Simplicity 040267A-0 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation

Ce manuel convient également à

Installation Manual
GEN12AD, GEN15AD, GEN20AD
Questions?
Help is just a moment away!
Call: Generator Helpline
877-369-9400 M-F 8-5 CT
Residential
Generator Systems
Rheem Manufacturing Company
Randleman, NC 27317
877-369-9400
Copyright © 2010 Rheem Manufacturing Company. All rights
reserved. No part of this material may be reproduced or transmitted
in any form by any means without the express written permission of
Rheem Manufacturing Company.
Thank you for purchasing this quality-built Rheem / Ruud residential generator. We are pleased that you’ve placed your
confidence in the Rheem or Ruud brand. When operated and maintained according to the instructions in the operator’s
manual, your residential generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with residential generator
systems and how to avoid them. This generator system is designed and intended only for use as an optional residential
standby system that provides an alternate source of electric power and to serve loads such as heating, refrigeration systems,
and communication systems that, when stopped during any power outage, could cause discomfort or inconvenience. Save
these original instructions for future reference.
This generator system requires professional installation before use. Your installer should follow the instructions completely
Where to Find Us
You never have to look far to find support and service for your generator. Consult your Yellow Pages. There are many
Rheem and Ruud authorized service dealers who provide quality service. You can also contact customer service by phone at
877-369-9400 between 8:00 AM and 5:00 PM CT.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Date of Purchase __________________________
Generator
Model Number __________________________
Model Revision __________________________
Serial Number __________________________
Engine
Model Number __________________________
Serial Number __________________________
3
Table of Contents
Important Safety Instructions........................4
Installation ....................................7
Installing Dealer/Contractor Responsibilities ........................7
Delivery Inspection............................................7
Shipment Contents............................................7
The Gaseous Fuel System .....................................11
Fuel Consumption ...........................................13
Fuel Pipe Sizing .............................................13
System Connectors ..........................................14
Grounding the Generator ......................................15
System Control Panel.........................................16
Final Installation Considerations ................................17
Initial Start-up (No Load)......................................17
Test Shutdown(s) Procedure ...................................19
Fuel Conversion .............................................21
12000 Watt Schematic Diagram ................................22
12000 Watt Wiring Diagram ...................................23
15000, 18000, and 20000 Watt Schematic Diagram .................24
15000, 18000, and 20000 Watt Wiring Diagram ....................25
Controls ..................................... 26
Operation .................................... 26
Automatic Operation Sequence .................................26
Setting Exercise Timer ........................................26
Installation Inspection ........................................26
4
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a
degree or level of hazard seriousness. A safety symbol
may be used to represent the type of hazard. The signal
word NOTICE is used to address practices not related to
personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that
it is safe for you and others. You must also make sure that
the procedure, work method or operating technique that you
choose does not render the generator system unsafe.
Explosion
Fire
Electrical Shock
Rotating Parts
Hot Surface
Toxic Fumes
Chemical BurnExplosive PressureAuto Start
Lift Hazard
Read Manual
WARNING Running engine gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide can cause headache,
fatigue, dizziness, vomiting, confusion, seizures,
nausea, fainting or death.
Operate generator ONLY outdoors.•
Install a battery operated carbon monoxide alarm near •
the bedrooms.
Keep exhaust gas from entering a confined area through •
windows, doors, ventilation intakes, or other openings.
WARNING Storage batteries give off explosive
hydrogen gas during recharging.
Slightest spark will ignite hydrogen
and cause explosion.
Battery electrolyte fluid contains
acid and is extremely caustic.
Contact with battery contents will cause severe
chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
DO NOT dispose of battery in a fire. Recycle battery.•
DO NOT allow any open flame, spark, heat, or lit cigarette •
during and for several minutes after charging a battery.
DO NOT open or mutilate the battery.•
Wear protective goggles, rubber apron, rubber boots and •
rubber gloves.
Remove watches, rings, or other metal objects.•
Use tools having insulated handles.•
WARNING The engine exhaust from this product
contains chemicals known to the State of California to
cause cancer, birth defects, or other reproductive harm.
WARNING Certain components in this product and
related accessories contain chemicals known to the
State of California to cause cancer, birth defects, or
other reproductive harm. Wash hands after handling.
Save These Instructions
5
WARNING Generator produces hazardous voltage.
Failure to properly ground generator can result
in electrocution.
Failure to isolate generator from power utility can
result in death or injury to electric utility workers
due to backfeed of electrical energy.
When using generator for backup power, notify •
utility company.
DO NOT touch bare wires or bare receptacles.•
DO NOT use generator with electrical cords which are •
worn, frayed, bare or otherwise damaged.
DO NOT handle generator or electrical cords while •
standing in water, while barefoot, or while hands or feet
are wet.
If you must work around a unit while it is operating, •
stand on an insulated dry surface to reduce the risk of a
shock hazard.
DO NOT allow unqualified persons or children to operate •
or service generator.
In case of an accident caused by electrical shock, •
immediately shut down the source of electrical power and
contact the local authorities. Avoid direct contact with
the victim.
Despite the safe design of the generator, operating this •
equipment imprudently, neglecting its maintenance or
being careless can cause possible injury or death.
Remain alert at all times while working on this equipment. •
Never work on the equipment when you are physically or
mentally fatigued.
Before performing any maintenance on the generator, •
disconnect the battery cable indicated by a NEGATIVE,
NEG or (-) first. When finished, reconnect that cable last.
After your system is installed, the generator may crank •
and start without warning any time there is a power
failure. To prevent possible injury, always set the
generator’s system switch to OFF, remove the service
disconnect from the disconnect box AND remove the
15 Amp fuse BEFORE working on the equipment.
WARNING Propane and Natural Gas are extremely
flammable and explosive.
Fire or explosion can cause severe burns
or death.
Install the fuel supply system according to NFPA 37 and •
other applicable fuel-gas codes.
Before placing the generator into service, the fuel system •
lines must be properly purged and leak tested.
After the generator is installed, you should inspect the fuel •
system periodically.
NO leakage is permitted.•
DO NOT operate engine if smell of fuel is present or other •
explosive conditions exist.
DO NOT smoke around the generator. Wipe up any oil •
spills immediately. Ensure that no combustible materials
are left in the generator compartment. Keep the area near
the generator clean and free of debris.
WARNING Contact with muffler area can result in
serious burns.
Exhaust heat/gases can ignite combustibles
or structures causing a fire.
DO NOT touch hot parts and AVOID hot exhaust gases.•
Allow equipment to cool before touching.•
DO NOT install the generator closer than 5 feet (1.5m) •
from any combustibles or structures with combustible
walls having a fire resistance rating of less than 1 hour.
Keep at least minimum distances shown in • General
Location Guidelines to insure for proper generator cooling
and maintenance clearances.
It is a violation of California Public Resource Code, •
Section 4442, to use or operate the engine on any forest-
covered, brush-covered, or grass-covered land unless
the exhaust system is equipped with a spark arrester, as
defined in Section 4442, maintained in effective working
order. Other states or federal jurisdictions may have
similar laws.
Contact the original equipment manufacturer, retailer, or
dealer to obtain a spark arrester designed for the exhaust
system installed on this engine.
Replacement parts must be the same and installed in the •
same position as the original parts.
6
notICE Improper treatment of generator can damage it
and shorten its life.
Use generator only for intended uses.•
If you have questions about intended use, contact your •
authorized dealer.
Operate generator only on level surfaces.•
Adequate, unobstructed flow of cooling and ventilating air •
is critical to correct generator operation.
The Oil Fill, Oil Drain and the Control Panel doors must be •
installed whenever the unit is running.
DO NOT expose generator to excessive moisture, dust, •
dirt, or corrosive vapors.
Despite the safe design of the generator, operating this •
equipment imprudently, neglecting its maintenance or
being careless can cause possible injury or death.
Remain alert at all times while working on this equipment. •
Never work on the equipment when you are physically or
mentally fatigued.
DO NOT start engine with air cleaner or air cleaner •
cover removed.
DO NOT insert any objects through cooling slots.•
DO NOT use the generator or any of its parts as a step. •
Stepping on the unit can cause stress and break parts.
This may result in dangerous operating conditions from
leaking exhaust gases, fuel leakage, oil leakage, etc.
If connected devices overheat, turn them off and •
disconnect them from generator.
Shut off generator if: •
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
notICE Exceeding generators wattage/amperage
capacity can damage generator and/or electrical devices
connected to it.
Start generator and let engine stabilize before connecting •
electrical loads.
WARNING Starter and other rotating parts can
entangle hands, hair, clothing, or accessories.
NEVER operate generator without protective housings, •
covers, or guards in place.
DO NOT wear loose clothing, jewelry or anything that may •
be caught in the starter or other rotating parts.
Tie up long hair and remove jewelry.•
Before servicing, remove 15 Amp fuse from control panel •
and disconnect Negative (NEG or -) battery cable.
CAUTION Installing the 15A fuse could cause the
engine to start.
Observe that the 15 Amp fuse has been removed from the •
control panel for shipping.
DO NOT install this fuse until all plumbing and wiring has •
been completed and inspected.
CAUTION Excessively high operating speeds increase
risk of injury and damage to generator.
Excessively low speeds impose a heavy load on generator.
DO NOT tamper with governed speed. Generator supplies •
correct rated frequency and voltage when running at
governed speed.
DO NOT modify generator in any way.•
WARNING Hazardous Voltage - Contact with power
lines can cause electric shock or burn.
Lifting Hazard / Heavy Object - Can cause
muscle strain or back injury.
If lifting or hoisting equipment is used, DO NOT contact •
any power lines.
DO NOT lift or move generator without assistance.•
Use lifting pipes as described in • Lifting the Generator.
The unit may shift on the lifting pipes during movement,
which can cause injury.
DO NOT lift unit by roof as damage to generator •
will occur.
7
Installation
Equipment Description
This product is intended for use as an optional residential
generator system which provides an alternate source
of electric power and to serve loads such as heating,
refrigeration systems, and communication systems that,
when stopped during any power outage, could cause
discomfort or inconvenience. This product does not qualify
for emergency standby as defined by NFPA 70 (NEC).
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
Only current licensed electrical and plumbing
professionals should attempt residential generator system
installations. Installations must strictly comply with all
applicable codes, industry standards and regulations.
Home Owner Responsibilities
 • Readandfollowtheinstructionsgiveninthe
operator’s manual.
 • Followaregularscheduleinmaintaining,caringfor
and using your residential generator, as specified in the
operator’s manual.
If you have questions about intended use, ask your installer
or dealer or call 877-369-9400 between 8:00 AM and
5:00 PM CT.
Installing Dealer/Contractor Responsibilities
 • Readandobservethesafetyrules.
 • InstallonlyanULapprovedtransferswitchthatis
compatible with the generator.
 • Readandfollowtheinstructionsgiveninthis
installation and start-up manual.
If operating the generator below 40°F (5°C), it is HIGHLY
RECOMMENDED that a Cold Weather Kit (includes oil
warmer and battery warmer) and a Cold Weather Breather Kit
(includes engine duct) be installed. These items are available
at your local servicing dealer.
Unpacking Precautions
The unit is shipped bolted to its mounting pad, ready
for installation. Avoid damage from dropping, bumping,
collision, etc. Store and unpack carton with the proper side
up, as noted on the shipping carton.
Delivery Inspection
After removing the carton, carefully inspect the generator for
any damage that may have occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight
bill and affix his signature under the consignor’s memo of
loss or damage. If loss or damage is noted after delivery,
separate the damaged materials and contact the carrier
for claim procedures. Missing or damaged parts are
not warranted.
Shipment Contents
The generator is supplied with:
 • Pre-attachedmountingpad
 • Fully-servicedoil/lubricatingsystem
 • Flexiblefuelhook-uphose
 • Installationandstart-upmanual
 • Operator’smanual
 • Engineoperator’smanual
 • Installationchecklist
 • Spareaccessdoorkeys
 • Spare15AmpATO-typefuse
 • Two-pinconnectorplug
 • Ten-pinconnectorplug
 • Touchuppaint
 • RemoteLEDindicatorkit(LED/plate/screws)
Not Included:
 • Startingbattery(seepage17)
 • Connectingwireandconduit
 • Fuelsupplyvalves/plumbing
 • Crane,liftingstraps,chainsorcables
 • Two48”lengthsof1”pipe(NOTconduit)
 • Holepunchesfor16gasteel
 • Torquescrewdriver,5to50inch-poundrange
 • Voltage/frequencymeter
 • Variousspecialtoolsandequipment
8
Generator Placement
Before installing generator, consult with home owner and
convey the following guidelines which may affect the desired
installation location.
Install generator outdoors in an area which will not
accumulate deadly exhaust gas. DO NOT install generator
where exhaust gas could accumulate and enter inside or be
drawn into a potentially occupied building. Ensure exhaust
gas is kept away from any windows, doors, ventilation intakes
or other openings that can allow exhaust gas to collect in a
confined area. Prevailing winds and air currents should be
taken into consideration when positioning generator.
General Location Guidelines
 • InstalltheunitoutdoorsONLY.
 • Placetheunitinapreparedlocationthatisflatandhas
provisions for water drainage.
 • Installtheunitinalocationwheresumppump
discharge, rain gutter down spouts, roof run-off,
landscape irrigation, or water sprinklers will not flood
the unit or spray the enclosure and enter any air inlet
our outlet openings.
 • Installtheunitwhereitwillnotaffectorobstruct
any services (including covered, concealed and
underground), such as telephone, electric, fuel,
irrigation, air conditioning, and so forth.
 • Installtheunitwhereairinletandoutletopeningswill
not become obstructed by leaves, grass, snow, etc. If
prevailing winds will cause blowing or drifting, you may
need to construct a windbreak to protect the unit.
 • Installthegeneratorascloseaspossibletothetransfer
switch and fuel supply to reduce the length of wiring,
conduit, and piping.
Laws or local codes may regulate the distance to the
fuel supply.
The minimum (MIN) clearances from aerial view of generator
(B) to combustible (D), and non-combustible (A) materials is
shown below.
 • Thesedistancesareprovidedtogivegeneratorlocation
guidance relative ONLY to combustibles, generator
cooling, and maintenance.
 • Theminimumdistancesinthefigureareasshown.
All four sides of the generator cannot be enclosed
or restricted, even if the minimum distances are
maintained. DO NOT connect (A) and/or (D) to (E)
 • Aroofcannotbeused.
 • Exhaust(C) must not be allowed to accumulate.
A Non-Combustible material with Fire Resistant Rating of
1 hour or greater
B Residential Standby Generator
C Engine Exhaust
D Combustible Material or Structure with a Fire
Resistance Rating of less than 1 hour.
E Any structure or material. DO NOT connect (A) and/or
(D) to (E).
A
B
E
D
E
C
3’
(1m)
5’ (1.5m)
5’ (1.5m) 5’ (1.5m)
2’
(62cm)
5’ (1.5m)
WARNING Exhaust heat/gases can ignite combustibles
or structures causing a fire.
DO NOT install the generator closer than 5 feet (1.5m) •
from any combustibles or structures with combustible
walls having a fire resistance rating of less than 1 hour.
WARNING Running engine gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide can cause headache,
fatigue, dizziness, vomiting, confusion, seizures,
nausea, fainting or death.
Operate generator ONLY outdoors.•
Install a battery operated carbon monoxide alarm near •
the bedrooms.
Keep exhaust gas from entering a confined area through •
windows, doors, ventilation intakes, or other openings.
9
The generator is shipped already attached to its mounting
pad. Unless mandated by local code, a concrete slab is
not required.
If mandated by local code, construct a concrete slab at least
3 inches thick and 6 inches longer and wider than the unit.
Attachunittoslabwith1/4”diameter(minimum)masonry
anchor bolts long enough to retain the unit.
Electrical and Fuel Inlet Locations
The 3/4 inch N.P.T. fuel inlet connector (B) and electrical
inlet location (A) is shown here:
Lifting the Generator
The generator weighs more than 530 pounds (240 kg).
Proper tools, equipment and qualified personnel should be
used in all phases of handling and moving the generator.
Two48”lengthsof1”pipe(C), supplied by the installer, are
required to lift the generator manually. Insert pipes through
the lifting holes (D) located near the unit’s base.
Youmayalsolifttheunitusinga“hookandhoist”method
attached to the lifting pipes, provided that you use a spreader
bar to ensure that the chains or cables DO NOT touch the
generator’s roof.
After unit is in place, fill the lifting holes with the supplied
lifting hole plugs. Retouch any chipped paint with supplied
touch-up paint.
C
D
WARNING Hazardous Voltage - Contact with power
lines can cause electric shock or burn.
Lifting Hazard / Heavy Object - Can cause
muscle strain or back injury.
If lifting or hoisting equipment is used, DO NOT contact •
any power lines.
DO NOT lift or move generator without assistance.•
Use lifting pipes as described in • Lifting the Generator.
The unit may shift on the lifting pipes during movement,
which can cause injury.
DO NOT lift unit by roof as damage to generator •
will occur.
A
B
10
Access Ports
The residential generator is equipped with an enclosure that
has several access doors, as shown. The doors are named
for a significant component located behind them, as follows::
A Control Panel door (cover to be attached by installer)
B Fuel Inlet Port (shown for reference)
C Oil Drain door
D Oil Fill door
E Exhaust Port
The access doors must be installed whenever the unit
is running to assure proper cooling, reduce noise and for
added safety.
Each generator is shipped with a set of identical keys. These
keys fit the locks that secure the access ports.
To open access door:
1. Insert key into lock of access door handle and turn key
one quarter turn counterclockwise.
2. Grasp door’s handle and turn one quarter turn
counterclockwise to open. Remove key.
To close access door:
1. Close door and turn door’s handle one quarter
turn clockwise.
2. Insert key into lock of door handle and turn key one
quarter turn clockwise. Remove key.
WARNING Contact with muffler and engine parts can
result in serious burns.
DO NOT touch hot parts and AVOID hot exhaust gases.•
Allow equipment to cool before touching.•
B
A C D E
11
The Gaseous Fuel System
The information below is provided to assist gaseous fuel
system technicians in planning installations. In no way
should this information be interpreted to conflict with
applicable fuel gas codes. Consult with your local fuel
supplier or Fire Marshall if questions or problems arise.
TO THE INSTALLER: Consult with the generator owner(s)
and convey any technical considerations that might
affect their installation plans before applying these
general guidelines.
The following general rules apply to gaseous fuel
system piping:
 • Thepipingshouldbeofamaterialthatconformsto
federal and local codes, rigidly mounted and protected
against vibration.
 • Pipingshouldbeprotectedfromphysicaldamage
where it passes through flower beds, shrub beds, and
other cultivated areas where damage could occur.
 • Installtheflexible,gaseoushose(supplied)between
the generator fuel Inlet port and rigid piping to prevent
thermal expansion or contraction from causing
excessive stress on the piping material.
Where local conditions include earthquake, tornado, unstable
ground, or flood hazards, special consideration shall be
given to increase strength and flexibility of piping supports
and connections.
 • Pipingmustbeofthecorrectsizetomaintainthe
required supply pressures and volume flow under
varying generator load conditions with all gas
appliances connected to the fuel system turned on
and operating.
 • Useapipesealantorjointcompoundapprovedfor
use with NG/LPG on all threaded fittings to reduce the
possibility of leakage.
 • Installedpipingmustbeproperlypurgedand
leak tested, in accordance with applicable codes
and standards.
Consider the following factors when planning to install the
fuel supply system:
 • Airdensityislessathighaltitudes,resultinginless
available engine power. Specifically, engine power will
decrease 3.5% for each 1,000 feet (300 meters) above
sea level and 1% for each 10° F (5.6°C) above 77°F
(25°C). Make sure you and your installer consider these
factors when determining total generator load..
 • Thegeneratorengineisfittedwithafuelmixersystem
that meets the specifications of the California Air
ResourcesBoardfor“tamper-proof”fuelsystems.
 • Aminimumofoneaccessible,approvedmanual
shutoff valve shall be installed in the fuel supply line
within 6 ft (1.8 m) of the generator. A union or flanged
connection shall be provided downstream from this
valve to permit removal of controls.
 • Naturalgasfuelsupplypressureatthegenerator’sfuel
inlet port should be between 5 to 7 inches of water
(in. W.C.) at full load with all gas appliances turned on
and operating.
 • LPgasfuelsupplypressureshouldbe11to14inches
of water (in. W.C.) at full load with all gas appliances
turned on and operating.
CAUTION The supplied flexible gaseous pipe is not to
be installed underground or in contact with the ground.
The entire flexible gaseous pipe must be visible for •
periodic inspection and must not be concealed within nor
contact nor run through any wall, floor, or partition.
WARNING Propane and Natural Gas are extremely
flammable and explosive.
Fire or explosion can cause severe burns
or death.
LP gas is heavier than air and will settle in low areas.•
Natural gas is lighter than air and will collect in •
high areas.
The slightest spark can ignite these fuels and cause •
an explosion.
DO NOT light a cigarette or smoke.•
WARNING Propane and Natural Gas are extremely
flammable and explosive.
Fire or explosion can cause severe burns
or death.
Before placing the generator into service, the fuel system •
lines must be properly purged and leak tested.
No leakage is permitted.•
12
The generator has been factory set to run on natural gas
or LP gas. If you need to change the 12 kW or 15 kW
units from natural gas to LP gas, the unit will need to be
reconfigured, as described in Fuel Conversion. The 18 kW
and 20 kW generators cannot be converted from natural gas
to LP gas or vice versa.
It is recommended that the fuel connection incorporate the
following components:
 • Amanualfuelshut-offvalvelocatedintheinteriorof
the building.
 • Amanualfuelshut-offvalvelocatedoutsidethe
building, just before the generator unit.
 • Wheretheformationofhydratesoriceisknownto
occur, piping should be protected against freezing. The
termination of hard piping should include a sediment
trap where condensate is not likely to freeze.
 • Amanometerportshouldbeprovided.
The manometer port permits temporary installation of
a manometer to ensure that the engine receives the
correct fuel pressure to operate efficiently throughout its
operating range.
When the initial test runs are completed, the manometer
is removed and the port is plugged. A typical final fuel
connection assembly is shown here, where (A) is the fuel
supply and (B) goes to the generator.
B
A
13
Fuel Consumption
Estimated fuel supply requirements at half and full load for
natural gas and LP vapor fuels are shown below.
Natural Gas LP Vapor
1/2 Load Full Load 1/2 Load Full Load
12 kW 102 C 195 C 41 C 79 C
102,000 B 195,000 B 103,000 B 197,000 B
15 kW 126 C 242 C 56 C 108 C
126,000 B 242,000 B 140,000 B 270,000 B
18 kW 160 C 293 C N/A N/A
160,000 B 293,000 B N/A N/A
20 kW N/A N/A 70.4 C 141.5 C
N/A N/A 176,825 B 353,650 B
C = Cubic feet per hour
B = BTU’s per hour
Physical Properties LP Vapor Natural
Gas
Normal Atmospheric State Gas Gas
Boiling Point (in °F):
Initial
End
-44
-44
-259
-259
Heating Value:
BTU per gallon (Net LHV*)
BTU per gallon (gross**)
Cubic feet (gas)
83,340
91,547
2,500
63,310
1,000
Density*** 36.39 57.75
Weight† 4.24 2.65
Octane Number:
Research
Motor
110+
97
110+
* LHV (Low Heat Value) is the more realistic rating.
** Gross heat value does not consider heat lost in the form of water
during combustion.
*** Densityisgivenin“CubicFeetofGasperGallonofLiquid”.
† Weightisgivenin“PoundsperGallonofLiquid”.
NPT 10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ft
3/4” 346 293 240 192 163 145 132 120 113 106 99
1” 653 549 446 360 307 274 250 230 211 197 187
Natural Gas Pipe Size - Gas Flow chart, in cubic feet per hour, specific gravity=0.65
NPT 10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ft
3/4” 277 192 158 126 107 95 87 79 74 69 65
1” 428 360 293 236 202 180 164 151 139 129 123
Liquid Propane (LP) Gas Pipe Size - Gas Flow chart, in cubic feet per hour, specific gravity=1.50
Fuel Pipe Sizing
The tables below provide the maximum capacity of pipe in cubic feet of gas per hour for gas pressures of 0.5 psi or less and a
pressure drop of 0.3 in. water column. Specific gravity of gas is shown.
Listed values compensate for a nominal amount of restriction from bends, fittings, etc. If an unusual number of fittings, bends,
or other restrictions are used, please refer to federal and local codes.
Withdrawal Rate 32° F 20° F 10° F 0° F -10° F -30° F -40° F
50 CFH 115 115 115 250 250 400 600
100 CFH 250 250 250 400 500 1000 1500
150 CFH 300 400 500 500 1000 1500 2500
200 CFH 400 500 750 1000 1200 2000 2500
300 CFH 750 1000 1500 2000 2500 4000 5000
Required Propane Tank Size
The required size of the propane tank at various temperatures when kept at least half full is shown below in the chart. Given
the gas withdrawal rate and the lowest average winter temperature, an installer can specify the required LP storage tank size.
14
B
A
C
D
E
F
G
System Connectors
Except for the power output and grounding connectors, all signal wire connections are made to removable two- or ten-pin
connector plugs. Compare this illustration with your generator to familiarize yourself with the location of these important
connections. Count down to the proper pin location on the control board since visual alignment with the decal can
be misleading:
A - Ten-pin Connector Plug
B - Fault Contacts Use NO, COM and NC to hook up a
siren, light, etc. to alert you in case of a fault. Contacts
reverse state (NO goes to NC and vice versa) upon a
fault condition.
C - Transfer Switch Communication — Connect to transfer
switch control board for communication interface using
18AWG copper twisted pair wire.
D - Remote LED Output — Use this to hook up the remote
LED supplied with the generator. The remote LED will
turn on and off in a series of blinks if certain faults are
detected in the generator.
E - +12 Volt DC, .5 Amp Output Internal power supply.
F - 240 Volt Utility — Use to hook up the 240V utility leads
from the transfer switch to the generator.
G - Two-pin Connector Plug
 • Forpoweroutputconnection,useminimum300volt75°C-90°Ccopperwire
of the AWG specified in this table (ref. NEC Table 310.16, 100 ft. Use National
Electric Code for correction factors and wire size calculations.):
 • ForUtilityCircuitconnectionuse#14AWGminimum300volt75°C-90°C
copper wire.
 • Fortransferswitchcommunicationuse#18AWGtwistedpairconductors,nogreaterthan200ftinlength,300volt
75°C-90°C copper wire.
 • Whenconnectingtotheconnectorplugs,fastenonlyonewiretoeachconnectorscrew.
 • Torqueconnectorplugscrewsto7in-lb(7.9Newtonmeter).
Generator Wire Size (AWG)
12 kW 8
15 kW 6
18 kW & 20 kW 4
15
Generator AC Connection System
A single-phase, three-wire AC connection system is used
in the generator. The stator assembly consists of a pair
of stationary windings with two leads brought out of each
winding. The junction of leads 22 and 33 forms the neutral
lead, as shown schematically and as wiring diagram. A
complete schematic and wiring diagram can be found later in
this manual.
Neutral is not bonded to ground at generator.
Grounding the Generator
Ground the generator per applicable codes, standards, and
regulations. The generator GND lug is located inside the
control panel door under the circuit breaker cover.
Utility Circuit Connection
“240VUtility”leadsmustberoutedinconduit.The
“240VUtility”leadsdeliverpowertothegenerator’scircuit
board, optional battery warmer and optional oil warmer. This
power also charges the battery. When power on these leads
is lost, the generator will start.
Using provided 2 pin connector plug and installer-supplied
minimum 300V, 14 AWG copper wire, connect each control
circuit terminal in the generator to the two-amp fuse
terminals in the automatic transfer switch.
When making connections, obey wire type and torque
specifications printed on the circuit breaker and neutral/
ground connector.
Transfer Switch Communication
(Units with ACCM II or later transfer switch only)
Using#18AWGtwistedpairconductors,nogreaterthan
200 ft in length, connect Tx Rx and Tx Rx GND from the
generator control panel (A) to GND and T/R on the transfer
switch control board (B).
33
240V
11
22
44
11
22
44
120V
120V
0
Neutral
Power Winding
Circuit
Breaker
Ground
To Transfer Switch
Line 1
Neutral
Neutral
Ground
Line 2
Circuit
Breaker
B
A
16
Fault Detection System
The generator may have to run for long periods of time with
no operator present. For that reason, the system is equipped
with sensors that automatically shut down the generator
in the event of potentially damaging conditions, such as
low oil pressure, high temperature, over speed, and other
conditions. Refer to Fault Detection System in the operator’s
manual for more detailed information.
The owner will use the remote LED indicator to observe
the status of the generator system. The remote LED will
turn on and off in a series of blinks if certain faults are
detected in the generator system. Consult with the owner
for a convenient location. Locate the electrical box in an
area visible by the home owner such as near a garage door
opener or security control panel.
To install the remote LED indicator:
1. Push the LED through the mounting plate from
the front until it snaps in place. The LED is
polarity sensitive.
2. Using provided 10 pole connector and installer-supplied
minimum 18 AWG wire, connect the remote LED to the
generator control board. Use wire nuts to attach wire to
LED leads.
3. Attach mounting plate to installer-supplied electrical box.
System Control Panel
The generator control panel, located inside the generator
housing, is shown below.
Brief descriptions of the controls used during installation are:
A – SET EXERCISE Used to set exercise cycle start time.
B - System Switch Switches modes to OFF or AUTO.
C - 15 Amp Fuse —- Protects DC control circuits.
D - MANUAL OVER-RIDE Used to manually start and stop
the generator.
E - Digital Display Displays running time in hours or
fault codes.
F - Circuit Breaker Must be ON to supply power to the
transfer switch.
More information may be found in Controls in the
operator’s manual.
System Switch
This two-position switch is the most important control on
the generator and is used as follows:
 • AUTO”positionisthenormaloperatingposition.If
a utility power outage is sensed, the system will start
the generator. When utility power is restored, lets the
engine stabilize internal temperatures, shuts off the
generator, and waits for the next utility power outage.
 • OFF”positionturnsoffrunninggenerator,prevents
unit from starting and resets any detected faults.
15 Amp Fuse
Protects the generator DC control circuits. If the fuse has
‘blown’ (melted open) or was removed, the engine cannot
crank or start. Replace the fuse using only an identical
ATO 15A fuse. One spare fuse is supplied with the unit.
If fuse was blown or removed, you will need to reset the
exercise timer (see Setting Exercise Timer).
B
A
C
E FD
17
Final Installation Considerations
Air Shrouds
The unit’s air shrouds are shipped loose in the carton. Attach
each shroud to the door panels as follows:
1. Position shroud’s locating pins over matching door
panel holes.
2. Press in on shroud until it snaps in place.
3. Confirm shroud pins are fully engaged in door holes.
Engine Oil
The engine is shipped from the factory pre-run and filled
with synthetic oil (API SJ/CF 5W-30). This allows for system
operation in a wide range of temperature and climate
conditions. Before starting the engine, check oil level and
ensure that engine is serviced as described in the engine
operator’s manual.
The use of synthetic oil does not alter the required oil
change intervals described in the engine operator’s manual.
Battery
The installer must supply and install a sealed, valve-
regulated, lead-acid rechargeable starting battery. The
starting battery MUST conform to the specifications shown
below in the chart.
Battery Specifications
Volts 12 Volt DC
Amps (MIN) 600 CCA (cold cranking amps)
Type AGM (Absorbed glass mat)
Terminal Hardware M6
Dimensions (MAX):
Width 5.5 inches (140mm)
Length 9.0 inches (230mm)
Height 8.25 inches (210mm)
Install the battery as described in Servicing the Battery in
the Maintenance section of the operator’s manual. Installer
mustconnectbatterychargewire(wire#13)topositive
battery terminal! Always make sure the NEGATIVE cable is
connected last.
Fuel Supply System
Ensure that all fuel pipe connections are tight, secure and
without leaks.
Ensure that all gas line shutoff valves are OPEN and that
adequate fuel pressure is available whenever automatic
operation is desired.
Initial Start-up (No Load)
Unit has been set-up for NG operation at the factory.
Fuel conversion, if needed, must be completed prior to
performing these steps. See Fuel Conversion later in
this section.
Before operating the generator or placing it into service,
inspect the entire installation carefully. Then begin testing the
system without any electrical loads connected, as follows:
1. Remove four screws that hold circuit breaker cover to
air intake guard.
2. Connect an accurate frequency meter to line side of
generator’s main circuit breaker.
3. Set generator’s main circuit breaker to ON
(closed) position.
4. Install 15 Amp fuse in control panel.
5. Set generator’s system switch to AUTO.
6. Push and hold MANUAL OVER-RIDE button on control
panel for about six seconds. Engine will start.
When the generator is started for the very first time, it
will require that air in the gaseous fuel lines be purged.
This may take a few minutes.
7. Listen for unusual noises, vibration or other indications
of abnormal operation. Check for oil leaks while
engine runs.
8. Let engine warm up for about five minutes to allow
internal temperatures to stabilize.
WARNING Battery posts, terminals and related
accessories contain lead and lead compounds,
chemicals known to the State of California to
cause cancer and reproductive harm. Wash hands
after handling.
notICE Any attempt to crank or start the engine before
it has been properly serviced with the recommended oil
will result in equipment failure.
Refer to • Maintenance in the Operator’s manual and engine
manual for oil fill information.
Damage to equipment resulting from failure to follow this •
instruction will void engine and generator warranty.
18
9. Check generator output at load side of circuit breaker.
Voltage should be 239-262 Volts, frequency should be
62.0 - 62.5 Hz.
If either parameter is outside these ranges, perform
Engine Adjustment described later in this section.
10. Check generator output between one generator
connection lug and neutral lug, then between other
generator connection lug and neutral lug. In both cases,
voltage reading should be between 119-131 Volts.
DO NOT proceed until you are certain that generator AC
voltage and frequency are correct and within the stated
limits. To obtain the proper generator frequency, see
Engine Adjustment.
11. Push and hold MANUAL OVER-RIDE button on control
panel again until engine stops.
12. Reinstall circuit breaker enclosure cover.
Engine Adjustment
There are regional variances in the composition of gaseous
fuel. If the generator output voltage or frequency measured
during Initial Start-Up is outside the listed ranges, the
combustibility of the gas supplied at the installation site may
be substantially different from the fuel used at the factory.
To adjust the engine for this difference, proceed as follows.
1. Remove four screws that hold circuit breaker cover to
air intake guard.
2. Connect an accurate frequency meter to line side of
generator’s main circuit breaker.
3. Ensure that the 15 Amp fuse is installed.
4. Set the generator’s main circuit breaker ON.
5. Set the generator’s system switch to AUTO.
6. Push MANUAL OVER-RIDE on control panel. When the
engine starts, allow it to warm up for five minutes.
7A. For a 12 kW generator, normal no load frequency is
62.0 to 62.5 Hz. If adjustment is needed at no load,
slowly rotate the governor adjustment nut (A) clockwise
and/or counterclockwise until frequency is 62.0 to
62.5 Hz.
7B. For a 15 kW, 18 kW or 20 kW generator,
normal no load frequency is 62.0 to 62.5 Hz. If
adjustment is needed at no load, slowly rotate the
governor adjustment screw (B) clockwise and/or
counterclockwise until frequency is 62.0 to 62.5 Hz.
8. Turn service disconnect to transfer switch OFF.
After a short time delay, transfer switch will connect
to generator.
9. Load generator to full load.
10. After load stabilizes, frequency should be
above 57.0 Hz.
11. If frequency is below 57.0 Hz, slowly rotate the
governor adjustment clockwise and/or counterclockwise
until frequency is above 57.0 Hz.
12. Turn service disconnect to transfer switch ON. Transfer
switch will connect to utility power after five minutes.
13. Push and hold MANUAL OVER-RIDE on control panel
until engine stops.
14. After the engine has stopped:
• Ifanadjustmentwasmadeinstep11,repeatsteps
2 through 7.
• Ifanadjustmentwasnotmadeinstep11,proceed
to step 15.
If no load frequency falls out of the no load range
shown in step 7 after full load adjustment is made,
contact an authorized service center.
15. Reinstall circuit breaker enclosure cover.
B
A
19
Test Shutdown(s) Procedure
The installer will test the system to verify that diagnostic
messages are correctly shown on the system control panel
digital display, as follows
FC_1 - Low Battery
No test procedure required for this fault.
FC_2 - Low Oil Pressure:
Locatewire#85connectedtotheoilpressureswitch.Shown
here is the oil pressure switch (D) and the oil filter location
(C) for the 12kW generator:
Shown here is the oil pressure switch (D) and the oil filter
location (C) for the 15kW, 18 kW and 20 kW generators:
Connectaninstaller-suppliedjumperwiretowire#85.
With the system switch in AUTO position, push and hold
MANUAL OVER-RIDE to start the generator. With the
generator running, connect other end of jumper to a good
ground location such as the engine block. The generator will
shut down and FC_2 will be displayed on the system control
panel. Remove the jumper wire. Turn the system switch to
OFF for 30 seconds to clear the fault.
FC_3 - Low Voltage
With the system switch in AUTO position, push and hold
MANUAL OVER-RIDE to start the generator. With the
generator running at no load, turn the generator circuit
breaker to OFF. The generator should shut down and
FC_3 will be displayed on the system control panel. Turn the
system switch to OFF for 30 seconds to clear the fault. Turn
the circuit breaker to ON position.
FC_4 - Engine Does Not Start
With the generator not running, turn the installer supplied
manual fuel valve to the OFF position. With the system
switch in AUTO, turn off utility power. The engine will crank,
attempting to start. After approximately a two-minute start
attempt (10 seconds of crank, 10 seconds of rest) the
generator should terminate the start attempt and FC_4 will
be displayed on the system control panel. Turn the system
switch to OFF for 30 seconds to clear the fault. Turn the
installer supplied fuel valve to the ON position.
FC_5 - Low Frequency
With the system switch in AUTO position, push and hold
MANUAL OVER-RIDE to start the generator. Locate the
governor lever and SLOWLY lower engine speed. Do NOT
change engine speed using the governor adjustment. When
the generator reaches a speed slower than 55 Hz for three
seconds the generator will shut down and FC_5 will be
displayed on the system control panel. Turn the system
switch to OFF for 30 seconds to clear the fault.
FC_6 - Engine Overspeed
With the system switch in AUTO position, push and hold
MANUAL OVER-RIDE to start the generator. Locate the
governor lever and SLOWLY raise engine speed. Do NOT
change engine speed using the governor adjustment.
When the generator output frequency is 65-70 Hz after
three seconds the generator will shut down and FC_6 will
be displayed on the system control panel. If the generator
output frequency is greater than 70 Hz the generator will
shut down immediately. Turn the system switch to OFF for
30 seconds to clear the fault.
C
D
C
D
20
FC_7 - High Temperature
Locatewire#95connectedtothetemperatureswitch.
Shown here is the temperature switch (B) and the oil filter
location (A) for the 12kW generator:
Shown here is the temperature switch (A) and the oil filter
location (B) for the 15kW, 18 kW and 20 kW generators:
Connectaninstaller-suppliedjumperwiretowire#95.
With the system switch in AUTO position, push and hold
MANUAL OVER-RIDE to start the generator. With the
generator running, connect other end of jumper to a good
ground location such as the engine block. The generator
should shut down and display FC_7 on the system control
panel. Remove the jumper wire. Turn the system switch to
OFF for 30 seconds to clear the fault.
FC_8 - Transfer Switch Fault
(Units with ACCM II or later transfer switch only)
Verify that utility power is present at the automatic transfer
switch. With the system switch in AUTO position, carefully
remove one of the 2 Amp fuses from the transfer switch.
FC_8 will display on the system control panel. Carefully
reinstall the fuse in the transfer switch, then turn the system
switch to OFF for 30 seconds to clear the fault.
Analyze Test Results
If any test procedure above does not cause the generator
to shut down and display the indicated fault, repair the fault
condition before putting the unit into service.
A
B
A
B
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

Simplicity 040267A-0 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation
Ce manuel convient également à