wattstopper LMCP-LI48 Guide d'installation

Taper
Guide d'installation

Ce manuel convient également à

Wattstopper
®
DLM – GE12 SWS or TLC Relay to LMCP Retrofit Kit
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 24812 –11/23 rev. 2
Catalog Number • Numéro de Catalogue • Número de Catálogo: LMCP-GE12
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
LMCP-GE12 RETROFIT KIT INSTALLATION
Step 1: Remove all interior components leaving relays and
power supply only.
Fig. 1: Example GE12
panel assembly
Fig. 2: After removing
interior items
Step 2: Install LMRD/LMPI adapter plate and card.
Fig. 3: Adapter plate mounting details
Step 3:
Connect LMRD card to LMPI.
Connect relays to LMRD cards.
Connect power to LMPI.
(See Relay Connection Details for DIP Switch settings and
power supply connection details.)
Fig. 4: Connection details
Step 4: Apply upgrade label.
Fig. 5: Label location suggestion
Mounting plate screw
locations (Total 4 #6-32
screws for mounting plate)
LMCP-GE12-MP
(Part #841494)
LMPI
(Part #17162)
LMRD-12
(Part #16694)
2
RELAY CONNECTION DETAILS
Option 1:
5-pin connector
DIP Switch Setting
1, 2, 3, 4, 6 Reserved (OFF)
5ON (for GE relays)
OFF (for HDR relays)
7ON: Relays ON/OFF during PnL
OFF: Only pilot LEDs ON/OFF during PnL
8ON: Pilot LEDs follow logic
OFF: Pilot LEDs follow Pilot
Option 2:
3-pin connector (no pilot)
DIP Switch Setting
1, 2, 3, 4, 6 Reserved (OFF)
5ON (50 ms pulse width)
7ON: Relays ON/OFF during PnL
OFF: Only pilot LEDs ON/OFF during PnL
8ON
Power supply connection detail
12345678
ON
12345678
ON
3
Existing Panel Wiring Options Converted LMCP Retrofit Wiring
3-Wire Momentary
w/o Pilot
LV Switch to Single Relay terminal.
If multiple relays controlled, use
wiring to an LMIN-104 instead
Red
On
Black
Off
Yellow
Pilot
White
Com
3-Wire Momentary
w/ or w/o Pilot
LV Switch to Single Relay terminal.
If multiple relays controlled, use
wiring to an LMIN-104 instead
Red
On
Black
Off
Yellow
Pilot
White
Com
Red
On
Black
Off
Yellow
Pilot
White
Com
2-Wire Momentary
Red
On
Black
Off
Yellow
Pilot
White
Com
2-Wire Maintained
Pilot
P
Com
C
Signal
S
Com
C
3-Wire Momentary
w/o Pilot
OR
Pilot
P
Com
C
Signal
S
Com
C
On
Off
Com
On
Off
Com
On
Com
On
Com
Pilot
On
Off
Com
On
Com
Off, now
Pilot
On and Off wires now
commoned together
(at switch or in panel)
and landed on the
“S” terminal
Replacement 2-Wire
Momentary w/ Pilot
(Ex: LVSW-10x)
On wire used for
Momentary contact,
but Off wire now
being used as Pilot
Pilot
P
Com
C
Signal
S
Com
C
3-Wire Momentary
w/ or w/o Pilot
On and Off wires now commoned
together (at switch or in panel)
and landed on the “S” terminal
On
Off
Com
Pilot
Red
On
Black
Off
Yellow
Pilot
White
Com
2-Wire Momentary
On
Com
LMCP Panels cannot accept Maintained switches.
Add an LMIN-104 and use wiring diagrams as
described in LMIN -104 installation instructions.
LMRD Board
Relay & Switch Terminals
Relay Block
P C CS
Switch Block
RETROFIT LOW VOLTAGE SWITCH WIRING CONVERSION
Existing low voltage switches may be converted for operation with the LMCP retrofit panel. Retrofit panel input terminals are limited to
toggle operation only. Any existing ON or OFF buttons wired to LMCP terminals will operate as toggle buttons. If this is unacceptable,
use the LMIN-104 DLM Low Voltage Input Module for wiring conversions, which supports many input operations including ON-only and
OFF-only. See LMIN-104 product documentation for more details.
NOTE: Prior to converting for operation with the DLM system, any existing switch wiring must be verified to not run with line voltage
wiring. Line voltage wiring can magnetically couple voltage onto low voltage wiring and will cause improper operation.
NOTE: Wiring shown is applicable to ON/OFF retrofit panels only. 0-10V retrofit options are not available, nor is wiring shown
compatible with 0-10V LMCP panel relay cards.
800.879.8585
www.legrand.us/wattstopper
No. 24812 – 11/23 rev. 2
© Copyright 2023 Legrand All Rights Reserved.
© Copyright 2023 Tous droits réservés Legrand.
© Copyright 2023 Legrand Todos los derechos reservados.
Wattstopper warranties its products to be free
of defects in materials and workmanship for a
period of five (5) years. There are no obligations
or liabilities on the part of Wattstopper for
consequential damages arising out of, or in
connection with, the use or performance of this
product or other indirect damages with respect
to loss of property, revenue or profit, or cost of
removal, installation or reinstallation.
Wattstopper garantit que ses produits sont
exempts de défauts de matériaux et de fabrication
pour une période de cinq (5) ans. Wattstopper
ne peut être tenu responsable de tout dommage
consécutif causé par ou lié à l’utilisation ou
à la performance de ce produit ou tout autre
dommage indirect lié à la perte de propriété, de
revenus, ou de profits, ou aux coûts d’enlèvement,
d’installation ou de réinstallation.
Wattstopper garantiza que sus productos
están libres de defectos en materiales y mano
de obra por un período de cinco (5) años. No
existen obligaciones ni responsabilidades por
parte de Wattstopper por daños consecuentes
que se deriven o estén relacionados con el
uso o el rendimiento de este producto u otros
daños indirectos con respecto a la pérdida
de propiedad, renta o ganancias, o al costo
de extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
PARTS LIST
Part Description Part Number Quantity Part Description Part Number Quantity
LMRD-12 #16694 1Cable
Assembly #841449 1
LMPI #17162 1Screw #6-32
L=5/16 #17686 10
LMCP-GE12-MP #841494 1
* SWS and TLC are products and property of General Electric (GE).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

wattstopper LMCP-LI48 Guide d'installation

Taper
Guide d'installation
Ce manuel convient également à

dans d''autres langues