Simplicity 040276B-01 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation

Ce manuel convient également à

Questions?
Help is just a moment away!
Call: Generator Helpline
800-743-4115 M-F 8-5 CT
Generator Systems
Installation Manual
12000, 15000 & 20000 Watt
Not
for
Reproduction
Thank you for purchasing this quality-built Briggs & Stratton home generator. We’re pleased that you’ve placed your
confidence in the Briggs & Stratton brand. When operated and maintained according to the instructions in the operator’s
manual, your home generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with residential generator
systems and how to avoid them. This generator system is designed and intended only for use as an optional home standby
system that provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and
communication systems that, when stopped during any power outage, could cause discomfort or inconvenience. Save these
original instructions for future reference.
This generator system requires professional installation before use. The installer should follow the instructions completely.
Where to Find Us
You never have to look far to find support and service for your generator. Consult your Yellow Pages. There are many
Briggs & Stratton authorized service dealers who provide quality service. You can also contact Technical Service by phone at
800-743-4115 between 8:00 AM and 5:00 PM CT., or click on Find a Dealer at BRIGGSandSTRATTON.COM, which provides a
list of authorized dealers.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Date of Purchase ____________________________
Generator
Model Number ____________________________
Model Revision ____________________________
Serial Number ____________________________
Engine
Model Number ____________________________
Serial Number ____________________________
Briggs & Stratton Power Products Group, LLC
P.O. Box 702
Milwaukee, WI 53201-0702
Copyright © 2011. All rights reserved. No part of this material
may be reproduced or transmitted in any form without the express
written permission of Briggs & Stratton Power Products Group, LLC.
Not
for
Reproduction
3
Table of Contents
Important Safety Instructions........................4
Installation ....................................7
Equipment Description.........................................7
Home Owner Responsibilities ...................................7
Installing Dealer/Contractor Responsibilities ........................7
Cold Weather Kit .............................................7
Unpacking Precautions ........................................7
Delivery Inspection............................................7
Installation Checklist ..........................................8
Shipment Contents............................................8
Generator Placement ..........................................9
Placement of Standby Generator to REDUCE THE RISK OF CARBON MONOXIDE
POISONING..............................................................10
Placement of Standby Generator to REDUCE THE RISK OF FIRE .......11
Examples of standby generator locations to reduce the risk of fire: .....12
Other General Location Guidelines...............................15
Electrical and Fuel Inlet Locations ...............................16
Lifting the Generator .........................................16
Access Ports ...............................................17
The Gaseous Fuel System .....................................18
Fuel Consumption ...........................................19
Fuel Pipe Sizing .............................................19
System Connectors ..........................................20
Fuel Conversion .............................................21
Generator AC Connection System ...............................22
Grounding the Generator ......................................22
Utility Circuit Connection ......................................22
Transfer Switch Communication ................................22
Fault Detection System .......................................23
System Control Panel.........................................23
Final Installation Considerations ................................24
Initial Start-up (No Load)......................................24
Engine Adjustment...........................................25
Controls ..................................... 26
Operation .................................... 26
Automatic Operation Sequence .................................26
Setting Exercise Timer ........................................26
Installation Inspection ........................................26
12000 Watt Schematic Diagram ................................28
12000 Watt Wiring Diagram ...................................29
15000 and 20000 Watt Schematic Diagram .......................30
15000 and 20000 Watt Wiring Diagram ..........................31
Not
for
Reproduction
4
Save These Instructions
WARNING Running engine gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide could result
in death, serious injury, headache, fatigue,
dizziness, vomiting, confusion, seizures, nausea
or fainting.
• Operate this product ONLY outdoors in an area that will
not accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors,
ventilation intakes, soffit vents, crawl spaces, open garage
doors or other openings that can allow exhaust gas
to enter inside or be drawn into a potentially occupied
building or structure.
• Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions/recommendations. Smoke alarms cannot
detect carbon monoxide gas.
WARNING Storage batteries give off explosive
hydrogen gas during recharging.
Slightest spark will ignite hydrogen
and cause explosion, resulting
in death, serious injury and/or
property damage.
Battery electrolyte fluid contains acid and is
extremely caustic.
Contact with battery contents could cause severe
chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette
during and for several minutes after charging a battery.
• DO NOT open or mutilate the battery.
• Wear protective goggles, rubber apron, rubber boots and
rubber gloves.
• Remove watches, rings, or other metal objects.
• Use tools having insulated handles.
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a
degree or level of hazard seriousness. A safety symbol
may be used to represent the type of hazard. The signal
word NOTICE is used to address practices not related to
personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that
it is safe for you and others. You must also make sure that
the procedure, work method or operating technique that you
choose does not render the generator system unsafe.
Explosion
Fire
Electrical Shock
Rotating Parts
Hot Surface
Toxic Fumes
Chemical BurnExplosive PressureAuto Start
Lift Hazard
Read Manual
WARNING The engine exhaust from this product
contains chemicals known to the State of California to
cause cancer, birth defects, or other reproductive harm.
WARNING Certain components in this product and
related accessories contain chemicals known to the State
of California to cause cancer, birth defects, or other
reproductive harm. Wash hands after handling.
Not
for
Reproduction
5
WARNING Generator produces hazardous voltage.
Failure to properly ground generator could result
inelectrocution.
Failure to isolate generator from utility power could
result in death or serious injury to electric utility
workers due to backfeed of electrical energy.
• When using generator for backup power, notify
utility company.
• DO NOT touch bare wires or bare receptacles.
• DO NOT use generator with electrical cords which are
worn, frayed, bare or otherwise damaged.
• DO NOT handle generator or electrical cords while
standing in water, while barefoot, or while hands or
feet are wet.
• If you must work around a unit while it is operating,
stand on an insulated dry surface to reduce the risk of
a shock hazard.
• DO NOT allow unqualified persons or children to operate
or service generator.
• In case of an accident caused by electrical shock,
immediately shut down the source of electrical power and
contact the local authorities. Avoid direct contact with
the victim.
• Despite the safe design of the generator, operating this
equipment imprudently, neglecting its maintenance or
being careless could cause possible injury or death.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically
or mentally fatigued.
• Before performing any maintenance on the generator,
disconnect the battery cable indicated by a NEGATIVE,
NEG or (-) first. When finished, reconnect that cable last.
• After your system is installed, the generator may crank
and start without warning any time there is a power
failure. To prevent possible injury, always set the
generator’s system switch to OFF, remove the service
disconnect from the disconnect box AND remove the
15 Amp fuse BEFORE working on the equipment.
WARNING Propane and Natural Gas are extremely
flammable and explosive, which could cause
burns, fire or explosion resulting in death,
serious injury and/or property damage.
• Install the fuel supply system according to NFPA 37 and
other applicable fuel-gas codes.
• Before placing the generator into service, the fuel system
lines must be properly purged and leak tested.
• After the generator is installed, you should inspect the fuel
system periodically.
• NO leakage is permitted.
• DO NOT operate engine if smell of fuel is present or other
explosive conditions exist.
• DO NOT smoke around the generator. Wipe up any oil
spills immediately. Ensure that no combustible materials
are left in the generator compartment. Keep the area near
the generator clean and free of debris.
WARNING Hazardous Voltage - Contact with power
lines could cause electric shock or burns,
resulting in death or serious injury.
Lifting Hazard / Heavy Object - Could result
in serious injury.
• If lifting or hoisting equipment is used, DO NOT contact
any power lines.
• DO NOT lift or move generator without assistance.
• Use lifting pipes as described in Lifting the Generator.
• DO NOT lift unit by roof as damage to generator
will occur.
Not
for
Reproduction
6
WARNING Starter and other rotating parts could
entangle hands, hair, clothing, or accessories
resulting in serious injury.
• NEVER operate generator without protective housings,
covers, or guards in place.
• DO NOT wear loose clothing, jewelry or anything that
could be caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
• Before servicing, remove 15 Amp fuse from control panel
and disconnect Negative (NEG or -) battery cable.
CAUTION Installing the 15A fuse could cause the
engine to start at any time without warning
resulting in minor or moderate injury.
• Observe that the 15 Amp fuse has been removed from the
control panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has
been completed and inspected.
CAUTION Excessively high operating speeds could
result in minor injury and/or equipment damage,
Excessively low speeds impose a heavy load on generator.
• DO NOT tamper with governed speed. Generator supplies
correct rated frequency and voltage when running at
governed speed.
• DO NOT modify generator in any way.
NOTICE Improper treatment of generator could damage it
and shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, contact your
authorized dealer.
• Operate generator only on level surfaces.
• Adequate, unobstructed flow of cooling and ventilating air
is critical to correct generator operation.
• The access panels/doors must be installed whenever the
unit is running.
• DO NOT expose generator to excessive moisture, dust,
dirt, or corrosive vapors.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically
or mentally fatigued.
• DO NOT start engine with air cleaner or air cleaner
cover removed.
• DO NOT insert any objects through cooling slots.
• DO NOT use the generator or any of its parts as a step.
Stepping on the unit could cause stress and break parts.
This may result in dangerous operating conditions from
leaking exhaust gases, fuel leakage, oil leakage, etc.
• If connected devices overheat, turn them off and
disconnect them from generator.
Shut off generator if
- electrical output is lost;
- equipment sparks, smokes, or emits flames;
- unit vibrates excessively;
- unit makes unusual noises.
WARNING
Exhaust heat/gases could ignite combustibles
or structures resulting in death, serious
injury and/or property damage. Contact with
muffler area could cause burns resulting in
serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Exhaust outlet side of weatherproof enclosure must
have at least 5 ft. (1.5 m) minimum clearance from any
structure, shurbs, trees or any kind of vegetation.
• Standby generator weatherprrof enclosure must be at
least 5 ft. (1.5 m) from windows, doors, any wall opening,
shrubs or vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang or trees.
• DO NOT place weatherproof enclosure under a deck or
other type of structure that may confine airflow.
• Use only flexible fuel line provided. Connect provided fuel
line to generator, DO NOT use with or substitute any other
flexible fuel line.
• Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
• Keep at least minimum distances shown in General
Location Guidelines to insure for proper generator cooling
and maintenance clearances.
• It is a violation of California Public Resource Code,
Section 4442, to use or operate the engine on any forest-
covered, brush-covered, or grass-covered land unless
the exhaust system is equipped with a spark arrester, as
defined in Section 4442, maintained in effective working
order. Other states or federal jurisdictions may have
similar laws.
Contact the original equipment manufacturer, retailer, or
dealer to obtain a spark arrester designed for the exhaust
system installed on this engine.
• Replacement parts must be the same and installed in the
same position as the original parts.
Not
for
Reproduction
7
Installation
Equipment Description
This product is intended for use as an optional system
which provides an alternate source of electric power and
to serve loads such as heating, refrigeration systems, and
communication systems that, when stopped during any
power outage, could cause discomfort or inconvenience.
This product does not qualify for emergency standby as
defined by NFPA 70 (NEC).
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
Only current licensed electrical and plumbing
professionals should attempt generator system
installations. Installations must strictly comply with all
applicable codes, industry standards and regulations.
Home Owner Responsibilities
 • Readandfollowtheinstructionsgiveninthe
operator’smanual.
 • Followaregularscheduleinmaintaining,caringfor
and using your generator, as specified in the operator’s
manual.
 • Carbonmonoxidedetector(s)MUSTbeinstalledand
maintained indoors according to the manufacturer’s
instructions/recommendations. Smoke alarms cannot
detect carbon monoxide gas.
If you have questions about intended use, ask your installer
or dealer or call 877-369-9400 between 8:00 AM and
5:00PM CT.
Installing Dealer/Contractor Responsibilities
 • Readandobservethesafetyrules.
 • InstallonlyanULapprovedtransferswitchthatis
compatible with the generator.
 • Readandfollowtheinstructionsgiveninthis
installation and start-up manual.
 • Installationmuststrictlycomplywithallapplicable
codes, industry standards, laws, and regulations.
 • Allowsufficientroomonallsidesofthegeneratorfor
maintenance and servicing.
Cold Weather Kit
If operating the generator below 40°F (5°C), it is HIGHLY
RECOMMENDED that a Model 6030 Cold Weather Kit
(includes oil warmer and battery warmer) and on 15kw
and 20kw, Model 6174 Cold Weather Breather Kit (includes
engine duct) be installed. These items are available at your
local servicing dealer.
If you need more information on this matter, please call
(888) 575-8226, between 8:00 AM and 5:00 PM CT.
Unpacking Precautions
The unit is shipped bolted to its mounting pad, ready
for installation. Avoid damage from dropping, bumping,
collision, etc. Store and unpack carton with the proper side
up, as noted on the shipping carton.
Delivery Inspection
After removing the carton, carefully inspect the generator for
any damage that may have occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight
bill and affix his signature under the consignor’s memo of
loss or damage. If loss or damage is noted after delivery,
separate the damaged materials and contact the carrier
for claim procedures. Missing or damaged parts are
notwarranted.
Not
for
Reproduction
8
Shipment Contents
The generator is supplied with:
 • Pre-attachedmountingpad
 • Fully-servicedoil/lubricatingsystem
 • Flexiblefuelhook-uphose
 • Installationandstart-upmanual
 • Operator’smanual
 • Spareaccessdoorkeys
 • Spare15AmpATO-typefuse
 • Two-pinconnectorplug
 • Ten-pinconnectorplug
 • Touchuppaint
Not Included:
 • Carbonmonoxidedetector(s)
 • Smokedetector(s)
 • Startingbattery(seepage24)
 • Connectingwireandconduit
 • Fuelsupplyvalves/plumbing
 • Crane,liftingstraps,chainsorcables
 • Two48”lengthsof1”pipe(NOTconduit)
 • Holepunchesfor16gasteel
 • Torquescrewdriver,5to50inch-poundrange
 • Voltage/frequencymeter
 • Variousspecialtoolsandequipment
Proper installation of the home generator requires the
completion of the following tasks:
Carbon Monoxide (CO) Detector
Carbon Monoxide (CO) detector in working order.
Placement
Required permits have been obtained.
Generator placed in a Carbon Monoxide (CO) safe
zone. See Placement of Standby Generator to
Reduce the Risk of Carbon Monoxide Poisoning.
Generator placed in a fire safe zone. See Placement
of Standby Generator to Reduce the Risk of Fire.
Generator placed in a water damage safe zone. See
Other General Location Guidelines.
Generator placed in a utility safe zone. See Other
General Location Guidelines.
Generator placed in a debris free zone. See Other
General Location Guidelines.
Fuel
Generator is connected to fuel source with flexible
fuel line, has no fuel leaks and conforms to local
codes. See The Gaseous Fuel System.
Proper fuel pressure has been measured with all
gas appliances operating. See The Gaseous Fuel
System.
Fuel system has been configured for the proper
fuel supply: Natural gas (NG) or liquefied petroleum
( LP). See Fuel Conversion.
Electrical
Generator neutral is connected to Automatic Transfer
Switch. See Generator AC Connection System.
Generator is grounded. See Grounding the
Generator.
Generator is connected to the transfer switch with
the specified wiring. See Utility Circuit Connection
and Transfer Switch Communication.
Generator is connected to the transfer switch with
the specified wiring. #18AWG twisted pair wiring
from the generator control panel to the transfer
switch is installed in a separate conduit from
high voltage wires unless the insulation rating on
all wiring is rated for 600V See Transfer Switch
Communication.
Dipswitches in most transfer switches must be set
to correspond to the wattage of the generator. See
Transfer Switch Operator/Installation Manual.
Operation
Cold weather kit is installed, if required. See Cold
Weather Kit.
Correct battery type is installed and fully charged.
See Final Installation Considerations.
Generator engine oil level is at full mark. See Final
Installation Considerations.
Utility was shut off to test the operation of generator
and transfer switch. Note any fault codes and make
corrections as required.
Installation Checklist
Not
for
Reproduction
9
Generator Placement
Before installing generator, consult with home owner and
convey the following requirements, which must be satisfied
before the installation is complete.
There are two equally important safety concerns in regards to
carbon monoxide poisoning and fire. There are also several
general location guidelines that must be met before the
installation in considered complete.
Exhaust Side of the Generator
A - Exhaust outlet side of weatherproof enclosure
WARNING Running engine gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide could result in death
serious injury, headache, fatigue, dizziness,
vomiting, confusion, seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that wil
not accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors,
ventilation intakes, soffit vents, crawl spaces, open garage
doors or other openings that can allow exhaust gas
to enter inside or be drawn into a potentially occupied
building or structure.
• Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions/recommendations. Smoke alarms cannot
detect carbon monoxide gas.
A
Not
for
Reproduction
10
All fossil fuel burning equipment, such as standby
generators, contains carbon monoxide (CO) gas in the
engine exhaust. CO gas is odorless, colorless and tasteless
and is unlikely to be noticed until a person is overcome.
CO gas can kill you so it is required that the following is
included as part of the installation:
 • Installgeneratoroutdoorsinanareathatwillnot
accumulate deadly exhaust gas.
 • DONOTinstallgeneratorwhereexhaustgascould
accumulate and enter inside or be drawn into a
potentially occupied building or structure.
 • BylawitisrequiredinmanystatestohaveaCarbon
Monoxide (CO) detector in operating condition in
your home. Carbon monoxide detector(s) (A) MUST
be installed and maintained indoors according to the
manufacturer’s instructions / recommendations. A CO
monitor is an electric device that detects hazardous
levels of CO. When there is a buildup of CO, the
monitor will alert the occupants by flashing visual
indicator light and alarm. Smoke alarms cannot detect
CO gas.
 • Yourneighbor(s)homemaybeexposedtotheengine
exhaust from your standby generator and must be
considered when installing your standby generator.
 • Ensureexhaustgasiskeptawayfrom:
B - windows
C - doors
D - ventilation intakes
E - soffit vents
F - garage doors
G - crawl spaces or other openings that can allow
exhaust gas to enter inside or be drawn into a
potentially occupied building or structure.
Placement of Standby Generator to REDUCE THE RISK OF CARBON MONOXIDE POISONING
The arrows in the figure below point to POTENTIAL points of entry for Carbon Monoxide Gas.
A
F
C
D
B
E
G
Not
for
Reproduction
11
 • Directthestandbygeneratorexhaustawayfromor
parallel to the building or structure. DO NOT direct
the generator exhaust towards a potentially occupied
building, structure, windows, doors, ventilation intakes,
soffit vents, crawl spaces, open garage doors or other
openings where exhaust gas could accumulate and
enter inside or be drawn into potentially occupied
building or structure.
 • DONOTplacestandbygeneratorinanyareawhere
leaves or debris normally accumulates. Position
standby generator in an area where winds will carry
the exhaust gas away from any potentially occupied
building or structure.
Placement of Standby Generator to REDUCE THE
RISK OF FIRE
The National Fire Protection Association (NFPA) standard
NFPA 37 establishes criteria for minimizing the hazard
of fire during the installation and operation of stationary
combustion engines. NFPA 37 limits the spacing of an
enclosed generator from openings in walls, structures, and
combustible materials outside the enclosure.
The placement requirements provided are based on
compliance to NFPA 37 2010 section 4.1.4.
WARNING
Exhaust heat/gases could ignite combustibles
or structures resulting in death, serious injury and/
or property damage.
• Exhaust outlet side of weatherproof enclosure must
have at least 5 ft. (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
• Standby generator weatherproof enclosure must be at
least 5 ft. (1.5 m) from windows, doors, any wall opening,
shrubs or vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang or trees.
• DO NOT place weatherproof enclosure under a deck or
other type of structure that may confine airflow.
• Use only flexible fuel line provided. Connect provided fuel
line to generator, DO NOT use with or substitute any other
flexible fuel line.
• Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
• DO NOT place weatherproof enclosure in manner other
than shown in illustrations.
Standby
Generator
Exhaust
Gas
Not
for
Reproduction
12
Examples of standby generator locations to
reduce the risk of fire:
Legend for Generator Locations to reduce the risk of fire:
A - Standby weatherproof enclosure must be at least
5 ft. (1.5 m) from windows, doors, any wall opening,
shrubs, or vegetation over 12 inches (30.5 cm) in
height.
B - Exhaust oulet side of weatherproof enclosure must
have at least 5 ft. (1.5 m) minimum clearance from any
structure, overhang or trees.
C - Standby weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang, or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of coverend structure that may confine airflow.
Single Combustible Structure Installation
A
Standby
Exhaust
Direction
A
B
Standby
A
Exhaust
Direction
B
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
Not
for
Reproduction
13
Legend for Generator Locations to reduce the risk of fire:
A - Standby weatherproof enclosure must be at least
5 ft. (1.5 m) from windows, doors, any wall opening,
shrubs, or vegetation over 12 inches (30.5 cm) in
height.
B - Exhaust oulet side of weatherproof enclosure must
have at least 5 ft. (1.5 m) minimum clearance from any
structure, overhang or trees.
C - Standby weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang, or trees.
Dual Combustible Structure Installation
A
A
A
A
5 ft. (1.5 m) min.
Exhaust
Direction
Standby
B
5 ft. (1.5 m) min.
Standby
Exhaust
Direction
Exhaust
Direction
B
C
B
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
Center of
Exhaust Panel
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
Not
for
Reproduction
14
Single Structure Installation with Structure Having a Fire Resistance Rating of at Least 1 Hour
Legend for Generator Locations to reduce the risk of fire:
A - Standby weatherproof enclosure must be at least
5 ft. (1.5 m) from windows, doors, any wall opening,
shrubs, or vegetation over 12 inches (30.5 cm) in
height.
B - Exhaust oulet side of weatherproof enclosure must
have at least 5 ft. (1.5 m) minimum clearance from any
structure, overhang or trees.
C - Standby weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang, or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of coverend structure that may confine airflow.
A
Exhaust
Direction
Standby
A
B
A
Standby
Exhaust
Direction
B
A
A
Exhaust
Direction
Standby
B
5 ft. (1.5 m) min.
2 ft. (0.6 m) min.
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
2 ft. (0.6 m) min.
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
3 ft. (0.9 m) min.
5 ft. (1.5 m) min.
Not
for
Reproduction
15
Dual Structure Installation with Structure Having a Fire Resistance Rating of at Least 1 Hour
Legend for Generator Locations to reduce the risk of fire:
A - Standby weatherproof enclosure must be at least
5 ft. (1.5 m) from windows, doors, any wall opening,
shrubs, or vegetation over 12 inches (30.5 cm) in
height.
B - Exhaust oulet side of weatherproof enclosure must
have at least 5 ft. (1.5 m) minimum clearance from any
structure, overhang or trees.
C - Standby weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang, or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of coverend structure that may confine airflow.
Other General Location Guidelines
 • Placethestandbygeneratorinapreparedlocation
that is flat and has provisions for water drainage.
 • Installthestandbygeneratorinalocationwhere
sump pump discharge, rain gutter down spouts, roof
run-off, landscape irrigation, or water sprinklers will
not flood the unit or spray the enclosure and enter
any air inlet or outlet openings.
 • Installthestandbygeneratorwhereitwillnotaffect
or obstruct any services including covered, concealed
and underground, such as telephone, electric, fuel
(natural gas / LPG vapor), irrigation, air conditioning,
cable, septic, sewer, well and so forth.
 • Installthestandbygeneratorgeneratorwhereleaves,
grass, snow, etc. will not obstruct air inlet and outlet
openings. If prevailing winds will cause blowing or
drifting, you may need to construct a windbreak to
protect the unit.
A
A
Standby
Exhaust
Direction
B
A
A
A
A
Standby
Exhaust
Direction
B
3 ft. (0.9 m)
Standby
Exhaust
Direction
B
2 ft. (0.6 m) min.
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
2 ft. (0.6 m) min.
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
5 ft. (1.5 m) min.
2 ft. (0.6 m) min.
5 ft. (1.5 m) min.
min.
2 ft. (0.6 m)
min.
Not
for
Reproduction
16
Electrical and Fuel Inlet Locations
The 3/4 inch N.P.T. fuel inlet connector (B) and electrical
inlet location (A) is shown here:
Lifting the Generator
The generator weighs more than 530 pounds (240 kg).
Proper tools, equipment and qualified personnel should be
used in all phases of handling and moving the generator.
Two48”lengthsof1”pipe(C), supplied by the installer, are
required to lift the generator manually. Insert pipes through
the lifting holes (D) located near the unit’s base.
Youmayalsolifttheunitusinga“hookandhoist”method
attached to the lifting pipes, provided that you use a spreader
bar to ensure that the chains or cables DO NOT touch the
generator’s roof.
After unit is in place, fill the lifting holes with the supplied
lifting hole plugs. Retouch any chipped paint with supplied
touch-up paint.
A
B
C
D
WARNING Hazardous Voltage - Contact with power
lines could cause electric shock or burns,
resulting in death or serious injury.
Lifting Hazard / Heavy Object - Could result
in serious injury.
• If lifting or hoisting equipment is used, DO NOT contact
any power lines.
• DO NOT lift or move generator without assistance.
• Use lifting pipes as described in Lifting the Generator.
• DO NOT lift unit by roof as damage to generator
will occur.
Not
for
Reproduction
17
Access Ports
The generator is equipped with an enclosure that has
several access doors, as shown. The doors are named for a
significant component located behind them, as follows:
A - Control Panel door (cover to be attached by installer)
B - Fuel Inlet Port (shown for reference)
C - Oil Drain door
D - Oil Fill door
E - Exhaust Port
The access doors must be installed whenever the unit
is running to assure proper cooling, reduce noise and for
added safety.
Each generator is shipped with a set of identical keys. These
keys fit the locks that secure the access ports.
To open access door:
1. Insert key into lock of access door handle and turn key
one quarter turn counterclockwise.
2. Grasp door’s handle and turn one quarter turn
counterclockwise to open. Remove key.
To close access door:
1. Close door and turn door’s handle one quarter
turnclockwise.
2. Insert key into lock of door handle and turn key one
quarter turn clockwise. Remove key.
B
A C
D E
Not
for
Reproduction
18
The Gaseous Fuel System
The information below is provided to assist gaseous fuel
system technicians in planning installations. In no way
should this information be interpreted to conflict with
applicable fuel gas codes. Consult with your local fuel
supplier or Fire Marshall if questions or problems arise.
TO THE INSTALLER: Consult with the generator owner(s)
and convey any technical considerations that might
affect their installation plans before applying these
general guidelines.
The following general rules apply to gaseous fuel
system piping:
 • Thepipingshouldbeofamaterialthatconformsto
federal and local codes, rigidly mounted and protected
against vibration.
 • Pipingshouldbeprotectedfromphysicaldamage
where it passes through flower beds, shrub beds, and
other cultivated areas where damage could occur.
 • Installtheflexiblesteelfuelline(B) (supplied) between
the generator fuel inlet port (A) and rigid piping to
prevent thermal expansion or contraction from causing
excessive stress on the piping material.
 • Aunion(C) or flanged connection shall be provided
downstream to permit removal of controls.
 • Amanometerportshouldbeprovided(D). When
the initial test runs are completed, the manometer
is removed and the port is plugged. The manometer
port permits temporary installation of a manometer
to ensure that the engine receives the correct fuel
pressure to operate efficiently throughout its operating
range.
 • Wheretheformationofhydratesoriceisknownto
occur, piping should be protected against freezing. The
termination of hard piping should include a sediment
trap (F) where condensate is not likely to freeze.
 • Aminimumofoneaccessible,approvedmanualshutoff
valve (E) shall be installed in the fuel supply line within
6 ft. (180 cm) of the generator.
 • Aminimum10ft.(3m)sectionofgaspipebetween
the primary fuel regulator and the generator fuel inlet
connection (acts as accumulator for high block loads).
 • Amanualfuelshut-offvalvelocatedintheinteriorof
the building.
 • Wherelocalconditionsincludeearthquake,
tornado, unstable ground, or flood hazards, special
consideration shall be given to increase strength and
flexibility of piping supports and connections.
 • Pipingmustbeifthecorrectsizetomaintainthe
required supply pressures and volume flow under
varying generator load conditions with all gas
appliances connected to the fuel system turned on and
operating.
 • Useapipesealantorjointcompoundapprovedfor
use with NG/LPG on all threaded fittings to reduce the
possibility of leakage.
 • Installedpipingmustbeproperlypurgedandleak
tested, in accordance with applicable codes and
standards.
Fuel Pressure
Both LP vapor and natural gas fuel supply pressure at the
generator’s fuel inlet port should be between the following
levels at full load with all gas appliances turned on and
operating.
 • NGis5-7”W.C.
 • LPis11-14”W.C.
Ensure that all gas line shutoff valves are OPEN and that
adequate fuel pressure is available whenever automatic
operation is desired.
Power Loss
Air density is less at high altitudes, resulting in less available
engine power. Specifically, engine power will decrease 3.5%
for each 1,000 feet (300 meters) above sea level and 1% for
each 10° F (5.6°C) above 77°F (25°C). Make sure you and
your installer consider these factors when determining total
generator load.
B
A
C
D
F
E
WARNING Propane and Natural Gas are extremely
flammable and explosive, which could cause
burns, fire or explosion resulting in death,
serious injury and/or property damage.
• LP gas is heavier than air and will settle in low areas.
• Natural gas is lighter than air and will collect in high
areas.
• The slightest spark could ignite these fuels and cause an
explosion.
• DO NOT light a cigarette or smoke.
WARNING Propane and Natural Gas are extremely
flammable and explosive, which could cause
burns, fire or explosion resulting in death,
serious injury and/or property damage.
• Before placing the generator into service, the fuel system
lines must be properly purged and leak tested.
• No leakage is permitted.
Not
for
Reproduction
19
Fuel Consumption
Estimated fuel supply requirements at half and full load for
natural gas and LP vapor fuels are shown below.
Natural Gas LP Vapor
1/2 Load Full Load 1/2 Load Full Load
12 kW 102 C 195 C 41 C 79 C
102,000 B 195,000 B 103,000 B 197,000 B
15 kW 126 C 242 C 56 C 108 C
126,000 B 242,000 B 140,000 B 270,000 B
20 kW N/A N/A 70.4 C 141.5 C
N/A N/A 176,825 B 353,650 B
C = Cubic feet per hour
B = BTU’s per hour
Physical Properties LP Vapor Natural
Gas
Normal Atmospheric State Gas Gas
Boiling Point (in °F):
Initial
End
-44
-44
-259
-259
Heating Value:
BTU per gallon (Net LHV*)
BTU per gallon (gross**)
Cubic feet (gas)
83,340
91,547
2,500
63,310
1,000
Density*** 36.39 57.75
Weight† 4.24 2.65
Octane Number:
Research
Motor
110+
97
110+
* LHV (Low Heat Value) is the more realistic rating.
** Gross heat value does not consider heat lost in the form of water
during combustion.
*** Densityisgivenin“CubicFeetofGasperGallonofLiquid”.
† Weightisgivenin“PoundsperGallonofLiquid”.
NPT 10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ft
3/4” 346 293 240 192 163 145 132 120 113 106 99
1” 653 549 446 360 307 274 250 230 211 197 187
Natural Gas Pipe Size - Gas Flow chart, in cubic feet per hour, specific gravity=0.65
NPT 10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ft
3/4” 277 192 158 126 107 95 87 79 74 69 65
1” 428 360 293 236 202 180 164 151 139 129 123
Liquid Propane (LP) Gas Pipe Size - Gas Flow chart, in cubic feet per hour, specific gravity=1.50
Fuel Pipe Sizing
The tables below provide the maximum capacity of pipe in cubic feet of gas per hour for gas pressures of 0.5 psi or less and a
pressure drop of 0.3 in. water column. Specific gravity of gas is shown.
Listed values compensate for a nominal amount of restriction from bends, fittings, etc. If an unusual number of fittings, bends,
or other restrictions are used, please refer to federal and local codes.
Withdrawal Rate 32° F 20° F 10° F 0° F -10° F -30° F -40° F
50 CFH 115 115 115 250 250 400 600
100 CFH 250 250 250 400 500 1000 1500
150 CFH 300 400 500 500 1000 1500 2500
200 CFH 400 500 750 1000 1200 2000 2500
300 CFH 750 1000 1500 2000 2500 4000 5000
Required Propane Tank Size
The required size of the propane tank at various temperatures when kept at least half full is shown below in the chart. Given
the gas withdrawal rate and the lowest average winter temperature, an installer can specify the required LP storage tank size.
Not
for
Reproduction
20
B
A
C
D
E
F
G
System Connectors
Except for the power output and grounding connectors, all signal wire connections are made to removable two- or ten-pin
connector plugs. Compare this illustration with your generator to familiarize yourself with the location of these important
connections. Count down to the proper pin location on the control board since visual alignment with the decal can
bemisleading:
A - Ten-pin Connector Plug
B - Fault Contacts — Use NO, COM and NC to hook up a
siren, light, etc. to alert you in case of a fault. Contacts
reverse state (NO goes to NC and vice versa) upon a
faultcondition.
C - Transfer Switch Communication — Connect to transfer
switch control board for communication interface using
18AWG copper twisted pair wire.
D - Remote LED Output — Use this to hook up the optional
remote LED. The remote LED will turn on and off in
a series of blinks if certain faults are detected in the
generator.
E - +12 Volt DC, .5 Amp Output — Internal power supply.
F - 240 Volt Utility — Use to hook up the 240V utility leads
from the transfer switch to the generator.
G - Two-pin Connector Plug
 • Forpoweroutputconnection,useminimum300volt75°C-90°Ccopperwire
of the AWG specified in this table (ref. NEC Table 310.16, 100 ft. Use National
Electric Code for correction factors and wire size calculations.):
 • ForUtilityCircuitconnectionuse#14AWGminimum300volt75°C-90°C
copperwire.
 • Fortransferswitchcommunicationuse#18AWGtwistedpairconductors,nogreaterthan200ftinlength,300volt
75°C-90°C copper wire.
 • Whenconnectingtotheconnectorplugs,fastenonlyonewiretoeachconnectorscrew.
 • Torqueconnectorplugscrewsto7in-lb(7.9Newtonmeter).
Generator Wire Size (AWG)
12 kW 8
15 kW 6
20 kW 4
Not
for
Reproduction
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88

Simplicity 040276B-01 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation
Ce manuel convient également à