Ideal 61-955 SureTrace Circuit Tracers Manuel utilisateur

Catégorie
Testeurs de réseau câblé
Taper
Manuel utilisateur
#61-955
#61-957
#61-959
SureTrace™ Circuit Tracers
Instruction Manual
Register your product and access more information at www.idealindustries.com
Page 2
Table of Contents
•฀ Safety฀Information ..................................................................................3
•฀ Introduction ............................................................................................4
•฀ Callouts฀of฀Features
•฀ Transmitter ............................................................................................................5
•฀ Receiver ................................................................................................................6
•฀ Test฀Lead฀Kit฀ ........................................................................................................ 8
•฀ Inductive฀Clamp฀with฀Battery฀Pack ........................................................................ 9
•฀ Theory฀of฀Operation
•฀ Signal฀Generation฀and฀Detection ..........................................................................9
•฀ Open฀versus฀Closed฀Circuits ................................................................................9
•฀ Remote฀Return฀Path ............................................................................................10
•฀ Applications
•฀ Pre-test฀Operation ............................................................................................... 11
•฀ Locating฀Circuit฀Breakers/Fuses .........................................................................12
•฀ Tracing฀Wires .....................................................................................................13
•฀ Tracing฀Low฀Voltage฀and฀Data฀Cables ................................................................13
•฀ Finding฀Opens ....................................................................................................14
•฀ Finding฀Shorts ....................................................................................................15
•฀ Sorting฀Bundled฀Wires ........................................................................................16
•฀ Tracing฀Underground .......................................................................................... 17
•฀ Inductive฀Clamp฀Uses ......................................................................................... 18
•฀ Battery฀Replacement ............................................................................. 20
•฀ Fuse฀Replacement ................................................................................ 21
•฀ Maintenance ......................................................................................... 22
•฀ Service฀and฀Replacement฀Parts ............................................................ 22
•฀ Specifications฀ ...................................................................................... 22
•฀ Warranty฀Statement .............................................................................. 24
Page 3
Read first: Safety Information
Understand฀and฀follow฀operating฀instructions฀carefully.฀Use฀the฀tracer฀only฀as฀specified฀in฀
this฀manual;฀otherwise,฀the฀protection฀provided฀by฀the฀tracer฀maybe฀impaired.฀฀
WARNING
To฀avoid฀electric฀shock,฀personal฀injury,฀or฀death,฀follow฀these฀instructions:
•฀ Before฀using฀or฀connecting฀the฀tracer,฀visually฀inspect฀to฀ensure฀the฀cases฀are฀not฀
cracked฀and฀back฀case฀is฀securely฀in฀place.฀Do฀not฀use฀if฀tracer฀appears฀damaged.฀
•฀ Before฀using฀the฀test฀leads,฀inspect฀carefully฀for฀damaged฀insulation,฀exposed฀metal฀or฀
cracked฀probes.฀Do฀not฀use฀leads฀if฀they฀appear฀damaged.฀
•฀ This฀product฀is฀only฀to฀be฀used฀by฀persons฀trained฀and฀experienced฀in฀working฀with฀high฀
voltages,฀and฀who฀are฀aware฀of฀the฀dangers฀and฀precautions฀to฀be฀taken฀when฀working฀
in฀such฀environments.฀Observe฀lockout฀and฀tagout฀protocols฀where฀appropriate.฀
•฀ Never฀use฀the฀tracer฀with฀a฀remote฀ground฀in฀patient฀care฀areas.฀Ground฀currents฀
generated฀by฀the฀tracer฀may฀create฀a฀shock฀hazard฀for฀electrically฀susceptible฀patients.
•฀ Always฀test฀the฀remote฀ground฀system฀to฀confirm฀that฀its฀resistance฀is฀less฀than฀100฀
ohms฀from฀remote฀ground฀to฀circuit฀neutral.
•฀ Always฀check฀circuits฀to฀verify฀that฀the฀hot,฀neutral฀and฀ground฀are฀wired฀correctly.
•฀ Do฀not฀use฀tracer฀if฀it฀operates฀abnormally฀as฀protection฀maybe฀impaired.
•฀ Do฀not฀use฀during฀electrical฀storms฀or฀in฀wet฀weather.
•฀ Do฀not฀use฀around฀explosive฀gas,฀dust,฀or฀vapor.
•฀ Do฀not฀apply฀more฀than฀the฀rated฀voltage฀to฀the฀tracer.
•฀ Do฀not฀use฀without฀the฀batteries฀and฀the฀back฀case฀properly฀installed.
•฀ Remove฀the฀test฀leads฀from฀the฀circuit฀prior฀to฀removing฀the฀battery฀cover.
•฀ Do฀not฀attempt฀to฀repair฀this฀unit฀as฀it฀has฀no฀user-serviceable฀parts.
•฀ Use฀only฀approved฀connecting฀leads.฀Do฀not฀use฀improvised฀connections฀that฀could฀
present฀a฀safety฀hazard.฀
•฀ Always฀ensure฀that฀test฀leads฀are฀secured฀so฀that฀they฀cannot฀be฀accidentally฀snagged฀
or฀tripped฀over.฀
•฀ When฀switching฀on฀the฀transmitter,฀always฀verify฀that฀the฀three฀indicator฀LEDs฀
illuminate฀briefly฀on฀power฀up.฀
•฀ The฀Line฀Energized฀feature฀provides฀an฀additional฀safety฀alert.฀If฀the฀฀฀฀indicator฀is฀not฀
illuminated,฀always฀independently฀confirm฀the฀status฀of฀the฀line฀to฀be฀absolutely฀sure.฀
CAUTION
To฀protect฀yourself,฀think฀“Safety฀First”:
•฀ Voltages฀exceeding฀30VAC฀or฀60VDC฀pose฀a฀shock฀hazard฀so฀use฀caution.
•฀ Use฀appropriate฀personal฀protective฀equipment฀such฀as฀safety฀glasses,฀face฀shields,฀
insulating฀gloves,฀insulating฀boots,฀and/or฀insulating฀mats.
•฀ Never฀ground฀yourself฀when฀working฀on฀an฀electrical฀circuit.
•฀ Always฀make฀the฀ground฀or฀neutral฀connection฀first,฀and฀remove฀last฀when฀using฀clip฀
leads or adaptor cord.
Page 4
Introduction
The฀SureTrace™฀Circuit฀Tracers฀are฀powerful,฀versatile,฀easy-to-use฀troubleshooting฀test฀
tools฀for฀finding฀breakers฀and฀hidden฀wire฀problems฀in฀residential/commercial/industrial฀
environments.฀These฀tracers฀work฀on฀closed฀(energized)฀and฀open฀(de-energized)฀circuits.฀฀
They฀identify฀circuit฀breakers,฀find฀opens฀and฀shorts,฀and฀trace฀wires฀behind฀walls.
The฀tracers฀are฀available฀in฀three฀configurations.฀Each฀kit฀contains฀the฀same฀transmitter
(TR-955)฀and฀test฀lead฀kit฀(TL-956).฀The฀955฀kit฀has฀a฀Receiver฀(RC-955)฀with฀an฀LED฀
display,฀and฀a฀Hard฀Case฀(C-955).฀The฀957฀kit฀has฀a฀Receiver฀(RC-959)฀with฀a฀super-bright฀
OLED฀display฀and฀a฀Hard฀Case฀(C-955).฀The฀959฀kit฀also฀has฀the฀high-end฀Receiver฀
(RC-959),฀adds฀an฀Inductive฀Clamp฀(IC-958)฀with฀Battery฀Pack฀(BP-958),฀and฀a฀larger฀
Hard฀Case฀(C-959).฀฀
Key Features
•฀ Numeric฀value฀and฀variable฀audible฀tone฀for฀easy-to-understand฀tracing
•฀ Super-bright฀display฀for฀easy-viewing
•฀ Peak฀detecting฀bar฀graph฀for฀instantaneous฀signal฀strength฀indication
•฀ Identifies฀breakers฀and฀fuses
•฀ Pinpoints฀opens฀and฀shorts
•฀ Traces฀wires฀behind฀walls
•฀ Can฀be฀used฀on฀de-energized/energized฀circuits฀from฀0-600V฀AC/DC
•฀ Will฀not฀affect฀GFCIs฀or฀other฀sensitive฀equipment฀on฀the฀line
•฀ Low฀battery฀indication
•฀ Cat฀III-600V฀safety฀rating
#61-955 #61-957 #61-959
Transmitter Callout Features
1. Output Jacks
฀ Non-polarized,฀standard฀banana฀plug฀type.
2. Power Indicator
฀ When฀the฀transmitter฀is฀On,฀the฀฀฀฀฀฀LED฀illuminates฀฀
฀ indicating฀that฀a฀signal฀is฀being฀produced.฀฀
3. Line Energized Indicator
฀ The฀transmitter฀continuously฀monitors฀the฀voltage฀
฀ across฀its฀output฀terminals.฀If฀greater฀than฀30฀volts฀
฀ AC฀or฀40฀volts฀DC฀is฀present,฀the฀฀฀฀LED฀indicator
฀ illuminates.฀The฀transmitter฀also฀communicates฀the฀
฀ line฀voltage฀state฀to฀the฀receiver.฀
4. Low Battery Indicator
฀ When฀the฀batteries฀approach฀the฀10%฀discharge฀
฀ point,฀the฀฀฀฀฀LED฀lights.฀Once฀the฀batteries฀
฀ are฀depleted,฀the฀LED฀flashes.฀At฀this฀point,฀the฀
฀ batteries฀are฀fully฀exhausted,฀and฀the฀unit฀forces฀
power down.
5. Power Button
฀ Depress฀the฀฀฀฀฀฀button฀to฀switch฀power฀on฀and฀enable฀
฀ the฀transmit฀function.฀Depress฀again฀to฀conserve฀battery฀
฀ power฀when฀not฀in฀use.
6. Operating Voltage Range
฀ Operates฀on฀energized/de-energized฀circuits฀from฀0฀to฀600V฀AC/DC.
7. Battery Compartment
฀ Holds฀(4)฀AA฀batteries.฀฀
8. Safety
฀ Rated฀for฀use฀in฀Cat฀III-600V฀environments.฀Incorporates฀a฀high-energy,฀fast-acting฀
protection fuse.
Additional฀Notes
•฀ The฀transmitter’s฀signal฀does฀not฀affect฀sensitive,฀electronic฀equipment฀on฀the฀circuit.฀฀
•฀ In฀a฀closed฀circuit,฀because฀the฀transmitter฀generates฀a฀small฀test฀current,฀its฀signal฀
can฀be฀detected฀upstream฀through฀the฀feeder฀panel฀and฀the฀distribution฀transformer.฀฀
The฀strength฀of฀the฀signal฀is฀reduced฀as฀it฀passes฀through฀the฀transformer฀in฀inverse฀
proportion฀to฀the฀turns฀ratio฀of฀the฀transformer.฀฀
•฀ Can฀be฀used฀on฀GFCI฀protected฀circuits.
TR-959
1
5
6
8
7
2
3
4
Page 5
Page 6
RC-955
1
4
5
3
2
6
7
Receiver Callout Features
1. Super Bright Display
฀ See฀next฀page฀for฀features.
2. Sensitivity Mode:
Depressthisbuttontoselect฀the฀mode฀of฀sensitivity*:฀
Mode฀ RC-955฀ RC-959฀ Antenna฀Strength
4฀ ฀ highest฀sensitivity
฀ (default฀mode)
3฀ ฀฀ ฀ high-medium
฀ sensitivity
2฀ ฀ medium-low฀
฀ sensitivity
1฀ ฀ lowest฀sensitivity฀
฀ for฀breakers
* See Additional Notes on next page for guidelines on
mode selection.
3. Audible Indication
฀ Depress฀this฀button฀to฀turn฀the฀sound฀On/Off.฀If฀On฀
฀ is฀selected,฀a฀variable฀pitch/tone฀is฀produced฀-฀
฀ directly฀proportional฀to฀the฀signal฀strength.
4. Battery Power
฀ On฀RC-955,฀depress฀this฀button฀at฀anytime฀to฀display฀the฀useful฀battery฀life฀
฀ remaining฀on฀the฀LED฀segments.฀On฀RC-959,฀battery฀life฀is฀continuously฀displayed
฀ on฀the฀main฀screen.฀Batteries฀must฀be฀replaced฀when฀฀฀฀฀฀฀฀฀฀displays฀on฀main฀screen฀of฀฀
฀ RC-955฀and฀฀฀฀฀฀฀฀appears฀on฀RC-959.
5. Power Button
฀ Depress฀to฀switch฀power฀on฀and฀enable฀operation.฀Depress฀again฀to฀conserve฀battery฀
฀ power฀when฀not฀in฀use.
6. Battery Compartment
฀ Holds฀(3)฀AA฀batteries.฀฀
7. Safety
฀ Rated฀for฀use฀in฀Cat฀III-600V฀environments.
Page 7
RC-955฀Display
1.฀ Bright,฀2-digit฀฀LED฀display.฀(180°฀Rotating)
2.฀ Displays฀the฀powered฀line฀status฀received฀
฀ from฀the฀transmitter.
3.฀ “0-99”฀numeric฀indication฀of฀
฀ signal฀strength.
4.฀ Indicator฀lights฀when฀audible฀tone
฀ is฀disabled.
5.฀ Peak฀detector฀shows฀instantaneous฀
฀ changes฀in฀signal฀strength.
RC-959฀Display
1.฀ Super-bright฀OLED฀display฀(90°฀rotating).
2.฀ Displays฀the฀powered฀line฀status฀received
฀ from฀the฀transmitter.
3.฀ Indicates฀On/Off฀status฀of฀the฀
฀ audible฀tone.
4.฀ Low฀Battery฀Indicator.฀Flashes
฀ when฀10%฀battery฀life฀remains.
5.฀ “0-99”฀numeric฀indication฀of฀signal฀strength.
6.฀ Displays฀the฀sensitivity฀setting.
7.฀ Peak฀detector฀shows฀instantaneous฀changes฀in฀signal฀strength.
Additional฀Notes
•฀ Sensitivity฀mode฀selection฀–฀general฀guidelines:
•฀ Start฀out฀at฀maximum฀sensitivity฀(฀฀฀฀฀฀฀฀)฀until฀the฀receiver฀finds฀the฀circuit฀under฀
test.฀If฀the฀receiver฀is฀too฀sensitive,฀then฀reduce฀the฀sensitivity฀using฀the฀฀฀฀฀฀฀
฀ ฀ button฀until฀the฀receiver’s฀display฀does฀not฀peg฀at฀“99”฀continuously.
•฀ Use฀฀฀฀฀฀฀฀฀฀฀mode฀for฀tracing:฀(a)฀in฀closed฀circuits฀while฀using฀the฀outlet฀plug฀
adapter฀(rather฀than฀the฀25’฀lead฀and฀a฀remote฀return฀path฀setup),฀(b)฀in฀open฀
circuits,฀(c)฀underground,฀(d)฀and฀anywhere฀else฀more฀signal฀detection฀is฀needed.฀฀
•฀ Use฀฀฀฀฀฀฀฀฀฀mode฀to฀reduce฀the฀level฀of฀sensitivity฀if฀the฀highest฀sensitivity฀range฀
has฀signal฀saturation฀(display฀is฀pegging฀at฀“99”฀continuously).
•฀ Use฀฀฀฀฀฀฀฀mode฀for฀tracing฀(a)฀in฀closed฀circuits฀while฀using฀the฀25’฀lead฀and฀a฀
remote฀return฀path,฀(b)฀and฀when฀previous฀mode฀has฀signal฀saturation฀of฀“99.”฀฀
•฀ Use฀Breaker฀฀฀฀฀฀฀฀mode฀for฀(a)฀identifying฀circuit฀breakers฀and฀fuses,฀(b)฀
pinpointing฀individual฀wires฀from฀a฀bundle,฀(c)฀and฀when฀previous฀mode฀has฀
signal saturation.
1
4
2
5 6 7
3
1 42 5
3
Page 8
•฀ Receiver฀Orientation
•฀ The฀indication฀of฀received฀signal฀intensity฀depends฀on฀how฀the฀receiver฀is฀pointed฀
in฀relation฀to฀the฀source฀of฀the฀signal.฀If฀the฀receiver฀is฀pointed฀away฀from฀the฀
signal฀source฀then฀there฀will฀be฀a฀low฀value฀indicated฀on฀the฀receiver.฀If฀the฀
receiver฀is฀rotated฀about฀the฀axis฀of฀main฀antenna฀sensitivity,฀the฀signal฀varies฀in฀
strength฀as฀the฀antenna฀is฀pointed฀at฀and฀then฀away฀from฀the฀circuit฀being฀traced.฀฀
•฀ Therefore,฀rotate฀the฀receiver฀over฀the฀wire฀being฀traced฀until฀the฀highest฀reading฀
is฀displayed.฀If฀during฀tracing,฀the฀signal฀is฀reduced,฀the฀wire฀may฀have฀changed฀
directions฀(e.g.฀from฀horizontal฀travel฀across฀a฀wall฀to฀vertical฀travel฀up฀a฀wall).฀฀
Rotate฀the฀receiver฀to฀find฀the฀strongest฀signal฀again.฀฀
•฀ Use฀the฀back฀of฀the฀receiver฀to฀sweep฀the฀wall฀or฀floor฀and฀determine฀the฀circuit’s฀
general฀location.฀Use฀the฀nose฀of฀the฀receiver฀to฀pinpoint฀its฀location.
•฀ Steel฀conduit฀attenuates฀(weakens)฀the฀signal฀radiating฀from฀the฀wires฀inside฀the฀
conduit.฀Aluminum฀conduit฀significantly฀attenuates฀the฀signal.฀So,฀the฀receiver฀
should฀be฀set฀at฀a฀higher฀sensitivity฀and฀may฀need฀to฀be฀placed฀closer฀to฀the฀
circuit฀to฀obtain฀a฀stronger฀signal฀detection.฀฀
Test Lead Kit(TL-956)
A฀complete฀test฀lead฀kit฀is฀supplied฀for฀use฀with฀the฀transmitter:฀฀
1.฀ TLOP-956฀Outlet฀Plug฀Adapter
for plugging into standard
฀ 120VAC฀outlets.
2.฀ TLBP-956฀(2)฀Blade฀Prongs฀
for inserting into a separate
฀ outlet฀with฀a฀remote฀neutral฀
฀ conductor฀as฀a฀return฀path.
3.฀ TLGP-956฀Ground฀Prong฀for฀
inserting into a separate outlet
฀ with฀remote฀ground฀conductor฀
฀ as฀a฀return฀path.
4.฀ TLAC-956฀(2)฀Alligator฀Clips฀
฀ for฀connecting฀directly฀to฀bare฀
wires and grounding points.
5.฀ TLA1-956฀(2)฀3’฀Lead฀Adapters฀for฀use฀with฀above฀clips฀and฀prongs฀to฀connect฀to฀bare฀
wires and grounding points.
6.฀ TLA2-956฀25’฀Lead฀Adapter฀for฀use฀with฀above฀clips฀and฀prongs฀to฀connect฀to฀remote฀
return฀paths.
123
46
5
Page 9
SureTrace™
1
2
4
5
367
Inductive Clamp (IC-958)฀with Battery Pack (BP-958) Callout Features
1.฀ 1”฀(25mm)฀Jaw฀Opening.
2.฀ Powerful฀coil฀induces฀a฀low฀voltage฀
signal onto a closed circuit.
3.฀ 6’฀cord฀attaches฀to฀the฀battery฀
฀ pack฀for฀power.
4.฀ Protective฀case.฀
5.฀ (8)฀C-cell฀batteries.
6.฀ Input฀jack฀for฀clamp฀cord.
7.฀ Hang฀mount฀for฀magnetic฀strap.฀
Magnetic Strap (not shown)
•฀ Hooks฀onto฀the฀battery฀pack.
•฀ Magnet฀attaches฀to฀metal฀cabinets,฀
฀ panels,฀electrical฀boxes,฀etc.
•฀ Velcro฀strap฀wraps฀around฀and฀hangs฀
฀ from฀non-magnetic฀objects.
Theory of Operation
The฀tracer฀consists฀of฀a฀transmitter฀and฀a฀receiver.฀The฀transmitter฀produces฀a฀unique฀
signal฀onto฀the฀circuit฀to฀be฀traced.฀The฀receiver฀detects฀this฀unique฀signal฀when฀placed฀in฀
the฀proper฀orientation฀to฀the฀wires฀being฀traced฀or฀breakers฀being฀identified.฀The฀receiver฀
provides฀a฀numeric฀value฀and฀a฀variable฀pitch/tone฀that฀increase฀as฀the฀signal฀becomes฀
stronger.
The฀transmitter฀sends฀a฀32฀kilohertz,฀fixed-amplitude,฀time-modulated฀signal฀that฀injects฀a฀
voltage฀onto฀the฀circuit฀to฀be฀traced,฀which฀then฀induces฀an฀electromagnetic฀field฀onto฀the฀
circuit.
Whether the circuit is open or closed greatly affects the strength of the electromagnetic
field.
In฀an฀open฀circuit,฀no฀current฀can฀flow,฀so฀the฀electromagnetic฀field฀produced฀is฀much฀
weaker.฀However,฀in฀a฀closed฀circuit,฀the฀injected฀voltage฀induces฀a฀current฀flow,฀which฀
produces฀a฀much฀stronger฀electromagnetic฀field.฀This฀is฀the฀optimal฀method฀for฀tracing฀as฀
this฀much฀stronger฀signal฀allows฀the฀receiver฀to฀detect฀it฀from฀a฀greater฀distance฀away฀from฀
the฀circuit฀being฀traced.฀฀
Here฀are฀some฀examples฀of฀Open/Closed฀Circuits:
Remote฀Return฀Path
Electromagnetic฀fields฀radiate฀counter-clockwise฀in฀relation฀to฀the฀current฀flow.฀For฀
example,฀current฀flows฀out฀on฀a฀hot฀conductor฀and฀returns฀on฀the฀neutral.฀This฀change฀in฀
opposite฀current฀flow฀also฀creates฀opposing฀magnetic฀fields.฀So,฀when฀these฀two฀opposing฀
conductors฀are฀close฀together,฀the฀two฀magnetic฀fields฀tend฀to฀cancel฀each฀other฀out.฀This฀
canceling฀effect฀diminishes฀the฀circuit’s฀ability฀to฀radiate฀the฀transmitter’s฀strong฀signal฀
making฀it฀more฀difficult฀for฀the฀receiver฀to฀detect฀the฀signal.฀฀
Page 10
Breaker
Energized
Breaker
Energized
Breaker
Energized
Light฀On
(Load)
Breaker
De-Energized
Closed฀Loop
Closed฀Loop Closed฀Loop
Closed฀Loop Open฀Loop
Open฀Loop Open฀Loop
Stronger
Stronger Stronger
Stronger Weaker
Weaker Weaker
Page 11
To฀avoid฀the฀canceling฀effect฀of฀the฀opposing฀magnetic฀fields฀and฀optimize฀the฀
transmitted฀signal,฀the฀conductor฀to฀be฀traced฀should฀be฀separated฀from฀the฀return฀
conductor฀by฀utilizing฀a฀remote฀return฀path.฀฀
The฀simplest฀method฀is฀to฀use฀the฀25’฀test฀lead฀to฀connect฀to฀a฀remote฀return฀path,฀such฀
as฀a฀neutral฀or฀ground฀from฀another฀circuit฀or฀a฀water฀pipe.฀When฀identifying฀breakers,฀
the฀hot฀and฀neutral฀are฀already฀separated฀at฀the฀electrical฀panel฀so฀the฀use฀of฀the฀AC฀
outlet adapter is sufficient.
If฀unsure฀that฀the฀remote฀return฀path฀chosen฀is฀a฀good฀one,฀use฀a฀multimeter฀to฀measure฀
the฀resistance฀between฀the฀circuit฀neutral฀and฀the฀remote฀return฀path.฀If฀>100Ω,฀a฀
different฀return฀path฀should฀be฀selected.
Applications
Pre-test Operation
Prior฀to฀finding฀a฀breaker฀or฀tracing฀a฀circuit,฀it฀is฀good฀practice฀to฀test฀the฀receiver฀by฀
holding฀it฀near฀the฀powered฀transmitter฀or฀inductive฀clamp.฀A฀numeric฀indication฀of฀“99”฀
and฀strong฀audible฀sound฀ensures฀that฀it฀is฀working฀properly.฀฀
Weak฀Signal฀Setup
Signals฀Cancel
Strong฀Signal฀Setup
No฀Signal฀Canceling Strong฀Signal฀Setup
No฀Signal฀Canceling
Circuit
under
test
Separate฀Circuit
Water฀Pipe
Page 12
Locating Circuit Breakers and Fuses
Applications฀include฀identifying฀the฀breaker฀that฀protects฀the฀circuit฀under฀test,฀finding฀the฀
correct฀breaker฀to฀de-energize฀the฀circuit,฀and฀labeling฀a฀breaker฀panel.
1)฀฀ Connect฀the฀transmitter฀to฀the฀circuit฀that฀needs฀to฀be฀identified฀and฀power฀it฀on.฀฀
฀ The฀procedure฀is฀the฀same฀whether฀the฀circuit฀is฀energized฀or฀de-energized.฀But,฀a฀
฀ much฀stronger฀signal฀is฀produced฀using฀an฀energized฀(closed)฀circuit.
2)฀฀ Turn฀on฀the฀receiver฀and฀go฀to฀the฀panel.฀฀
a)฀฀ If฀more฀than฀one฀panel฀exists,฀set฀the฀receiver฀to฀฀฀฀฀฀฀฀฀฀mode฀and฀touch฀the฀nose฀
to฀each฀panel฀cover฀until฀the฀panel฀with฀the฀strongest฀signal฀is฀identified.฀฀
b)฀ If฀the฀receiver฀is฀detecting฀more฀than฀one฀panel฀with฀a฀strong฀signal,฀reduce฀the฀
sensitivity฀range฀and฀repeat฀the฀step฀above.
3)฀฀ Open฀the฀panel฀cover,฀set฀the฀receiver฀to฀Breaker฀฀฀฀฀฀฀mode.฀The฀receiver฀should฀be฀
positioned฀on฀its฀side฀to฀orientate฀the฀antenna฀properly.฀
4)฀฀ Slide฀the฀nose฀of฀the฀receiver฀down฀each฀breaker฀in฀the฀panel.฀The฀breaker฀with฀the฀
highest฀numeric฀reading฀is฀the฀correct฀breaker.฀฀฀
฀ If฀two฀or฀more฀breakers฀have฀the฀same฀numeric฀values,฀tip฀the฀nose฀of฀the฀
receiver฀up฀and฀then฀down฀at฀45º฀angles฀and฀note฀the฀numeric฀values฀on฀each฀
of฀the฀questionable฀breakers.฀Only฀the฀correct฀breaker฀will฀show฀a฀strong฀signal฀
in฀all฀positions.฀Or,฀pull฀the฀panel฀cover,฀and฀place฀the฀nose฀on฀each฀of฀the฀
individual฀hot฀wires฀for฀a฀more฀certain฀determination.
5)฀฀ When฀the฀correct฀breaker฀is฀tripped฀(opened),฀the฀signal฀will฀drop฀significantly.฀And,฀
the฀฀฀฀฀will฀disappear฀from฀the฀receiver’s฀display.฀The฀฀฀฀฀LED฀on฀the฀transmitter฀will฀
also turn off.
Tracing Wires
Applications฀include฀finding฀the฀locations฀of฀cable฀runs฀and฀identifying฀other฀devices฀and฀
loads฀on฀the฀circuit.
1)฀฀ Connect฀the฀transmitter฀to฀the฀circuit฀to฀be฀traced฀and฀power฀it฀on.
a)฀ For฀optimal฀tracing,฀leave฀the฀circuit฀energized฀to฀create฀a฀closed฀loop.฀
b)฀฀ If฀the฀circuit฀is฀de-energized,฀then฀connect฀transmitter฀to฀the฀neutral฀and฀ground฀
conductors to create a closed loop.
2)฀฀ Turn฀on฀the฀receiver฀and฀use฀the฀default฀maximum฀sensitivity฀(฀฀฀฀฀฀฀฀฀).
3)฀฀ Starting฀several฀feet฀from฀the฀transmitter,฀use฀a฀sweeping฀motion฀and฀the฀back฀of฀the฀
receiver฀to฀find฀the฀strongest฀signal฀location฀behind฀the฀wall,฀above฀the฀ceiling,฀or฀under฀
the฀floor.฀฀
a)฀฀ If฀the฀signal฀is฀too฀strong,฀reduce฀the฀sensitivity฀range.฀฀
b)฀฀ Ifthesignalistooweak,utilizea฀remotereturnpathforthetransmitter.Then,reduce
thesensitivityrangeonthereceiverandrepeatstep#3.
4)฀฀ Continue฀following฀the฀highest฀reading฀until฀the฀end฀of฀the฀circuit฀is฀found.฀฀
Tracing Low Voltage and Data Cable
Applications฀include฀tracing฀
coax,฀twisted฀pair,฀Cat฀5,฀alarm฀
and฀telephone฀wire.
Follow฀the฀instructions฀for฀
Tracing฀Wires฀behind฀walls฀using฀
the฀de-energized฀method฀and฀a฀
remote฀ground฀for฀a฀return฀path.฀
Page 13
Stronger฀Signal
Connect฀to
Ground
(Shield฀of฀Coax)
If฀possible,฀ground
the฀far฀end฀of฀the฀
cable฀shield.
OR
Weaker฀Signal
Finding Opens
Applications฀include฀locating฀dead฀circuits,฀finding฀the฀source฀of฀an฀open฀(broken฀point)฀in฀
a฀hot/neutral/ground฀conductor,฀and฀determining฀the฀end฀of฀a฀circuit฀run.
1)฀฀ Connect฀the฀transmitter฀to฀the฀open฀circuit฀and฀power฀it฀on.
2)฀฀ Turn฀on฀the฀receiver฀and฀use฀the฀default฀maximum฀sensitivity.
3)฀฀ Starting฀several฀feet฀from฀the฀transmitter,฀use฀a฀sweeping฀motion฀and฀the฀back฀of฀the฀
receiver฀to฀find฀the฀strongest฀signal฀location฀behind฀the฀wall,฀above฀the฀ceiling฀or฀
under฀the฀floor.฀฀
a)฀฀ If฀the฀signal฀is฀too฀strong,฀reduce฀the฀sensitivity฀range.฀฀
b)฀฀ Ifthesignalistooweak,connectoneleadofthetransmitterintotheopenconductor
andconnecttheotherleadto฀a฀remotereturnpath.Then,repeatstep#3.
4)฀฀ Continue฀following฀the฀highest฀reading฀until฀the฀signal฀starts฀to฀fall฀off.฀This฀is฀the฀
location฀of฀the฀open.฀Reduce฀the฀sensitivity฀range฀and฀use฀the฀nose฀of฀the฀receiver฀to฀
pinpoint฀the฀open฀on฀the฀circuit.฀
If฀the฀open฀is฀not฀found฀after฀tracing฀the฀length฀of฀the฀run,฀the฀conductor฀may฀be฀capacitively฀
coupled.฀This฀condition฀causes฀a฀signal฀bleed-off฀onto฀the฀other฀adjacent฀conductors.฀To฀
remove฀this฀effect,฀ground฀the฀adjacent฀conductors฀and฀minimize฀the฀distance฀between฀the฀
transmitter฀connection฀and฀the฀open.฀
Page 14
Separate฀Circuit
Finding Shorts
Applications฀include฀determining฀causes฀of฀breakers฀tripping,฀fuses฀blowing,฀and฀current฀
leaking฀on฀the฀ground฀conductor.฀The฀tracer฀locates฀the฀origin฀of฀the฀ground฀fault฀or฀dead-
short฀in฀these฀circuits.฀฀
1)฀฀ Connect฀the฀transmitter฀to฀the฀shorted฀circuit฀and฀power฀it฀on.
a)฀ One฀lead฀should฀be฀connected฀to฀the฀faulted฀conductor฀and฀the฀other฀lead฀to฀
ground.
b)฀ If฀the฀ground฀fault฀is฀in฀metallic฀conduit,฀then฀the฀conduit฀is฀the฀ground.
c)฀ If฀possible,฀ground฀the฀adjacent฀conductors.
2)฀฀ Turn฀on฀the฀receiver฀and฀use฀the฀default฀maximum฀sensitivity฀(฀฀฀฀฀฀฀฀฀฀).
3)฀฀ Starting฀several฀feet฀from฀the฀transmitter,฀use฀a฀sweeping฀motion฀and฀the฀back฀of฀the฀
receiver฀to฀find฀the฀strongest฀signal฀location฀behind฀the฀wall,฀above฀the฀ceiling,฀or฀
under฀the฀floor.฀฀
c)฀฀ If฀the฀signal฀is฀too฀strong,฀reduce฀the฀sensitivity฀range.฀฀
d)฀ Ifthesignalistooweak,connectoneleadofthetransmitterintotheopenconductor
andconnecttheotherleadto฀a฀remotereturnpath.Then,repeatstep#3.
4)฀฀ Continue฀following฀the฀highest฀reading฀until฀the฀signal฀starts฀weakening.฀This฀is฀the฀
point฀of฀the฀fault฀as฀the฀signal฀flows฀to฀ground฀instead฀of฀continuing฀strongly฀down฀
the฀hot฀conductor.฀Reduce฀the฀sensitivity฀range฀and฀use฀the฀nose฀of฀the฀receiver฀to฀
pinpoint฀the฀source฀of฀the฀fault.฀฀
Page 15
Tripped
Circuit
Breaker
Stronger฀Signal Weaker฀Signal
Short฀
to฀Ground
Breaker
Panel
Page 16
Sorting Bundled Wires
Applications฀include฀identifying฀a฀specific฀circuit฀amongst฀several฀circuits฀in฀a฀filled฀
conduit,฀sorting฀wires฀in฀a฀wire฀harness,฀identifying฀coax฀cable฀and฀twisted฀pair฀cable฀in฀a฀
termination฀box.
1)฀฀ Connect฀the฀transmitter฀to฀the฀circuit฀to฀be฀traced฀and฀power฀it฀on.
a)฀฀ Clip฀one฀test฀lead฀to฀the฀known฀end฀of฀the฀wire฀to฀be฀traced฀or฀identified.
b)฀฀ Clip฀the฀other฀test฀lead฀to฀a฀remote฀return฀path.
2)฀฀ Turn฀on฀the฀receiver฀and฀set฀it฀to฀the฀least฀sensitivity฀(฀฀฀฀).
3)฀฀ Go฀to฀the฀other฀end฀of฀the฀wire฀run฀and฀sort฀out฀the฀individual฀wire฀using฀the฀nose฀of฀
the฀receiver.฀฀
a)฀฀ If฀the฀signal฀is฀too฀strong,฀separate฀the฀wires฀more฀from฀the฀bundle฀when฀testing.฀฀
b)฀฀ If฀the฀signal฀is฀too฀weak,฀then฀increase฀the฀sensitivity฀range฀on฀the฀receiver฀and฀
repeat฀step฀#3.
4)฀฀ Continue฀sorting฀until฀the฀wire฀with฀the฀highest฀reading฀is฀identified.฀฀฀฀
Page 17
Tracing Underground
These฀circuit฀tracers฀are฀not฀underground฀cable฀locators.฀But,฀in฀some฀environments฀they฀
can฀be฀used฀to฀trace฀buried฀cables,฀conduit,฀or฀metal฀pipe.
1)฀฀ Connect฀the฀transmitter฀to฀the฀circuit฀to฀be฀traced฀and฀power฀it฀on.
a)฀ If฀possible,฀create฀a฀closed฀circuit฀by฀grounding฀the฀other฀end.
b)฀฀ If฀possible,฀ground฀the฀adjacent฀conductors฀to฀eliminate฀capacitive-coupling฀
effects฀that฀can฀cause฀signal฀bleed-over.
c)฀฀ Utilize฀a฀remote฀return฀path฀to฀maximize฀the฀signal฀produced.
2)฀฀ Turn฀on฀the฀receiver฀and฀use฀the฀maximum฀sensitivity฀default฀(฀฀฀฀฀฀฀฀฀).
3)฀฀ Use฀a฀sweeping฀motion฀and฀the฀back฀of฀the฀receiver฀to฀find฀the฀strongest฀signal฀
underground.
a)฀฀ If฀the฀signal฀is฀too฀strong,฀reduce฀the฀sensitivity฀range.฀฀
b)฀฀ If฀the฀signal฀is฀too฀weak,฀then฀check฀the฀quality฀of฀the฀ground฀connections฀
(<100Ω)฀and฀repeat฀step฀#3.
4)฀Continue฀following฀the฀highest฀reading฀until฀the฀end฀of฀the฀circuit฀is฀found.฀฀
OR
Service
Panel
Outside
Receptacle
Keep฀two฀
paths฀separate
from฀each฀other
25฀Feet
Distance
Connect฀to
Ground฀Rod
Page 18
Inductive Clamp Applications
WARNING: ฀The฀clamp฀does฀not฀have฀any฀indicators฀to฀sense฀if฀a฀circuit฀is฀
energized.฀The฀line฀energized฀feature฀(฀฀฀฀฀)฀on฀the฀receiver฀only฀works฀with฀the฀transmitter฀
(TR-955).฀฀
The฀inductive฀clamp฀is฀powered฀solely฀by฀the฀battery฀pack.฀It฀generates฀its฀own฀specific,฀
time฀modulated฀signal,฀and฀by฀transformer฀action,฀couples฀that฀signal฀onto฀the฀energized฀or฀
de-energized฀circuit฀to฀be฀traced.฀฀
Always฀disconnect฀the฀battery฀pack฀from฀the฀clamp฀when฀not฀in฀use฀to฀conserve฀battery฀
power.
For฀the฀clamp฀to฀propagate฀a฀signal฀onto฀the฀circuit฀to฀be฀traced,฀the฀circuit฀must฀be฀closed฀
at฀the฀end฀where฀the฀clamp฀is฀applied,฀at฀a฀minimum.฀To฀maximize฀the฀signal฀produced,฀
both฀ends฀of฀the฀circuit฀should฀be฀closed฀to฀create฀a฀complete฀loop.฀Refer฀to฀the฀diagrams฀
for proper setup.
Three฀typical฀applications฀where฀the฀inductive฀clamp฀may฀be฀used฀in฀replace฀of฀the฀
transmitter:
•฀ Identifying฀downstream฀loads฀from฀a฀breaker
•฀ Tracing฀conduit
•฀ Tracing฀industrial฀control฀circuits
Page 19
Identifying฀downstream฀loads฀from฀a฀breaker.
1)฀฀ Remove฀the฀panel฀cover฀and฀clamp฀around฀the฀hot฀wire฀of฀the฀energized฀(closed)฀circuit.
•฀ To฀maximize฀the฀signal,฀close฀the฀far฀end฀of฀the฀circuit฀by฀plugging฀in฀and฀turning฀
฀ ฀ on฀a฀work฀light฀or฀other฀load฀into฀the฀furthest฀outlet;฀hence,฀making฀a฀complete฀
loop.
2)฀฀ Hang฀the฀battery฀pack฀onto฀the฀panel฀with฀the฀magnetic฀strap.
3)฀฀ Plug฀the฀clamp฀into฀the฀battery฀pack.
4)฀฀ Set฀the฀receiver฀to฀the฀highest฀sensitivity฀mode฀(฀฀฀฀฀฀฀฀)฀and฀trace฀the฀circuit฀to฀the฀furthest฀
outlet฀while฀identifying฀all฀outlets฀and฀loads฀connected฀to฀the฀circuit.฀If฀the฀Receiver฀is฀
฀ saturated,฀reduce฀the฀sensitivity฀range.
Tracing฀Conduit.
1)฀฀ Clamp฀around฀the฀metallic฀conduit฀to฀be฀traced.฀If฀possible,฀ground฀the฀far฀end฀of฀the฀
conduit฀to฀close฀the฀loop.฀This฀can฀be฀created฀using฀the฀25’฀lead฀and฀alligator฀clips฀to฀clip฀
onto฀the฀end฀of฀the฀conduit฀or฀electrical฀box฀with฀one฀clip฀and฀a฀remote฀neutral฀or฀water฀
pipe฀with฀the฀other฀alligator฀clip.
2)฀฀ Hang฀the฀battery฀pack฀onto฀the฀panel฀or฀conduit฀with฀the฀magnetic฀strap.
Weaker฀Signal฀-฀Open
Stronger฀Signal฀-฀Closed
Light฀On
(Load)
Breaker
Energized
Breaker
Energized
Page 20
3)฀฀ Plug฀the฀clamp฀into฀the฀battery฀pack.
4)฀฀ Set฀the฀receiver฀to฀the฀highest฀sensitivity฀(฀฀฀฀฀฀฀฀)฀mode฀and฀trace฀the฀conduit.฀If฀the฀
Receiver฀is฀saturated,฀reduce฀the฀sensitivity฀range.
Tracing฀industrial฀control฀circuits.
1)฀฀ Ensure฀that฀the฀circuit฀is฀energized฀(closed฀at฀the฀panel)฀at฀a฀minimum.฀To฀maximize฀the฀
signal,฀close฀the฀other฀end฀of฀the฀circuit฀by฀turning฀on฀a฀load,฀such฀as฀a฀motor฀or฀pump.
2)฀฀ Clamp฀around฀the฀hot฀wire฀of฀this฀energized฀(closed)฀circuit.
3)฀฀ Use฀the฀magnetic฀strap฀to฀hang฀the฀battery฀pack฀onto฀the฀panel฀or the฀motor฀control฀
cabinet.
4)฀฀ Plug฀the฀clamp฀into฀the฀battery฀pack.
5)฀฀ Set฀the฀receiver฀to฀the฀highest฀sensitivity฀(฀฀฀฀฀฀฀฀)฀mode฀and฀trace฀the฀circuit฀to฀the฀other฀
end.฀If฀the฀receiver฀is฀saturated,฀reduce฀the฀sensitivity฀mode.
Battery Replacement
Note:฀฀Use฀only฀good฀quality฀alkaline฀batteries฀for฀maximimum฀operating฀life.฀
Always฀replace฀with฀a฀complete฀set฀of฀new฀batteries฀of฀the฀same฀type.฀
Remove฀batteries฀as฀soon฀as฀they฀become฀exhausted฀to฀avoid฀
damage฀due฀to฀leakage.
Transmitter:
Ensure฀that฀the฀test฀leads฀are฀removed฀from฀the฀output฀
jacks฀and฀the฀circuit฀under฀test.
1)฀฀ Remove฀the฀battery฀cap฀by฀loosening฀the฀screw.
2)฀฀ Replace฀batteries฀with฀(4)฀new฀AA฀batteries.
3)฀฀ Re-fit฀cap฀and฀re-tighten฀the฀screw.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Ideal 61-955 SureTrace Circuit Tracers Manuel utilisateur

Catégorie
Testeurs de réseau câblé
Taper
Manuel utilisateur