
subjected to operator abuse or neglect. To receive full value
from the warranty, the operator must maintain the system as
instructed in the Maintenance section.
Servicing the System
Before performing any generator maintenance, always
perform the following steps:
1. Set generator’s circuit breaker to its OFF position.
2. Set control panel system switch to OFF.
3. Remove 15 Amp fuse from control panel.
4. Utility voltage is present at generator control panel.
Disconnect power before servicing control panel by
removing the fuses from the transfer switch.
5. After all servicing has been completed, reinstall fuses in
transfer switch, replace 15 Amp fuse in control panel,
set system switch and circuit breaker ON and reset
exercise timer. See Setting Exercise Timer.
Service Code Detection System
The generator may have to run for long periods of time with
no operator present. For that reason, the system is equipped
with sensors that automatically shut down the generator in
the event of potentially damaging conditions, such as low oil
pressure, high temperature, over speed, and other conditions.
The generator’s control board shows service code
descriptions scrolling across the digital display. The service
code descriptions are listed below:
Low Battery Voltage
Low Oil Pressure
Under Voltage
Over Voltage
Engine Does Not Start
Low Frequency
Engine Overspeed
High Oil Temperature
Transfer Switch Service code
No Wireless Communication (Optional)
Battery Charge Circuit
Reset Service code Detection System
The operator must reset the service code detection system
each time it activates. To do so, press the control board OFF
button for 5 seconds. Once the display turns off, leave it off
for at least 30 seconds. Remedy the service code condition,
then return the home generator to service by pressing and
holding the control board AUTO button and installing the 15
Amp fuse (if removed).
Low Battery Voltage
This service code is indicated by Low Battery Voltage scrolling
across the digital display and a single flash on the wireless
monitor. This condition occurs if the battery voltage drops
below the preset value. Causes for this problem may be a
service code battery or battery charge circuit. See Battery
Charge Circuit,
Remove the 15 Amp fuse and disconnect the battery from
the generator. Test the battery voltage. If voltage meets
specifications, take the battery to a local battery store for
analysis. Or contact your local service center for assistance.
Reinstall the battery (replace if necessary - see Battery in Final
Installation Considerations in the installation manual). Then
reset the service code detection system, as described earlier.
Low Oil Pressure
This service code is indicated by Low Oil Pressure scrolling
across the digital display and two flashes on the wireless
monitor. The unit is equipped with an oil pressure switch
that uses normally closed contacts held open by engine oil
pressure during operation. Should oil pressure drop below
the 8 psi range, switch contacts close and the engine will shut
down.
To remedy the low oil pressure condition, add the
recommended oil to the FULL mark on the dipstick.
If the low oil pressure condition still exists, the engine will
start, then shut down again. The service code code will
appear. In this case, contact an authorized dealer.
Under Voltage
This service code is indicated by Under Voltage scrolling
across the digital display and three flashes on the wireless
monitor. This condition is caused by a restriction in the
fuel flow, the electronic governing system not functioning
properly, a broken or disconnected signal lead, a failed
alternator winding, the control board circuit breaker is open,
or the generator is overloaded.
To remedy the problem, contact your installer or an authorized
dealer.
Over Voltage
This service code is indicated by Over Voltage scrolling across
the digital display and three flashes on the wireless monitor.
This feature protects devices connected to the transfer switch
by shutting the generator down if the generator output voltage
happens to increase above the preset limit.
This condition is most likely caused by a failed voltage
regulator, alternator excitation circuit or a load imbalance. To
remedy the problem, contact your installer or an
authorized dealer.
Engine Does Not Start
This service code is indicated by Engine Does Not Start
scrolling across the digital display and four flashes on the
wireless monitor. This feature prevents the generator from
damaging itself if it continually attempts to start in spite
of another problem, such as no fuel supply. Each time the
system is directed to start, the unit will crank for 10 seconds,
pause for 10 seconds, and repeat. If the system does not
begin producing electricity after approximately 2 minutes, the
unit will stop cranking.
The most likely cause of this problem is no fuel supply or
incorrect fuel selector setting. See Fuel Selection Switch in the
installation manual. Check the internal and external fuel shut
off valves to ensure they are fully open. Other causes could be
failed spark plug(s), a loose electronic governor connection,
a failed engine ignition, or the engine air filter is clogged. You
may need to contact your installer for assistance if you can’t
remedy these problems.
Low Frequency
This service code is indicated by Low Frequency scrolling
across the digital display and five flashes on the wireless
monitor. This feature protects devices connected to the
transfer switch by shutting the generator down if the engine
runs slower than 55 Hz for three seconds. This condition is
caused by a failed engine component, electronic govenor
system, or by excessive loads on the generator. To resolve the
problem, contact your installer or an authorized dealer.
Engine Overspeed
This service code is indicated by Engine Overspeed scrolling
across the digital display and six flashes on the wireless
monitor. This condition can be caused by a problem within the
electronic govenor system.
To resolve the problem, contact your installer or an authorized
dealer.
High Oil Temperature
This service code is indicated by High Oil Temperature
scrolling across the digital display and seven flashes on the
wireless monitor. The contacts of the temperature switch
are normally open. If the engine temperature exceeds a
predetermind temperature, the service code is detected and
the engine shuts down.
Common causes for this condition include running the unit
with an access door removed, obstructed air inlet or exhaust
port, or debris in the engine compartment or running unit with
roof open.
To resolve the problem, let the engine cool down and remove
any accumulated debris and obstructions. Ensure that the
access doors are installed and the roof is closed whenever the
unit is running. If problem persists, contact your installer or
an authorized dealer.
Transfer Switch Service code
This service code is indicated by Transfer Switch Service
code scrolling across the digital display (if transfer switch is
equipped with service codedetection) and eight flashes on the
wireless monitor.
The most likely cause of this service code is a blown fuse
in the transfer switch. To remedy the problem, contact your
installer or an authorized dealer.
Battery Charge Circuit
This service code is indicated by Battery Charge Circuit
scrolling across the digital display. The most likely cause is
an electrical problem with the control panel. To remedy the
problem, contact your installer or an authorized dealer.
16 BRIGGSandSTRATTON.COM
Generator Maintenance
Generator maintenance consists of keeping the unit
clean. Operate the unit in an environment where it will
not be exposed to excessive dust, dirt, moisture or any
corrosive vapors. Cooling air louvers on the enclosure
must not become clogged with snow, leaves, or any other
foreign material. To prevent generator damage caused by
overheating, keep the enclosure cooling inlets and outlets
clean and unobstructed at all times.
Check the cleanliness of the unit frequently and clean when
dust, dirt, oil, moisture or other foreign substances are visible
on its exterior/interior surface. Inspect the air inlet and outlet
openings inside and outside the enclosure to ensure air flow
is not blocked.
DO NOT use direct spray from a garden hose to clean generator.
Water can enter the engine and generator and cause problems.
Cleaning the Generator
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Clean generator as desired.
Use a damp cloth to wipe exterior surfaces clean.
Use a soft, bristle brush to loosen caked on dirt, etc.
Use a vacuum cleaner to pick up loose dirt and debris.
Use low pressure air (not to exceed 25 psi) to blow
away dirt. Inspect cooling air slots and openings on
the generator. These openings must be kept clean
andunobstructed.
4. Reinstall 15 Amp fuse in control panel.
5. Set generator’s system switch to AUTO.
6. Reset exercise timer. See Setting Exercise Timer.
NOTICE Improper treatment of generator can damage it
and shorten its life.
DO NOT expose generator to excessive moisture, dust,
dirt, or corrosive vapors.
DO NOT insert any objects through cooling slots.
Engine Maintenance
The maintenance of an engine and related components are
critical to its operating performance and lifespan. Industrial
engines operate in an environment that often include hot
and cold temperatures and extreme dust. The recommended
maintenance schedule is listed in this section, however,
environmental operating conditions and additional installed
equipment may require more frequent inspection and
servicing. The owner and/or authorized service technician
should review the operating conditions of the equipment to
determine the inspection and maintenance intervals. Proper
engine cooling and lubrication are very important, so pay
particular attention to these matters.
Engine Oil
The engine is shipped from the factory pre-run and filled
with non-synthetic oil (API SL 10W-30). This allows for
system operation in a wide range of temperature and
climateconditions.
Oil Recommendation
Select and engine oil viscosity that will best match the
prevailing daytime temperature.
The oil must meet GM specification 9986231. Motor oils
meeting this spec receive the API (American Petroleum
Institure) starburst symbol:
HOT WEATHER
COLD WEATHER
SAE 10W-30
PREFERRED
SAE 15W-40
FOR THE BEST FUEL ECONOMY AND COLD STARTING, SELECT THE LOWEST
SAE VISCOSITY GRADE OIL FOR THE EXPECTED TEMPERATURE RANGE
IF NEITHER SAE 10W-30
NOR SAE 15W-40 GRADE
OILS ARE AVAILABLE, SAE
30 GRADE MAY BE USED AT
TEMPERATURES ABOVE 4
DEGREES C (40F), SAE 40
GRADE AY BE USED AT
TEMPERATURES ABOVE 27
DEGREES C (80F).
DO NOT USE SAE 10W-40
GRADE OIL OR ANY OTHER
GRADE NOT RECOMMENDED
RECOMMENDED SAE VISCOSITY GRADE ENGINE OILS
40°F (4°C)
It is noted that the GF-4 oils are also “backward compatible”
and are equal or better than previous grades of oil in all
aspects.
Synthetic Oils
Synthetic Oils have been available for use in industrial
engines for a relatively long period of time and may offer
advantages in cold and hot temperatures. However, it is not
known if synthetic oils provided operational or economic
benefits over conventional petroleum-based oils in industrial
engines. Use of synthetic oils does not permit the extension
of oil change intervals.
17
Checking Engine Oil Level
NOTICE: It is important to be careful when checking engine
oil level. Oil must be maintained between the “ADD” and
the “FULL” mark on the dipstick. To ensure that you are not
getting a false reading, make sure the following steps are
taken before checking the oil level.
1. Stop engine.
2. Set control board system switch to OFF.
3. Remove 15 Amp fuse from control panel.
4. Allow approximately five minutes for the oil to drain
back into the oil pan.
5. Remove the dipstick. Wipe with a clean cloth or paper
towel and reinstall. Push the dipstick all the way into the
dipstick tube.
6. Remove the dipstick and note the amount of oil on the
dipstick. The oil level must be between the “ADD” and
“FULL” marks.
7. If the oil level is below the “ADD” mark, reinstall the
dipstick and proceed to step 6.
8. Remove the oil filler cap from the valve cover.
9. Add the required amount of oil to bring the level up to,
but not over, the “FULL” mark on the dipstick. Reinstall
the oil filler cap to the valve rocker arm cover and wipe
any excess oil clean.
Changing Engine Oil
KEEP OUT OF REACH OF CHILDREN. DON’T
POLLUTE. CONSERVE RESOURCES. RETURN
USED OIL TO COLLECTION CENTERS.
Change oil while the engine is still warm from running.
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Place oil drain hose (B) into an approved container.
4. Open valve (A) located on bottom of oil pan.
5. When oil has drained, replace brass fitting on hose.
6. Remove oil filter and dispose of properly.
7. Before installing a new oil filter, lightly lubricate the oil
filter gasket with fresh, clean oil.
8. Install the oil filter by hand until the gasket contacts the
oil filter adapter, then tighten the oil filter ½ to ¾ turn.
9. Add the required amount of oil to bring the level up to,
but not over the “FULL” mark on the dipstick. Reinstall
the oil filler cap to valve rocker arm cover and wipe any
excess oil clean.
10. If all engine servicing is complete, replace 15 Amp fuse
in control panel and reset exercise timer. See Setting
Exercise Timer in Operation.
To make the task of adding oil more convenient, we
recommend use of a funnel attached to a length of tubing
long enough to reach from the Coolant Fill door to the oil fill
opening on the engine valve cover.
18 BRIGGSandSTRATTON.COM
Engine Coolant System
It is important that the cooling system of the engine be
maintained properly to ensure proper performance and
longevity.
Engine V-Belts
The engine installed in this equipment uses drive belt(s) that
drive the water pump and alternator. The drive belt(s) are an
integral part of the cooling and charging system and should
be inspected according to the maintence schedule. When
inspecting the belts, check for:
• Cracks
Chunking of the belt
• Splits
Material hanging loose from the belt
Glazing, hardening
If any of these conditions exist, the belt should be replaced.
The cooling system must be maintained according to the
recommended maintenance schedule and inspection should
include:
The regular removal of dust, dirt, and debris from the
radiator core and fan shroud.
Inspection of coolant hoses and components for leaks,
especially at the radiator hose connections. Tighten
hose clamps if necessary.
Check radiator hoses for swelling, separation,
hardening, cracks, or any type of deterioration.
Inspect the radiator cap to ensure proper sealing.
NOTICE: Alcohol or methanol based anti-freeze or plain
water are not recommended for use in the cooling system at
any time.
With the engine cold, check the coolant level in the coolant
recovery bottle (see Controls). Specifications for the coolant
system can be found in the Maintenance chart of this manual.
Coolant Specification - ethylene glycol 50-50 mixture w/
distilled water.
Coolant
WARNING Hot pressurized coolant could cause serious
injury.
DO NOT open radiator cap when hot.
Before servicing, allow coolant to cool.
19
Generator Electrical System Maintenance
The generator’s electrical system incorporates computers to
control various related components. The electrical system
connections and ground circuits require good connections.
Follow the recommended maintenance schedule located in
the Maintenance section of this manual.
When inspecting the electrical system, check the following:
Check positive (+) and negative (-) battery cables for
corrosion, rubbing, chafing, burning, and ensure tight
connections at both ends.
Check battery for cracks or damage to the case. Replace
as necessary.
Inspect engine wire harness for rubbing, chafing,
pinching, burning, and cracks or breaks in the wiring.
Verify that the engine harness connectors are correctly
locked in.
Inspect ignition coil wire for hardening, cracking,
chafing, burning, separation, and split boot covers.
Inspect spark plug wires for hardening, cracking,
chafing, burning, separation, and split boot covers.
Replace spark plugs at the required intervals per the
recommended maintenance schedule.
Verify that all electrical components are securely
mounted to the engine or chassis.
Verify that any additional electrical services installed by
the owner are properly installed in the system.
Engine Air Cleaner
Once each year service the air cleaner, as follows. If
operating in a dusty environment, service more often.
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Remove filter cartridge - Remove the service cover by
disengaging three clips and detaching cover, starting
with the bottom two clips and the top clip last. Gently
move the end of the filter back and forth, then rotate
while pulling straight out.
4. Clean outlet tube and check Vacuator™ valve - Use
a clean cloth to wipe the filter sealing
surface and the outlet tube surfaces.
Make sure that all contaminant is
removed before the new filter is inserted.
Be careful to not damage the sealing area
on the tube.
Visually check and physically squeeze Vacuator valve
attached to service cover to make sure it is flexible and
not inverted, damaged orplugged.
5. Clean filter - Use a soft bristle brush to loosen dirt
and a vacuum cleaner to remove dirt and debris. Low
pressure air (not to exceed 25 psi) may also be used to
blow away dirt. Replace filter cartridge if any holes are
detected in filter media.
6. Install clean filter properly - Insert the filter carefully.
Seat the filter by hand, making certain it is completely
into the air cleaner housing before securing the cover
in place. To complete a tight seal, apply pressure by
hand at the outer rim of the filter, not the flexible center.
(Avoid pushing on the center of the urethane end cap.)
No cover pressure is required to hold the seal.
NEVER use the service cover to push the filter into
place! Using the cover to push the filter in could cause
damage to the housing, cover, or fasteners and will void
the warranty. If the service cover hits the filter before
it is fully in place, remove the cover and push the filter
(by hand) further into the air cleaner and try again. The
cover should go on with no extra force.
7. Reinstall service cover - Once the filter is in place,
reinstall the service cover, positioning the cover with
the arrow and the word TOP to the top. Fasten the top
clip first, the bottom two clips last. Make sure that all
mounting bands, clamps, bolts, and connections in the
entire air cleaner system are tight and verify absence of
holes in piping - repair if needed.
8. Replace 15 Amp fuse in control panel.
9. Set control board system switch to ON.
20 BRIGGSandSTRATTON.COM
Battery
Servicing of batteries is to be performed or supervised
by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel away
frombatteries.
Servicing the Battery
If it is necessary to service the battery, proceed as follows:
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Service or replace battery as required. See Battery
in Final Installation Considerations in the installation
manual for specific battery needed.
4. Connect red battery cable to battery positive terminal
(indicated by POSITIVE, POS, or (+)).
5. Connect black battery cable to negative battery terminal
(indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative battery
terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
8. Set generator’s system switch to AUTO.
9. Reset exercise timer. See Setting Exercise Timer.
DON’T POLLUTE. CONSERVE RESOURCES,
RETURN USED BATTERY TO RECYCLING
COLLECTION CENTER.
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Disconnect negative battery cable from negative battery
terminal (indicated by NEGATIVE, NEG, or (-)).
4. Charge battery with battery charger at 2 Amps until
battery holds 12 Volts. DO NOT exceed 13.7 volts when
charging battery.
5. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative battery
terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
8. Set generator’s system switch to AUTO.
9. Reset exercise timer. See Setting Exercise Timer.
WARNING Battery posts, terminals and related
accessories contain lead and lead compounds - chemicals
known to the State of California to cause cancer and
reproductive harm. Wash hands after handling.
NOTICE Failure to disconnect negative battery cable will
result in equipment failure.
DO NOT attempt to jump start the generator.
Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
CAUTION With the system switch set to AUTO,
the engine could crank and start at any
time without warning, resulting in minor or
moderateinjury.
To prevent possible injury that could be caused by such
sudden starts, always set the system switch to OFF if
performing maintenance on the system.
Remove the 15 Amp fuse before working on or around the
generator or transfer switch.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116