LG PRARH1 Guide d'installation

Catégorie
Climatiseurs split-system
Taper
Guide d'installation
www.lg.com
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
TYPE : Auxiliary Heater Relay Kit (for Multi V Product)
MODEL : PRARH1
P/NO : MFL65920004
ENGLISH FRANÇAIS
ESPAÑOL
2 Auxiliary Heater Relay Kit
IMPORTANT!
CAUTION
: Improper installation, adjustment, alteration, service or maintenance can void the warranty.
The weight of the condensing unit requires caution and proper handling procedures when lifting
or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Safety Precautions
• Always wear safety eye wear and work gloves when installing equipment.
• Never assume electrical power is disconnected. Check with meter and equipment.
NOTE TO INSTALLING DEALER: The Owners Instructions and Warranty are to be given to the owner
or prominently displayed near the indoor Furnace/Air Handler Unit.
When wiring:
Electrical shock can cause severe personal injury or death. Only a qualified,
experienced electrician should attempt to wire this system.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When installing...
... in a wall: Make sure the wall is strong enough to hold the unit's weight.
It may be necessary to construct a strong wood or metal frame to provide added support.
... in a room: Properly insulate any tubing run inside a room to prevent "sweating" that can cause
dripping and water damage to wall and floors.
When servicing
• Turn the power OFF at the main power box(mains) before opening the unit to check or repair
electrical parts and wiring.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have
been left inside the unit being serviced.
WARNING
WARNING
• Installation must adapt with local building codes or with the Nation al Electrical code NFPA 70/ANSI C1-1993
(or current edition ) along with Canadian Electrical Code Part1 CSA C.22.1
• The information contained in the manual is intended for use by a qualified service technician familiar with safety
procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property
damage, personal injury and/or death.
Please read this instruction sheet completely before installing the product.
This air conditioning system meets strict safety and operating standards. As the installer or service person,
it is an important part of your job to install or service the system so it operates safely and efficiently.
Installation Manual 3
Auxiliary Heater Relay Kit INSTALLATION MANUAL
TABLE OF CONTENTS
1. Safety Precautions ............................................................................................................4
2. Included Items....................................................................................................................5
3. Assembly Diagram ............................................................................................................6
4. Electrical Wiring...............................................................................................................12
5. Installer Setting................................................................................................................13
6. Control map of AUX HEATER.........................................................................................15
7. Troubleshooting Guide ...................................................................................................17
4 Auxiliary Heater Relay Kit
To prevent injury to the user or other people and property damage, the following instructions
must be followed.
n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness
is classified by the following indications.
1. Electric works should be carried out according to ‘The technology requirement on the elec-
tric installation’, The wiring standard and this manual by a qualified personnel.
2.
If the installation is not complete, electric shock or fire may occur, or death or injury can be caused.
3. If the capacity of the power circuit is insufficient or its installation was not done completely,
this may cause electric shock, fire or etc..
4. If the installation was done by a user, there may be incompleteness, which may cause elec-
tric shock, fire, injury and death.
5. When operating the machine (applying power to the machine), do not carry out any electric
work and do not put hand or finger into it. This may cause electric shock, injury and death.
6. Use only UL1996 approved heater.
n Meanings of symbols used in this manual are as shown below.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage.
Be sure not to do.
Be sure to follow the instruction.
WARNING
1. Before installation, read this manual and carry out the works according to it.
2. Before installation, be sure to check all the included items. (However, be sure to use all
kinds of certified products when purchasing the items other than those provided by LG at
your local store.)
3. Be sure to carry out the earth work. (However, do not connect the unit to gas pipe, water
pipe, a lightning rod and a phone earth line. In addition, if the earth was not completely
done, this may cause electric shock and fire.)
CAUTION
1. Safety Precautions
Safety Precautions
Installation Manual 5
ENGLISH
Item Auxliary Heater Relay Kit Screw Insulation Installation Manual
Q’ty 1 2 2 1
Model
2. Included Items
• PRARH1 applies to High Static Duct, Low Static Duct, 1Way CST, 2Way CST, 4Way CST and Ceiling
Suspended types.
(Unit : inch)
Figure
PRARH1
Included Items
2-19/32
1-13/32
7-9/32
6-23/32
2-19/32
2-7/32
1-7/16
3-13/32
Aux heater
communication lines
6 Auxiliary Heater Relay Kit
Assembly Diagram
Check the distance between PRARH1 and a control box
when connecting anchor bolts.
9/16
Auxiliary Heater communication lines
(under AC24V,over AWG24)
These wires should not make
contact with high voltage lines.
To indoor unit PCB
(CN-PTC)
AB AB
3. Assembly Diagram
n High Static Duct
Wiring
Note: While connecting the PRARH1, attach insulation at the rear of the control box cover
where it receives screws as shown in Fig. A.
Please clean up the remaining wires after installation.
Step1. Open control box cover. Step2. Assemble PRARH1 with control box cover.
Step3. Open the cover of PRARH1 and connect wires. Step4. Assemble control box cover.
Assembly Diagram - PRARH1
(Unit : inch)
CAUTION
Assembly Diagram
Installation Manual 7
ENGLISH
n Low Static Duct
Check the distance between PRARH1 and the top of model
when connecting anchor bolts.
4 13/32
Auxiliary Heater communication lines
(under AC24V,over AWG24)
These wires should not make
contact with high voltage lines.
To indoor unit PCB
(CN-PTC)
AB AB
Wiring
Fig. A
Control box cover
screw
Insulation
Note: While connecting the PRARH1, attach insulation at the rear of the control box cover
where it receives screws as shown in Fig. A.
Please clean up the remaining wires after installation.
Aux heater communication lines
Step1. Open control box cover. Step2. Assemble PRARH1 with control box cover.
Step3. Open the cover of PRARH1 and connect wires. Step4. Assemble control box cover.
(Unit : inch)
CAUTION
8 Auxiliary Heater Relay Kit
n 1 Way CST
Auxiliary Heater communication lines
(under AC24V,over AWG24)
These wires should not make
contact with high voltage lines.
To indoor unit PCB
(CN-PTC)
AB AB
Wiring
Assembly Diagram
Aux heater
communication
lines
Step1. Open front panel. Step2. Assemble PRARH1 with cabinet.
Step3. Open the cover of PRARH1 and connect wires. Step4. Assemble control box cover and front panel.
Fig. A
Control box cover
screw
Insulation
Note: While connecting the PRARH1, attach insulation at the rear of the control box cover
where it receives screws as shown in Fig. A.
Please clean up the remaining wires after installation.
Installation Manual 9
ENGLISH
n 2 Way CST
Auxiliary Heater communication lines
(under AC24V,over AWG24)
These wires should not make
contact with high voltage lines.
To indoor unit PCB
(CN-PTC)
AB AB
Wiring
Assembly Diagram
Aux heater
communication
lines
Step1. Open front panel. Step2. Assemble PRARH1 with cabinet.
Step3. Open the cover of PRARH1 and connect wires. Step4. Assemble control box cover and front panel.
Fig. A
Control box cover
screw
Insulation
Note: While connecting the PRARH1, attach insulation at the rear of the control box cover
where it receives screws as shown in Fig. A.
Please clean up the remaining wires after installation.
10 Auxiliary Heater Relay Kit
n 4 Way CST
Auxiliary Heater communication lines
(under AC24V,over AWG24)
These wires should not make
contact with high voltage lines.
To indoor unit PCB
(CN-PTC)
Aux heater
communication lines
AB AB
Check the attached direction to the indoor unit.
Aux heater
communication lines
Wiring
Assembly Diagram
Aux heater
communication lines
Aux heater
communication lines
Aux heaterAux heater
communication linescommunication lines
Aux heater
communication lines
Aux heater
communication lines
Step1. Open front panel. Step2. Assemble PRARH1 with cabinet.
Step3. Open the cover of PRARH1 and connect wires. Step4. Assemble control box cover and front panel.
CAUTION
Fig. A
Control box cover
screw
Insulation
Note: While connecting the PRARH1, attach insulation at the rear of the control box cover
where it receives screws as shown in Fig. A.
Please clean up the remaining wires after installation.
Installation Manual 11
ENGLISH
Assembly Diagram
n Ceiling Suspended
D < 3.3ft
Auxiliary heater relay kit should be installed with in 3.3ft from the product.
Otherwise heater may cause malfunction.
Auxiliary Heater communication lines
(under AC24V,over AWG24)
These wires should not make
contact with high voltage lines.
To indoor unit PCB
(CN-PTC)
AB AB
Wiring
Aux heater
communication
lines
Step1. Mount relay kit on the wall. Step2. Connect wires and assemble cover.
Do not install PRARS0 at,
- Places which exposed to rain or any water.
Other wise it may leads to electric shock, fire, injury or sometimes even fatality.
CAUTION
CAUTION
Note: Please clean up the remaining wires after installation.
12 Auxiliary Heater Relay Kit
4. Electrical Wiring
Note
• Use only UL1996 approved heater.
• Do not the Duct Heater. Use Base Bord Heater instead.
CN-PTC1
PRARH1
Heater1
Relay Circuit
Resistance
Heater
L
N
AC24V
DC12V
CN_PTC
Relay
Electric Baseboard Heater
Heater
Terminal block
Heater2
Relay Circuit
Resistance
Heater
L
N
AC24V
Relay
Electric Baseboard Heater
Heater
Terminal block
Electrical Wiring
• The wire should not be exposed to outside otherwise it may leads to malfunction of
machine or sometimes fire due to wire damage.
• Wrong wiring also cause fire, malfunction or damage to the machine.
• The installation voltage should be with in 24V otherwise it may leads to electric shock,
fire, injury or fatality.
WARNING
Duct Heater Base Bord Heater
Installation Manual 13
ENGLISH
Installer Setting
Function Code Existing condition
Select existing condition
of each code by pressing
button.
(00: not installed,
01 : installed)
3
Press button to save.
4
If pressing button long for 3
seconds, it enters into Thermostat
installer setup mode.
- If pressing once shortly, it enters into
user setup mode. Please press
more than 3 seconds for sure.
1
If pressing button repeatedly, it moves to
the selected option function code as picture
below.
2
Pressing button will exit settings mode.
After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
When exiting without pressing set button,
the manipulated value is not reflected.
5
Function
Auxiliary heater
Code
25
5. Installer Setting
Wired Remote Controller(Accessory)
Setting feature for indoor unit when Auxiliary Heater Relay Kit is newly installed, or installed unit is removed.
Installer setting mode is to set the detailed function of the remote controller.
If it is not properly set then it may leads to problem to the product , user injury as well
as property damage. Therefore these setting must be done by a certified installer.
Any installation or change carried out by a non certified person, he should be responsi-
ble for the results and it will void free service also.
CAUTION
If you want to operate Auxiliary Heater Relay Kit, you should have Wired or Wireless Remote Controller
below.
Model : PREMTB10U
14 Auxiliary Heater Relay Kit
Installer Setting
Function Function Code Setting Value
Remote Controller LCD
3 : Set to Auxiliary heater
Auxiliary heater
2
4 : Cancel Auxiliary heater
5 : Check Auxiliary heater Installation
Installer Setting Code Table
23
24
25
The indoor unit displays during the heating mode, the Auxiliary heater is automatically turned on, but it is not
displayed on the wireless remote controller.
NOTE
Wireless Remote Controller(Accessory)
It can only be set during heating operation.
1
Press the SET/CLEAR button to reserve or cancel the Electric
heater function.
2
Press the FUNCTION SETTING button
3 times.
Electric heater symbol will blink.
Model : PQWRHQ0FDB
Control map of AUX HEATER
Installation Manual 15
ENGLISH
n Mode 1. Normal
1) Function operation : It operates when Aux Heater was set by the Installer option of wired remote con-
troller, or when it was set by a wireless remote controller.
- Wired remote control installer function: 25:01
- Installer function setting by wireless remote control : 2.3 / Release : 2.4
2) The details of Aux heater control
- Heater output on/off is controlled depending on the room temperature during the heater on opera-
tion.
Heater 1 on/off
While Heater1 Off, if Room Temp < Set Point -1.0 ℃ Heater1 ON
While Heater1 On, if Room Temp ≥ Set Point Heater1 OFF
Heater 2 on/off
While Heater2 off, if Room Temp < Set Point 1.5℃ ON
While Heater2 On, if Room Temp ≥ Set Point 0.5℃ OFF
Heater delay Time
Heater output On: Heater 1 is On after 2 seconds from the Heater Off.
Heater 2 On is on after one minute
Heater output off : Others
※ It does not apply to some products.
6. Control map of AUX HEATER
Set temp
Heater 1
OFF
OFF
OFF
OFF
ON
ON
Heater 2
Set temp -0.5°C
Set temp -1.0°C
Set temp -1.5°C
16 Auxiliary Heater Relay Kit
Control map of AUX HEATER
n Mode 2. Primary Heater
1) Function operation
a. When primary heater is set by wired / wireless remote controller after the setting of aux heater
function, the Aux. heater is used as the main heating, and H/P used as the auxiliary heating con-
cept during the operation of Heating & Heater.
(In this case, the heating TH ON / OFF value is changed to the following set value.)
b. Installers CODE (Set 'Add Installers' at the Aux heater settings)
- Primary heater setting by wired remote controller: 36:01
- Primary heater setting by wired remote controller: 36:00
- Primary heater setting by wireless remote control : 1.A
- Primary heater release by wireless remote control : 1.B
2) Primary heater control details
- Heater output On/Off is controlled depending on the room temperature while heater operation is On.
Heater1 On/Off
Ind. Temp ≥ Set Temp +0.5℃ Heater Off
Ind. Temp < Set Temp -0.5℃ Heater On (1st Stage Heat On)
Heater2 On/Off
Ind. Temp ≥ Set Temp Heater Off
Ind. Temp < Set Temp -1.0℃ Heater On (2nd Stage Heat On)
Heating Thermal On / Off
Ind. Temp ≥ Set Temp -0.5℃ Thermo. Off
Ind. Temp < Set Temp -1.5℃ Thermo. On (3rd Stage Heat On)
Heater delay Time
Heater output On : Heater 1 is On after two seconds lapse from Heating & Heater Off, and Heater
2 is On after one minute lapse
Heater output off: Others
※ It does not apply to some products.
Set temp
Heater 1
OFF
OFF
OFF
OFF
ON
ON
OFF OFFON
Heater 2
TH ON/OFF
Set temp -0.5°C
Set temp +0.5°C
Set temp -1.0°C
Set temp -1.5°C
Troubleshooting Guide
Installation Manual 17
ENGLISH
7. Troubleshooting Guide
Symptom Check Action
AUX HEATER
does not work.
Is air conditioner power turned on?
- Check the circuit breaker.
- Check the AUX HEATER RELAY KIT installa-
tion status.
Is the cable correctly connected bete-
ween the air conditioner andAUX
HEATER RELAY KIT?
- Connect the cable between the air conditioner
and AUX HEATER RELAY KIT.
Is the cable correctly connected
between AUX HEATER and
AUX HEAER REWLAY KIT?
- Refer to the installation method in the installa-
tion manual and check again.
Is there any problem with wireless
remote controller?
(If wireless remote controller is used)
- Replace the battery or insert again according
to the polarity(+,-).
- If there is a leakage of the battery fluid in the
remote controller, replace the battery.
18 Auxiliary Heater Relay Kit
www.lg.com
MANUEL D'INSTALLATION
CLIMATISEUR
• Lisez ce manuel d'installation dans son intégralité avant d'installer le produit.
• L'installation doit être réalisée en respectant les normes locales en vigueur et
effectuée uniquement par un personnel qualifié.
• Après l'avoir lu attentivement, conservez ce manuel d'installation afin de
pouvoir vous y reporter ultérieurement.
TYPE : Kit relais du dispositif chauffant auxiliaire (pour produits Multi V)
MODÈLE : PRARH1
FRANÇAIS
2 Kit relais du dispositif chauffant auxiliaire
IMPORTANT !
ATTENTION
:
Toute installation, réglage, modification, entretien ou maintenance incorrect peut annuler la garantie.
Le poids de l'unité groupe compresseur-condenseur impose des procédures appropriées d'attention et de manipulation
lors des opérations de levage ou de déplacement afin d'éviter tout risque de blessures. Évitez surtout les contacts avec les bords tranchants ou pointus.
Consignes de sécurité
L'installation des équipements nécessite que les intervenants portent toujours des lunettes et des gants de sécurité.
Ne considérez jamais que l'alimentation électrique est déconnectée. Vérifiez toujours avec les appareils appropriés.
NOTE DESTINÉE AU REVENDEUR INSTALLATEUR
: Les modes d'emploi et garanties doivent être remis au client ou placés de façon
évidente à proximité de l'unité générateur d'air chaud / armoire de traitement d'air.
Lors du câblage :
Une décharge électrique peut causer des blessures graves ou un accident mortel.
Le câblage de ce système ne peut être confié qu'à un électricien qualifié et expérimenté.
Ne mettez pas l'appareil sous tension tant que tous les câblages et raccordements de tuyaux n'ont pas été terminés ou réalisés, puis vérifiés.
• Ce système utilise des tensions électriques élevées et dangereuses. Lors du câblage, reportez-vous soigneusement au
schéma de câblage et à ces instructions.
Tout raccordement incorrect ou mise à la terre incorrecte peut causer des accidents provoquant des blessures, voire la mort.
• La mise à la terre doit être effectuée conformément aux codes électriques locaux.
Branchez tous les câbles fermement. Un câblage desserré peut provoquer une surchauffe aux points de connexion avec le risque de déclenchement d'un incendie.
Lors de l'installation...
... dans un mur :
Vérifiez que le mur est suffisamment solide pour contenir le poids de l'appareil.
Il sera peut-être nécessaire de construire un cadre robuste en bois ou en métal comme complément de support.
... dans une pièce
:
Isolez de façon appropriée toute la tubulure présente dans la pièce afin de prévenir
toute "transpiration" avec le risque de voir le mur et le plancher endommagés par l'écoulement de
l'eau.
Lors des opérations d'entretien
• Avant d'ouvrir l'appareil pour des contrôles ou réparations des pièces électriques et du câblage,
mettez l'appareil hors tension (OFF) au niveau du boîtier d'alimentation principal (secteur).
• Une fois les opérations terminées, nettoyez le site et vérifiez bien qu'aucun déchet métallique ou
morceau de câblage n'ait été oublié à l'intérieur de l'appareil ayant fait l'objet de l'entretien.
AVERTISSEMENT
AVERTISSEMENT
• Les informations contenues dans ce manuel s'adressent à des techniciens qualifiés habitués aux procédures de
sécurité et équipés des outils et instruments de test appropriés.
• Tout manquement à une lecture soignée et au suivi précis de toutes les instructions de ce manuel peut se traduire
par un dysfonctionnement des équipements, des dommages aux biens, des blessures et/ou accidents mortels.
Lisez cette fiche d'instructions entièrement avant d'installer le produit.
Ce système de climatisation répond strictement aux normes de sécurité et de fonctionnement. En tant que personne chargée de l'installation ou de l'entretien
de cet appareil, une part importante de votre travail d'installation ou d'entretien de ce système consiste à ce qu'il fonctionne efficacement en toute sécurité.
L'installation doit s'adapter aux codes du bâtiment local ou avec le National Electrical Code NFPA 70/ANSI C1-1993
(ouédition en vigueur), ainsi que le Code électrique canadien CSA C.22.1 Part1.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54

LG PRARH1 Guide d'installation

Catégorie
Climatiseurs split-system
Taper
Guide d'installation

dans d''autres langues