Danby DAS180DBAHWDB Le manuel du propriétaire

Catégorie
Climatiseurs split-system
Taper
Le manuel du propriétaire
DANBY PRODUCTS LIMITED, ONTARIO, CANADA N1H 6Z9
DANBY PRODUCTS INC., FINDLAY, OHIO, USA 45840
OWNER’S MANUAL
MANUEL DU PROPRIÉTAIRE
MANUAL DEL PROPIETARIO
www.Danby.com
2019.12.17
DAS180DBAHWDB
FOR ANY QUESTIONS OR CONCERNS REGARDING INSTALLATION OR SERVICING OF THIS UNIT,
PLEASE CONTACT THE DEALER OR BUILDER WHO SOLD THE UNIT.
_____________________________________________________________________
POUR TOUTE QUESTION OU PRÉOCCUPATION CONCERNANT L’INSTALLATION OU L’ENTRETIEN
DE CET APPAREIL, VEUILLEZ CONTACTER LE REVENDEUR OU LE CONSTRUCTEUR QUI A VENDU
L’APPAREIL.
__________________________________________________________________
PARA CUALQUIER PREGUNTA O INQUIETUD RELACIONADA CON LA INSTALACIÓN O SERVICIO DE
ESTA UNIDAD, PÓNGASE EN CONTACTO CON EL DISTRIBUIDOR O CONSTRUCTOR QUE VENDIÓ LA
UNIDAD.
SPLIT AIR CONDITIONER
Installation Guide ............................................... 1 - 30
CLIMATISEUR DIVISÉ
Guide d’installation........................................... 31 - 60
AIRE ACONDICIONADO DIVIDIDO
Guía de instalación............................................ 61 - 90
1
SAVE THESE INSTRUCTIONS!
Important Safety Information
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
SAFETY PRECAUTIONS
Incorrect installation due to ignoring instructions
can cause serious damage or injury.
When connecting refrigerant piping, do not let
substances or gases other than the specifi ed
refrigerant enter the lines as this will lower the
unit’s capacity and can cause abnormally high
pressure in the refrigeration system, which can
lead to explosion or injury.
Installation must be performed by a certifi ed
HVAC technician. Defective installation can
cause water leakage, electrical shock or fi re.
In North America, installation must be performed
in accordance with the requirement of NEC and
CEC by authorized personnel only.
Contact an HVAC technician or the sales agent
for information on repair or maintenance of this
appliance.
Only use the included accessories, parts and
specifi ed parts for installation. Using non-
standard parts can cause water leakage,
electrical shock, fi re and can cause the unit to
fail.
Install the appliance in a fi rm location that can
support the unit’s weight. If the chosen location
cannot support the appliance’s weight, or if
the installation is not completed properly, the
appliance may fall and cause serious injury or
damage.
For all electrical work, follow all local and
national wiring standards and regulations and
this manual. You must use an independent circuit
and single outlet to supply power. Do not connect
other appliances to the same outlet. Insuffi cient
electrical capacity or defects in electrical work
can cause electrical shock or fi re.
For all electrical work, use all specifi ed cables.
Connect cables tightly and clamp them securely
to prevent external forces from damaging the
terminal. Improper electrical connections can
overheat and cause electrical shock or fi re.
All wiring must be correctly arranged to ensure
that the control board can close properly. If the
control board cover is not closed properly, it
can lead to corrosion and cause the connection
points on the terminal to overheat, catch fi re or
cause electrical shock.
In certain functional environments, such as
kitchens, server rooms, etc., the use of specially
designed air conditioning units is highly
recommended.
This appliance is not intended for use by persons
(including children) whose physical, sensory or
metal capabilities may be different or reduced, or
who lack experience or knowledge, unless such
persons receive supervision or training to operate
the appliance by a person responsible for their
safety.
Do not install the appliance in a location that
may be exposed to combustible gas leaks.
If combustible gas accumulates around the
appliance, it may cause fi re.
Do not operate this appliance in a wet room
such as a bathroom or laundry room. Too
much exposure to water can cause electrical
components to short circuit.
The appliance must be properly grounded or
electric shock can occur.
Install drainage piping according to the
instructions in this manual. Improper drainage
may cause water damage.
NOTE ABOUT FLUORINATED GASES
This appliance contains fl uorinated gasses. For
specifi c information on the type and amount of
gas, refer to the relevant label on the appliance
itself.
Installation, service, maintenance and repair of
this appliance must be performed by a certifi ed
HVAC technician.
Uninstallation and recycling must be performed
by a certifi ed HVAC technician.
If the appliance has a leak detection system
installed, it must be checked for leaks at least
every 12 months. When the appliance is
checked for leaks, proper record keeping of all
checks is strongly recommended.
2
ACCESSORIES
The air conditioning system comes with the following accessories. Use all of the installation parts and
accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock,
re or may cause the equipment to fail.
Part Image Quantity
Mounting plate 2
Mounting plate fi xing screw ST3.9 x 25
10
Clip anchor 10
Remote control 2
Dry battery AAA.LR03 4
Seal 2
Drain joint
2
INSTALLATION INSTRUCTIONS
3
INSTALLATION SUMMARY
Note: Illustrations in this manual are for explanatory purposes only. The actual shape of the appliance may
be slightly different. The actual shape shall prevail.
Wall Mounting Plate
Front Panel
Louver
Power Cable
Drainage Pipe
Signal Cable
Refrigerant Pipe
Remote Control
Outdoor Unit
Power Cable
Functional Filter
On Front of Main Filter
INSTALLATION INSTRUCTIONS
Note: The model DAS180DBAHWDB can be attached to multiple indoor units. See the next page for
details.
4
INSTALLATION SUMMARY
When installing multiple indoor units to a single outdoor unit, ensure that the length of the refrigerant pipe
and the drop height between the indoor and outdoor units meet the following requirements:
INSTALLATION INSTRUCTIONS
49ft (15m)
49ft (15m)
32.8ft (10m)
Outdoor Unit
Outdoor Unit
Outdoor Unit
Indoor Unit
Indoor units that can be used in combination Number of connected units 1 - 5 units
Compressor stop/start frequency Stop time 3 minutes or more
Power source voltage
Voltage fl uctuation within ± 10% of rated voltage
Voltage drop during start within ± 15% of rated voltage
Interval unbalance within ± 3% of rated voltage
Units are in meters/feet 1 drive 2 1 drive 3 1 drive 4 1 drive 5
Max. length for all rooms 40/131 60/197 80/262 80/262
Max. length for one indoor unit 25/82 30/98 35/115 35/115
Max. height difference between indoor and outdoor 15/49 15/49 15/49 15/49
Max. height difference between indoor units 10/33 10/33 10/33 10/33
5
INSTALLATION SUMMARY - INDOOR UNIT
INSTALLATION INSTRUCTIONS
6
INSTALLATION SUMMARY - INDOOR UNIT
INSTALLATION INSTRUCTIONS
7
INDOOR UNIT INSTALLATION
Before installing the indoor unit, refer to the label on the product box to ensure that the model number on the
indoor unit matches the model number on the outdoor unit. The indoor unit model number will end with a “-I”
and the outdoor unit model number will end with a “-O”, otherwise they should be identical.
Step 1: Select Installation Location
Proper installation locations meet the following standards:
Good air circulation.
• Convenient drainage.
Noise from the unit will not be disturbing.
Firm and solid location that will not vibrate.
Strong enough to support the weight of the unit.
At least 1 m (3 feet) away from all other electrical devices, such as televisions, radios and computers,
which could impact the infrared remote signal.
Do not install the indoor unit in locations that have the following:
Near any source of heat, steam or combustible gas.
Near fl ammable items such as curtains or clothing.
Near any obstacle that might block air circulation.
Near any doorway.
In direct sunlight.
Refer to the below illustration to ensure proper distance from surrounding walls and ceiling:
INSTALLATION INSTRUCTIONS
8
Step 2: Attach Mounting Plate To Wall
The mounting plate is the device that attaches the indoor unit on the wall.
1. Remove the screw that attaches the mounting plate to the back of the indoor unit.
2. Place the mounting plate against the wall in the location where the indoor unit will be installed.
3. Drill holes for the mounting screws, ensuring that the screws enter wall studs that can support the weight
of the unit.
4. Secure the mounting plate to the wall with the provided screws. Ensure that the mounting plate is fl at
against the wall.
Note: If the wall is made of brick, concrete or similar material, drill 5 mm (0.2 in) diameter holes in the wall
and insert the provided sleeve anchors. Secure the mounting plate to the wall by tightening the screws into
the clip anchors.
Mounting Plate Dimensions
Different models have different mounting plates. To ensure
that there is ample room to mount the indoor unit, check
the diagrams below which show the two different types of
mounting plates along with the following dimensions:
Width of mounting plate.
Height of mounting plate.
Width of indoor unit relative to mounting plate.
Height of indoor unit relative to mounting plate.
Recommended position of wall hole, both to the left and
right of the indoor unit.
Relative distance between screw holes.
INSTALLATION INSTRUCTIONS
10.1 cm (4”)
17.9 cm (7.05”)
13.6 cm (5.35”)
3.7 cm (1.45”)
29 cm (11.4”)
4.9 cm (1.95”)
Right rear wall
hole 6.5 cm (2.5”)
Indoor unit outline
72.2 cm (28.45”)
4.9 cm (1.95”)
22.8 cm (8.98”)
22.9 cm (9.01”)
40.1 cm (15.78”)
12.6 cm (4.96”)
4.2 cm (1.65”)
29.7 cm (11.7”)
Left rear wall
hole 6.5 cm (2.5”)
Left rear wall
hole 6.5 cm (2.5in)
Right rear wall
hole 6.5 cm (2.5”)
Indoor unit outline
80.2 cm (31.6”)
5.8 cm (2.28”)
4.7 cm (1.85”)
Model B
Model A
34.8 cm (13.7”)
9
Step 3: Drill Wall Hole For Connective Piping
A hole must be drilled through the wall to the outside to accommodate the refrigerant piping, the drainage
pipe and the signal cable that will connect the indoor and outdoor units.
1. Determine the location of the wall hole based on the position of the mounting plate. See Step 2 for
mounting plate dimensions.
2. The wall hole should have a 65 mm (2.5 in) diameter and it should be drilled on a downward angle to
facilitate drainage. The outdoor end of the hole should be lower than the indoor end of the hole by 5 - 7
mm (0.2 - 0.275 in).
3. Place the protective wall cuff in the hole. This will protect the edges of the hole and will help seal the
hole once the installation is complete.
Note: When drilling the wall hole, make sure to avoid wires, plumbing and other sensitive components that
could be within the wall.
INSTALLATION INSTRUCTIONS
10
Step 4: Prepare Refrigerant Piping
The refrigerant piping is inside an insulating sleeve attached to the back of the
unit. The piping must be prepared before passing it through the hole in the wall.
Refer to the Refrigerant Piping Connection section for detailed instructions on
pipe fl aring and fl are torque requirements, etc.
1. Based on the position of the wall hole relative to the mounting plate, choose
the side from which the piping will exit the unit.
2. If the wall hole is behind the unit, leave the knock out panel in place. If the
wall hole is to the side of the indoor unit, remove the plastic knock out panel
from the side of the unit. This will create a slot through which the piping can
exit the unit. Use needle nose pliers if the plastic panel is diffi cult to remove.
3. Use scissors to cut down the length of the insulating sleeve to reveal
approximately 15 cm (6 in) of the refrigerant piping. This serves two
Knock out panel
purposes:
To facilitate the Refrigerant Piping Connection process
To facilitate gas leaks checks and allow a check for dents in the pipe
4. If existing connective piping is already embedded in the wall, proceed directly to Step 5: Connect The
Drain Hose. If there is no embedded piping, connect the indoor unit’s refrigerant piping to the connective
piping that will join the indoor and outdoor units.
5. Based on the position of the wall hole relative to the mounting plate, determine the necessary angle of
the piping. Grip the refrigerant piping at the base of the bend.
6. Slowly, with even pressure, bend the piping toward the wall hole. Do not dent or damage the pipe
during the process.
Note on Piping Angle
Refrigerant piping can exit the indoor unit from four different angles:
• Left-hand side
• Left rear
• Right-hand side
• Left rear
CAUTION
Be extremely careful not to dent or damage the piping
while bending them away from the unit. Any dents in
the piping will affect the unit’s performance.
INSTALLATION INSTRUCTIONS
11
Step 5: Connect the Drain Hose
By default, the drain hose is attached to the left-hand side of the unit, when facing the back of the unit. It can
also be attached to the right-hand side.
1. To ensure proper drainage, attach the drain hose on the same side of the unit as the refrigerant piping.
2. Attach the drain hose extension (purchased separately) to the end of the drain hose.
3. Wrap the connection point fi rmly with Tefl on tape to ensure a good seal and prevent leaks.
4. For the portion of the drain hose that will remain indoors, wrap it with foam pipe insulation to prevent
condensation.
5. Remove the air fi lter and pour a small amount of water into the drain pan to make sure that water fl ows
from the unit smoothly.
Note on Drain Hose Placement
Do not kink the drain hose.
Do not create a water trap.
Do not put the end of the drain hose in water or a container that will collect water.
Note: To prevent unwanted leaks, plug the unused drain hole with the provided rubber plug.
See below for examples of correct drain hose installation:
INSTALLATION INSTRUCTIONS
12
BEFORE PERFORMING ELECTRICAL WORK, READ THESE REGULATIONS
1. All wiring must comply with local and national electrical codes and must be installed by a licensed
electrician.
2. All electrical connections must be made according to the Electrical Connection Diagram located on the
panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to
the client and refuse to install the unit until the safety issue is resolved.
4. Power voltage should be within 90 - 100% of rated voltage. Insuffi cient power supply can cause
malfunction, electrical shock or fi re.
5. If connecting power to fi xed wiring, install a surge protector and main power switch with a capacity of
1.5 times the maximum current of the unit.
6. If connecting power to fi xed wiring, a switch or circuit breaker that disconnects all poles and has a
contact separation of at least 3 mm (1.8 in) must be incorporated in the fi xed wiring. The qualifi ed
technician must use an approved circuit breaker or switch.
7. Only connect the unit to an individual branch circuit outlet. Do not connect another appliance to that
outlet.
8. Make sure to properly ground the appliance.
9. Every wire must be fi rmly connected. Loose wiring can cause the terminal to overheat, resulting in product
malfunction and possible fi re.
10. Do not let wires touch or rest against the refrigerant tubing, the compressor or any moving parts within
the unit.
WARNING
BEFORE PERFORMING ANY ELECTRICAL WIRING WORK,
TURN OFF THE MAIN POWER TO THE SYSTEM.
WARNING
All wiring must be performed in accordance with the wiring
diagram located on the inside of the indoor unit’s wire cover.
Do not mix up live and null wires. This is dangerous and can
cause the appliance to malfunction.
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
Connect the wiring to the terminals as identifi ed with their respective matched numbers on the terminal block
of the indoor and outdoor units. For example, see the following US models: Terminal L1(A) on the outdoor
unit must connect with terminal L1 on the indoor unit.
Run the main power cord through the lower line outlet of the cord clamp.
One-two mo
d
e
l
s:
Model A
Model E Model F Model G
Model B Model C Model D
13
14
Step 6: Connect the Signal Cable
The signal cable enables communication between the indoor and outdoor units. You must fi rst choose the
right cable size before preparing it for connection.
Cable types:
Indoor Power Cable (if applicable): H05W-F or H05V2V2-F
Outdoor Power Cable: H07RN-F
Signal Cable: H07RN-F
Minimum Cross Sectional Area of
Power and Signal Cables
Appliance Amps (A) AWG
10 18
13 16
18 14
25 12
30 10
CHOOSE THE RIGHT SIZE CABLE
The size of the power supply cable, signal cable, fuse and
switch needed is determined by the maximum current in the unit.
The maximum current is indicated on the rating plate located on
the side panel of the unit. Refer to this rating plate to choose the
right cable, fuse and switch.
Take Note of Fuse Specifi cations
The air conditioner circuit board (PCB) is designed with a fuse to provide over current protection. The
specifi cations of the fuse are printed on the circuit board, such as: T3.15A/250VAC, T5A/250VAC, etc.
1. Prepare the cable for connection:
a. Using wire strippers, strip the rubber jacket from both ends of the signal cable to reveal
about 40 mm (1.57 in) of the wires inside.
b. Strip the insulation from the ends of the wires.
c. Using wire crimper, crimp u-type lugs on the ends of the wires.
2. Open the front panel of the indoor unit.
3. Using a screwdriver, open the wire box cover on the right side of the unit. This will reveal the terminal
block.
4. Unscrew the cable clamp below the terminal block and place it to the side.
5. Facing the back of the unit, remove the plastic panel on the bottom left-hand side.
6. Feed the signal wire through this slot, from the back of the unit to the front.
7. Facing the front of the unit, match the wire colours with the labels on the terminal block, connect the u-lug
and fi rmly screw each wire to its corresponding terminal.
8. After checking to make sure every connection is secure, use the cable clamp to fasten the signal cable to
the unit. Screw the cable clamp down tightly.
9. Replace the wire cover on the front of the unit and the plastic panel on the back.
The wiring diagram is
located on the inside of
the wire cover on the
indoor unit.
Note: Pay attention to the live
wire. While crimping wires,
make sure to distinguish the Live
(“L”) Wire and other wires.
INSTALLATION INSTRUCTIONS
15
Step 7: Wrap piping and cables
Before passing the piping, drain hose and the signal cable through the wall hole, bundle them together to
save space, protect them and insulate them.
1. Bundle the drain hose, refrigerant pipes and signal cable.
Note: Ensure that the drain hose is at the bottom of the bundle. Putting the drain hose at the top of the bundle
can cause the drain pan to overfl ow, which can lead to fi re or water damage.
2. Using adhesive vinyl tape, attach the drain hose to the underside of the refrigerant pipes.
3. Using insulation tape, wrap the signal wire, refrigerant pipes and drain hose tightly together.
Note: While bundling these items together, do not intertwine or cross the signal cable with any other wiring.
Note: When wrapping the bundle, keep the ends of piping unwrapped. Access is required to test for leaks
at the end of the installation process.
INSTALLATION INSTRUCTIONS
16
Step 8: Mount the Indoor Unit
If new connective piping was installed to the outdoor unit, complete the following:
1. If the refrigerant piping has already been passed through the wall, proceed to step 4.
2. Otherwise, double check that the ends of the refrigerant pipes are sealed to prevent dirt or foreign
materials from entering the pipes.
3. Slowly pass the wrapped bundle of refrigerant pipes, drain hose and signal wire through the hole in the
wall.
4. Hook the top of the indoor unit on the upper hook of the mounting plate.
5. Check that the unit is hooked fi rmly on mounting by applying slight pressure to the left and right-hand
sides of the unit. The unit should not jiggle or shift.
6. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps
onto the hooks along the bottom of the mounting plate.
7. Check that the unit is fi rmly mounted by applying slight pressure to the left and right-hand sides of the
unit.
If refrigerant piping is already embedded in the wall, complete the following:
1. Hook the top of the indoor unit on the upper hook of the mounting plate.
2. Use a bracket or wedge to prop up the unit, allowing enough room to connect the refrigerant piping,
signal cable and drain hose.
3. Connect the drain hose and refrigerant piping. Refer to the Refrigerant Piping Connection section for
more information.
4. Keep the pipe connection point exposed to perform the leak test. Refer to the Electrical Checks and Leak
Checks section for more information.
5. After the leak test, wrap the connection point with insulation tape.
6. Remove the bracket or wedge that is propping up the unit.
7. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps
onto the hooks along the bottom of the mounting plate.
Unit is Adjustable
The hooks on the mounting plate are smaller than the holes on the back of the unit. The unit can be adjusted
left or right by approximately 30 - 50 mm (1.25 - 1.95 in) depending on the model.
INSTALLATION INSTRUCTIONS
17
OUTDOOR UNIT INSTALLATION
Step 1: Select installation location
Before installing the outdoor unit, choose an appropriate location for the unit. Proper installation locations
meet the following requirements:
Good air circulation and ventilation.
Firm and solid; the location can support the unit and will not vibrate.
Noise from the unit will not be disturbing.
The unit will be protected from prolonged periods of direct sunlight, rain or snow.
The location must meet the special requirements outlined below:
Do not install the unit in the following locations:
Near obstacles that will block air inlets or outlets.
Near a public street, crowded areas or where noise from the unit will disturb others.
Near animals or plants that could be harmed by hot air discharge.
Near any source of combustible gas.
In a location that is exposed to large amounts of dust.
In a location that is exposed to large amounts of salty air.
Special Considerations For Extreme Weather
If the unit is exposed to heavy wind, install the unit so that the air outlet fan is at a 90° angle to the direction
of the wind. If needed, build a barrier in front of the unit to protect it from the wind.
If the unit is exposed to heavy rain or snow, build a shelter above the unit to protect it. Be careful not to
obstruct air fl ow around the unit.
If the unit is exposed to salty air, use an outdoor unit that is specially designed to resist corrosion.
INSTALLATION INSTRUCTIONS
18
Step 2: Install the drain joint
Before bolting the outdoor unit in place, install the drain joint at the bottom of the unit. There are two types of
drain joint depending on the type of unit.
1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
2. Insert the drain joint into the hole in the base pan of the unit.
3. Rotate the drain joint 90° until it clicks in place facing the front of the unit.
4. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during
heating mode.
The base hole for the drain joint can be found on the bottom of the unit.
Note For Cold Climates
In cold climates, ensure that the drain hose is positioned as close to vertical as possible to encourage swift
water drainage. If water drains too slowly it can freeze inside the drain hose and fl ood the unit.
INSTALLATION INSTRUCTIONS
19
Step 3: Anchor the outdoor unit
The outdoor unit can be anchored to the ground or to a wall-mounted bracket.
The following is a list of outdoor unit sizes and the distance between their mounting feet. Prepare the
installation base of the unit according to the dimensions and images below.
If the unit will be ground mounted, follow the below instructions:
1. Mark the positions for four expansion bolts based on dimensions in the unit mounting dimensions chart.
2. Pre-drill holes for expansion bolts.
3. Clean concrete dust away from holes.
4. Place a nut on the end of each expansion bolt.
5. Hammer expansion bolts into the pre-drilled holes.
6. Remove the nuts from the expansion bolts and place outdoor unit on the bolts.
7. Put washer on each expansion bolt and then replace the nuts.
8. Using a wrench, tighten each nut until snug.
WARNING
When drilling into concrete,
eye protection should be
worn at all times.
If the unit will be wall mounted, follow the below instructions:
1. Mark the positions of the bracket holes based on dimensions in the unit mounting dimensions chart.
2. Pre-drill holes for expansion bolts.
3. Clean concrete dust away from holes.
4. Place a washer and a nut on the end of each expansion bolt.
5. Thread the expansion bolts through the holes on the mounting brackets, put mounting brackets in position
and hammer the expansion bolts into the wall.
6. Check that the mounting brackets are level.
7. Carefully lift the unit and place its mounting feet on the brackets.
8. Bolt the unit fi rmly to the brackets.
Note: To reduce vibrations and noise of a wall-mounted unit, install the unit with rubber gaskets.
Unit Mounting Dimensions Chart
Model Number Unit Dimensions (W x H x D)
Distance A
(mm / in)
Distance B
(mm / in)
DAS180DBAHWDB 922x715x379 (36.3”x28.2”x14.9”) 540 (21.26”) 350 (13.8”)
INSTALLATION INSTRUCTIONS
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92

Danby DAS180DBAHWDB Le manuel du propriétaire

Catégorie
Climatiseurs split-system
Taper
Le manuel du propriétaire