Simplicity 076032-00 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur

Ce manuel convient également à

Generator Systems
Operator’s Manual
Liquid-Cooled
Generator System
NOT
FOR REPRODUCTION
2 BRIGGSandSTRATTON.COM
Thank you for purchasing this quality-built Briggs & Stratton generator. We’re pleased that you’ve placed your confidence in
the Briggs & Stratton brand. When operated and maintained according to the instructions in this manual, your generator will
provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with standby generators and
how to avoid them. Because we do not necessarily know all the applications this equipment could be used for, it is important
that you read and understand these instructions thoroughly before attempting to start or operate this equipment. This product
is only for use as an optional generator system which provides an alternate source of electric power and to serve loads such
as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause
discomfort or inconvenience.
Save these original instructions for future reference.
This generator requires professional installation before use. Refer to the separate installation manual for full information.
Your installer should follow the instructions completely.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your generator. Consult your Yellow Pages. There
are thousands of Briggs & Stratton authorized service dealers worldwide who provide quality service. You can also contact
Technical Service by phone at 800743-4115, or click on Find a Dealer at BRIGGSandSTRATTON.COM, which provides a list of
authorized dealers.
Generator and engine model and serial numbers should be recorded in the installation manual.
Briggs & Stratton Power Products Group, LLC
P.O. Box 702
Milwaukee, WI 53201-0702
Copyright © 2013. All rights reserved. No part of this material
may be reproduced or transmitted in any form without the express
written permission of Briggs & Stratton Power Products Group, LLC.
NOT
FOR REPRODUCTION
3
Table of Contents
Important Safety Instructions........................4
Installation ....................................7
For the Installing Dealer/Contractor: ..............................7
Owner Orientation ............................................7
Fuel Factors .................................................8
Generator Location............................................8
Delivery Inspection............................................9
Controls ..................................... 10
System Control Panel.........................................12
Access Ports ...............................................13
Operation .................................... 14
Automatic Operation .........................................14
Setting Exercise Timer ........................................15
Maintenance .................................. 15
Fault Detection System .......................................15
Generator Maintenance .......................................17
Engine Maintenance..........................................18
Battery ....................................................21
Storage....................................................22
Maintenance Chart.............................. 23
Troubleshooting................................ 24
Warranty..................................... 25
Product Specifications ........................... 28
NOT
FOR REPRODUCTION
4 BRIGGSandSTRATTON.COM
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a degree
or level of hazard seriousness. A safety symbol may be used
to represent the type of hazard. The signal word NOTICE is
used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that
it is safe for you and others. You must also make sure that
the procedure, work method or operating technique that you
choose does not render the generator system unsafe.
Fire
Toxic Fumes
Explosive Pressure
Rotating Fan Blade
Lift Hazard Read Manual
Exploding BatteryRotating Belt/Pulley
Chemical BurnAuto Start
Hot SurfaceRotating Parts
Electrical ShockExplosion
WARNING The engine exhaust from this product
contains chemicals known to the State of California to
cause cancer, birth defects, or other reproductive harm.
WARNING Certain components in this product and
related accessories contain chemicals known to the State
of California to cause cancer, birth defects, or other
reproductive harm. Wash hands after handling.
WARNING Running engine gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide could result in death,
serious injury, headache, fatigue, dizziness,
vomiting, confusion, seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will
not accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors,
ventailation intakes, soffit vents, crawl spaces, open
garage doors or other openings that can allow exhaust
gas to enter inside or be drawn into a potentially occupied
building or structure.
• Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions/recommendations. Smoke alarms cannot
detect carbon monoxide gas.
WARNING Storage batteries give off explosive
hydrogen gas during recharging.
Slightest spark will ignite hydrogen
and cause explosion, resulting in
death or serious injury.
Battery electrolyte fluid contains
acid and is extremely caustic.
Contact with battery contents could cause severe
chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette
during and for several minutes after charging a battery.
• DO NOT open or mutilate the battery.
• Wear protective goggles, rubber apron, rubber boots and
rubber gloves.
• Remove watches, rings, or other metal objects.
• Use tools having insulated handles.
NOT
FOR REPRODUCTION
5
WARNING Generator produces hazardous voltage.
Failure to properly ground generator could result
inelectrocution.
Failure to isolate generator from utility power could
result in death or serious injury to electric utility
workers due to backfeed of electrical energy.
• DO NOT touch bare wires or bare receptacles.
• DO NOT use generator with electrical cords which are
worn, frayed, bare or otherwise damaged.
• DO NOT handle generator or electrical cords while
standing in water, while barefoot, or while hands or feet
are wet.
• If you must work around a unit while it is operating,
stand on an insulated dry surface to reduce the risk of a
shock hazard.
• DO NOT allow unqualified persons or children to operate
or service generator.
• In case of an accident caused by electrical shock,
immediately shut down the source of electrical power and
contact the local authorities. Avoid direct contact with
the victim.
• Despite the safe design of the generator, operating this
equipment imprudently, neglecting its maintenance or
being careless could cause possible injury or death.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• Before performing any maintenance on the generator,
disconnect the battery cable indicated by a NEGATIVE,
NEG or (-) first. When finished, reconnect that cable last.
• After your system is installed, the generator may crank
and start without warning any time there is a power
failure. To prevent possible injury, always set the
generator’s system switch to OFF, remove the service
disconnect from the disconnect box AND remove the
15 Amp fuse BEFORE working on the equipment.
WARNING Hazardous Voltage - Contact with power
lines could cause electric shock or burns,
resulting in death or serious injury.
Lifting Hazard / Heavy Object - Could result
in serious injury.
• If lifting or hoisting equipment is used, DO NOT contact
any power lines.
• DO NOT lift or move generator without assistance.
• DO NOT lift unit by roof as damage to generator
will occur.
WARNING Propane and Natural Gas are extremely
flammable and explosive, which could cause
burns, fire or explosion resulting in death or
serious injury.
• Install the fuel supply system according to NFPA 37 and
other applicable fuel-gas codes.
• Before placing the generator into service, the fuel system
lines must be properly purged and leak tested.
• After the generator is installed, you should inspect the fuel
system periodically.
• NO leakage is permitted.
• DO NOT operate engine if smell of fuel is present or other
explosive conditions exist.
• DO NOT smoke around the generator. Wipe up any oil
spills immediately. Ensure that no combustible materials
are left in the generator compartment. Keep the area near
the generator clean and free of debris.
WARNING Exhaust heat/gases could ignite
combustibles or structures resulting in
death or serious injury.
Contact with muffler area could cause
burns resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• Exhaust outlet side of weatherproof enclosure must
have at least 5 ft. (1.5m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
• Standby generator weatherproof enclosure must be at
least 5 ft. (1.5m) from windows, doors, any wall opening,
shrubs or vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang, or trees.
• DO NOT place weatherproof enclosure under a deck or
other type of structure that may confine airflow.
• Use only flexible fuel line provided. Connect provided fuel
line to generator. DO NOT use with or substitute any other
flexible fuel line.
• Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
• Keep at least minimum distances shown in General
Location Guidelines to insure for proper generator cooling
and maintenance clearances.
• Replacement parts must be the same and installed in the
same position as the original parts.
NOT
FOR REPRODUCTION
6 BRIGGSandSTRATTON.COM
WARNING Moving parts could crush and cut.
Starter and other rotating parts could
entangle hands, hair, clothing, or
accessories resulting in serious injury.
• NEVER operate generator without protective housings,
covers, or guards in place.
• DO NOT wear loose clothing, jewelry or anything that
could be caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
• Before servicing, remove 15 Amp fuse from control panel
and disconnect Negative (NEG or -) battery cable.
WARNING Hot pressurized coolant could cause serious
injury.
• DO NOT open radiator cap when hot.
• Before servicing, allow coolant to cool.
CAUTION Installing the 15A fuse could cause the
engine to start at any time without warning
resulting in minor or moderate injury.
• Observe that the 15 Amp fuse has been removed from the
control panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has
been completed and inspected.
CAUTION Excessively high operating speeds could
result in minor injury and/or equipment damage.
Excessively low speeds impose a heavy load on generator.
• DO NOT tamper with governed speed. Generator supplies
correct rated frequency and voltage when running at
governed speed.
• DO NOT modify generator in any way.
NOTICE Improper treatment of generator could damage it
and shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, contact your
authorized dealer.
• Operate generator only on level surfaces.
• Adequate, unobstructed flow of cooling and ventilating air
is critical to correct generator operation.
• The access panels/door must be installed whenever the
unit is running.
• DO NOT expose generator to excessive moisture, dust,
dirt, or corrosive vapors.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• DO NOT start engine with air cleaner or air cleaner
cover removed.
• DO NOT insert any objects through cooling slots.
• DO NOT use the generator or any of its parts as a step.
Stepping on the unit could cause stress and break parts.
This may result in dangerous operating conditions from
leaking exhaust gases, fuel leakage, oil leakage, etc.
• If connected devices overheat, turn them off and
disconnect them from generator.
• Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
-unit makes unusual noises.
NOT
FOR REPRODUCTION
7
Installation
We sincerely appreciate your patronage. For this reason, we
have made every effort to provide for a safe, streamlined
and cost-effective installation. Because each installation is
unique, it is impossible to know of and advise the trade of all
conceivable procedures and methods by which installation
might be achieved. Neither could we know of possible
hazards and/or the results of each method or procedure.
For these reasons, only current licensed electrical and
plumbing professionals should attempt generator system
installations. Installations must strictly comply with all
applicable codes, industry standards andregulations.
Your generator is supplied with this “Operator’s Manual”
and a separate “Installation Manual”. These are important
documents and should be retained by the owner after the
installation has been completed.
This product is only for use as an optional generator system
which provides an alternate source of electric power and
to serve loads such as heating, refrigeration systems, and
communication systems that, when stopped during any power
outage, could cause discomfort or inconvenience.
NOTICE This product does NOT qualify for either an
emergency standby or legally required standby system as
defined by NFPA 70 (NEC).
• Emergencygeneratorsystemsareintendedto
automatically supply illumination, power, or both, to
designated areas and equipment in the event of failure
of the normal supply. Emergency systems may also
provide power for such functions as ventilation where
essential to maintain life, where current interruption of
the normal supply would produce serious life safety or
health hazards.
• LegallyRequiredstandbygeneratorsystemsare
intended to automatically supply power to selected
loads in the event of failure of the normal source
which could create hazards or hamper rescue or fire-
fighting operations.
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the right
to change, alter, or otherwise improve the product and this
document at any time without prior notice.
Only current licensed electrical and plumbing professionals
should attempt generator system installations. Installations
must strictly comply with all applicable codes, industry
standards, laws and regulations.
For the Installing Dealer/Contractor:
For most applications, the Installation manual contains all
the information required to properly install and start the
generator. This operator’s manual describes routine operation
and owner maintenanceprocedures.
If you need more information in this matter, please call
800743-4115, between 8:00 AM and 5:00 PM CT.
Owner Orientation
This section provides generator owners with the information
necessary to achieve the most satisfactory and cost effective
installation possible.
The illustrations are for typical circumstances and are meant
to familiarize you with the installation options available
with your generator. A thorough understanding of these
options will provide fundamental control over the cost of
your installation, as well as ensure your final satisfaction
andsecurity.
Federal and local codes, appearance, noise levels, fuel types,
and distances are the factors that must be considered when
negotiating with an installation professional. Remember
that as the distance from the existing electrical service and
gaseous fuel supply increases, and the number of 90 degree
bends in the fuel supply increases, compensations in piping
and wiring materials must be made. This is necessary to
comply with local codes and overcome electrical voltage
drops and gaseous fuel pressure drops.
The factors mentioned above will have a direct affect on
the overall price of your generator installation.
In some areas you may need to acquire electrical permits
for installing the generator, building permits for installing
gas lines, and permits for noise allowances. Your installer
should check your local codes AND obtain the permits before
installing the system.
For the Owner:
To help you make informed choices and communicate
effectively with your installation contractor(s), read and
understand Owner Orientation in this manual before
contracting or starting your generatorinstallation.
To arrange for proper installation, contact the store at which
you purchased your generator, your dealer, a licensed
electrician or your utility power provider.
The generator warranty is VOID unless the system is
installed by licensed electrical and plumbingprofessionals.
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
The Emission Control System for this generator is warranted
for standards set by the U.S. Environmental Protection
Agency and by the California Air Resources Board (CARB).
NOT
FOR REPRODUCTION
8 BRIGGSandSTRATTON.COM
Fuel Factors
An important consideration affecting the entire installation
is the type of fuel used by your generator. The system was
factory tested and adjusted using either natural gas or liquid
propane (LP vapor). For proper engine function, factors
that are inherent to each of these fuels, your location and
the duration of possible utility interruptions are important
considerations in the following fuel guidelines:
 • Useclean,dryfuel,freeofmoistureorany
particulate material. Using fuels outside the following
recommended values may cause performanceproblems.
 • Inenginessetuptorunonpropane(LP),commercial
grade HD5 propane with a minimum fuel energy of 2500
BTUs/ft3 with maximum propylene content of 5% and
butane and heavier gas content of 2.5% and minimum
propane content of 90%.
Natural gas rating will depend on specific fuel but typical
derates are between 10 to 20% off the LP gas rating.
Power Decrease at High Altitude or High Temperature
Air density is less at high altitudes, resulting in less available
engine power. Specifically, engine power will decrease 3%
for each 1,000 feet (300 meters) above sea level and 1% for
each 10° F (5.6°C) above 77°F (25°C). Make sure you and
your installer consider these factors when determining total
generator load.
Delivery Inspection
Carefully inspect the generator for any damage that may have
occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss
or damage. If loss or damage is noted after delivery, separate
the damaged materials and contact the carrier and your
installer for claim procedures. Missing or damaged parts are
not warranted.
The generator is supplied with:
 • Fully-servicedcoolantsystem
 • Fully-servicedoil/lubricatingsystem
 • Flexiblefuelhook-uphose
 • Installationandstart-upmanual
 • Operator’smanual
 • Spareaccessdoorkeys
 • Spare15Afuse
 • Tenpinconnector
 • Touchuppaint
 • RemoteLEDindicatorkit(LED/plate/screws)
To be supplied by installer:
 • Startingbattery
 • Reinforcedconcretemountingpad
 • Connectingwireandconduit
 • Fuelsupplyvalves/plumbing
 • Variousspecialtytools/equipment
WARNING
Propane and Natural Gas are extremely
flammable and explosive, which could cause
burns, fire or explosion resulting in death or
serious injury.
• The generator is equipped with an automatic safety gas
“fuel shut-off” valve.
• DO NOT operate the equipment if the “fuel shut-off” valve
is missing or inoperative.
NOT
FOR REPRODUCTION
9
Generator Location
The actual physical location of your generator has a direct
affect on:
1. The amount of plumbing required to fuel your generator.
2. The amount of wiring required to control and connect
your generator.
Specific location guidelines are discussed in the installation
manual. Acquaint yourself with that information and confer
with your installer. Be sure to ask how your site might
affect installation costs and compliance with local codes
andstandards.
 • Installgeneratoroutdoorsinanareathatwillnot
accumulate deadly exhaust gas.
 • DONOTinstallgeneratorwhereexhaustgascould
accumulate and enter inside or be drawn into a
potentially occupied building or structure.
 • BylawitisrequiredinmanystatestohaveaCarbon
Monoxide (CO) detector in operating condition in your.
Carbon monoxide detector(s) (A) MUST be installed
and maintained indoors according to the manufacturer’s
instructions/recommendations. A CO monitor is an
electronic device that detects hazardous levels of CO.
When there is a buildup of CO, the monitor will alert the
occupants by flashing visual indicator light and alarm.
Smoke alarms cannot detect CO gas.
 • Ensureexhaustgasiskeptawayfromanywindows,
doors, ventilation intakes, soffit vents, crawl spaces,
open garage doors or other openings that can
allow exhaust gas to enter inside or be drawn into a
potentially occupied building or structure. Neighboring
structures may be exposed to the engine exhaust from
your standby generator and must be considered when
installing your standby generator.
 • Windandaircurrentsshouldbetakeninto
consideration when positioning generator.
See the installation manual for full details on safe generator
location.
WARNING Running engine gives off carbon monoxide,
an odorless, colorless, poison gas.
Breathing carbon monoxide could result in death,
serious injury, headache, fatigue, dizziness,
vomiting, confusion, seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will
not accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors,
ventilation intakes, soffit vents, crawl spaces, open garage
doors or other openings that can allow exhaust gas
to enter inside or be drawn into a potentially occupied
building or structure.
• Carbon monoxide detector(s) MUST be installed and
maintained indoors according to the manufacturer’s
instructions/recommendations. Smoke alarms cannot
detect carbon monoxide gas.
WARNING Exhaust heat/gases could ignite
combustibles or structures resulting in death or serious
injury.
• Exhaust outlet side of weatherproof enclosure must
have at least 5 ft. (1.5 m) minimum clearance from any
structure, shrubs, trees, or any kind of vegetation.
• Standby generator weatherproof enclosure must be at
least 5 ft. (1.5 m) from windows, doors, any wall opening,
shrubs or vegetation over 12 in. (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from any
structure, overhang or trees.
• DO NOT place weatherproof enclosure under a deck or
other type of structure that may confine airflow.
• USE ONLY flexible steel fuel line provided. Connect
provided fuel line to generator. DO NOT use with or
substitute any other flexible fuel line.
• Smoke detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Carbon monoxide alarms cannot
detect smoke.
• DO NOT place weatherproof enclosure in manner other
than shown in illustrations.
A
A
NOT
FOR REPRODUCTION
10 BRIGGSandSTRATTON.COM
Controls
35 kW Generator
Read this operator’s manual and Important Safety Instructions before operating your generator.
Compare the illustrations of this model with your generator to familiarize yourself with the locations of various
controls and adjustments. Save this manual for future reference.
J
L
MN
P
R
A
B
H
S
C
D
F
GE
H
K
Generator is pictured with access doors removed for clarity
and screen guard open for clarity.
Exhaust Port — High-performance muffler lowers
engine noise to comply with most codes.
Coolant Fill Door — Provides access for servicing
engine coolant.
Air Cleaner — Protects engine by filtering dust and
debris out of intake air.
Battery Door opening — Provides access to starting
battery and air cleaner.
Engine Label — Identifies engine model and type.
Oil Dip Stick — Used to check the engine oil level.
Oil Fill Cap — Remove to service the engine with
recommended oil.
Screen Guard — Prevents fingers from touching
radiator fan and houses the coolant recovery bottle.
Must stay closed while generator is in use.
Coolant Recovery Bottle — Located on inside of screen
guard. Provides visual indicator of engine coolant level.
Oil Filter — Filters engine oil to prolong system life.
Fuel Inlet — Fuel supply is connected here.
Oil Drain Hose — Provided to facilitate oil changing.
ID Label (located on base) — Identifies unit by
serial number.
Circuit Breaker Enclosure - Equipped with removable
bottom to assist with conduit connection.
Control Panel Door opening — Provides access to
control panel, oil filter, etc. (Cover door not shown.)
Control Panel — Used for various test, operation and
maintenance functions. See System Control Panel.
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
NOT
FOR REPRODUCTION
11
Circuit Breaker — Protects the system from shorts and
other over-current conditions. Must be ON to supply
power to the automatic transfer switch.
SET EXERCISE — Used to set the exercise cycle start
time and day-of-the-week. Exercise cycle only occurs in
AUTO mode.
MANUAL OVER-RIDE— With system switch in AUTO
position, push the manual over-ride button for six seconds
to start the generator. To turn off the generator, push and
hold the manual over-ride button until engine stops.
15 Amp Fuse — Protects the generator DC control
circuits. If the fuse has ‘blown’ (melted open) or was
removed, the engine cannot crank or start. Replace the
fuse using only an identical ATO 15 Amp fuse.
System Switch — This two-position switch is the most
important control on the system and is used as follows:
•“AUTO”positionisthenormaloperatingposition.
If a utility power outage is sensed, the system
will start the generator. When utility power is
restored, AUTO lets the engine stabilize internal
temperatures, shuts off the generator, and waits
for the next utility power outage.
•“OFF”positionturnsoffrunninggenerator,
prevents unit from starting and resets any detected
faults, except ENG- fault codes.
Digital Display — Displays the total number of hours
the generator has been running, fault codes, and engine
malfunctions related to emissions components.
• Hourmeterisdisplayedasaconstantnumber
and indicates the total hours of operation. Used to
schedule maintenance tasks.
• Faultconditionsaredisplayedasanalpha-numeric,
and will flash “FC_” followed by a fault code number.
Used for troubleshooting operational problems
associated with the generator. All fault conditions are
described in Fault Detection System.
• Malfunctionsrelatedtoemissioncomponentsare
displayed as “ENG-”. The display will flash hours
and “ENG-” in three second intervals. The engine
will continue to operate, but an authorized service
technician must be notified to diagnose, repair, and
reset the fault condition. Engine malfunctions are
described in Fault Detection System.
fault codes:
FC_1 - low battery voltage
FC_2 - low oil pressure
FC_3 - low voltage
FC_4 - engine does not start
FC_5 - low frequency
FC_6 - engine overspeed
FC_7 - high temperature
FC_8 - transfer switch
FC_9 - over voltage
A
D
B
E
C
F
A
B
C
D
E
F
System Control Panel
Compare this control panel illustration with your generator to familiarize yourself with the location of these important controls:
NOT
FOR REPRODUCTION
12 BRIGGSandSTRATTON.COM
Access Ports
The generator is equipped with an enclosure that has
several access doors. The doors are named for a significant
component located behind them, as follows::
A - Fuel Inlet port (shown for reference)
B - Control Panel door
C - Exhaust opening (shown for reference)
D - Coolant Fill door
E - Battery door
F - Muffler door
The enclosure also includes muffler and radiator access
panels, used for cleaning those components. Those panels
should remain closed at all other times to assure proper
cooling, reduce noise, and for added safety.
Each generator is supplied with a set of identical keys. These
keys fit the locks that secure the access doors.
To open access door:
1. Insert key into lock of access door handle and turn key
one quarter turn counterclockwise.
2. Grasp door’s handle and turn one quarter turn
counterclockwise to open. Remove key.
3. Coolant Fill door is unlocked in the same manner. It can
be used for adding coolant or oil.
To close access door:
1. Close door and turn door’s handle one quarter
turnclockwise.
2. Insert key into lock of door handle and turn key one
quarter turn clockwise. Remove key.
Screen Guard
To gain access to the engine and cooling system
components:
1. Remove two screws (A) and washers at top and bottom
of screen guard.
2. The screen guard will swing open to allow access to the
engine and the cooling system components.
WARNING Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
A
B
C
D
E
F
A
B
C
F
D
E
A
A
NOT
FOR REPRODUCTION
Operation
Important Owner’s Considerations
Engine Oil
This engine is shipped from the factory pre-run and filled
with non-synthetic oil (API SL 10W-30W). This allows
for system operation in a wide range of temperature and
climate conditions. Before starting the engine, check oil
level and ensure that engine is serviced as described in the
Maintenance section.
Coolant System
This engine is shipped from the factory filled with a
50-50 mix of automotive (ethylene glycol) anti-freeze and
water. This will provide optimum year round protection
against freezing, boiling and corrosion. The coolant system
incorporates an optional water heater that operates when
ambient temperature is below 80ºF AND utility power is
present at the transfer switch. Before starting the engine,
check coolant level as described in the Maintenance section.
Battery
The installer must supply a valve-regulated, rechargeable
12 volt DC starting battery. See Battery in Final Installation
Considerations in the installation manual.
15 Amp Fuse
The generator’s 15 Amp fuse is critical to correct system
operation. The 15 Amp fuse was removed at the factory to
prevent the unit from starting during shipping. Your installer
will ensure the fuse is properly installed upon completion of
the installation.
NOTICE Any attempt to crank or start the engine before it
has been properly serviced with the recommended coolant
or oil will result in equipment failure.
• Refer to the Maintenance section for coolant and oil fill
information.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
WARNING Battery posts, terminals and related
accessories contain lead and lead compounds - chemicals
known to the State of California to cause cancer and
reproductive harm. Wash hands after handling.
Automatic Operation
To select automatic operation, do the following:
1. Confirm 15 Amp fuse is installed in control panel.
2. Set the main distribution panel circuit breaker that
sends utility voltage to the transfer switch to ON.
3. Set the generator’s circuit breaker to its ON position.
4. Set the control panel system switch to AUTO.
Checking Automatic Operation
To check the system for proper automatic operation, proceed
as follows:
1. Turn OFF the service disconnect or main distribution
panel circuit breaker sending power to the automatic
transfer switch.
When utility voltage is lost and the sensor has timed
out, the engine will crank and start. Let the system go
through its entire automatic operation sequence.
2. With the generator output supplying its loads, turn ON
the service disconnect or main distribution panel circuit
breaker that supplies utility power to the automatic
transfer switch.
3. The automatic transfer switch will transfer loads back
to utility power after a 5 minute minimum run time and
utility power is available.
4. The generator will run for an additional one minute for
engine cool down, then shut down.
If utility power is restored and generator does not shut down
after 10 minutes, set system switch to OFF and contact your
installer or local service center.
This completes the test procedures for automatic operation.
The generator will now start automatically and will supply
power to the transfer switch when utility power islost.
CAUTION Installing the 15A fuse could cause the
engine to start at any time without warning
resulting in minor or moderate injury.
• Observe that the 15 Amp fuse has been removed from the
control panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has
been completed and inspected.
NOT
FOR REPRODUCTION
14 BRIGGSandSTRATTON.COM
Setting Exercise Timer
The generator is equipped with an exercise timer that
will start and exercise the system once every seven days.
During this exercise period, the unit runs for approximately
20 minutes and then shuts down. Electrical load transfer
DOES NOT occur during the exercise cycle (unless an utility
power outage occurs).
A button on the control panel is labeled “SET EXERCISE”
(see System Control Panel). The specific day and the
specific time of day this button is pressed is programmed
into the control board memory. This date and time is then
used to automatically initiate the system exercise cycle. The
“SETEXERCISE” legend on the control panel will flash until
the set exercise cycle is set.
To perform the Set Exercise procedure:
1. Choose the day and time you want your generator to
exercise.
2. On that day and time, press and hold “SET EXERCISE”
for three seconds.
The “Set Exercise” display will illuminate then turn off
to confirm that the exercise timer has been set. Then
release the button.
The unit will crank and run the exercise cycle. During
the cycle, “Set Exercise” will illuminate.
Once the exercise cycle is complete, the unit will turn off
and “Set Exercise” will no longer be displayed.
The exercise cycle may be discontinued at anytime by
turning the System Switch to OFF.
3. The unit will then start and run it’s 20 minute
exercisecycle.
For example, if you press SET EXERCISE on Sunday morning
at 10:00 AM, the unit will run an immediate exercise cycle
and an exercise cycle every following Sunday at 10:00 AM
(+/- 1/2 hour).
“Set Exercise” will only work if the unit is in the AUTO mode
and this exact procedure is followed. The exerciser will need
to be re-set if the 15 Amp fuse is removed or changed, or if
the starting battery is disconnected.
If you want to change the day and time the unit exercises,
simply perform the “Set Exercise” procedure at the exact
weekday and time you want it to take place.
Generator will not exercise if timer is not set.
Maintenance
The generator warranty does not cover items that have been
subjected to operator abuse or neglect. To receive full value
from the warranty, the operator must maintain the system as
instructed in the Maintenance section.
Servicing the System
Before performing any generator maintenance, always
perform the following steps:
1. Set generator’s circuit breaker to its OFF position.
2. Set control panel system switch to OFF.
3. Remove 15 Amp fuse from control panel.
4. Utility voltage is present at generator control panel.
Disconnect power before servicing control panel by
removing the fuses from the transfer switch.
5. After all servicing has been completed, reinstall fuses in
transfer switch, replace 15 Amp fuse in control panel,
set system switch and circuit breaker ON and reset
exercise timer. See Setting Exercise Timer.
Fault Detection System
The generator may have to run for long periods of time with
no operator present. For that reason, the system is equipped
with sensors that automatically shut down the generator in
the event of potentially damaging conditions, such as low oil
pressure, high temperature, over speed, and otherconditions.
The generator’s control panel has a digital display that shows
fault codes, like “FC_1”. The table below lists the detected
fault, the fault code as displayed on the control panel, and the
number of LED flashes (also described as ‘blinks’) seen on
the remote LED indicator.
Fault Description Fault Codes LED Flashes
Low battery voltage FC_1 1
Low oil pressure FC_2 2
Low voltage FC_3 3
Engine fails to start FC_4 4
Low frequency FC_5 5
Engine overspeed FC_6 6
High temperature FC_7 7
Transfer switch fault FC_8 8
Over Voltage FC_9 9
Emission Related Fault
ENG-
No Flash
The remote LED indicator is installed at a convenient inside
location. The LED will remain lit when the generator is in
AUTO. Should a system fault be detected, the LED will turn
on and off in a series of blinks that identify the problem. The
blink pattern is repeated with a brief pause between each
series of blinks.
NOT
FOR REPRODUCTION
Reset Fault Detection System
The operator must reset the fault detection system each
time it activates. To do so, place the control panel system
switch in the OFF position for 30 seconds or more. Remedy
the fault condition, then return the generator to service by
installing the 15 Amp fuse, placing the system switch in the
AUTO position, and resetting the exercise timer. See Setting
Exercise Timer in Operation.
A description of each fault and suggested remedies are
asfollows:
No LED - Discharged Battery
If there is a detected fault condition but the LED is not
blinking, this is because the battery is completely discharged.
To remedy the problem, remove the 15 Amp fuse and
disconnect the battery from the generator. Take the battery to
a local battery store for analysis. Reinstall battery after it has
been fully recharged, connecting the NEGATIVE cable last.
Then reset the fault detection system, as described earlier.
Low Battery Voltage (FC_1)
This fault is indicated by fault code FC_1 and one blink on the
LED indicator. This condition occurs if the generator cannot
start because the starting battery output power is below that
needed to crank the engine. Causes for this problem may be
a faulty battery or battery charge circuit.
To remedy the problem, contact your local service center to
check the battery charge output. Remove the 15 Amp fuse
and disconnect the battery from the generator. Take the
battery to a local battery store for analysis.
Reinstall the battery (replace if necessary - see Battery in
Final Installation Considerations in the installation manual).
Then reset the fault detection system, as described earlier.
Low Oil Pressure (FC_2)
This fault is indicated by fault code FC_2 and two blinks on
the remote LED indicator. The unit is equipped with an oil
pressure switch that uses normally closed contacts held open
by engine oil pressure during operation. Should oil pressure
drop below the 8 psi range, switch contacts close and the
engine is shut down.
To remedy the low oil pressure condition, add the
recommended oil to the FULL mark on the dipstick.
If the low oil pressure condition still exists, the engine will
start, then shut down again. The fault code will appear and
the LED will flash. In this case, contact an authorized dealer.
Low Voltage (Generator, FC_3)
This fault is indicated by fault code FC_3 and three blinks on
the LED indicator. This condition is caused by a restriction in
the fuel flow, a broken or disconnected signal lead, a failed
alternator winding, the control panel circuit breaker is open,
or the generator is overloaded.
To remedy the problem, contact your installer or an
authorized dealer.
Engine Fail To Start (FC_4)
This fault is indicated by fault code FC_4 and four blinks on
the LED indicator. This feature prevents the generator from
damaging itself if it continually attempts to start in spite
of another problem, such as no fuel supply. Each time the
system is directed to start, the unit will crank for 10seconds,
pause for 10 seconds, and repeat. If the system does not
begin producing electricity after approximately 2minutes, the
unit will stop cranking and the LED will blink.
Check to make sure the generator’s circuit breaker is in the
ON position in order for the sensing leads to verify that the
unit is running.
The most likely cause of this problem is no fuel supply.
Check the internal and external fuel shut off valves to
ensure they are fully open. Other causes could be failed
spark plug(s), failed engine ignition, or the engine air filter
is clogged. You may need to contact your installer for
assistance if you can’t remedy these problems.
Low Frequency (FC_5)
This fault is indicated by fault code FC_5 and five blinks on
the LED indicator. This feature protects devices connected
to the transfer switch by shutting the generator down if the
engine runs slower than 55 Hz for three seconds.
This condition is caused by a failed engine component or by
excessive loads on the generator. To remedy the problem,
contact your installer or an authorized dealer.
Engine Overspeed (FC_6)
This fault is indicated by fault code FC_6 and six blinks on
the LED indicator. This feature protects devices connected
to the transfer switch by shutting the generator down if
the engine happens to run faster than the preset limit. The
overspeed fault is detected as follows:
•Ifthegeneratoroutputfrequencyis65-70Hz,afterthree
seconds, the generator will shut down.
•Ifthegeneratoroutputfrequencyisgreaterthan70Hz,
the generator will shut down immediately.
This condition is caused by a failed engine component.
To remedy the problem, contact your installer or an
authorizeddealer.
NOT
FOR REPRODUCTION
16 BRIGGSandSTRATTON.COM
High Temperature (FC_7)
This fault is indicated by fault code FC_7 and seven blinks on
the LED indicator. The fault occurs if the engine temperature
exceeds the limit set in the engine ECU. If the engine
temperature exceeds approximately 110°C (230°F), the fault
is detected and the engine shuts down.
Common causes for this condition include running the
unit with all access doors removed, obstructed air inlet or
exhaust port, low oil or coolant level, or debris in the engine
compartment or radiator.
To resolve the problem, let the engine cool down and remove
any accumulated debris and obstructions. Ensure that all
access doors are installed whenever the unit is running.
Transfer Switch Fault (FC_8)
This fault is indicated by fault code FC_8 and eight blinks
on the LED indicator (if transfer switch is equipped with
faultdetection).
The most likely cause of this fault is a blown fuse in the
transfer switch. To remedy the problem, contact your installer
or an authorized dealer.
Over Voltage (FC_9)
This fault is indicated by fault code FC_9 and nine blinks on
the LED indicator. This feature protects devices connected
to the transfer switch by shutting the generator down if the
generator output voltage happens to increase above the
preset limit.
The overvoltage fault is detected as follows:
•Ifthegeneratoroutputvoltageis40%overratedvoltage,
the generator will shut down immediately.
This condition is most likely caused by a failed voltage
regulator, alternator excitation circuit or a load imbalance. To
remedy the problem, contact your installer or an
authorized dealer.
ENG-
The engine is equipped with on-board diagnostics that moni-
tor the operation of emission related components. If an emis-
sion related problem has been detected, the system control
panel display will alternate between run hours and ENG- in
three second intervals while the generator is running. If ENG-
displays while the generator is running, a diagnostic trouble
code may be set or a problem may exist in the system which
has caused the engine emissions to go outside the standards
certified by the Environmental Protection Agency. It is the
responsibility of the operator to contact an authorized service
technician to repair this condition.
Generator Maintenance
Generator maintenance consists of keeping the unit
clean. Operate the unit in an environment where it will
not be exposed to excessive dust, dirt, moisture or any
corrosive vapors. Cooling air louvers on the enclosure
must not become clogged with snow, leaves, or any other
foreign material. To prevent generator damage caused by
overheating, keep the enclosure cooling inlets and outlets
clean and unobstructed at all times.
Check the cleanliness of the unit frequently and clean when
dust, dirt, oil, moisture or other foreign substances are visible
on its exterior/interior surface. Inspect the air inlet and outlet
openings inside and outside the enclosure to ensure air flow
is not blocked.
DO NOT use direct spray from a garden hose to clean generator.
Water can enter the engine and generator and cause problems.
Cleaning the Generator
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Clean generator as desired.
 • Useadampclothtowipeexteriorsurfacesclean.
 • Useasoft,bristlebrushtoloosencakedondirt,etc.
 • Useavacuumcleanertopickuploosedirtanddebris.
 • Uselowpressureair(nottoexceed25psi)toblow
away dirt. Inspect cooling air slots and openings on
the generator. These openings must be kept clean
andunobstructed.
4. Reinstall 15 Amp fuse in control panel.
5. Set generator’s system switch to AUTO.
6. Reset exercise timer. See Setting Exercise Timer.
NOTICE Improper treatment of generator can damage it
and shorten its life.
• DO NOT expose generator to excessive moisture, dust,
dirt, or corrosive vapors.
• DO NOT insert any objects through cooling slots.
NOT
FOR REPRODUCTION
17
Engine Maintenance
The maintenance of an engine and related components are
critical to its operating performance and lifespan. Industrial
engines operate in an environment that often include hot
and cold temperatures and extreme dust. The recommended
maintenance schedule is listed in this section, however,
environmental operating conditions and additional installed
equipment may require more frequent inspection and
servicing. The owner and/or authorized service technician
should review the operating conditions of the equipment to
determine the inspection and maintenance intervals. Proper
engine cooling and lubrication are very important, so pay
particular attention to these matters.
Engine Oil
The engine is shipped from the factory pre-run and filled
with non-synthetic oil (API SL 10W-30). This allows for
system operation in a wide range of temperature and
climateconditions.
Oil Recommendation
Select and engine oil viscosity that will best match the
prevailing daytime temperature.
The oil must meet GM specification 9986231. Motor oils
meeting this spec receive the API (American Petroleum
Institure) starburst symbol:
HOT WEATHER
COLD WEATHER
SAE 10W-30
PREFERRED
SAE 15W-40
FOR THE BEST FUEL ECONOMY AND COLD STARTING, SELECT THE LOWEST
SAE VISCOSITY GRADE OIL FOR THE EXPECTED TEMPERATURE RANGE
IF NEITHER SAE 10W-30
NOR SAE 15W-40 GRADE
OILS ARE AVAILABLE, SAE
30 GRADE MAY BE USED AT
TEMPERATURES ABOVE 4
DEGREES C (40F), SAE 40
GRADE AY BE USED AT
TEMPERATURES ABOVE 27
DEGREES C (80F).
DO NOT USE SAE 10W-40
GRADE OIL OR ANY OTHER
GRADE NOT RECOMMENDED
RECOMMENDED SAE VISCOSITY GRADE ENGINE OILS
40°F (4°C)
It is noted that the GF-4 oils are also “backward compatible”
and are equal or better than previous grades of oil in all
aspects.
Synthetic Oils
Synthetic Oils have been available for use in industrial
engines for a relatively long period of time and may offer
advantages in cold and hot temperatures. However, it is not
known if synthetic oils provided operational or economic
benefits over conventional petroleum-based oils in industrial
engines. Use of synthetic oils does not permit the extension
of oil change intervals.
Checking Engine Oil Level
NOTICE: It is important to be careful when checking engine
oil level. Oil must be maintained between the “ADD” and
the “FULL” mark on the dipstick. To ensure that you are not
getting a false reading, make sure the following steps are
taken before checking the oil level.
1. Stop engine.
2. Set control board system switch to OFF.
3. Remove 15 Amp fuse from control panel.
4. Allow approximately five minutes for the oil to drain
back into the oil pan.
5. Remove the dipstick. Wipe with a clean cloth or paper
towel and reinstall. Push the dipstick all the way into the
dipstick tube.
6. Remove the dipstick and note the amount of oil on the
dipstick. The oil level must be between the “ADD” and
“FULL” marks.
7. If the oil level is below the “ADD” mark, reinstall the
dipstick and proceed to step 6.
8. Remove the oil filler cap from the valve cover.
9. Add the required amount of oil to bring the level up to,
but not over, the “FULL” mark on the dipstick. Reinstall
the oil filler cap to the valve rocker arm cover and wipe
any excess oil clean.
NOT
FOR REPRODUCTION
18 BRIGGSandSTRATTON.COM
Engine Coolant System
It is important that the cooling system of the engine be
maintained properly to ensure proper performance and
longevity.
Engine V-Belts
The engine installed in this equipment uses drive belt(s) that
drive the water pump and alternator. The drive belt(s) are an
integral part of the cooling and charging system and should
be inspected according to the maintence schedule. When
inspecting the belts, check for:
 • Cracks
 • Chunkingofthebelt
 • Splits
 • Materialhangingloosefromthebelt
 • Glazing,hardening
If any of these conditions exist, the belt should be replaced.
The cooling system must be maintained according to the
recommended maintenance schedule and inspection should
include:
 • Theregularremovalofdust,dirt,anddebrisfromthe
radiator core and fan shroud.
 • Inspectionofcoolanthosesandcomponentsforleaks,
especially at the radiator hose connections. Tighten
hose clamps if necessary.
 • Checkradiatorhosesforswelling,separation,
hardening, cracks, or any type of deterioration.
 • Inspecttheradiatorcaptoensurepropersealing.
NOTICE: Alcohol or methanol based anti-freeze or plain
water are not recommended for use in the cooling system at
any time.
With the engine cold, check the coolant level in the coolant
recovery bottle (see Controls). Specifications for the coolant
system can be found in the Maintenance chart of this manual.
Coolant Specification - ethylene glycol 50-50 mixture w/
distilled water.
Coolant
WARNING Hot pressurized coolant could cause serious
injury.
• DO NOT open radiator cap when hot.
• Before servicing, allow coolant to cool.
Changing Engine Oil
KEEP OUT OF REACH OF CHILDREN. DON’T
POLLUTE. CONSERVE RESOURCES. RETURN
USED OIL TO COLLECTION CENTERS.
Change oil while the engine is still warm from running.
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Place oil drain hose (B) into an approved container.
4. Open valve (A) located on bottom of oil pan.
5. When oil has drained, replace brass fitting on hose.
6. Remove oil filter and dispose of properly.
7. Before installing a new oil filter, lightly lubricate the oil
filter gasket with fresh, clean oil.
8. Install the oil filter by hand until the gasket contacts the
oil filter adapter, then tighten the oil filter ½ to ¾ turn.
9. Add the required amount of oil to bring the level up to,
but not over the “FULL” mark on the dipstick. Reinstall
the oil filler cap to valve rocker arm cover and wipe any
excess oil clean.
10. If all engine servicing is complete, replace 15 Amp fuse
in control panel and reset exercise timer. See Setting
Exercise Timer in Operation.
To make the task of adding oil more convenient, we
recommend use of a funnel attached to a length of tubing
long enough to reach from the Coolant Fill door to the oil fill
opening on the engine valve cover.
A
A
B
B
NOT
FOR REPRODUCTION
19
Generator Electrical System Maintenance
The generator’s electrical system incorporates computers to
control various related components. The electrical system
connections and ground circuits require good connections.
Follow the recommended maintenance schedule located in
the Maintenance section of this manual.
When inspecting the electrical system, check the following:
 • Checkpositive(+) and negative (-) battery cables for
corrosion, rubbing, chafing, burning, and ensure tight
connections at both ends.
 • Checkbatteryforcracksordamagetothecase.Replace
as necessary.
 • Inspectenginewireharnessforrubbing,chafing,
pinching, burning, and cracks or breaks in the wiring.
 • Verifythattheengineharnessconnectorsarecorrectly
locked in.
 • Inspectignitioncoilwireforhardening,cracking,
chafing, burning, separation, and split boot covers.
 • Inspectsparkplugwiresforhardening,cracking,
chafing, burning, separation, and split boot covers.
 • Replacesparkplugsattherequiredintervalsperthe
recommended maintenance schedule.
 • Verifythatallelectricalcomponentsaresecurely
mounted to the engine or chassis.
 • Verifythatanyadditionalelectricalservicesinstalledby
the owner are properly installed in the system.
Engine Air Cleaner
Once each year service the air cleaner, as follows. If
operating in a dusty environment, service more often.
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Remove filter cartridge - Remove the service cover by
disengaging three clips and detaching cover, starting
with the bottom two clips and the top clip last. Gently
move the end of the filter back and forth, then rotate
while pulling straight out.
4. Clean outlet tube and check Vacuator™ valve - Use a
clean cloth to wipe the filter sealing surface and the
outlet tube surfaces. Make sure that all contaminant is
removed before the new filter is inserted. Be careful to
not damage the sealing area on the tube.
Visually check and physically squeeze Vacuator valve
attached to service cover to make sure
it is flexible and not inverted, damaged
orplugged.
5. Clean filter - Use a soft bristle brush
to loosen dirt and a vacuum cleaner to
remove dirt and debris. Low pressure air (not to exceed
25 psi) may also be used to blow away dirt. Replace
filter cartridge if any holes are detected in filter media.
6. Install clean filter properly - Insert the filter carefully.
Seat the filter by hand, making certain it is completely
into the air cleaner housing before securing the cover
in place. To complete a tight seal, apply pressure by
hand at the outer rim of the filter, not the flexible center.
(Avoid pushing on the center of the urethane end cap.)
No cover pressure is required to hold the seal.
NEVER use the service cover to push the filter into
place! Using the cover to push the filter in could cause
damage to the housing, cover, or fasteners and will void
the warranty. If the service cover hits the filter before
it is fully in place, remove the cover and push the filter
(by hand) further into the air cleaner and try again. The
cover should go on with no extra force.
7. Reinstall service cover - Once the filter is in place,
reinstall the service cover, positioning the cover with
the arrow and the word TOP to the top. Fasten the top
clip first, the bottom two clips last. Make sure that all
mounting bands, clamps, bolts, and connections in the
entire air cleaner system are tight and verify absence of
holes in piping - repair if needed.
8. Replace 15 Amp fuse in control panel.
9. Set control board system switch to ON.
NOT
FOR REPRODUCTION
20 BRIGGSandSTRATTON.COM
Battery
Servicing of batteries is to be performed or supervised
by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel away
frombatteries.
Servicing the Battery
If it is necessary to service the battery, proceed as follows:
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Service or replace battery as required. See Battery
in Final Installation Considerations in the installation
manual for specific battery needed.
4. Connect red battery cable to battery positive terminal
(indicated by POSITIVE, POS, or (+)).
5. Connect black battery cable to negative battery terminal
(indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative battery
terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
8. Set generator’s system switch to AUTO.
9. Reset exercise timer. See Setting Exercise Timer.
DON’T POLLUTE. CONSERVE RESOURCES,
RETURN USED BATTERY TO RECYCLING
COLLECTION CENTER.
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Disconnect negative battery cable from negative battery
terminal (indicated by NEGATIVE, NEG, or (-)).
4. Charge battery with battery charger at 2 Amps until
battery holds 12 Volts. DO NOT exceed 13.7 volts when
charging battery.
5. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative battery
terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
8. Set generator’s system switch to AUTO.
9. Reset exercise timer. See Setting Exercise Timer.
WARNING Battery posts, terminals and related
accessories contain lead and lead compounds - chemicals
known to the State of California to cause cancer and
reproductive harm. Wash hands after handling.
NOTICE Failure to disconnect negative battery cable will
result in equipment failure.
• DO NOT attempt to jump start the generator.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
CAUTION With the system switch set to AUTO,
the engine could crank and start at any
time without warning, resulting in minor or
moderateinjury.
• To prevent possible injury that could be caused by such
sudden starts, always set the system switch to OFF if
performing maintenance on the system.
• Remove the 15 Amp fuse before working on or around
the generator or transfer switch.
NOT
FOR REPRODUCTION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88

Simplicity 076032-00 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur
Ce manuel convient également à