Saia-Burgess Controls AG
Bahnhofstrasse 18 I CH-3280 Murten I Schweiz
T +41 26 580 30 00 I F +41 26 580 34 99
www.sbc-support.com
Assembly and operating instructions Type ALD1B5FS
32 A bidirectional Single Phase active power energy meter with S-Bus interface, Pic. 1
Description
Energy meter with S-Bus interface enables the reading of all
relevant data like meter reading, electricity, voltage, power
(active and reactive) and cos phi.
Indicating elements
(Pic. 4)
T
(kWh)
■
Indicates the total consumption
T
(kWh)
■
Indicates the total feeding back
P (kW)
■
Indicates the instantaneous power
Current = consumption (pos.)
Current = feeding back (neg.)
U (V)
■
Indicates the voltage
I (A)
■
Indicates the current
2000 pulses/kWh
■
Pulsates according to the amount
of used power.
Technical data
Connection
■
Pic. 2
diagram
Dimensions
■
Pic. 3
Accuracy class
■
B according to EN50470-3,
1 according to IEC62053-21
Reference, Maxi-
■
Iref = 5 A, Imax = 32 A, Ist = 20 mA
mum, initial current
operating voltage
■
230 VAC, 50 Hz
Tolerance −20%/+15%
Counting range
■
00 000,00…999 999,9 kWh
Connections
■
Conductor cross-section max. 6 mm
2
,
Main circuit screwdriver pozi no. 1, slot no. 1,
torque 1,2 Nm
Connections
■
Conductor cross-section max. 2,5 mm
2
,
Control circuit screwdriver pozi no. 0, slot no.1,
torque 0,5 Nm
Operating
■
−25… +55°C (noncondensing
temperature according standard EN50470)
Environment
■
Mechanical M2
Electromagnetic E2
Notes before connecting
In order to avoid moisture in the meter due to condensate
build-up, acclimatise the meter at room temperature for
about half an hour before connecting.
Attention!
These devices must only be installed by a professional
electrician, otherwise there is the risk of re or the risk of
an electric shock.
Declaration of Conformity CE
We, Saia-Burgess Controls Ltd., CH 3280 Murten (Switzer-
land), herewith declare, on our own responsibility that
the products:
■
ALD1B5FS00A3A00
which this certicate refer to, are in accordance with the
directive 2004/22/EG (MID) and the following standards:
■
EN50470 parts 1 and 3 (electronic meter), of
October 2006.
ESD on equipment side: 13 kV.
Murten, 30.04.2013
Conformity Assessment Body:
METAS-Cert, Nr. 1259
CH-3003 Bern-Wabern
Signed: Urs Tanner, Site Quality Leader
English
Installation instructions
The energy meter can be attached to a 35 mm rail
(EN60715TH35).
The meter can be used only in installation cabinets.
Operation of the LCD display
See page with LCD menu navigation.
4 319 5139 0E 03.2017 Subject to change without notice
Technical data S-Bus
Bus system S-Bus
Transmission rate 4800-9600-19 200-38 400-57 600-115 200.
The transmission Baud rate is automatically detected
Transmission mode Data
Bus length (max.) 1200 m (without repeater)
Response time: Write: up to 60 ms
Read: up to 60 ms
■
The communication is ready 30 s after the power on
■
The use of energy meter in bus with intensive communication could reduce the performance of the bus
■
Refresh time for the data is 5 s. For this reason one energy meter should be not polled faster as 5 s
■
254 devices could be connected to the S-Bus. With more than 128 devices, a repeater should be used
■
The interface don’t have a terminal resistor, this must be provided external
■
For a description of the used registers please look at the register page
Data transmission
■
Only «read/write» register instructions are recognized
■
Only one register can be written at the same time
■
The device will respond «NAK» if more than 1 register is written
■
Up to 10 Registers could be read at the same time
■
The device will respond «NAK» if more than 10 registers are read
■
The device will not respond to any unknown query
■
The device has a voltage monitoring system. In case of voltage drop,
registers are stored in EEPROM (transmission rate) etc.
Changing the S-Bus direct on device
■
In the menu, go for «U»
■
Push long (≥ 2 s) ➞ «SBUS-ADR»
■
Push short ➞ S-Bus address +1, push long ➞ S-Bus address +10
■
If the desired address is reached, wait until the main display appears again.
English
R Read Write Description Unit
0 x Firmware-Version Ex: «11» = FW 1.1
1 x Number of supported registers will give «29»
2 x Number of supported ags will give «0»
3 x Baudrate BPS
4 x Not used will give a «0»
5 x Type/ASN function will give «ALD1»
6 x Type/ASN function will give «B5FS»
7 x Type/ASN function
will give «00Ax»
x : 2 = Non MID
x : 3 = MID
8 x Type/ASN function will give «A00»
9 x HW Version Ex: «11» = FW 1.1
10 x Not used will give a «0»
11 x Serial number Serial number High
12 x Serial number Serial number Low
13 x Not used will give a «0»
14 x Status
«0» = no Problem
«1» = Problem with last communication request
15 x S-Bus timeout ms
16 x x S-Bus address
17 x Error ags 0 : No error / 1 : Error
18 x Not used will give «0»
19 x Energy direction register
0 = energy direction «consumption»
4 = energy direction «feeding back»
20 x Counter total «energy consumption»
10
-2
kWh. (multiplier 0,01)
Ex: 00912351= 009123,51 kWh
21 x Counter total «energy feeding back»
10
-2
kWh. (multiplier 0,01)
Ex: 00912351= 009123,51 kWh
22 x Not used will give «0»
23 x Not used will give «0»
24 x Eective voltage V (Ex: 230 = 230 V)
25 x Eective current
10
-1
A (multiplier 0,1)
Ex: 314 = 31,4 A
26 x
Eective active power
positive: Energy “ “ negative: Energy “ “
10
-2
kW (multiplier 0,01)
Ex: 1545 = 15,45 kW
27 x Eective reactive power
10
-2
kVAr (multiplier 0,01)
Ex: 1545 = 15,45 kVar
28 x cos phi
10
-2
(multiplier 0.01)
Ex: 67 = 0.67
Register
The following registers are available. The registers 4, 10, 11, 13, 18, 22 and 23 are not used and will give always the answer 0.
Method of operation
Energy is added as indicated by the arithmetic operator.
Positive output in the meter indicates that energy is being
supplied, while negative output indicates that energy is
being delivered.