STEP 1:
Unpack the CR-B troffer from its shipping
container.
STEP 2:
For units without power whip option, proceed to
STEP 3.
For units equipped with power whip, install
access plate cover attached to power whip onto
luminaire using screw provided.
STEP 3:
Install the (4) T-Bar clips included with the
luminaire (located in pre-pack fastened to
luminaire J-Box). See Figure 1.
STEP 4:
Place the CR-B troffer into the T-Bar Ceiling
panel. Ensure T-Bar clips are attached to the
T-Bar. See Figure 2.
2
1
TO INSTALL
IMPORTANT SAFETY INFORMATION
When using electrical equipment, basic safety precautions should always be followed including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. DANGER- Risk of shock- Disconnect power before installation.
DANGER - RISQUE DE CHOC - COUPER L’ALIMENTATION AVANT L’INSTALLATION
2. CAUTION – Installation and servicing should be performed by qualied personnel only. De-energize before opening.
ATTENTION – L’installation et l’entretien doivent être eectués par du personnel qualié seulement. Mettre hors tension avant l’ouverture
3. To reduce the risk of electric shock, disconnect both standard and emergency power supplies and converter connector of the emergency driver
before servicing.
Pour réduire le risque de décharge électrique, vous devez déconnecter à la fois le disjoncteur divisionnaire ou les fusibles et les alimentations
d’urgence avant l’entretien.
4. Do not use outdoors.
Ne pas utiliser à l’extérieur.
5. Do not let power supply cords touch hot surfaces.
Ne laissez pas les cordons d’alimentation toucher les surfaces chaudes.
6. Do not mount near gas or electric heaters.
Ne montez PAS près des appareils de chauage de gaz ou électriques.
7. Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or eyes, ush acid with fresh water
and contact a physician immediately.
Faites preuve de prudence lors de l’entretien des batteries. L’acide de batterie peut provoquer des brûlures de la peau et les yeux. Si l’acide est
versé sur la peau ou les yeux, rincer à l’eau acide frais et contacter un médecin immédiatement.
8. Equipment should be mounted in locations and heights where it will not readily be subjected to tampering by unauthorized personnel.
L’équipement doit être monté dans des endroits et à des hauteurs où il ne sera pas soumis à des altérations par des personnes non autorisées.
9. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
L’utilisation d’accessoires non recommandés par le fabricant peut causer une situation dangereuse.
10. Suitable for damp locations.
Convient Aux Emplacements Humides.
11. Max. mounting height: 10 ft.
Hauteur de montage max.: 10.
12. Access above ceiling required. Do not install insulation within 3” (76mm) of any part of the luminaire.
Accès requis au-dessus du plafond. Ne pas mettre l’isolant à moins de 3 po (76 mm) de toute partie du luminaire
13. Suitable for suspended ceilings.
14. Do not handle energized module with wet hands or when standing on wet or damp surfaces, or in water.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
NOTES:
The CR-B Series is for non-insulated ceiling applications using T-Bar ceiling grid , drywall grid adapters, and surface mount accessory kits.
Designed for use in 120-277V 60 Hz protected circuits (fuse box, circuit breaker). Supply wire sized in accordance with national and local electri-
cal wiring codes rated 90C or higher.
LPN05500X0002A0_A
2 of 4
STEP 5:
NOTE: For GTD luminaires skip to 0-10V
DIMMING section.
Drill 2.5” hole in ceiling at desired location
of test switch. Make sure test switch conduit
from luminaire will reach chosen location
STEP 6:
Insert test switch adapter into hole. Orient
test switch adapter as shown in Figure 3 and
secure with provided 2.5” nut until tight to
ceiling tile.
STEP 7:
Fasten test switch from the luminaire to the
test switch adapter using provided ¾” nut.
See Figure 3 for orientation.
010V DIMMING OPTION:
OPTION: Power whip (if installed), skip
STEPS 1-4. Refer directly to ELECTRICAL
CONNECTIONS to wire flying leads.
NOTE: Power whip is not supported for -GTD
options.
STEP 1:
Remove access plate to access the power wiring
chamber. See Figure 4.
If more wire space is needed, utilize the
expanded J-Box accessory EJBCR-5PK (sold
separately). See Figure 5. Using screw driver
blade, remove appropriate knockout from the
power wiring chamber access plate and route
input conduit.
STEP 2:
If dimming is being used, remove access plate to
access the dimming wires. See Figure 4.
If more wiring space is needed, utilize the
expanded J-Box accessory EJBCR-5PK (sold
separately). See Figure 5. Using screw driver
blade, remove appropriate knockout from the
dimming wiring chamber access plate and route
input conduit.
STEP 3:
Connect power conduit and dimming conduit
(if present) to access plates (and expanded
J-Box if needed). See Figure 4 and 5.
STEP 4:
Wire luminaire per ELECTRICAL
CONNECTIONS section.
EXPANDED JBOX ASSEMBLY OPTION:
In the case of through wiring with conductors
larger than 14 gauge, it is recommended to
utilize the EJBCR-5PK accessory to expand
the junction box volume, thereby allowing for
additional space for wiring and wiring fasteners.
EJBCR-5PK is supplied separately and attaches
to existing J-Box assembly. It is sold in
minimum quantities of five. See Figure 5.
4
5
Optional Power
Whip
(if installed)
Access Plate to Power
Supply Junction Box
Power Supply
Junction Box
Access Plate to Dimming
Junction Box
Dimming
Junction Box
EB Activation
Junction Box Cover
3
2.5” Nut
Test Switch Adapter
Ceiling
Test Switch From
Luminaire
3/4” Nut
LPN05500X0002A0_A
3 of 4
EMERGENCY DRIVER CHECK
NOTE: For short-term testing of the emergency function, the battery
must be charged for at least one hour. The battery must be charged for
at least 24 hours before conducting a long-term test.
STEP 1:
When AC power is applied, the charging indicator light is illuminated,
indicating the battery is being charged. When power fails, the
emergency driver automatically switches to emergency power,
operating the luminaire. When AC power is restored, the emergency
driver returns to the charging mode.
STEP 2:
Although no routine maintenance is required to keep the emergency
driver functional, it should be checked periodically to ensure that it is
working. The following schedule is recommended:
Visually inspect the charging indicator light monthly. It should be
illuminated.
Test the emergency operation of the fixture at 30-day intervals for
a minimum of 30 seconds. When the test switch is depressed, the
luminaire should operate.
Conduct a 90-minute discharge test once a year. The LED array
should operate for at least 90 minutes.
If the luminaire fails any of these checks, consult service personnel.
REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED
PERSONNEL
FCC NOTICE
CAUTION: Changes or modifications not expressly approved could void
your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
CAN ICES-005 (A)/NMB-005 (A)
Le présent appareil est conforme aux CNR d’Industrie Canada
applicables aux appareils radio exempts de licence. L’exploitation est
autorisée aux deux conditions suivantes : (1) l’appareil ne doit pas
produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout
brouillage radioélectrique subi, même si le brouillage est susceptible
d’en compromettre le fonctionnement.
ELECTRICAL CONNECTIONS- EB
NOTE: The emergency driver must be fed from
the same branch as the AC Driver.
STEP 1:
Make the following electrical connections:
In Power Supply Junction Box:
a. Connect the black luminaire lead to the
switched line or switched Hot 1.
b. Connect the yellow/black luminaire lead to the
unswitched supply or unswitched Hot 1.
c. Connect white luminaire lead to the neutral or Hot 2.
d. Connect the green or green/yellow and bare
ground leads to the supply ground lead.
In Dimming Junction Box:
e. If 0 -10V Dimming is used, connect the violet lead
to the supply positive dimming lead. If dimming is
not being used ensure to cap off the violet lead.
f. If 0 -10V Dimming is used, connect the pink lead
to the supply negative dimming lead. If dimming is
not being used ensure to cap off the pink lead.
STEP 2:
a. Reattach junction box lids over power and dimming
wire connections. Make sure no wires are pinched.
b. Supply AC power to luminaire.
STEP 3:
a. Remove EB activation junction box cover. See Figure 4.
b. Locate the (2) black/white leads in junction box and connect
them.
c. Replace EB activation junction box cover. Make sure no wires
are pinched.
DIM (-) PINK
DIM (+) VIOLET VIOLET
PINK
SUPPLY WIRING
(DIMMING OPTIONAL)
POWER SUPPLY
JUNCTION BOX
GROUND GREEN/YELLOW
YELLOW/BLACK
SWITCHED HOT 1 BLACK
UNSWITCHED HOT 1
WHITE
NEUTRAL
OR HOT 2
*** NOTE: DO NOT mate leads until installation
is complete and AC power is supplied
***BLACK/WHITE
***BLACK/WHITE
ENABLE
LEADS
LUMINAIRE EB
ACTIVATION
JUNCTION BOX
DIMMMING
JUNCTION BOX
GROUND *BARE
** NOTE: For Power Whip options
**RED
* NOTE: Not required on Power Whip options
LPN05500X0002A0_A
4 of 4
© 2023 Cree Lighting, A company of IDEAL INDUSTRIES. All rights reserved. For informational purposes only. Content
is subject to change. See www.creelighting.com/warranty for warranty and specifications. Cree® and the Cree Lighting
logo are registered trademarks of Cree, Inc. CR14™, CR22™ and CR24™ are trademarks of Cree Lighting, A company
of IDEAL INDUSTRIES.
www.creelighting.com
ELECTRICAL CONNECTIONS- GTD
NOTE: GTDU is internally wired as Branch Circuit
Emergency Lighting Transfer Switch (BCELTS).
STEP 1:
In Power Supply Junction Box:
a. Connect the black luminaire lead to the
unswitched line or unswitched Hot 1.
b. Connect the red luminaire lead to the
switched line or switched Hot 1.
c. Connect the white luminaire lead to the
normal panel neutral or Hot 2.
d. Connect the green or green/yellow and bare
ground leads to the supply ground lead.
e. Connect blue luminaire lead to the emergency Hot.
f. Connect blue/white luminaire lead
to the emergency neutral.
In Dimming Junction Box:
g. If 0 -10V Dimming is used, connect the violet lead
to the supply positive dimming lead. If dimming is
not being used ensure to cap off the violet lead.
h. If 0 -10V Dimming is used, connect the pink lead
to the supply negative dimming lead. If dimming is
not being used ensure to cap off the pink lead.
STEP 2:
a. Reattach junction box lid over power and dimming
wire connections. Make sure no wires are pinched.
b. Supply AC power to luminaire.
NORMAL PANEL NEUTRAL
OR HOT 2
SUPPLY WIRING
GROUND
WHITE
GREEN/YELLOW
POWER WIRING
JUNCTION BOX
DIM (-) PINK
DIM (+) VIOLET VIOLET
PINK
(DIMMING OPTIONAL)
DIMMMING
JUNCTION BOX
BLACK
SWITCHED HOT 1 RED
UNSWITCHED HOT 1
GROUND BARE
EMERGENCY HOT BLUE
EMERGENCY NEUTRAL BLUE/WHITE
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

CREE LIGHTING CR-B 10V1 w-EB or GT Guide d'installation

Catégorie
Accessoires de moto
Taper
Guide d'installation