Hubbell Wiring Device-Kellems PD1304 Guide d'installation

Taper
Guide d'installation
Español
Français
English
PD1304 (PAGE 1) 04/18
Wiring Device-Kellems
Hubbell Incorporated (Delaware)
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
NOTICE - READ BEFORE INSTALLING THIS DEVICE.
This pin-and-sleeve device conforms to International Elec-
trotechnical Commission Standards IEC 309-1 and 309-2.
DO NOT USE non-lEC devices in the same premises as
IEC devices, unless assured that no improper mating can
occur.
GENERAL INFORMATION
1. NOTICE: For installation by a qualied electrician in
accordance with national and local electrical codes and
the following instructions.
2. CAUTION: RISK OF ELECTRIC SHOCK. Disconnect
power before installing. Never wire energized electrical
components.
3. CAUTION: USE COPPER CONDUCTORS ONLY.
4. Check that the device's type and rating are suitable for
the application.
5. Select conductors having 90°C or higher rated insulation
and sufcient ampacity in accordance with the 60°C
column of National Electrical Code® Table 310-16 or
Canadian Electrical Code Table 2.
6. The pilot contact (if installed) is rated A600 pilot duty,
600 VAC 10A.
Installation Instructions
AVIS - LIRE AVANT D’INSTALLER CE DISPOSITIF.
Ce dispositif à plot et douille se conforme aux normes CEI
309-1 et 309-2 de la Commission Électrotechnique Interna-
tionale. NE PAS UTILISER des dispositifs à plot et douille
non CEI dans des locaux dotés de dispositifs CEI, à moins
d'être assuré qu'il est impossible d'établir un raccordement
impropre.
RENSEIGNEMENTS GÉNÉRAUX
1. AVIS - Doit être installé par un électricien qualié
conformément aux codes de l’électricité nationaux et
locaux et selon les directives suivantes.
2. ATTENTION - RISQUE DE CHOC ÉLECTRIQUE.
Débrancher le circuit avant de procéder au montage.
Ne jamais câbler des composants électriques dans un
circuit sous tension.
3. ATTENTION - EMPLOYER UNIQUEMENT DES
CONDUCTEURS EN CUIVRE.
4. S’assurer que le type et les caractéristiques nominales
de ce dispositif conviennent à l’application.
5. Choisir des conducteurs dont l’isolant a une résistance
thermique de 90ºC ou plus et de capacité de courant
admissible sufsante selon le tableau 2 du Code
canadien de l’électricité.
6. Le contact pilot (s'il est installe) est classe circuit de
commande A600, 600 V CA, 10A.
Terminal screws
Gasket
Mounting screws (4)
Body
Interior (Inlet)
Self-tapping screws (Inlet)
Terminal hole (Outlet)
Green & yellow grounding
conductor (Outlet)
Tornillos de borne
Junta
Tornillos de jación (4)
Envoltura
Interior (Entrada)
Tornillos autorroscantes (En-
trada)
Oricio de borne (Tomacorri-
ente)
Hilo de puesta a tierra verde y
amarillo (Tomacorriente)
Vis de borne
Garniture de joint
Vis de xation (4)
Carter
Intérieur (Entrée)
Vis autotaraudeuses
(Entrée)
Orice de borne (Prise)
File de MALT vert et jaune
(Prise)
DIBUJOS DE DESPIECE
ÉCLATÉS
EXPLODED VIEWS RECEPTACLE (OUTLET)
PRISE DE COURANT
TOMACORRIENTE
Directives de montage Instrucciones de instalación
INLET
ENTRÉE DE COURANT
ENTRADA DE CORRIENTE
PRISES et ENTRÉES de COURANT
PLOT et DOUILLE
PIN & SLEEVE
RECEPTACLES & INLETS
TOMAS y ENTRADAS de CORRIENTE
de PERNO y M A NG A
AVISO - LEER ANTES DE INSTALAR ESTE DISPOSITIVO.
Este dispositivo de perno y manga se ajusta a los normas CEI
309-1 y 309-2 de la Comisión Electrotécnica Internacional.
NO UTILIZAR dispositivos que no sean CEI en locales pro-
vistos con dispositivos CEI, a menos de asegurarse de que
será imposible que se produzca un acoplamiento indebido.
INFORMACIÓN GENERAL
1. AVISO - Para ser instalado por un electricista calicado,
de acuerdo con los códigos eléctricos nacionales y
locales, y siguiendo estas instrucciones.
2. CUIDADO - RIESGO DE CHOQUE ELÉCTRICO.
Desconectar la corriente antes de la instalación. No
conectar nunca componentes eléctricos en un circuito
energizado.
3. CUIDADO - UTILIZAR SOLAMENTE CONDUCTORES
DE COBRE.
4. Asegurarse de que el tipo y las características nominales
del dispositivo sean apropiados para la aplicación.
5. Elegir conductores con una resistencia térmica del
aislante de 90ºC o más y de capacidad eléctrica suciente
según la columna 60ºC de la tabla 310-16 de la Norma
ocial mexicana NOM-001-SEMP.
6. El contacto piloto (si existe instalado) esta clasicado
para usarse como circuito de mando
A600, 600 V CA, 10A.
English Français Español
PD1304 (PAGE 2) 04/18
Tableau 2
CAPACITÉ du NATIONAL 20 A 30 A 60 A 100 A
DISPOSITIF INTERNAT'L 16 A 32 A 63 A
Longueur de pouces 1 1 1
dénudage -cond. mm 25 25 25 40
Couple de serrage lb•po 20 20 75 75
Vis de borne N•m 2.5 2.5 8.5 8.5
Couple de serrage lb•po 20 20
Vis de borne pilote N•m 2.5
INSTALLATION - Receptacle (Outlet)
Wiring Instructions
a) Strip each conductor as shown in Table 2. DO NOT
TIN CONDUCTORS.
b) Feed conductors through the gasket
c) Twist wire strands together on each conductor.
d) Loosen terminal screws. Insert conductors fully into
proper terminals as identied in Table 1.
e) Tighten terminal screws to torque shown in Table 2.
f) TAKE CAUTION THAT THERE ARE NO STRAY
WIRE STRANDS.
INSTALLATION - Inlet
1. Disassemble Device
Remove the interior from the body (loosen two screws
visible from front; screws may be captive in interior).
2. Wiring Instructions
a) Strip each conductor as shown in Table 2. DO NOT
TIN CONDUCTORS
b) Feed conductors through the gasket and the body.
c) Twist wire strands together on each conductor.
d) Loosen terminal screws. Insert conductors fully into
proper terminals as identied in Table 1.
e) Tighten terminal screws to torque shown in Table 2.
f) TAKE CAUTION THAT THERE ARE NO STRAY
WIRE STRANDS.
3. Reassemble Device
Assemble interior by tightening two screws until interior
is rmly seated in housing. Screws may continue to turn
after interior is seated. This is normal and harmless.
4. Mounting Details
Tighten mounting screws to 15-20 lbin (1.7-2.3 Nm).
INSTALLATION - Prise de courant
Méthode de câblage
a) Dénuder les conducteurs selon le Tableau 2. NE PAS
ÉTAMER LES CONDUCTEURS.
b) Passer les conducteurs dans l'ouverture de la garniture
de joint.
c) Torsader ensemble les brins de chaque conducteur.
d) Desserrer les vis de borne. Insérer les conducteurs à
fond dans les bornes appropriées conformément au
Tableau 1.
e) Serrer les vis de borne selon le couple indiqué au Tab-
leau 2.
f) S’ASSURER QUE TOUS LES BRINS SONT BIEN
INSÉRÉS.
INSTALLATION - Entrée de courant
1. Démonter le dispositif
Retirer l’intérieur du carter (desserrer les deux vis visibles
de l’avant; les vis peuvent être du type imperdable).
2. Méthode de câblage
a) Dénuder les conducteurs selon le Tableau 2. NE PAS
ÉTAMER LES CONDUCTEURS.
b) Passer les conducteurs dans l'ouverture de la garniture
de joint et le carter.
c) Torsader ensemble les brins de chaque conducteur.
d) Desserrer les vis de borne. Insérer les conducteurs à
fond dans les bornes appropriées conformément au
Tableau 1.
e) Serrer les vis de borne selon le couple du Tableau 2.
f) S’ASSURER QUE TOUS LES BRINS SONT BIEN
INSÉRÉS.
3. Remonter le dispositif
Assembler l’intérieur en serrant les deux vis jusqu’à ce
qu’il repose solidement dans le carter. Il arrive qu’on pu-
isse continuer à tourner les vis une fois l’intérieur en place.
Cela est normal et sans conséquence.
4. Détails de montage
Serrer les vis de xation à un couple de 1,7 à 2,3 Nm.
INSTALACIÓN - Tomacorriente
Instrucciones de cableado
a) Pelar los conductores como se muestra en la Tabla 2.
NO ESTAÑAR LOS CONDUCTORES.
b) Pasar los conductores por el hueco de la junta.
c) Torcer el conjunto de los hilos de cada conductor.
d) Aojar los tornillos de los bornes. Insertar los conduc-
tores a fondo en los bornes correspondientes como se
indica en la Tabla 1.
e) Ajustar los tornillos de los bornes como se indica en la
Tabla 2.
f) ASEGURARSE DE QUE NO QUEDEN HILOS SUEL-
TOS.
INSTALACIÓN - Entradas
1. Desarmar el dispositivo (Ver dibujo de despiece).
Retirar el interior de la envoltura (aojar los dos tornillos
visibles desde el frente, que pueden ser de tipo cautivo).
2. Instrucciones de cableado
a) Pelar los conductores como se muestra en la Tabla 2.
NO ESTAÑAR LOS CONDUCTORES.
b) Pasar los conductores por el hueco de la junta.
c) Torcer el conjunto de los hilos de cada conductor.
d) Aojar los tornillos de los bornes. Insertar los conduc-
tores a fondo en los bornes correspondientes como se
indica en la Tabla 1.
e) Ajustar los tornillos de los bornes como se indica en la
Tabla 2.
f) ASEGURARSE DE QUE NO QUEDEN HILOS SUEL-
TOS.
3. Volver a armar el dispositivo
Armar el interior ajustando los dos tornillos hasta que
apoye rmamente en la envoltura. Quizás los tornillos
puedan seguir girando una vez colocado el interior en su
lugar; se trata de algo normal y sin consecuencias.
4. Detalles de montave
Ajustar los tornillos de jación con un par de 1,7 a 2,3
Nm.
TABLEAU DE REPÉRAGE DES BORNES
BORNE CONDUCTEUR
Vert. Vis verte à Conducteur de MALT1 de l'appareil
tête hexagonale (Vert ou vert et jaune ou nu)
«W», blanc, «N» Conducteur d'alimentation mis à la
terre. Neutre (blanc ou gris)
L1, L2, L3 ou sans marque Conducteur d'alimentation non mis à
R1, S2, T3 ou sans marque la terre (Vivant).
X, Y, Z ou sans marque
Pilote Conducteur du circuit de commande
Tableau 1
1MALT = Mise à la terre
Tabla 2
CAPACIDAD del NACIONAL 20 A 30 A 60 A 100 A
DISPOSITIVO INTERNAC'L 16 A 32 A 63 A
Pelar los
conductores mm 25 25 25 40
Ajustar los tornillos de
bornes con un par de... N•m 2.5 2.5 8.5 8.5
Ajustar los tornillos del
piloto con un par de... N•m 2.5 2.5
Tabla 1
TABLA DE IDENTIFICACIÓN DE LOS BORNES
BORNE CONDUCTOR
Verde. Tornillo verde Conductor de puesta a tierra del equipo
de cabeza hexagonal (verde o verde y amarillo o desnudo)
«W», blanco, «N» Conductor de alimentación puesto a tierra,
Conductor neutro (blanco o gris)
L1, L2, L3 o sin marca Conductor de alimentación no puesto a
R1, S2, T3 o sin marca tierra (Vivo).
X, Y, Z o sin marca
Piloto Conductor del circuito de control
DEVICE RATING DOMESTIC 20 A 30 A 60 A 100 A
FOREIGN 16 A 32 A 63 A
Conductor Strip inch 1 1 1
Length mm 25 25 25 40
Torque Terminal lb•in 20 20 75 75
Screws N•m 2.5 2.5 8.5 8.5
Torque Pilot lb•in 20 20
terminal Screws N•m 2.5 2.5
Table 2
TERMINAL POLARITY IDENTIFICATION TABLE
TERMINAL CONDUCTOR
Green,
Equipment Grounding Conductor
Green Hex Head Screw (Green or Green/Yellow or Bare)
W, White, N Grounded Circuit Conductor
Neutral (White or Gray)
L1, L2, L3 or blank
R1, S2, T3 or blank Ungrounded Circuit Conductor,
X, Y, Z or blank (Line, Hot)
Pilot Control circuit conductor
Table 1
  • Page 1 1
  • Page 2 2

Hubbell Wiring Device-Kellems PD1304 Guide d'installation

Taper