6 VC Series Manual
Environment
Air surrounding the water heater, venng, and vent
terminaon(s) is used for combuson and must be free
of any compounds that cause corrosion of internal
components. These include corrosive compounds that
are found in aerosol sprays, detergents, bleaches,
cleaning solvents, oil based paints/ varnishes, and
refrigerants. The air in beauty shops, dry cleaning
stores, photo processing labs, and storage areas for pool
supplies oen contains these compounds. Therefore it
is recommended that outdoor models be used for these
locaons where possible.
The water heater, venng, and vent terminaon(s)
should not be installed in any areas where the air may
contain these corrosive compounds. If it is necessary for
a water heater to be located in areas which may contain
corrosive compounds, the following instrucons are
strongly recommended.
IMPORTANT CONSIDERATIONS FOR:
Indoor/Internal Water Heaters
DO NOT Install in areas where air for combuson
can be contaminated with chemicals.
Before installaon, consider where air has the
ability to travel within the building to the water
heater.
Where possible, install the water heater in a sealed
closet so that it is protected from the potenal of
contaminated indoor air.
Chemicals that are corrosive in nature should not
be stored or used near the water heater.
Outdoor/External Water Heaters and Vent
Terminaons of Indoor/Internal Water Heaters
Install the water heater as far away as possible
from exhaust vent hoods.
Install as far away as possible from air inlet vents.
Corrosive fumes may be released through these
vents when air is not being brought in through
them.
Chemicals that are corrosive in nature should not
be stored or used near the water heater or vent
terminaon.
Damage and repair due to corrosive compounds in the
air is not covered by warranty.
Consideraon of care for your water heater should
include evaluaon of water quality.
The water must be potable, free of corrosive chemicals,
sand, dirt, or other contaminates. It is up to the
installer to ensure the water does not contain corrosive
chemicals, or elements that can aect or damage the
heat exchanger. Water that contains chemicals
exceeding the levels below aect and damage the heat
exchanger. Replacement of the heat exchanger due to
water quality damage is not covered by the warranty.
Maximum Level
Total Hardness Up to 200 mg / L
Aluminum * Up to 0.2 mg / L
Chlorides * Up to 250 mg / L
Copper * Up to 1.0 mg / L
Dissolved Carbon Dioxide (CO2) Up to 15.0 mg / L or PPM
Iron * Up to 0.3 mg / L
Manganese * Up to 0.05 mg / L
pH * 6.5 to 8.5
TDS (Total Dissolved Solids) * Up to 500 mg / L
Zinc * Up to 5 mg / L
Determine Installaon Locaon
Water Quality
* Source: Part 143 Naonal Secondary Drinking Water
Regulaons
If you install this water heater in an area that is known
to have hard water or that causes scale build-up the
water must be treated and/or the heat exchanger
ushed regularly.
When scale build-up in the heat exchanger begins to
aect the performance of the water heater, a diagnosc
code “LC#” will display. Flush the heat exchanger to
prevent damage to it. Scale build up is caused by hard
water set at a high temperature.
Rinnai oers Southeastern Filtraon’s “ScaleCuer
Water Condioning System” that oers superior lime
scale prevenon and corrosion control by feeding a
blend of control compounds into the cold water
supply.
You must ensure that clearances will be met and that
the vent length will be within required limits. Consider
the installaon environment, water quality, and need
for freeze protecon. Requirements for the gas line,
water lines, electrical connecon, and condensate
disposal can be found in their respecve installaon
secons of this manual.
Part Number Descripon
103000038
Southeastern Filtratrion
ScaleCuer System 3/4” Feed
103000039
ScaleCuer Rell