LPN05500X0002A0_A
3 of 4
EMERGENCY DRIVER CHECK
NOTE: For short-term testing of the emergency function, the battery
must be charged for at least one hour. The battery must be charged for
at least 24 hours before conducting a long-term test.
STEP 1:
When AC power is applied, the charging indicator light is illuminated,
indicating the battery is being charged. When power fails, the
emergency driver automatically switches to emergency power,
operating the luminaire. When AC power is restored, the emergency
driver returns to the charging mode.
STEP 2:
Although no routine maintenance is required to keep the emergency
driver functional, it should be checked periodically to ensure that it is
working. The following schedule is recommended:
• Visually inspect the charging indicator light monthly. It should be
illuminated.
• Test the emergency operation of the fixture at 30-day intervals for
a minimum of 30 seconds. When the test switch is depressed, the
luminaire should operate.
• Conduct a 90-minute discharge test once a year. The LED array
should operate for at least 90 minutes.
If the luminaire fails any of these checks, consult service personnel.
REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED
PERSONNEL
FCC NOTICE
CAUTION: Changes or modifications not expressly approved could void
your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
CAN ICES-005 (A)/NMB-005 (A)
Le présent appareil est conforme aux CNR d’Industrie Canada
applicables aux appareils radio exempts de licence. L’exploitation est
autorisée aux deux conditions suivantes : (1) l’appareil ne doit pas
produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout
brouillage radioélectrique subi, même si le brouillage est susceptible
d’en compromettre le fonctionnement.
ELECTRICAL CONNECTIONS- EB
NOTE: The emergency driver must be fed from
the same branch as the AC Driver.
STEP 1:
Make the following electrical connections:
In Power Supply Junction Box:
a. Connect the black luminaire lead to the
switched line or switched Hot 1.
b. Connect the yellow/black luminaire lead to the
unswitched supply or unswitched Hot 1.
c. Connect white luminaire lead to the neutral or Hot 2.
d. Connect the green or green/yellow and bare
ground leads to the supply ground lead.
In Dimming Junction Box:
e. If 0 -10V Dimming is used, connect the violet lead
to the supply positive dimming lead. If dimming is
not being used ensure to cap off the violet lead.
f. If 0 -10V Dimming is used, connect the pink lead
to the supply negative dimming lead. If dimming is
not being used ensure to cap off the pink lead.
STEP 2:
a. Reattach junction box lids over power and dimming
wire connections. Make sure no wires are pinched.
b. Supply AC power to luminaire.
STEP 3:
a. Remove EB activation junction box cover. See Figure 4.
b. Locate the (2) black/white leads in junction box and connect
them.
c. Replace EB activation junction box cover. Make sure no wires
are pinched.
DIM (-) PINK
DIM (+) VIOLET VIOLET
PINK
SUPPLY WIRING
(DIMMING OPTIONAL)
POWER SUPPLY
JUNCTION BOX
GROUND GREEN/YELLOW
YELLOW/BLACK
SWITCHED HOT 1 BLACK
UNSWITCHED HOT 1
WHITE
NEUTRAL
OR HOT 2
*** NOTE: DO NOT mate leads until installation
is complete and AC power is supplied
***BLACK/WHITE
***BLACK/WHITE
ENABLE
LEADS
LUMINAIRE EB
ACTIVATION
JUNCTION BOX
DIMMMING
JUNCTION BOX
GROUND *BARE
** NOTE: For Power Whip options
**RED
* NOTE: Not required on Power Whip options