Ashcroft KX1 Mode d'emploi

Catégorie
Chargeurs de batterie
Taper
Mode d'emploi
Montagebeispiele:
Mounting:
Montage:
KX1, KXD, KJ1, KXK, NXH,
KCK
1) Dichtring DIN 16 258
1) gasket DIN 16 258
1) joint DIN 16 258
2) Anschlusszapfen DIN 16 288
2) pressure connection DIN 16 288
2) connexions DIN 16 288
Fig. 1
KXF, KXFHT, KJ1, KJ1HT
1) Dichtring (USIT)
1) gasket (USIT)
1) joint (USIT)
2) Anschlussstutzen
2) pressure connection
2) connexions
Fig. 2
KXF, KXFHT
frontbündig dichtend
front sealed
joint conique
1) Schweißmuffe (Option)
1) weld in adapter (option)
1) Adapteur à souder (option)
2) Anschlussstutzen
2) pressure connection
2) connexions
Fig. 3
Anschlussplan:
Connection plan:
Tableau de raccordement:
K-SENSOR-BA Rev. V 13/09/2006
Betriebsanleitung
Druckmessumformer
Operating Instructions
Pressure Transmitters
Instructions de Service
Capteurs de pression
KX1, KXD, KXF, KXFHT,
KJ1, KJ1HT,
KXK, NXH, KCK
Ashcroft Instruments GmbH
Germany/Deutschland/Allemagne
Max-Planck-Straße 1
D-52499 Baesweiler
+49 (0) 24 01 80 80
Fax: +49 (0) 24 01 80 81 25
England/Angleterre
Unit 5 William James House
Cowley Road, Cambridge CB4 0WX
+44 (0) 12 23 39 55 00
Fax: +44 (0) 12 23 39 55 01
France/Frankreich
„206“ ZA Le Mandinet Rue des Campanules
F-77185 Lognes
+33 (0) 1 60 37 25 30
Fax: +33 (0) 1 60 37 25 39
1. Montagebedingungen
- Zul. Umgebungstemperatur: -30 ... 85 °C (Ex-Schutz -20 ... 75 °C).
- Zul. Messstofftemperatur: -30 ... 85 °C (KXFHT, KJ1HT -30 ... 200 °C,
Ex-Schutz -20 ... 75 °C) Abweichungen bei Sonderbauformen sind
möglich.
- Die angegebene Schutzart wird bei montiertem Steckverbinder erreicht.
Die Verwendung eines innenbelüfteten Kabels ist von Vorteil.
- Die Einbaulage ist beliebig.
2. Montage
- Dichtfläche des Druckanschlusses nach DIN 16 288 (z. B. G 1/4 oder G
1/2) vor Verschmutzung und Beschädigung schützen.
- Abdichtung:
- Geeignete Dichtscheibe verwenden (vgl. Fig. 1).
Sonderanschlüsse wie NPT- oder Innengewinde nach anwendungs-
technischen Normen abdichten.
Typ KXF ,KXFHT, KJ1 und KJ1HT (mit frontbündiger Membrane):
- Abdichten durch Dichtkonus (Fig. 3) oder Dichtring am Sechskant
(Fig. 2).
- Dichtkonus vor dem Einbau mit geeignetem Schmiermittel (z. B.
Molykote, Vaseline) schmieren; (anwendungstechnische Fragen
berücksichtigen; empfohlenes Anzugsdrehmoment ca. 70 Nm).
Passende Einschweißmuffen sind als Zubehör erhältlich. Anzugs-
drehmoment am Sechskant des Druckanschlusses aufbringen.
Achtung !
- Elektrostatische Entladungen vermeiden. Gehäuse erden.
- Druckmessumformer nur gemäß Anschlusstabelle bzw. Typenschild
anschließen.
- Keine Gegenstände in die Druckkanalbohrung einführen.
- Messbereich bzw. zulässigen Überdruck nicht überschreiten.
- Keinen Druckstrahl auf die Membrane richten.
- Bei Ausführungen mit frontbündiger Membran (KXF, KXFHT, KJ1,
KJ1HT): Membrane unter keinen Umständen deformieren. Membrane
kann bereits mit den Fingern unzulässig deformiert werden !
- Die Anforderungen der EN 50 281-1-1 (Ex-Schutz) z.B. in Bezug auf
Temperaturen und Staubauflagen sind zu erfüllen.
3. Elektrischer Anschluss
- Zulässige Speisespannung: 12 ... 30 VDC (12 ... 26 VDC bei eigensi-
cherer Ausführung).
- Anschluss gemäß Anschlusstabelle bzw. laut Typenschild-Angaben.
- Bei Ausführung in Zündschutzart II 2 GD, EEx ib IIC T6/T5 (eigensi-
cher) sicherheitstechnische Grenzwerte (U
i
= 26 V, I
i
= 100 mA, P
i
= 0,6
W, C
i
18 nF, L
i
8 µH) beachten.
4. Inbetriebnahme
- Auch in Druckspitzen den zulässigen Überdruck nicht überschreiten.
- Bei extremen Bedingungen (Wasserhammer) Schutzelemente einbau-
en (z. B. Dämpfungselemente, Prallplatten).
5. Abgleich
- Der Druckmessumformer ist werksseitig abgeglichen (kalibriert).
- Nullpunkt und Verstärkung können über Potentiometer nachgestellt
werden. Dazu Steckverbinder bzw. Kabelflansch vorsichtig demontie-
ren. Das Nullpunktpotentiometer ist mit einer Markierung versehen.
Wenn vorhanden, muss erst das EMV-Modul entfernt werden. Beim
Zusammenbau auf guten Kontakt des EMV-Moduls zum Gehäuse ach-
ten.
6. Wartung / Störung
- Der Druckmessumformer ist wartungsfrei.
- Im Störungsfall Verdrahtung, Spannungsversorgung und Einbau über-
prüfen.
- Bei nicht behebbaren Störungen wenden Sie sich bitte an unsere Nie-
derlassungen und Vertretungen, die Ihnen mit Beratung und Service
zur Verfügung stehen.
Technische Änderungen vorbehalten !
1. Installation requirements
- Ambient temperature: -30 ... 85 °C (Ex-proof -20 … 75 °C).
- Process temperature: -30 ... 85 °C (KXFHT, KJ1HT -30 … 200 °C,
Ex-proof -20 … 75 °C). Other limits are possible at special series.
- The stated protection degrees is achieved with connector completely
mounted.
- The using of a cable with vent tube is advantageous.
- Mounting position: no effect
2. Mounting
- Protect sealing surface of process - connection according to
DIN 16 288 (e.g. G 1/4 or G 1/2) against dirt and damage.
- Sealing:
- Use suitable gasket (Fig. 1).
Special threads (NPT or female threads) seal according existing
standards.
Type KXF ,KXFHT, KJ1 and KJ1HT (front seated diaphragm):
- Sealing by metal cone (Fig. 3) or a gasket at the hexagon (Fig. 2).
- Lubricate sealing cone with a suitable lubricant (e. g. Molykote,
Vaseline) according to application; advisable torque screw approx.
70 Nm; apply torque to hexagon surface only. Suitable weld in
adapters are available.
Attention !
- Avoid electrostatic discharge. Earth case.
- Connect wirings according connection table respectively pressure
transmitter-label.
- Do not insert objects into the pressure bore.
- Do not exceed range or admissible overpressure.
- Do not aim pressurized jets at the diaphragm.
- Pressure transmitters with front seated diaphragms (KXF, KXFHT, KJ1,
KJ1HT): be careful, diaphragm could be damaged even by touching !
- The requirements of EN 50 281-1-1 (Ex-proof) e.g. in relation to tem-
perature and contamination with dust have to be fulfilled.
3. Electrical connection
- Supply voltage: 12 ... 30 VDC (12 ... 26 VDC for intrinsically safe ver-
sion).
- Wiring according wiring table respectively pressure transmitter-label.
- For pressure transmitters with protection class II 2 GD, EEx ib IIC T6/T5
(intrinsically safe) please note the critical limits (U
i
= 26 V, I
i
= 100 mA,
P
i
= 0,6 W, C
i
18 nF,
L
i
8 µH).
4. Operation
- Even in pressure peaks, never exceed the overpressure limit.
- Take suitable precaution (e.g. pressure snubbers) under extreme con-
ditions.
5. Adjustment
- The pressure transmitter is factory calibrated.
- Zero and span can be adjust by potentiometers. Remove electrical
connector or cable flange carefully. The zero potentiometer is marked.
When installed, you have to dismount first the RFI-module. When as-
semble take care for good contact between
RFI-module and case.
6. Maintenance or default
- The pressure transmitter is free of maintenance.
- In case of any default check wiring, power supply and mounting.
- If the default is not on wiring or mounting apply for assistance from
ourselves or our agents. We will assist you with advice and service.
Modification reserved !
1. Conditions de montage
- Température ambiante: -30 ... 85 °C (version anti déflagrant -20 … 75 C).
- Température du fluide: -30 … 85 °C (KXFHT, KJ1HT -30 ... 200 °C,
version anti déflagrant -20 … 75 C). D'autres limites de température
sont possibles sur des modèles spéciaux.
- Les degrés de protection sont atteints lorsque les connexions sont
complètement installées.
- Position de montage: indifférente
2. Montage
- Protéger la surface du joint du raccordement process suivant les nor-
mes DIN 16 288 (par exemple G 1/4 ou G 1/2) contre l'encrassement et
la détérioration.
- Etanchéité:
- Utiliser un joint adapté (Fig. 1).
- Raccords spéciaux (NPT ou femelle) suivant les normes en vigueur.
Type KXF ,KXFHT, KJ1 et KJ1HT (à membrane affleurante):
- Par un joint conique (Fig. 3) ou un joint à la base de la connexion (Fig. 2).
- Lubrifier le joint conique avec un lubrifiant adapté (ex. Molykote,
Vaseline) en fonction des applications; couple de serrage préconi-
sé: 70 Nm environ; appliquer seulement sur les 6 pans de la
connexion. Adaptateurs à souder appropriés son disponibles.
Attention !
- Eviter les décharges électrostatiques. Prise de terre.
- Raccorder le capteur suivant le tableau ci-contre.
- Ne pas introduire de corps étrangers dans l'orifice de passage de la
pression.
- Ne pas dépasser l'échelle de mesure ou la pression maximum admissible.
- Ne pas diriger de jets de pression sur la membrane.
- Capteurs à membrane affleurante (KXF, KXFHT, KJ1, KJ1HT): manipu-
ler avec soin, la membrane peut être endommagée simplement au tou-
cher !
- Veuillez respecter les réquisitions de la norme EN 50 281-1-1 concer-
nant températures en dépositions des poussières pour zones dange-
reuses.
3. Raccordement électrique
- Tension d'alimentation: 12 ... 30 VDC (12 ... 26 VDC pour sécurité
intrinsèque)
- Raccordement suivant le tableau ci-contre et les types de capteurs.
- Pour capteurs avec classe de protection II 2 GD, EEx ib IIC T6/T5
(sécurité intrinsèque) faire attention valeurs limites (U
i
= 26 V, I
i
= 100
mA, P
i
= 0,6 W, C
i
18 nF,
L
i
8 µH).
4. Mise en service
- Même en cas de pics de pression, ne jamais dépasser la surpression
admissible du capteur.
- Prendre les précaution nécessaires (par ex. limiteurs de pression dans
cas de conditions d'utilisation extrêmes.
5. Etalonnage
- Le capteur est étalonné en usine.
- Le zéro et la plage peuvent être réglés par des potentiomètres. Démon-
ter la raccordement électrique ou la bride du câble soigneusement. Le
potentiomètre du zéro est indiqué.
Quand monté le module de EMC doit être démonté. Pendant la mon-
tage il faut payer attention au bon contact entré le module EMC et le
boîtier.
6. Entretien / Défectuosités
- Le capteur est exempt d'entretien.
- En cas d'anomalies, vérifier les files, alimentation et la montage.
- Si l'anomalie ne se situe pas au niveau des fil ou du montage contacter
nous ou l'un de nos agents. Nous vous conseillerons et vous dirigerons
vers le service après - vente si nécessaire.
Sous réserve de modifications !
  • Page 1 1
  • Page 2 2

Ashcroft KX1 Mode d'emploi

Catégorie
Chargeurs de batterie
Taper
Mode d'emploi