Simplicity 076035-01 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation

Ce manuel convient également à

GE Home Generator Systems
48000 Watt Home
Generator System
Installation and
Start-Up Manual
2
Thank you for purchasing this quality-built GE home generator. We’re pleased that you’ve placed your confidence in the
GE brand. When operated and maintained according to the instructions in the operator’s manual, your home generator
will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with residential
generator systems and how to avoid them. This generator system is designed and intended only for use as an
optional home standby system that provides an alternate source of electric power and to serve loads such as heating,
refrigeration systems, and communication systems that, when stopped during any power outage, could cause
discomfort or inconvenience. Save these original instructions for future reference.
This home standby generator requires professional installation before use. The installer should follow the
instructions completely.
Where to Find Us
You never have to look far to find support and service for your generator. For quick service when you need
it most fill out the information below and keep your original receipt with this manual. You may contact
Customer Service at 888‑575‑8226 between 8:00 AM and 5:00 PM CT., or click on SERVICE & SUPPORT at
www.homestandbygeneratorsystems.com, which provides a list of authorized dealers.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Date of Purchase: _____________________________
Generator
Model Number _____________________________
Model Revision _____________________________
Serial Number _____________________________
Engine
Serial Number _____________________________
3
Table of Contents
Safety Rules................................................4
Installation ................................................7
Home Owner Responsibilities ..........................................7
Installing Dealer/Contractor Responsibilities............................7
Unpacking Precautions................................................7
Shipment Contents ...................................................8
Generator Location ...................................................8
Electrical and Fuel Inlet Locations.....................................10
The Gaseous Fuel System ............................................13
Fuel Conversion .....................................................14
Fuel Consumption ...................................................15
System Connectors ..................................................16
Grounding the Generator.............................................18
Final Installation Considerations ......................................20
Initial Start‑up (No Load) .............................................21
Operation.................................................22
Automatic Operation Sequence .......................................22
Setting Exercise Timer ...............................................22
Installation Inspection ...............................................23
Schematic Diagram........................................ 24
Wiring Diagram ........................................... 27
4
Safety Rules
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a degree
or level of hazard seriousness. A safety symbol may be used
to represent the type of hazard. The signal word NOTICE is
used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
Important Safety Instructions
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings
in this manual, and the tags and decals affixed to the unit
are, therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that it
is safe for you and others. You must also make sure that the
procedure, work method or operating technique that you
choose does not render the generator system unsafe.
Fire
Toxic Fumes
Explosive Pressure
Rotating Fan Blade
Lift Hazard Read Manual
Exploding BatteryRotating Belt/Pulley
Chemical BurnAuto Start
Hot SurfaceRotating Parts
Electrical ShockExplosion
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors.
• Install a battery operated carbon monoxide alarm near
the bedrooms.
• Keep exhaust gas from entering a confined area through
windows, doors, ventilation intakes, or other openings.
WARNING The engine exhaust from this product contains
chemicals known to the State of California to cause cancer, birth
defects, or other reproductive harm.
WARNING Certain components in this product and related
accessories contain chemicals known to the State of California
to cause cancer, birth defects, or other reproductive harm. Wash
hands after handling.
5
WARNING Storage batteries give off explosive hydrogen gas
during recharging.
Slightest spark will ignite hydrogen and
cause explosion, resulting in death, serious
injury and/or property damage.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents could cause severe chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette during
and for several minutes after charging a battery.
• DO NOT open or mutilate the battery.
• Wear protective goggles, rubber apron, rubber boots and
rubber gloves.
• Remove watches, rings, or other metal objects.
• Use tools having insulated handles.
WARNING Generator produces hazardous voltage.
Failure to properly ground generator could result
in electrocution.
Failure to isolate generator from power utility could result
in death or serious injury to electric utility workers due to
backfeed of electrical energy.
• When using generator for backup power, notify utility company.
• DO NOT touch bare wires or bare receptacles.
• DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
• DO NOT handle generator or electrical cords while standing in
water, while barefoot, or while hands or feet are wet.
• If you must work around a unit while it is operating, stand on an
insulated dry surface to reduce the risk of a shock hazard.
• DO NOT allow unqualified persons or children to operate or
service generator.
• In case of an accident caused by electrical shock, immediately
shut down the source of electrical power and contact the local
authorities. Avoid direct contact with the victim.
• Despite the safe design of the residential generator, operating
this equipment imprudently, neglecting its maintenance or being
careless could cause possible injury or death.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• Before performing any maintenance on the generator, disconnect
the battery cable indicated by a NEGATIVE, NEG or () first. When
finished, reconnect that cable last.
• After your system is installed, the generator may crank and start
without warning any time there is a power failure. To prevent
possible injury, always set the generator’s system switch to OFF,
remove the service disconnect from the disconnect box AND
remove the 15 Amp fuse BEFORE working on the equipment.
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death, serious injury and/or
property damage.
• Install the fuel supply system according to NFPA 37 and other
applicable fuel-gas codes.
• Before placing the generator into service, the fuel system lines
must be properly purged and leak tested.
• After the generator is installed, you should inspect the fuel
system periodically.
• NO leakage is permitted.
• DO NOT operate engine if smell of fuel is present or other
explosive conditions exist.
• DO NOT smoke around the generator. Wipe up any oil spills
immediately. Ensure that no combustible materials are left in the
generator compartment. Keep the area near the generator clean
and free of debris.
WARNING Hazardous Voltage - Contact with power lines could
cause electric shock or burn, resulting in death or
serious injury.
Lifting Hazard / Heavy Object - Could result in
serious injury.
• If lifting or hoisting equipment is used, DO NOT contact any
power lines.
• DO NOT lift or move generator without assistance.
• Use lifting pipes as described in Lifting the Generator.
• DO NOT lift unit by roof as damage to generator will occur.
6
CAUTION Excessively high operating speeds could result in
minor injury and/or equipment damage.
Excessively low speeds impose a heavy load on generator.
• DO NOT tamper with governed speed. Generator supplies correct
rated frequency and voltage when running at governed speed.
• DO NOT modify generator in any way.
WARNING Exhaust heat/gases could ignite combustibles or
structures resulting in death, serious injury and/or
property damage.
Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• DO NOT install the generator closer than 5 feet (1.5m) from any
combustibles or structures with combustible walls having a fire
resistance rating of less than 1 hour.
• Keep at least minimum distances shown in General Location
Guidelines to insure for proper generator cooling and
maintenance clearances.
• It is a violation of California Public Resource Code, Section 4442,
to use or operate the engine on any forest-covered, brush-
covered, or grass-covered land unless the exhaust system is
equipped with a spark arrester, as defined in Section 4442,
maintained in effective working order. Other states or federal
jurisdictions may have similar laws.
Contact the original equipment manufacturer, retailer, or dealer to
obtain a spark arrester designed for the exhaust system installed
on this engine.
• Replacement parts must be the same and installed in the same
position as the original parts.
WARNING Moving parts could crush and cut.
Starter and other rotating parts
could entangle hands, hair, clothing,
or accessories resulting in serious injury.
• NEVER operate generator without protective housings, covers, or
guards in place.
• DO NOT wear loose clothing, jewelry or anything that could be
caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
• Before servicing, remove 15 Amp fuse from control panel and
disconnect Negative (NEG or ) battery cable.
WARNING Hot pressurized coolant could cause serious injury
and/or property damage.
• DO NOT open radiator cap when hot.
• Before servicing, allow coolant to cool.
CAUTION Installing the 15A fuse could cause the engine
to start at any time without warning resulting in minor or
moderate injury.
• Observe that the 15 Amp fuse has been removed from the control
panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.
NOTICE Improper treatment of generator could damage it and
shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, contact your
authorized dealer.
• Operate generator only on level surfaces.
• Adequate, unobstructed flow of cooling and ventilating air is
critical to correct generator operation.
• The access panels/door must be installed whenever the unit
is running.
• DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• DO NOT start engine with air cleaner or air cleaner cover removed.
• DO NOT insert any objects through cooling slots.
• DO NOT use the generator or any of its parts as a step. Stepping
on the unit could cause stress and break parts. This may result in
dangerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
• If connected devices overheat, turn them off and disconnect them
from generator.
• Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
NOTICE Exceeding generators wattage/amperage capacity could
damage generator and/or electrical devices connected to it.
• Start generator and let engine stabilize before connecting
electrical loads.
7
• Readandfollowtheinstructionsgiveninthe
Operator’s Manual.
• Followaregularscheduleinmaintaining,caringfor
and using your home generator, as specified in the
Operator’s Manual.
Home Owner Responsibilities
The system is equipped with an optional water heater that is
activated when ambient temperature is less than 80°F AND
utility power is present at the transfer switch.
If you need more information on this matter, please call
888‑575‑8226, between 8:00 AM and 5:00 PM CT.
• Readandobservethesafetyrules.
• InstallonlyanULapprovedtransferswitchthatis
compatible with the generator.
• Readandfollowtheinstructionsgiveninthis
Installation and Start-up Manual.
Installing Dealer/Contractor Responsibilities
The unit is shipped ready for installation on a prepared
reinforced cement slab or engineered base. Avoid
damage from dropping, bumping, collision, etc. Store and
unpack carton with the proper side up, as noted on the
shipping carton.
Unpacking Precautions
Installation
This product is intended for use as an optional home
generator system which provides an alternate source
of electric power and to serve loads such as heating,
refrigeration systems, and communication systems that,
when stopped during any power outage, could cause
discomfort or inconvenience. This product does not qualify
for emergency standby as defined by NFPA 70 (NEC).
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
Only current licensed electrical and plumbing
professionals should attempt home generator system
installations. Installations must strictly comply with all
applicable codes, industry standards and regulations.
8
After removing the carton, carefully inspect the generator for
any damage that may have occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss or
damage. If loss or damage is noted after delivery, separate
the damaged materials and contact the carrier for claim
procedures. Missing or damaged parts are not warranted.
Delivery Inspection
The home generator system is supplied with:
• Fully-servicedcoolantsystem
• Fully-servicedoil/lubricatingsystem
• Flexiblefuelhook-uphose
• Installationandstart-upmanual
• Operator’smanual
• Accessdoorkeys
• Spare15AmpATO-typefuse
• Ten-pincontrolpanelconnector
• Touchuppaint
• RemoteLEDindicatorkit(LED/plate/screws)
Not Supplied:
• Startingbattery(seep.20)
• Reinforcedconcretepad
• Connectingwireandconduit
• Fuelsupplyvalves/plumbing
• Two60”lengthsof2”Schedule40pipe(NOTconduit)
• Crane,liftingstraps,chainsorcables
• Holepunchesfor7gasteel
• Torquescrewdriver,5to50inch-poundrange
• Voltage/frequencymeter
• Variousspecialtoolsandequipment
Shipment Contents
Before installing the generator, consult with the homeowner
and convey the following guidelines, which may affect the
desired location.
Generator Location
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors.
• Install a battery operated carbon monoxide alarm near
the bedrooms.
• Keep exhaust gas from entering a confined area through
windows, doors, ventilation intakes, or other openings.
WARNING Exhaust heat/gases could ignite combustibles
or structures resulting in death, serious injury and/or
property damage.
• DO NOT install the generator closer than 5 feet (1.5m) from any
combustibles or structures with combustible walls having a fire
resistance rating of less than 1 hour.
9
A Non-Combustible material with Fire Resistant Rating of
1 hour or greater
B Home Standby Generator
C Engine Exhaust
D Combustible Material or Structure with a Fire
Resistance Rating of less than 1 hour
E Any structure or material. DO NOT connect (A) and/or
(D) to (E)
Install generator outdoors in an area which will not
accumulate deadly exhaust gas. DO NOT install generator
where exhaust gas could accumulate and enter inside or be
drawn into a potentially occupied building. Ensure exhaust
gas is kept away from windows, doors, ventilation intakes or
other openings that could allow exhaust gas to collect in a
confined area. Prevailing winds and air currents should be
taken into consideration when positioning generator.
General Location Guidelines
• InstalltheunitoutdoorsONLY.
• Placetheunitonapreparedconcreteslabthatisflat,
level, and has provisions for water drainage.
• Installtheunitinalocationwheresumppump
discharge, rain gutter down spouts, roof run-off,
landscape irrigation, or water sprinklers will not flood
the unit or spray the enclosure and enter any air inlet
or outlet openings.
• Installtheunitwhereitwillnotaffectorobstruct
any services (including covered, concealed and
underground), such as telephone, electric, fuel,
irrigation, air conditioning, and so forth.
• Installtheunitwhereairinletandoutletopenings
will not become obstructed by leaves, grass, snow,
etc. If prevailing winds will cause blowing or drifting,
you may need to construct a windbreak to protect
the unit.
• Installthegeneratorascloseaspossibletothe
transfer switch and fuel supply to reduce the length of
wiring, conduit, and piping.
Laws or local codes may regulate the distance to the
fuel supply.
The minimum (MIN) clearances from aerial view of generator
(B) to combustible (D), and non-combustible (A) materials is
shown below.
• Thesedistancesareprovidedtogivegenerator
location guidance relative ONLY to combustibles,
generator cooling, and maintenance.
• Theminimumdistancesinthefigureareasshown.
All four sides of the generator cannot be enclosed
or restricted, even if the minimum distances are
maintained. DO NOT connect (A) and/or (D) to (E).
• Aroofcannotbeused.
• Exhaust(C) must not be allowed to accumulate.
C
DD
A
B
E E
10
Concrete Slab
At the appropriate location, construct a concrete slab:
• 28daycompressionstrengthof3000psi(200MPa)
• Minimum5”(13cm)thick
• Minimum6”(15cm)widerthanenclosureonallsides
(shown as D in figure)
• StrengthenslabwithNo.6reinforcingbars(on
12”(30.5cm)centers)or8ga.steelwirefabric(6”
(15cm) centers).
Avoid placing reinforcement in entrance stub-up area (shown
as (B)).
Attach unit to slab at four corner locations (A) with minimum
5/16”diameter(8mm)masonryanchorboltslongenoughto
secure the unit.
The fuel inlet location (C) and the concrete slab (D) are shown
for reference.
34-1/4”
87cm
14-3/4”
37.5cm
92”
233.7cm
51”
129.5cm
6”
15.2cm
5”
12.7cm
7-1/2”
19cm
C
D
A
B
Electrical and Fuel Inlet Locations
A through-slab power cable stub-up is preferred (see
figure above). If stub-up’s are not used, (F) indicates the
recommended location for punching holes for attaching
power conduit. The 1 inch N.P.T. fuel inlet connector (C) is
shown for reference.
C
F
A Holes located in base to anchor to pad
B Stub up Area
C Fuel Inlet
D Concrete slab
11
Remove circuit breaker box bottom plate prior to positioning
generator.Two60”lengthsof2”Schedule40pipe(A),
supplied by the installer, are required to lift the generator
onto cement pad. Insert pipes through the lifting holes (B)
located near the unit’s base.
Use a spreader bar to ensure that the chains, straps or
cables DO NOT touch the generator’s roof. Retouch any
chipped paint with supplied touch-up paint.
Lifting the Generator
The generator weighs more than 1,700 pounds (771 kg).
Proper tools, equipment and qualified personnel should be
used in all phases of handling and moving the generator.
A B
WARNING Hazardous Voltage - Contact with power lines could
cause electric shock or burn, resulting in death or
serious injury.
Lifting Hazard / Heavy Object - Could result in
serious injury.
• If lifting or hoisting equipment is used, DO NOT contact any
power lines.
• DO NOT lift or move generator without assistance.
• Use lifting pipes as described in Lifting the Generator.
• DO NOT lift unit by roof as damage to generator will occur.
12
F
C
E
D
A B
The generator is equipped with an enclosure that has
several access doors, as shown. The doors are named for a
significant component located behind them, as follows:
A - Fuel Inlet port (shown for reference)
B - Control Panel door (may be two doors)
C - Exhaust opening (shown for reference)
D - Coolant/Oil Fill door
E - Battery door
F - Muffler door
The Coolant Fill, Battery and Control Panel doors must be
installed whenever the unit is running to assure proper
cooling, reduce noise and for added safety. The enclosure
also includes muffler and radiator access panels, used for
cleaning those components. Those panels should remain
closed at all other times.
Access Ports
Each generator is shipped with a set of identical keys. These
keys fit the locks that secure the access ports.
To open access door:
1. Insert key into lock of access door handle and turn
key one quarter turn counterclockwise.
2. Grasp door’s handle and turn one quarter turn
counterclockwise to open. Remove key.
3. Coolant Fill door is unlocked in the same manner. It
can be used for adding coolant or oil.
To close access door:
1. Close door and turn door’s handle one quarter
turn clockwise.
2. Insert key into lock of door handle and turn key one
quarter turn clockwise. Remove key.
Additional force may be required to fully close and lock
the doors because they create a pressurized seal for the
generator enclosure.
WARNING Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
13
• Aminimumofoneaccessible,approvedmanual
shutoff valve (F) shall be installed in the fuel supply
line within 6 ft (1.8 m) of the home generator.
• Aminimum10ft.(3m)sectionofgaspipebetween
the primary fuel regulator and the generator fuel inlet
connection (acts as accumulator for high block loads).
• Amanualfuelshut-offvalvelocatedintheinteriorof
the building.
• Wherelocalconditionsincludeearthquake,
tornado, unstable ground, or flood hazards, special
consideration shall be given to increase strength and
flexibility of piping supports and connections.
• Pipingmustbeofthecorrectsizetomaintainthe
required supply pressures and volume flow under
varying generator load conditions with all gas
appliances connected to the fuel system turned on
and operating.
• Useapipesealantorjointcompoundapprovedfor
use with NG/LPG on all threaded fittings to reduce the
possibility of leakage.
• Installedpipingmustbeproperlypurgedand
leak tested, in accordance with applicable codes
and standards.
The information below is provided to assist gaseous fuel
system technicians in planning installations. In no way
should this information be interpreted to conflict with
applicable fuel gas codes. Consult with your local fuel
supplier or Fire Marshall if questions or problems arise.
TO THE INSTALLER: Consult with the home generator
owner(s) and convey any technical considerations that
might affect their installation plans before applying these
general guidelines.
The following general rules apply to gaseous fuel
system piping:
• Thepipingshouldbeofamaterialthatconforms
to federal and local codes, rigidly mounted and
protected against vibration.
• Pipingshouldbeprotectedfromphysicaldamage
where it passes through flower beds, shrub beds, and
other cultivated areas where damage could occur.
• Installtheflexible,gaseoushose(B)(supplied)between
the home generator Fuel Inlet port (A) and rigid piping
to prevent thermal expansion or contraction from
causing excessive stress on the piping material.
• Aunion(C)orflangedconnectionshallbeprovided
downstream from this valve to permit removal of
controls.
• Amanometerportshouldbeprovided(D).Adigital
manometer, P/N 19495, is available at your Briggs &
Stratton service center. When the initial test runs are
complete, the manometer is removed and the port
is plugged. The manometer port permits temporary
installation of a manometer to ensure that the
engine receives the correct fuel pressure to operate
efficiently throughout its operating range.
• Wheretheformationofhydratesoriceisknownto
occur, piping should be protected against freezing.
The termination of hard piping should include a
sediment trap (E) where condensate is not likely
to freeze.
The Gaseous Fuel System
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death, serious injury and/or
property damage.
• LP gas is heavier than air and will settle in low areas.
• Natural gas is lighter than air and will collect in high areas.
• The slightest spark could ignite these fuels and cause an explosion.
• DO NOT light a cigarette or smoke.
NOTICE The supplied flexible gaseous pipe is not to be installed
underground or in contact with the ground.
• The entire flexible gaseous pipe must be visible for periodic
inspection and must not be concealed within nor contact nor run
through any wall, floor, or partition.
A
B
C
D
E
F
A Generator Fuel Inlet
B Flexible Fuel Hose
C Union Fitting
D Manometer Test Port
E Sediment Trap
F Manual Shut-off Valve
14
There are numerous on-line or otherwise-published
references for fuel pipe sizing. For example, NFPA 54 -
National Fuel Gas Code, 2006 (Item #: 320-6031-06) is a
common resource. The installer should consider the specific
gravity of gas and compensate for a nominal amount of
restriction from bends, fittings, etc. If an unusual number of
fittings, bends, or other restrictions are used, refer to federal
and local codes for guidance.
Fuel Conversion
The unit is shipped from the factory calibrated for NG
operation. To convert the engine from NG to LP vapor, follow
these steps:
1. Set generator circuit breaker to OFF.
2. Set control panel system switch to OFF.
3. Remove 15 Amp fuse from system control panel.
4. Locate the fuel selector switch (A). Using a 6 mm Allen
wrench, turn the selector switch to either LP or NG.
5. Reinstall 15 Amp fuse in system control panel.
6. Set exercise timer.
Fuel Pipe Sizing
Air density is less at high altitudes, resulting in less available
engine power. Specifically, engine power will decrease 3.5% for
each 1,000 feet (300 meters) above sea level and 1% for each
10° F (5.6°C) above 77°F (25°C). Make sure you and your installer
consider these factors when determining total generator load.
Both LP vapor and natural gas fuel supply pressure at the
generator’s fuel inlet port should be between 7 to 11 inches
of water (in. W.C.) at full load with all gas appliances turned on
and operating.
Fuel Pressure
Power Loss
A
15
Fuel Consumption
Estimated fuel supply requirements at half and full load for
natural gas and LP vapor fuels are shown here.
Natural Gas LP Vapor
1/2 Load Full Load 1/2 Load Full Load
48kW 334 C 510 C 231 C 391 C
334,000 B 510,000 B 577,500 B 977,500 B
C = Cubic feet per hour
B = BTU’s per hour
Physical
Properties
LP Vapor Natural
Gas
Normal Atmospheric
State
Gas Gas
Boiling Point (in °F):
Initial
End
-44
-44
-259
-259
Heating Value:
BTU per gallon (Net
LHV*)
BTU per gallon (gross**)
Cubic feet (gas)
83,340
91,547
2,500
63,310
1,000
Density*** 36.39 57.75
Weight† 4.24 2.65
Octane Number:
Research
Motor
110+
97
110+
* LHV (Low Heat Value) is the more realistic rating.
** Gross heat value does not consider heat lost in the form of water during
combustion.
*** Densityisgivenin“CubicFeetofGasperGallonofLiquid”.
† Weightisgivenin“PoundsperGallonofLiquid”.
16
Low voltage connections to signal fault contacts, transfer switch communication, remote LED and auxiliary 12VDC power are
made via a removable ten-pin connector plug. Compare this illustration with your generator to familiarize yourself with the
location of these connections. Count down to the proper pin location on the control board since visual alignment with the
decal can be misleading:
System Connectors
A ‑ Ten Pin Connector Plug—Usedtoconnectsignalwires
to the control panel. Connect only one wire per terminal.
B ‑ Fault Contacts—UseNO,COMandNCtohookupa
siren, light, etc. to alert you in case of a fault. Contacts
reverse state (NO goes to NC and vice versa) upon a
fault condition.
C ‑ Transfer Switch Communication—Connecttotransfer
switch control board for communication interface using
18AWG twisted pair wire.
D ‑ Remote LED Output—Usethistohookuptheremote
LED supplied with the generator. The remote LED will
turn on and off in a series of blinks if certain faults are
detected in the generator.
E ‑ +12 Volt DC, .5 Amp Output—Internalauxiliary
power supply.
• Forpoweroutputconnection,use#1/0AWGminimum300volt,167°F-194°F(75°C-90°C)wire,(ref.NECTable310.16,
100 ft.(30 m) Use National Electric Code for correction factors and wire size calculations.)
• ForUtilityCircuitconnectionuse#14AWGminimum300volt,167°F-194°F(75°C-90°C)wire.
• Fortransferswitchcommunicationuse#18AWGtwistedpairconductors,nogreaterthan200ft(60m)inlength,
300 volt, 167 °F-194 °F (75 °C-90 °C) wire.
• Whenconnectingtotheten-pinconnectorplug,fastenonlyonewiretoeachconnectorscrew.
• Torqueconnectorplugscrewsto7in-lb(7.9Newtonmeter).
C
E
D
A
B
17
Generator AC Connection System
A single-phase, three-wire AC connection system is used in
the home generator. The stator assembly consists of a pair
of stationary windings with two leads brought out of each
winding. The junction of leads 22 and 33 forms the neutral
lead, as shown schematically and as wiring diagram. A
complete schematic and wiring diagram can be found later
in this manual.
Neutral is not bonded to ground at generator.
When making connections, obey wire type and torque
specifications shown on the circuit breaker and neutral/
ground connector.
10 A10 A
240 VAC
NG
44 11
22
120 V
120 V
240 V
44
11
33
Neutral
To Transfer Switch
Control
Board
Ground
Power Winding
Circuit
Breaker
Line 1
Optional
Water
Heater
Neutral
Neutral
To Transfer Switch
Utility Fuse Connection
Line 2 Ground
18
Fault Detection System
The generator may have to run for long periods of time with
no operator present. For that reason, the system is equipped
with sensors that automatically shut down the generator
in the event of potentially damaging conditions, such as
low oil pressure, high temperature, over speed, and other
conditions. Refer to Fault Detection System in the operator’s
manual for more detailed information.
The owner will use the remote LED indicator to observe
the status of the home generator system. The remote LED
will turn on and off in a series of blinks if certain faults are
detected in the generator system. Consult with the owner
for a convenient location. Locate the electrical box in an
area visible by the home owner such as near a garage door
opener or security control panel.
To install the remote LED indicator:
1. Push the LED through the mounting plate from
the front until it snaps in place. The LED is
polarity sensitive.
2. Using provided 10 pin connector and installer-
supplied minimum 18AWG wire, connect the remote
LED to the generator control board +LED and GND
connection. Use wire nuts to attach wire to LED leads.
3. Attach mounting plate to installer-supplied
electrical box.
Utility Circuit Connection
“240VUtility”leadsmustberoutedinconduit.The
“240VUtility”leadsdeliverpowertothegenerator’scircuit
board and optional water heater. This power also charges
the battery. When power on these leads is lost, the generator
will start.
Using installer-supplied #14 AWG minimum 300 volt
75°C-90°C wire, connect each ten-amp fuse terminal in the
alternator junction box to the two-amp fuse terminals in the
automatic transfer switch.
When making connections, obey wire type and torque
specifications printed on the circuit breaker and neutral/
ground connector.
Ground the generator per applicable codes, standards and
regulations. There are two generator GND lug locations.
The one inside the alternator junction box next to the circuit
breaker (A) is the primary lug and should suffice for most
applications. The second generator GND lug (B) is located
on the frame below the generator circuit breaker cover
and should ONLY be used for a ground rod located at the
generator, if required by local codes.
Grounding the Generator
A
B
C
19
System Control Panel
The home generator control panel, located inside the
generator housing, is shown below.
Brief descriptions of the controls used during installation are:
A ‑ Circuit Breaker —MustbeON to supply power to the
transfer switch. Breaker enclosure includes removable
bottom panel to assist with conduit connections.
B ‑ SET EXERCISE—Usedtosetexercisecyclestarttime.
C ‑ MANUAL OVER‑RIDE—Usedtomanuallystartandstop
the generator.
D ‑ 15 Amp fuse—ProtectsDCcontrolcircuits.Protects
the home generator DC control circuits. If the fuse has
‘blown’ (melted open) or was removed, the engine cannot
crank or start. Replace the fuse using only an identical
ATO 15 Amp fuse. One spare fuse is supplied with the
unit. If fuse was blown or removed, you will need to reset
the exercise timer (see Setting Exercise Timer).
E ‑ System Switch—Thistwo-positionswitchisthemost
important control on the home generator and is used as
follows:
• AUTO”positionisthenormaloperatingposition.Ifa
utility power outage is sensed, the system will start
the generator. When utility power is restored, lets the
engine stabilize internal temperatures, shuts off the
generator, and waits for the next utility power outage.
• OFF”positionturnsoffrunninggenerator,prevents
unit from starting and resets any detected faults.
F ‑ Digital Display—Displaysrunningtimeinhours,
fault codes, and engine malfunction.
G ‑ AVR Module—Locatedunderthiscover.
See Controls in the Operator’s Manual for more information.
C
E
D
A
B
F
20
Fuel Supply System
Ensure that all fuel pipe connections are tight, secure and
without leaks.
Ensure that all gas line shutoff valves are OPEN and that
adequate fuel pressure is available whenever automatic
operation is desired.
Engine Oil
The engine is shipped from the factory pre-run and filled
with non-synthetic oil (API SL 10W-30). This allows for system
operation in a wide range of temperature and climate
conditions. Before starting the engine, check oil level and
ensure that engine is serviced as described in the operator’s
manual.
Coolant System
The engine is shipped from the factory filled with a 50 50 mix
of automotive (Ethylene glycol) anti-freeze and water. This
will provide optimum year round protection against freezing,
boiling and corrosion. The coolant system incorporates
an optional water heater that operates when ambient
temperature is below 80ºF AND utility power is present at the
transfer switch. Periodically check coolant level as described
in the operator’s manual.
Final Installation Considerations
Battery
The installer must supply and install a valve-regulated
rechargeable starting battery. The starting battery MUST
conform to the specifications shown in this chart.
Battery Specifications
Volts 12 Volt DC
Amps (MIN) 650 CCA (cold cranking amps)
Type Valve Regulated Lead Acid (VRLA)
Terminal Hardware Post
Dimensions (MAX):
Width 7.5 inches (191mm)
Length 11.25 inches (286mm)
Height 10.0 inches (254mm)
Install the battery as described in Servicing the Battery in
the Maintenance section of the operator’s manual. Always
make sure the NEGATIVE cable is connected last.
NOTICE Any attempt to crank or start the engine before it has
been properly serviced with the recommended coolant or oil will
result in equipment failure.
• Refer to Maintenance in the operator’s manual for coolant and oil
fill information.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
WARNING Battery posts, terminals and related accessories
contain lead and lead compounds, chemicals known to the State
of California to cause cancer and reproductive harm. Wash hands
after handling.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88

Simplicity 076035-01 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation
Ce manuel convient également à