Legrand LTUB Series Lighting Integrator Panel Tub Enclosures Guide d'installation

Taper
Guide d'installation
Wattstopper
®
Lighting Integrator Panel Enclosures
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 24866 – 11/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: LTUB
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
DESCRIPTION AND OPERATION
The LTUB series 8/24/48 is the standard enclosure for a Wattstopper
Lighting Integrator (LI) Lighting Control Panel.
A complete panel assembly includes one each of:
1. Enclosure (LTUB series).
2. Interior with relays or contactors.
3. Power Supply (HPSM115/277).
4. Cover to match the Enclosure (LCVR series).
Separating these four components simplifies installation. The enclosure
can be mounted early to allow conduit installation and rough-in wiring. The
interior, which includes the relays or contactors and the termination blocks,
simply slides into the enclosure. The lighting circuits and low voltage control
wiring can then be terminated in the interior. Finally, the cover can be
screwed into place to complete the panel installation.
Environment
Mount in indoor area
32° to 131°F (0° to 50°C)
10 to 95% relative humidity, non-condensing
15 volts/meter, 10 KHz to 2 GHz maximum RFI
Stationary applications
If you have any questions, call our Service Team at: 888-852-2778.
/RZYROWDJH
VHFWLRQ
/LQHYROWDJHVHFWLRQ



/RZYROWDJHVHFWLRQ
/LQHYROWDJHVHFWLRQ
/LQHYROWDJHVHFWLRQ
/78%
/78%





 

/RZYROWDJHVHFWLRQ
/LQHYROWDJHVHFWLRQ
/LQHYROWDJHVHFWLRQ

/78%










Figure 1 - Line Voltage and Low Voltage Compartments
IMPORTANT
Shaded areas are for line voltage conduit entry only.
Non-shaded areas are for Class 2 conduit entry only.
800.879.8585
www.legrand.us/wattstopper
No. 24866 – 11/16 rev. 1
© Copyright 2016 Legrand All Rights Reserved.
© Copyright 2016 Tous droits réservés Legrand.
© Copyright 2016 Legrand Todos los derechos reservados.
Wattstopper warranties its products to be free
of defects in materials and workmanship for a
period of five (5) years. There are no obligations
or liabilities on the part of Wattstopper for
consequential damages arising out of, or in
connection with, the use or performance of this
product or other indirect damages with respect
to loss of property, revenue or profit, or cost of
removal, installation or reinstallation.
Wattstopper garantit que ses produits sont
exempts de défauts de matériaux et de fabrication
pour une période de cinq (5) ans. Wattstopper
ne peut être tenu responsable de tout dommage
consécutif causé par ou lié à l’utilisation ou
à la performance de ce produit ou tout autre
dommage indirect lié à la perte de propriété, de
revenus, ou de profits, ou aux coûts d’enlèvement,
d’installation ou de réinstallation.
Wattstopper garantiza que sus productos
están libres de defectos en materiales y mano
de obra por un período de cinco (5) años. No
existen obligaciones ni responsabilidades por
parte de Wattstopper por daños consecuentes
que se deriven o estén relacionados con el
uso o el rendimiento de este producto u otros
daños indirectos con respecto a la pérdida
de propiedad, renta o ganancias, o al costo
de extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
MOUNTING
The enclosure should be level, plumb and rigidly installed with hardware sufficient
to hold 100 lbs. (46 kg) minimum. See Figure 2 and the photos provided for a
typical mounting configuration. The product label should be in an upright, readable
position.
Multiple panels:
For surface mounting: Allow a minimum of 0.25” between adjacent
enclosures for shoebox cover clearance.
For ush mounting: The front flange should be flush with the finished wall
surface. Allow a minimum of 1.75” between adjacent enclosures for butt
alignment of flush covers.
Dimensions are shown in the table below. Be sure to allow adequate surface
spacing for the covers.
WIRING
Route line voltage wiring and Class 2 low voltage wiring from switches, sensors,
photocells, and dataline (if used) through the top, bottom, or sides of the enclosure
as shown in Figure 1.
Low voltage wire entry should be confined to the areas shown in white.
Line voltage wire entry should be confined to the areas shown in grey.
The Enclosure should be be level,
plumb, and rigidly mounted
Route wiring through the top, bottom, or sides
WARNING: MAKE SURE ALL POWER
IS OFF BEFORE WIRING. DO NOT
ENERGIZE WIRING UNTIL THE UNIT
IS FULLY ASSEMBLED. CONFORM TO ALL
APPLICABLE BUILDING AND ELECTRICAL
CODES WHEN MOUNTING THE ENCLOSURE.
2" TYP.
2
1
2" NIPPLE
CIRCUIT BREAKER PANEL
LINE-VOLTAGE WIRING FROM
SWITCHED LIGHTING CIRCUITS
LINE-VOLTAGE WIRING FROM
CIRCUIT BREAKER PANEL
LOW-VOLTAGE WIRING FROM SWITCHES,
SENSORS, PHOTOCELLS AND/OR DATALINE
Figure 2 – Typical Mounting Conguration
DIMENSIONS
LTUB8y Enclosure, LI panel
8 relay capacity
15.08” x 16.5” x 4.5”
LTUB24y Enclosure, LI panel
24 relay capacity
31.38” x 23.88” x 4.5”
LTUB48y Enclosure, LI panel
48 relay capacity
43.88 “x 23.88” x 4.5”
LCVR8S NEMA 1 surface cover, LI panel
8 relay capacity
5.36” x 16.84” x .75”
LCVR8F NEMA 1 flush cover, LI panel
8 relay capacity
17.06” x 18.48”
LCVR24S NEMA 1 surface cover, LI panel
24 relay capacity
31.66” x 24.16” x .75”
LCVR24F NEMA 1 flush cover, LI panel
24 relay capacity
33.35” x 25.85”
LCVR48S NEMA 1 surface cover, LI panel
48 relay capacity
44.90” x 24.19” x .75”
LCVR48F NEMA 1 flush cover, LI panel
48 relay capacity
45.85” x 25.85”
x = S (surface mount), F (flush mount)
y = blank (NEMA 1 (default)), S3R (NEMA 3R - not available for LTUB8), S4 (NEMA 4)
Note: Photos and dimensions given for NEMA1 Enclosures only.