Simplicity 040381-01 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation
GE Home Generator Systems
Home Generator System
Installation and
Start-Up Manual
is a trademark of General Electric Company
and is under license by Briggs & Stratton
Power Products Group, LLC.
Copyright ©. All rights reserved. No part of this material may be
reproduced or transmitted in any form without the express written
permission of Briggs & Stratton Power Products Group, LLC.
314669 Revision F
2
DATE OF PURCHASE
GENERATOR
Model Number
Model Number
Model Revision
Serial Number
ENGINE
Thank you for purchasing this quality-built GE home generator. We’re pleased that you’ve placed your confidence in the GE
brand. When operated and maintained according to the instructions in the operator’s manual, your home generator will provide
many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with standby generators and
how to avoid them. This product is only for use as an optional generator system which provides an alternate source of electric
power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any
power outage, could cause discomfort or inconvenience.
Save these original instructions for future reference.
This generator requires professional installation before use. The installer should follow the instructions completely.
Where to Find Us
You never have to look far to find support and service for your generator. For quick service when you need it most fill out the
information below and keep your original receipt with this manual. You may contact Customer Service at (888) 575-8226, or
click on SERVICE & SUPPORT at www.homestandbygeneratorsystems.com, which provides a list of authorized dealers.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
3
Table of Contents
Safety Rules.....................................................4
Installation .....................................................7
Home Owner Responsibilities......................................................7
Installing Dealer/Contractor Responsibilities .......................................7
Cold Weather Kit..................................................................8
Unpacking Precautions ...........................................................8
Delivery Inspection................................................................8
Shipment Contents ...............................................................8
Installation Checklist - GE Home Generator Systems................................9
Generator Placement ............................................................11
Placement of Standby Generator to REDUCE THE RISK OF CARBON MONOXIDE POISONING 12
Placement of Standby Generator to REDUCE THE RISK OF FIRE.....................14
National Fire Protection Association (NFPA) Standard NFPA 37 Requirements and Testing 16
Electrical and Fuel Inlet Locations ................................................17
Lifting the Generator.............................................................18
Concrete Anchoring of Unit.......................................................18
Access Panels ...................................................................19
The Gaseous Fuel System ........................................................21
Fuel Factors .....................................................................22
System Connectors ..............................................................25
Generator AC Connection System ................................................26
Grounding the Generator.........................................................26
Power Connections from Generator to Transfer Switch ............................27
System Control Board............................................................28
Menu ...........................................................................29
General Set Up Screen ...........................................................30
Control Panel Prompts ...........................................................31
Advanced Settings Screen........................................................32
Service Code Detection System...................................................33
Final Installation Considerations ..................................................33
Initial Start-up (No Load) .........................................................34
Electronic Governor System ......................................................35
Operation..................................................... 36
Automatic Operation Sequence ..................................................36
Setting Exercise Timer............................................................36
Wireless Monitor.................................................................38
Schematic / Wiring Diagrams ....................................................41
4
Safety Rules
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a degree
or level of hazard seriousness. A safety symbol may be used
to represent the type of hazard. The signal word NOTICE is
used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
Important Safety Instructions
Explosion
Fire
Electrical Shock
Rotating Parts
Hot Surface
Toxic Fumes
Chemical BurnExplosive PressureAuto Start
Lift Hazard
Read Manual
WARNING The engine exhaust from this product contains
chemicals known to the State of California to cause cancer, birth
defects, or other reproductive harm.
WARNING Certain components in this product and related
accessories contain chemicals known to the State of California
to cause cancer, birth defects, or other reproductive harm. Wash
hands after handling.
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
Keep exhaust gas away from any windows, doors, ventilation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings
in this manual, and the tags and decals affixed to the unit
are, therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that it
is safe for you and others. You must also make sure that the
procedure, work method or operating technique that you
choose does not render the generator system unsafe.
5
WARNING Storage batteries give off explosive hydrogen gas
during recharging.Slightest spark will
ignite hydrogen and cause explosion,
resulting in death, serious injury and/
or property damage.Battery electrolyte fluid contains acid and
is extremely caustic.Contact with battery contents could cause
severe chemical burns.A battery presents a risk of electrical shock
and high short circuit current.
DO NOT dispose of battery in a fire. Recycle battery.
DO NOT allow any open flame, spark, heat, or lit cigarette during
and for several minutes after charging a battery.
DO NOT open or mutilate the battery.
Wear protective goggles, rubber apron, rubber boots and
rubber gloves.
Remove watches, rings, or other metal objects.
Use tools having insulated handles.
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death, serious injury and/or
property damage.
Install the fuel supply system according to NFPA 37 and other
applicable fuel-gas codes.
Before placing the generator into service, the fuel system lines
must be properly purged and leak tested.
After the generator is installed, you should inspect the fuel
system periodically.
NO leakage is permitted.
DO NOT operate engine if smell of fuel is present or other
explosive conditions exist.
DO NOT smoke around the generator. Wipe up any oil spills
immediately. Ensure that no combustible materials are left in the
generator compartment. Keep the area near the generator clean
and free of debris.
WARNING Generator produces hazardous voltage.
Failure to properly ground generator could result
in electrocution.
Failure to isolate generator from utility
power could result in death or serious injury to electric utility
workers due to backfeed of electrical energy.
DO NOT touch bare wires or bare receptacles.
DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
DO NOT handle generator or electrical cords while standing in
water, while barefoot, or while hands or feet are wet.
If you must work around a unit while it is operating, stand on an
insulated dry surface to reduce the risk of a shock hazard.
DO NOT allow unqualified persons or children to operate or
service generator.
In case of an accident caused by electrical shock, immediately
shut down the source of electrical power and contact the local
authorities. Avoid direct contact with the victim.
Despite the safe design of the residential generator, operating
this equipment imprudently, neglecting its maintenance or being
careless could cause possible injury or death.
Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
Before performing any maintenance on the generator, disconnect
the battery cable indicated by a NEGATIVE, NEG or (-) first. When
finished, reconnect that cable last.
After your system is installed, the generator may crank and start
without warning any time there is a power failure. To prevent
possible injury, always set the generator’s system switch to OFF,
remove the service disconnect from the disconnect box AND
remove the 15 Amp fuse BEFORE working on the equipment.
WARNING Hazardous Voltage - Contact with power lines could
cause electric shock or burn, resulting in death or
serious injury.Lifting Hazard / Heavy Object - Could
result in serious injury.
If lifting or hoisting equipment is used, DO NOT contact any
power lines.
DO NOT lift or move generator without assistance.
Use lifting pipes as described in Lifting the Generator.
DO NOT lift unit by roof as damage to generator will occur.
6
WARNING Starter and other rotating parts could entangle
hands, hair, clothing, or accessories resulting in
serious injury.
NEVER operate generator without protective housings, covers, or
guards in place.
DO NOT wear loose clothing, jewelry or anything that could be
caught in the starter or other rotating parts.
Tie up long hair and remove jewelry.
Before servicing, remove 15 Amp fuse from control panel and
disconnect Negative (NEG or -) battery cable.
CAUTION Installing the 15A fuse could cause the engine
to start at any time without warning resulting in minor or
moderate injury.
Observe that the 15 Amp fuse has been removed from the control
panel for shipping.
DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.
CAUTION Excessively high operating speeds could result in
minor injury and/or equipment damage.
Excessively low speeds impose a heavy load on generator.
DO NOT tamper with governed speed. Generator supplies correct
rated frequency and voltage when running at governed speed.
DO NOT modify generator in any way.
NOTICE Improper treatment of generator could damage it and
shorten its life.
Use generator only for intended uses.
If you have questions about intended use, contact your
authorized dealer.
Operate generator only on level surfaces.
Adequate, unobstructed flow of cooling and ventilating air is
critical for correct generator operation.
The access panels/door must be installed whenever the unit
is running.
DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
DO NOT start engine with air cleaner or air cleaner cover removed.
DO NOT insert any objects through cooling slots.
DO NOT use the generator or any of its parts as a step. Stepping
on the unit could cause stress and break parts. This may result in
dangerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
If connected devices overheat, turn them off and disconnect them
from generator.
Shut off generator and contanct an authorized deaker if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively;
-unit makes unusual noises.
WARNING
Exhaust heat/gases could ignite combustibles
or structures resulting in death, serious injury
and/or property damage. Contact with muffler
area could cause burns resulting in serious injury.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
Exhaust outlet side of weatherproof enclosure must have
at least 5 ft. (1.5 m) minimum clearance from any structure,
shurbs, trees or any kind of vegetation.
Standby generator weatherproof enclosure must be at least
5 ft. (1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
Standby generator weatherproof enclosure must have
a minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang or trees.
DO NOT place weatherproof enclosure under a deck or
other type of structure that may confine airflow.
Use only flexible steel fuel line provided. Connect provided
fuel line to generator, DO NOT use with or substitute any
other flexible fuel line.
Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot detect
smoke.
Keep at least minimum distances shown in General
Location Guidelines to insure for proper generator cooling
and maintenance clearances.
It is a violation of California Public Resource Code, Section
4442, to use or operate the engine on any forest-covered,
brush-covered, or grass-covered land unless the exhaust
system is equipped with a spark arrester, as defined in
Section 4442, maintained in effective working order. Other
states or federal jurisdictions may have similar laws.
Contact Briggs and Stratton, retailer, or dealer to obtain a
spark arrester designed for the exhaust system installed on
this engine.
Replacement parts must be the same and installed in the
same position as the original parts.
7
Read and follow the instructions given in the
operator’s manual.
Follow a regular schedule in maintaining, caring for
and using your home generator, as specified in the
operator’s manual.
Home Owner Responsibilities
Read and observe the safety rules.
Install only an UL approved transfer switch that is
compatible with the generator.
Read and follow the instructions given in this
installation and start-up manual.
Installing Dealer/Contractor Responsibilities
Installation
This product is only for use as an optional generator system
which provides an alternate source of electric power and
to serve loads such as heating, refrigeration systems, and
communication systems that, when stopped during any
power outage, could cause discomfort or inconvenience.
NOTICE This product does NOT qualify for either an
emergency standby or legally required standby system as
defined by NFPA 70 (NEC).
Emergency generator systems are intended to
automatically supply illumination, power, or both,
to designated areas and equipment in the event of
failure of the normal supply. Emergency systems may
also provide power for such functions as ventilation
where essential to maintain life, where current
interruption of the normal supply would produce
serious life safety or health hazards.
Legally Required standby generator systems are
intended to automatically supply power to selected
loads in the event of failure of the normal source
which could create hazards or hamper rescue or fire-
fighting operations.
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
Only current licensed electrical and plumbing professionals
should attempt home generator system installations.
Installations must strictly comply with all applicable codes,
industry standards, laws and regulations.
Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions/ recommendations. Smoke alarms
cannot detect carbon monoxide gas.
Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
Installation must strictly comply with all applicable
codes, industry standards, laws, and regulations.
Allow sufficient room on all sides of the generator for
maintenance and servicing.
8
After removing the carton, carefully inspect the generator for
any damage that may have occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss or
damage. If loss or damage is noted after delivery, separate
the damaged materials and contact the carrier for claim
procedures. Parts damaged in shipping are not warranted.
Delivery Inspection
The home generator system is supplied with:
Oil (5W30 Synthetic)
Flexible steel fuel line
Installation and start-up manual
Operator’s manual
Spare access roof keys
Spare 15 Amp ATO-type fuse
Remote wireless monitor
• Antenna
Not included:
Carbon monoxide detector(s)
Smoke detector(s)
Starting battery
Connecting wire and conduit
Fuel supply valves/plumbing
Crane, lifting straps, chains or cables
Two 60” lengths of 3/4” nominal minimum scheduled
40 steel pipe (NOT conduit)
Torque screwdriver, 5 to 50 inch-pound range
Voltage/frequency meter
Two (2) AA batteries for remote wireless monitor
Shipment Contents
Avoid damage from dropping, bumping, collision, etc. Store
and unpack carton with the proper side up, as noted on the
shipping carton.
Unpacking Precautions
Cold Weather Kit
If operating the generator below 30°F (-1°C), it is HIGHLY
RECOMMENDED that a Model 6231 Cold Weather Kit
(includes oil warmers and battery warmer) be installed.
These items are available at your local servicing dealer.
For cold weather areas (below 0°F (-18°C)) it is also
recommended that a BCI, Size 75, wet lead-acid battery be
used of 630 CCA minimum.
If you need more information on this matter, please call
(888) 575-8226, between 8:00 AM and 5:00 PM CT.
30°F (-1°C)
9
Carbon Monoxide (CO) Detector/ Smoke Detector
Carbon Monoxide (CO) detector(s) installed and in working
order.
Smoke detector(s) installed and in working order.
Placement
Required permits have been obtained.
Generator placed in an area free from Carbon Monoxide
(CO) buildup. See Placement of Standby Generator to
Reduce the Risk of Carbon Monoxide Poisoning.
Generator placed in an area compliant to NFPA 37. See
Placement of Standby Generator to Reduce the Risk of
Fire.
Generator placed in an area free from water damage. See
Other General Location Guidelines.
Generator placed in an area free from utility and other
home systems. See Other General Location Guidelines.
Generator placed in a debris free zone. See Other General
Location Guidelines.
Generator placed on flat ground with provisions for water
drainage.See Other General Location Guidelines.
Fuel
Generator is connected to fuel source with steel flexible
fuel line, has no fuel leaks and conforms to local codes. See
The Gaseous Fuel System.
Proper fuel pressure has been measured with all gas
appliances operating. See The Gaseous Fuel System.
Fuel system has been configured for the proper fuel
supply: Natural gas (NG) or liquefied petroleum ( LP). See
Fuel Conversion.
Fuel type: (circle one) NG LP
Fuel pipe size used: (circle one) 3/4” 1” 1-1/4” 1-1/2”
See NFPA 54.
Fuel pressure at fuel inlet port with generator on and at
full load and all gas appliances turned on and operating
____________________.
Electrical
Generator neutral is connected to Automatic Transfer
Switch. See Generator AC Connection System.
Generator is grounded. See Grounding the Generator and
NFPA 70,NEC.
Generator is connected to the transfer switch with the
specified wiring. See Utility Circuit Connection and
Transfer Switch Communication.
Generator is connected to the transfer switch with the
specified wiring. #18AWG twisted pair wiring from the
generator control panel to the transfer switch is installed
in a separate conduit from high voltage wires unless
the insulation rating on all wiring is rated for 600V See
Transfer Switch Communication.
Dipswitches in most transfer switches must be set to
correspond to the wattage of the generator. See Transfer
Switch Operator/Installation Manual.
Operation
Cold weather kit is installed in temperatures below 40°F
(5°C). See Cold Weather Kit.
Correct battery type is installed and fully charged. See
Final Installation Considerations.
Generator engine oil level is at full mark. See Final
Installation Considerations.
Circuit breaker is in the ON position.
Utility was shut off to test the operation of generator and
transfer switch. Note any fault codes and make corrections
as required.
AC Voltage Output___________________________.
Frequency Output___________________________.
Installation Checklist - GE Home Generator Systems
Proper installation of the home generator requires the completion of the following tasks:
Owner Information
Name: _____________________________________________
Address: ___________________________________________
___________________________________________________
Phone/e-mail: _______________________________________
Unit Information
Generator Model: ____________________________________
Generator Serial Number: _____________________________
Installing Contractor Information
Name: _____________________________________________
Address: ___________________________________________
___________________________________________________
Phone/FAX: _________________________________________
Electrician: _________________________________________
Signature: __________________________________________
Plumber: ___________________________________________
Signature: _________________________________________
Inspector Information
Name: _____________________________________________
Address: ___________________________________________
___________________________________________________
Title: _______________________________________________
Inspection Date: _____________________________________
This generator has been installed per the manufacturer’s
instructions:
Installing Contractor Signature: ______________________________
Date: ____________________________________________________
10
Intentionally Left Blank
11
Generator Placement
Before installing the generator, consult with the homeowner
and convey the following requirements, which must be
satisfied before the installation is complete.
There are two equally important safety concerns in regards
to carbon monoxide poisoning and fire. There are also
several general location guidelines that must all be met
before the installation is considered complete.
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
Keep exhaust gas away from any windows, doors, ventilation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
Exhaust Side of the Generator
A
Exhaust outlet side of weatherproof enclosure.
B
Air inlet side of weatherproof enclosure.
A BB
12
Placement of Standby Generator to
REDUCE THE RISK OF CARBON MONOXIDE POISONING
All fossil fuel burning equipment, such as standby
generators, contains carbon monoxide (CO) gas in the engine
exhaust. CO gas is odorless, colorless and tasteless and is
unlikely to be noticed until a person is overcome. CO gas can
kill you so it is required that the following is included as part
of the installation:
Install generator outdoors in an area that will not
accumulate deadly exhaust gas.
DO NOT install generator where exhaust gas could
accumulate and enter inside or be drawn into a
potentially occupied building or structure.
By law it is required in many states to have a Carbon
Monoxide (CO) detector in operating condition in
your home. Carbon monoxide detector(s)
A
MUST
be installed and maintained indoors according to
the manufacturer’s instructions/ recommendations.
A CO monitor is an electronic device that detects
hazardous levels of CO. When there is a buildup of
CO, the monitor will alert the occupants by flashing
visual indicator light and alarm. Smoke alarms cannot
detect CO gas.
Your neighbor(s) home may be exposed to the engine
exhaust from your standby generator and must be
considered when installing your standby generator.
Ensure exhaust gas is kept away from:
windows
doors
ventilation intakes
soffit vents
garage doors
crawl spaces or other openings that can allow
exhaust gas to enter inside or be drawn into a
potentially occupied building or structure.
A
The arrows in the figure below point to POTENTIAL points of entry for Carbon Monoxide Gas.
B
C
D
E
F
G
13
DO NOT place standby generator in any area where
leaves or debris normally accumulates. Position
standby generator in an area where winds will carry
the exhaust gas away from any potentially occupied
building or structure.
Direct the standby generator exhaust away from or
parallel to the building or structure. DO NOT direct the
generator exhaust towards a potentially occupied
building, structure, windows, doors, ventilation intakes,
soffit vents, crawl spaces, open garage doors or other
openings where exhaust gas could accumulate and
enter inside or be drawn into a potentially occupied
building or structure.
ENGINE
EXHAUST
STANDBY
GENERATOR
14
Structure
Center of Exhaust Panel
Standby
Exhaust
Direction
5 ft (1.5 m)
5 ft (1.5 m)
B
C
Placement of Standby Generator to REDUCE THE RISK OF FIRE
Examples of standby generator locations to reduce the
risk of fire:
The National Fire Protection Association (NFPA) standard
NFPA 37 establishes criteria for minimizing the hazard
of fire during the installation and operation of stationary
combustion engines. NFPA 37 limits the spacing of an
enclosed generator from openings in walls, structures and
combustible materials outside the enclosure.
The placement requirements provided are based on
compliance to NFPA 37 2010 section 4.1.4 and a full-scale
demonstration fire test. Details of compliance testing can be
found in section National Fire Protection Association (NFPA)
standard NFPA 37 requirements and testing.
A
Standby weatherproof enclosure must be at least 5 ft
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
B
Exhaust outlet side of weatherproof enclosure must
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
C
Standby weatherproof enclosure must have a
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
Standby Weatherproof enclosure must have a
minimum of 18 inches (45.7 cm) clearance from any
structures with or without a fire rating.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
Vertical Clearances
Legend for Generator Locations to reduce the risk of fire.
WARNING
Exhaust heat/gases could ignite combustibles
or structures resulting in death, serious injury and/or
property damage.
Exhaust outlet side of weatherproof enclosure must have at least
5 ft. (1.5 m) minimum clearance from any structure, shrubs, trees
or any kind of vegetation.
Standby generator weatherproof enclosure must be at least
5 ft. (1.5 m) from windows, doors, any wall opening, shrubs or
vegetation over 12 inches (30.5 cm) in height.
Standby generator weatherproof enclosure must have a minimum
of 5 ft. (1.5 m) overhead clearance from any structure, overhang
or trees.
DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
Use only flexible steel fuel line provided. Connect provided fuel line
to generator, DO NOT use with or substitute any other flexible fuel
line.
Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/recommendations.
Carbon monoxide alarms cannot detect smoke.
DO NOT place weatherproof enclosure in manner other than
shown in illustrations.
D
15
A
Standby weatherproof enclosure must be at least 5 ft
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
B
Exhaust outlet side of weatherproof enclosure must
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
C
Standby weatherproof enclosure must have a
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
18 in (45.7 cm) min
Standby
Exhaust
Direction
A
A
B
Standby
Exhaust
Direction
A
A
B
5 ft (1.5 m) min
Standby
Exhaust
Direction
5 ft (1.5 m)
A A
B
Standby
Exhaust
Direction
A
B
Generator Installations
5 ft
(1.5 m)
5 ft (1.5 m) min
18 in (45.7 cm) min
5 ft
(1.5 m)
5 ft (1.5 m) min
18 in (45.7 cm) min
5 ft (1.5 m)
D
D
D
D D
DD
Standby Weatherproof enclosure must have a
minimum of 18 inches (45.7 cm) clearance from any
structures with or without a fire rating.
NOTICE The gures below show the minimum installation distances allowed to structures and items in the legend.
16
Requirements:
NFPA 37 2010, section 4. 1. 4, Engines Located Outdoors.
Engines, and their weatherproof housings if provided, that
are installed outdoors shall be located at least 1.5m (5 ft)
from openings in walls and at least 1.5 m (5 ft) from structures
having combustible walls. A minimum separation shall not be
required where either of the following conditions exist:
1. The adjacent wall of the structure has a fire resistance
rating of at least 1 hour.
2. The weatherproof enclosure is constructed
of noncombustible materials and it has been
demonstrated that a fire within the enclosure will not
ignite combustible materials outside the enclosure. *
Annex A Explanatory Material
A.4.1.4 (2) Means of demonstrating compliance are by means
of full-scale fire tests or by calculation procedures, such as
those given in NFPA 555, Guide on Methods for Evaluating
Potential for Room Flashover.
To comply with condition 2, the weatherproof enclosure has
been constructed completely of non-combustible materials
and full-scale fire tests have been conducted to demonstrate
that a fire within the enclosure will not ignite combustible
materials outside the enclosure.
National Fire Protection Association (NFPA) Standard NFPA 37 Requirements and Testing
Place the standby generator in a prepared location
that is flat and has provisions for water drainage.
Install the standby generator in a location where
sump pump discharge, rain gutter down spouts, roof
run-off, landscape irrigation, or water sprinklers will
not flood the unit or spray the enclosure and enter
any air inlet or outlet openings.
Install the standby generator where it will not affect or
obstruct any services (including covered, concealed
and underground), such as telephone, electric, fuel
(natural gas / LPG vapor), irrigation, air conditioning,
cable, septic, sewer, well and so forth.
Install the standby generator where leaves, grass,
snow, etc will not obstruct air inlet and outlet
openings. If prevailing winds will cause blowing or
drifting, you may need to construct a windbreak to
protect the unit.
Other General Location Guidelines
17
Electrical and Fuel Inlet Locations
The 3/4 inch N.P.T. fuel inlet connector
A
and electrical inlet
location
B
is shown below.
A ½ inch knock-out is provided for the electrical inlet. This
inlet may be enlarged or supplemented to accommodate
a maximum conduit size of 1 ½ inches. Ensure that the
installed conduit(s) enter the unit in the zone shown in the
drawing such that they properly enter the electrical box and
do not interfere with the fully opened roof.
A
B
The home generator is supplied with a base that, unless
mandated by local code, does not require a concrete slab.
18
Lifting the Generator
The generator weighs more than 500 pounds (227 kg). Proper
tools, equipment and qualified personnel should be used in
all phases of handling and moving the generator.
Two 60” lengths of 3/4” nominal minimum scheduled 40
steel pipe
A
, supplied by the installer, are required to lift the
generator manually. Insert pipes through the lifting holes
B
located near the unit’s base.
You may also lift the unit using a “hook and hoist” method
attached to the lifting pipes, provided that you use a
spreader bar to ensure that the chains or cables DO NOT
touch the generator’s roof.
WARNING Hazardous Voltage - Contact with power lines could
cause electric shock or burn, resulting in death or
serious injury.Lifting Hazard / Heavy Object - Could
result in serious injury.
If lifting or hoisting equipment is used, DO NOT contact any
power lines.
DO NOT lift or move generator without assistance.
Use lifting pipes as described in Lifting the Generator.
DO NOT lift unit by roof as damage to generator will occur.
In areas determined to be hurricane prone, it is
recommended to anchor the standby generator to concrete.
The concrete anchors must be rated to hold 800 lbs ( kg).
There are four 7/16 inch hole locations around the base
of generator in which to anchor the unit.
Concrete Anchoring of Unit
A
B
C
C
C
C
C
NOTICE Unless mandated by local or state code, a concrete
slab is not required.
19
Each generator is shipped with a set of identical keys. These
keys fit in the lock on the front removable panel. The roof
must be unlocked in order for it to open.
Access Panels
The generator is equipped with an enclosure that has several
access panels, as shown.
The access panels and the components located behind them
are listed below:
A - Roof (Control Panel, air filter, oil dipstick, and circuit
breaker)
B - Front Access Panel (oil drain and oil filter)
D - Battery Panel (battery and generator data label)
E - Rear Access Panel (fuel regulator, fuel selector, and
engine starter)
F - Control Panel Cover (field wiring and control wires)
B
A
A
B
C
C
D
E
D
E
B
20
To open roof:
1. Insert key into lock of front panel. Gently push
down on roof above the lock to aid in turning the key.
Turn key one quarter turn clockwise.
2. Lift roof to the open position.
To remove front panel:
1. Remove the two bolts that secure the panel to the
unit.
2. Lift panel to remove from unit.
To secure front panel:
1. Place panel in unit.
2. Secure the panel with two bolts.
To remove rear panel:
1. Ensure the roof is in the open position.
2. Remove the two bolts that secure the panel to the
unit.
3. Lift panel to remove from unit.
To secure rear panel:
1. Slide panel into place on unit.
2. Secure the panel with two bolts.
To remove battery panel:
1. Ensure the roof is in the open position.
2. Remove the two bolts that secure the panel to the
unit.
3. Lift up on panel and remove.
To secure battery panel:
1. Place panel in unit.
2. Secure the panel with two bolts.
A
B
C
D
A
B
C
D
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132

Simplicity 040381-01 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation