Generac RS7000E G0066751 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur
Owners Manual
RS5500 / RS7000E PowerDial
Series Portable Generators
*
NOT INTENDED FOR USE IN CRITICAL
LIFE SUPPORT APPLICATIONS.
*
DEADLY EXHAUST FUMES! USE
OUTSIDE, ONLY, FAR AWAY FROM
WINDOWS, DOORS AND VENTS!
*
SAVE THIS MANUAL. Provide this
manual to any operator of the generator.
Reference all appropriate documentation.
This manual should remain with the unit.
www.generac.com or 1-888-436-3722
WARNING!
California Proposition 65
Engine exhaust and some of its constituents are known to the state of California to cause cancer,
birth defects, and other reproductive harm.
WARNING!
California Proposition 65
This product contains or emits chemicals known to the state of California to cause cancer,
birth defects, and other reproductive harm.
i
Table of Contents
Unit Information ...........................................................i
Section 1 - Safety........................................................1
1.1 Read This Manual Thoroughly................................1
1.2 Safety Rules............................................................1
Section 2 - General Information.................................5
2.1 Unpacking...............................................................5
2.2 Assembly ................................................................5
2.3 Emissions Information.............................................6
2.4 Product Specifications ............................................7
2.5 Know The Generator...............................................7
2.6 Before Starting the Generator...............................10
Section 3 - Operation................................................13
3.1 How To Use The Generator..................................13
3.2 Generator Loads...................................................14
3.3 Wattage Reference Guide ....................................14
3.4 Starting The Generator (Electric Start) .................15
3.5 Starting The Generator (Manual/Recoil)
Starting..................................................................15
3.6 Stopping The Generator .......................................16
3.7 Restarting the Generator ......................................16
3.8 Low Oil Level Shutdown System ..........................16
Section 4 - Maintenance...........................................17
4.1 General Recommendations ..................................17
4.2 Generator Cleaning...............................................17
4.3 Service Intervals ...................................................17
4.4 Generator Storage ................................................22
Section 5 - Troubleshooting ....................................23
5.1 Troubleshooting Guide..........................................23
5.2 Replacement Service Parts ..................................24
Unit Information
Use this page to record important information about your
generator set.
R
e
Record the information found on your unit data label on
this page. The location of the unit data label is shown
here.
When contacting an Authorized Service Dealer about
parts and service, always supply the complete model
number and serial number of the unit.
Operation and Maintenance: Proper maintenance and
care of the generator ensures a minimum number of
problems and keep operating expenses at a minimum. It
is the operator’s responsibility to perform all safety
checks, to make sure that all maintenance for safe opera-
tion is performed promptly, and to have the equipment
checked periodically by an Authorized Service Dealer.
Normal maintenance, service and replacement of parts
are the responsibility of the owner/operator and, as such,
are not considered defects in materials or workmanship
within the terms of the warranty. Individual operating hab-
its and usage may contribute to the need for additional
maintenance or service.
When the generator requires servicing or repairs, contact
an Authorized Service Dealer for assistance. Authorized
service technicians are factory-trained and are capable of
handling all service needs.
MODEL NO:
SERIAL NO:
MODEL DATA
DECAL
ii
This page intentionally left blank.
RS5500 / RS7000E PowerDialSeries Portable Generators 1
Thank you for purchasing this model by Generac Power
Systems, Inc. This model is a compact, high perfor-
mance, air-cooled, engine driven generator designed to
supply electrical power to operate electrical loads where
no utility power is available or in place of utility due to a
power outage.
1.1 — READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact
the nearest Authorized Dealer for starting, operating and
servicing procedures.
The operator is responsible for proper and safe use of
the equipment. We strongly recommend that the operator
read this manual and thoroughly understand all instruc-
tions before using the equipment. We also strongly rec-
ommend instructing other users to properly start and
operate the unit. This prepares them if they need to oper-
ate the equipment in an emergency.
The generator can operate safely, efficiently and reliably
only if it is properly located, operated and maintained.
Before operating or servicing the generator:
Become familiar with and strictly adhere to all local,
state and national codes and regulations.
Study all safety warnings in this manual and on the
product carefully.
Become familiar with this manual and the unit before use.
The manufacturer cannot anticipate every possible cir-
cumstance that might involve a hazard. The warnings in
this manual, and on tags and decals affixed to the unit
are, therefore, not all inclusive. If using a procedure, work
method or operating technique that the manufacturer
does not specifically recommend, ensure that it is safe for
others. Also make sure the procedure, work method or
operating technique utilized does not render the genera-
tor unsafe.
THE INFORMATION CONTAINED HEREIN WAS
BASED ON MACHINES IN PRODUCTION AT THE
TIME OF PUBLICATION. GENERAC RESERVES THE
RIGHT TO MODIFY THIS MANUAL AT ANY TIME.
Save these instructions for future reference. If you
loan this device to someone, ALWAYS loan these
instructions to the individual as well.
1.2 — SAFETY RULES
Throughout this publication, and on tags and decals
affixed to the generator, DANGER, WARNING, CAUTION
and NOTE blocks are used to alert personnel to special
instructions about a particular operation that may be haz-
ardous if performed incorrectly or carelessly. Observe
them carefully. Their definitions are as follows:
INDICATES A HAZARDOUS SITUATION OR ACTION
WHICH, IF NOT AVOIDED, WILL RESULT IN DEATH
OR SERIOUS INJURY.
Indicates a hazardous situation or action which, if
not avoided, could result in death or serious injury.
Indicates a hazardous situation or action which,
if not avoided, could result in minor or moderate
injury.
NOTE:
Notes contain additional information important to a
procedure and will be found within the regular text
body of this manual.
These safety warnings cannot eliminate the hazards that
they indicate. Common sense and strict compliance with
the special instructions while performing the action or
service are essential to preventing accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type of
information each indicates is as follows:
This symbol points out important safety infor-
mation that, if not followed, could endanger
personal safety and/or property of others.
This symbol points out potential explosion
hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical
shock hazard.
*
$
!
+
Section 1 Safety
2 RS5500 / RS7000E PowerDial Series Portable Generators
WARNING: Hearing protection recommended.
1.2.1 — General Hazards
NEVER operate in an enclosed area, in a vehicle, or
indoors EVEN IF doors and windows are open.
For safety reasons, the manufacturer recommends
that the maintenance of this equipment is carried out
by an Authorized Dealer. Inspect the generator regu-
larly, and contact the nearest Authorized Dealer for
parts needing repair or replacement.
Operate generator only on level surfaces and where it
will not be exposed to excessive moisture, dirt, dust or
corrosive vapors.
Keep hands, feet, clothing, etc., away from drive belts,
fans, and other moving parts. Never remove any fan
guard or shield while the unit is operating.
Certain parts of the generator get extremely hot during
operation. Keep clear of the generator until it has
cooled to avoid severe burns.
Do NOT operate generator in the rain.
Do not alter the construction of the generator or
change controls which might create an unsafe operat-
ing condition.
Never start or stop the unit with electrical loads con-
nected to receptacles AND with connected devices
turned ON. Start the engine and let it stabilize before
connecting electrical loads. Disconnect all electrical
loads before shutting down the generator.
Do not insert objects through unit’s cooling slots.
When working on this equipment, remain alert at all
times. Never work on the equipment when physically
or mentally fatigued.
Never use the generator or any of its parts as a step.
Stepping on the unit can stress and break parts, and
may result in dangerous operating conditions from
leaking exhaust gases, fuel leakage, oil leakage, etc.
1.2.2 — Exhaust & Location Hazards
Never operate in an enclosed area or indoors!
NEVER use in the home, in a vehicle, or in partly
enclosed areas such as garages, EVEN IF doors and
windows are open! ONLY use outdoors and far from
open windows, doors, vents, and in an area that will
not accumulate deadly exhaust.
The engine exhaust fumes contain carbon monoxide,
which you cannot see or smell. This poisonous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death.
Adequate, unobstructed flow of cooling and ventilating
air is critical to correct generator operation. Do not
alter the installation or permit even partial blockage of
ventilation provisions, as this can seriously affect safe
operation of the generator. The generator MUST be
operated outdoors.
This exhaust system must be properly maintained. Do
nothing that might render the exhaust system unsafe
or in noncompliance with any local codes and/or stan-
dards.
Always use a battery operated carbon monoxide
alarm indoors, installed according to the manufactur-
ers instructions.
If you start to feel sick, dizzy, or weak after the genera-
tor has been running, move to fresh air IMMEDI-
ATELY. See a doctor, as you could have carbon
monoxide poisoning.
1.2.3 — Electrical Hazards
The generator produces dangerously high voltage
when in operation. Avoid contact with bare wires, ter-
minals, connections, etc., while the unit is running,
even on equipment connected to the generator.
Ensure all appropriate covers, guards and barriers are
in place before operating the generator.
Never handle any kind of electrical cord or device
while standing in water, while barefoot or while hands
or feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
The National Electric Code (NEC) requires the frame
and external electrically conductive parts of the gener-
ator be properly connected to an approved earth
ground. Local electrical codes may also require proper
grounding of the generator. Consult with a local elec-
trician for grounding requirements in the area.
*
RS5500 / RS7000E PowerDial Series Portable Generators 3
Use a ground fault circuit interrupter in any damp or
highly conductive area (such as metal decking or steel
work).
Do not use worn, bare, frayed or otherwise damaged
electrical cord sets with the generator.
Before performing any maintenance on the generator,
disconnect the engine starting battery (if equipped) to
prevent accidental start up. Disconnect the cable from
the battery post indicated by a NEGATIVE, NEG or (–)
first. Reconnect that cable last.
In case of accident caused by electric shock, immedi-
ately shut down the source of electrical power. If this
is not possible, attempt to free the victim from the live
conductor. AVOID DIRECT CONTACT WITH THE
VICTIM. Use a non-conducting implement, such as a
rope or board, to free the victim from the live conduc-
tor. If the victim is unconscious, apply first aid and get
immediate medical help.
1.2.4 — Fire Hazards
Gasoline is highly FLAMMABLE and its vapors are
EXPLOSIVE. Never permit smoking, open flames,
sparks or heat in the vicinity while handling gasoline.
Never add fuel while unit is running or hot. Allow
engine to cool completely before adding fuel.
Never fill fuel tank indoors. Comply with all laws
regulating storage and handling of gasoline.
Do not overfill the fuel tank. Always allow room for
fuel expansion. If tank is over-filled, fuel can overflow
onto a hot engine and cause FIRE or an EXPLOSION.
Never store generator with fuel in tank where gasoline
vapors might reach an open flame, spark or pilot light
(as on a furnace, water heater or clothes dryer). FIRE
or EXPLOSION may result. Allow unit to cool entirely
before storage.
Wipe up any fuel or oil spills immediately. Ensure that
no combustible materials are left on or near the gener-
ator. Keep the area surrounding the generator clean
and free from debris and maintain a clearance of five
(5) feet on all side to allow for proper ventilation of the
generator.
Do not insert objects through unit’s cooling slots.
Never operate the generator if connected electrical
devices overheat, if electrical output is lost, if engine
or generator sparks or if flames or smoke are
observed while unit is running.
Keep a fire extinguisher near the generator at all
times.
1.2.5 — Standards Index
1. National Fire Protection Association (NFPA) 70: The
NATIONAL ELECTRIC CODE (NEC) available from
www.nfpa.org
2. National Fire Protection Association (NFPA) 5000:
BUILDING CONSTRUCTION AND SAFETY CODE
available from www.nfpa.org
3. International Building Code available from
www.iccsafe.org
4. Agricultural Wiring Handbook available from
www.rerc.org , Rural Electricity Resource Council
P.O. Box 309 Wilmington, OH 45177-0309
5. ASAE EP-364.2 Installation and Maintenance of
Farm Standby Electric Power available from
www.asabe.org, American Society of Agricultural &
Biological Engineers 2950 Niles Road, St. Joseph,
MI 49085
This list is not all inclusive. Check with the Authority Hav-
ing Local Jurisdiction (AHJ) for any local codes or stan-
dards which may be applicable to your jurisdiction.
4 RS5500 / RS7000E PowerDial Series Portable Generators
This page intentionally left blank.
RS5500 / RS7000E PowerDial Series Portable Generators 5
2.1 — UNPACKING
Remove all packaging material.
Remove separate items.
Remove the generator from carton.
2.1.1 — Documents and Accessories
(not shown)
Check all contents. If any parts are missing or damaged,
call 1-888-436-3722.
Product Registration Cards
Warranty and Emission Sheets
1 - Owner’s Manual
1 - Quart Oil - SAE 30
1 - 20 ft. Extension Cord (if equipped)
1 - Battery Charger (7.0 kW only)
2.1.2 — Loose Components
1 - Handle Assembly (not in hardware bag)
2 - Rubber Feet (not in hardware bag) (M)
2 - Frame Foot (not in hardware bag) (L)
1 - Hardware Bag (containing the following):
— 2 - Cotter Pins (A)
— 2 - Washers (1/2 in) (B)
— 2 - Never-Flat Wheels (C)
— 2 - Axle Pins (D)
— 2 - Hex Flanged Nuts (M6) (E)
— 4 - Hex Bolt (M8) (F)
— 2 - Hex Bolt (M6) (G)
— 4 - Nut, Hex Flange (M8) (H)
— 2 - Nut, Acorn (M8) (J)
— 2 - Carriage Bolt (M8) (K)
2.2 — ASSEMBLY
The generator requires some assembly prior to usage. If
problems arise when assembling the generator, call 1-
888--436-3722.
2.2.1 — Required Tools
3/8 drive Ratchet
Sockets: 13, 12, 8 mm (1 ea)
Wrenches: 13, 10 mm (1 ea), 8 mm (2)
Needle nosed pliers
2.2.2 — Installing Wheels
NOTE:
The wheels are not intended for over-the-road use.
1. Install the Wheels as follows (Figure 2-1):
— Slide the Axle Pin (D) through the Wheel (C),
Wheel Bracket on the frame and a 5/8" Flat
Washer (B).
— Insert the Cotter Pin (A) through the Axle Pin. Use
the needle nosed pliers to bend open to lock in
place.
Figure 2-1. Wheel Assembly
2.2.3 — Installing Frame Feet
1. Install the Frame Foot Assemblies as shown (Figure
2-2).
— Slide the M8 Hex Bolts (F) through the holes in the
Frame Rail.
— Slide the Frame Foot (L) onto the Hex Head Bolts.
Then install the Locking Flange Nuts (H). Tighten
securely using a ratchet, 12 mm socket and
13 mm wrench.
— Slide the M6 Hex Bolt (G) through the Rubber
Foot (M) and Frame Foot (L). Then install M6 Hex
Flange Nut (E). Tighten securely using 10 mm
wrench and 8 mm socket.
2. Repeat the Step 1 to install the other Frame Foot
Assembly.
A
B C
D
Section 2 General Information
6 RS5500 / RS7000E PowerDial Series Portable Generators
Figure 2-2. Frame Foot Assemblies
2.2.4 — Installing Handle
1. Place the handle over the frame tabs as shown. (Fig-
ure 2-3).
2. Slide Carriage Bolts M8 (K) through the handle
brackets and tabs.
3. Place a nut (J) on each Carriage Bolt (K) and tighten
securely using a ratchet and a 13 mm socket.
Figure 2-3. Handle
2.2.5 — Battery Cables (7.0kW only)
NOTE:
The battery shipped with the generator has been fully
charged. The positive and negative cables are NOT
connected and must be attached prior to operation.
The NEGATIVE (black) (-) battery cable should:
1. Always be DISCONNECTED FIRST.
2. Always be CONNECTED LAST.
Use two 8 mm wrenches to tighten battery hardware.
Figure 2-4. Battery Connections
(7.0 kW only)
NOTE:
A battery may lose some of its charge when not in
use for prolonged periods of time. If the battery is
unable to crank the engine, plug in the 12V charger
included in the accessory box (see the Charging a
Battery - Section 4: Maintenance). RUNNING THE
GENERATOR DOES NOT CHARGE THE BATTERY.
2.3 — EMISSIONS INFORMATION
Locate the emissions compliance decal on the engine to
determine what standards the generator meets, and to
determine which warranty applies. This generator is certi-
fied to operate on gasoline. The emission control system
includes the following components (if equipped):
Air Induction System
— Intake Pipe / Manifold
— Air Cleaner
•Fuel System
— Carburetor/Mixer Assembly
— Fuel Regulator
Ignition System
— Spark Plug
— Ignition Module
Exhaust System
— Exhaust Manifold
— Muffler
— Pulsed Air Valve
— Catalyst
M
E
G
H
F
L
J
K
RS5500 / RS7000E PowerDial Series Portable Generators 7
2.4 — PRODUCT SPECIFICATIONS -
5.5 / 7.0
KW
2.4.1 — Generator Specifications
Rated Power ................................................ 5.5 / 7.0 kW
Surge Power ............................................6.87 / 8.75 kW
Rated AC Voltage...............................................120/240
Rated AC Load
Current @ 240V..............................22.9 / 29.2 Amps**
Current @ 120V..............................45.8 / 58.4 Amps**
Rated Frequency .............................60 Hz @3600 RPM
Phase.........................................................Single Phase
Operating Temperature Range .....0 °F (-8 °C) to 104 °F
(40 °C)*
* When operated above 77 °F (25 °C) there may be a decrease in
power.
** Maximum wattage and current are subject to, and limited by, such
factors as fuel Btu content, ambient temperature, altitude, engine
condition, etc. Maximum power decreases about 3.5% for each 1,000
feet above sea level; and will also decrease about 1% for each 10 °F
(-12.2 °C) above 60 °F (16 °C) ambient temperature.
2.4.2 — Engine Specifications - 5.5 / 7.0 kW
Displacement ...................389 cc/420 cc - 5.5 kW / 7 kW
Spark Plug Type................................... Champion N9YC
Spark Plug Gap...........0.028-0.031 inch (0.70-0.80 mm)
Fuel Capacity................6.7 gallons (25.4 liters) - 5.5 kW
......................................7.5 gallons (28.4 liters) - 7.0 kW
Oil Type................................................see Section 2.6.1
Oil Capacity..................................1.06 Quarts (1.0 liters)
Run Time at 50% Load ...11 Hour /12 hours - 5.5/7.0 kW
2.5 — KNOW THE GENERATOR
Compare the generator to Figures 2-5 through 2-7 to
become familiarized with the locations of various controls
and adjustments.
Read the Owners Manual and Safety Rules before
operating this generator.
1. 120/240 Volt AC, 30 Amp, Locking Receptacle
Supplies electrical power for the operation of 120
and/or 240 Volt AC, 30 Amp, single-phase, 60 Hz
electrical lighting, appliance, tool and motor loads.
2. Circuit Breakers (AC) – A 2-pole circuit breaker pro-
tects the rated output of the 30 Amp Twistlock outlet
(CSA only). Each duplex receptacle and the 30 Amp
Twistlock are provided with a push-to-reset circuit
breakers to protect against electrical overload
(49 State).
3. Hourmeter - Tracks hours of operation to perform
required maintenance.
4. Battery Charger Input (7.0 kW only) – Permits
recharging of the battery. A 12 volt charger is
included. A 1.50 Amp in-line fuse is located behind
the control panel to protect the battery when
charging.
5. 120 Volt AC, 20 Amp Duplex Outlets – Supplies
electrical power for the operation of 120 Volt AC, 20
Amp, single-phase, 60 Hz, electrical lighting, appli-
ance, tool and motor loads.
Figure 2-5. Control Panel - CSA
1
2
3
4
5
8 RS5500 / RS7000E PowerDial Series Portable Generators
Figure 2-6. Control Panel - 49 State
Figure 2-7. Generator Controls
6. Fuel Gauge - shows fuel level in tank.
7. Roll Over Valve - passes fuel vapors to the engine.
8. Battery - provides power for electric starter.
(7.0 kW only)
9. Oil Fill/Dipstick - check oil level and add oil here.
10. Oil Drain - drain plug for removing used oil from the
crankcase.
11. Handle – used to transport generator.
12. Recoil Starter - used to start engine manually.
13. Air Filter - filters air as it is drawn into the engine.
14. PowerDial – controls the operation of the ON/RUN/
STOP functions, choke and fuel valve.
15. Fuel Cap - remove to fill fuel tank.
16. Recovery Hose - vapor tube between roll over valve
and the engine.
17. Fuel Tank - holds fuel supply.
18. Muffler – quiets the engine.
19. Grounding Location - grounds the generator to an
approved earth ground here. See “Grounding the
Generator” for details.
5
1 2
3
4
7
6
13
12
11
10
9 8
15
16
18
17
14
19
RS5500 / RS7000E PowerDial Series Portable Generators 9
Figure 2-8. Oil Drain/Fill
2.5.1 — Connection Plugs
2.5.1.1 — 120 VAC, 20 Amp, Duplex
Receptacle
This is a 120 Volt outlet protected against overload by a
20 Amp push-to-reset circuit breaker (Figure 2-9). Use
each socket to power a NEMA 5-15P or 5-20P, 120 Volt
AC, single phase, 60 Hz electrical loads requiring up to a
combined 2400 watts (2.4 kW) or 20 Amps of current.
Use only high quality, well-insulated, 3-wire grounded
cord sets rated for 125 Volts at 20 Amps (or greater).
Keep extension cords as short as possible, preferably
less than 15 feet long, to prevent voltage drop and possi-
ble overheating of wires.
Figure 2-9. 120 Volt AC, 20 Amp, Duplex
Receptacle
2.5.1.2 — 120/240 VAC, 30 Amp Locking
Receptacle
Use a NEMA L14-30 Plug with this receptacle (rotate to
lock/unlock). Connect the supplied 4-wire grounded cord
set to the plug and to the desired load. The cord set
should be rated for 250 Volts AC at 30 Amps (or greater).
Figure 2-10. 120/240 VAC, 30 Amp
Receptacle
Use this receptacle to operate 120 Volt AC, 60 Hz, single
phase loads requiring up to 3600 watts (3.6 kW) of power
at 30 Amps or 240 Volt AC, 60 Hz, single phase loads
requiring up to 7,200 watts of power. The outlet is pro-
tected by two 25 Amp (5.5 kW) or two 30 Amp (7.0 kW)
push to reset or one 25 Amp or one 30 Amp 2 pole toggle
switch to reset (7.0 kW) circuit breaker.
2.5.2 — Extension Cord (if equipped)
Your generator comes with a 20 foot extension cord for
connecting appliances and other electrical devices to the
generator.
NOTE:
Never start or stop the engine with electrical devices
plugged into generator and devices turned on.
The colored dots on the extension cord are indicators for
evenly applying the loads to the generator. For example,
if two electrical devices are plugged in, place one into a
red labeled outlet and the other into a blue labeled outlet,
rather than two red or two blue outlets (Figure 2-11).
Figure 2-11. Extension cord
OIL DRAIN PLUG
DIPSTICK / FILL OPENING
9
10
5
1
BLUE DOTS RED DOTS
10 RS5500 / RS7000E PowerDial Series Portable Generators
2.5.3 — Hourmeter
The Hourmeter tracks hours of operation for scheduled
maintenance (Figure 2-12).
There will be a "CHG OIL" message every 100 hours.
The message will flash one hour (of run time) before and
one hour after each 100 hour interval, providing a two
hour window to perform service.
This message will actually begin flashing at 99 hours and
disable itself at 101 hours again, providing a two hour
window to perform the service.
Every 200 hours the "SVC" icon on the lower left hand
corner of the display will flash. The message will flash
one hour before and one hour after each 200 hour inter-
val providing a two hour window to perform service.
Figure 2-12. Hourmeter
When the hour meter is in the Flash Alert mode, the
maintenance message will always alternate with elapsed
time in hours and tenths. The hours will flash four times,
then alternate with the maintenance message four times
until the meter resets itself.
100 hours - CHG OIL — Oil Change Interval (Every
100 hrs)
200 hours - SVC — Service Air Filter (Every 200 hrs)
NOTE:
The hour glass graphic will flash on and off when the
engine is running. This signifies that the meter is
tracking hours of operation.
2.5.4 — PowerDial
The PowerDial controls the ON/OFF functions, choke
and fuel valve operation. (Figure 2-13)
The Number 1 position is used when initially starting
the engine. In this position, the fuel is on and the
choke is fully on (closed). Both the electric start or pull
(recoil) start can be used.
The PowerDial is rotated to position Number 2 during
normal operation and to gradually reduce the use of
the choke.
Rotating the PowerDial to the STOP position will stop
the engine and shut off the fuel valve flow.
Figure 2-13. PowerDial (RS7000E example shown)
2.6 — BEFORE STARTING THE GENERATOR
Prior to operating the generator:
Engine oil will need to be added.
Fill the fuel tank with unleaded fuel.
Battery cables will need to be connected.
(7.0 kW only)
2.6.1 — Adding Engine Oil
The generator has been shipped WITHOUT oil. All oil
should meet minimum American Petroleum Institute
(API) Service Class SJ, SL or better. Use no special addi-
tives. Select the oil's viscosity grade according to the
expected operating temperature (also see chart).
Above 40 °F (4.4 °C), use SAE 30
Below 40 °F (4.4 °C) and down to 10 °F (-12.2 °C),
use SAE 10W-30
All temperatures, use synthetic SAE 5W-30
HOUR GLASS
GRAPHIC
RESET BUTTON
(IF EQUIPPED)
0000.0
3
RS5500 / RS7000E PowerDial Series Portable Generators 11
Any attempt to start the engine before it has been
properly serviced with the recommended oil may
result in an engine failure.
1. Place generator on a level surface (not to exceed 15°
in any direction).
2. Clean area around oil fill and remove oil fill cap/dip-
stick.
3. Wipe dipstick clean (Figure 2-14).
4. Slowly fill engine with oil through the oil fill opening.
Stop filling occasionally to check oil level. Fill until the
level is at the upper mark on the dipstick. Be careful
not to over fill.
Figure 2-14. Oil Fill/Dipstick
5. Install oil fill cap and finger tighten securely.
6. Check engine oil level before starting each time
thereafter.
2.6.2 — Adding Fuel
Never fill fuel tank indoors. Never fill fuel
tank when engine is running or hot. Avoid
spilling gasoline on a hot engine. Allow
engine to cool entirely before filling fuel tank.
DO NOT light a cigarette or smoke when
filling the fuel tank.
Do not overfill the fuel tank. Always leave
room for fuel expansion. If the fuel tank is
overfilled, fuel can overflow onto a hot
engine and cause FIRE or EXPLOSION. Wipe
up any spilled fuel immediately.
Use the following instructions for adding gasoline:
Use regular UNLEADED gasoline with the generator
engine. Do not mix oil with gasoline.
Do not use gasoline with more than 10% alcohol such
as E85 or ethanol.
Clean area around fuel fill cap, remove cap.
Slowly add unleaded gasoline to fuel tank. Be careful
not to overfill (Figure 2-15).
Install fuel cap and wipe up any spilled gasoline.
Figure 2-15. Fuel Fill Level
IMPORTANT: It is important to prevent gum deposits
from forming in fuel system parts such as the carburetor,
fuel hose or tank during storage. Alcohol-blended fuels
(called gasohol, ethanol or methanol) can attract mois-
ture, which leads to separation and formation of acids
during storage. Acidic gas can damage the fuel system of
an engine while in storage. To avoid engine problems,
the fuel system should be emptied or treated with a com-
mercially available fuel stabilizer before storage of 30
days or longer. See the "Storage" section. Never use
engine or carburetor cleaner products in the fuel tank as
permanent damage may occur.
*
FULL
ADD
9
$
$
DO NOT Fill Above Lip
Fuel
Fuel Tank
12 RS5500 / RS7000E PowerDial Series Portable Generators
This page intentionally left blank.
RS5500 / RS7000E PowerDial Series Portable Generators 13
3.1 — HOW TO USE THE GENERATOR
See the "To Start the Engine" section for how to safely
start and stop the generator and how to connect and dis-
connect loads. If there are any problems operating the
generator, please call 1-888-436-3722.
Never operate in an enclosed area or indoors!
NEVER use in the home, in a vehicle, or in
partly enclosed areas such as garages, EVEN
IF doors and windows are open! ONLY use out-
doors and far from open windows, doors,
vents, and in an area that will not accumulate
deadly exhaust.
The engine exhaust fumes contain carbon
monoxide, which you cannot see or smell. This
poisonous gas, if breathed in sufficient con-
centrations, can cause unconsciousness or
even death.
Adequate, unobstructed flow of cooling and
ventilating air is critical to correct generator
operation. Do not alter the installation or per-
mit even partial blockage of ventilation provi-
sions, as this can seriously affect safe
operation of the generator. The generator
MUST be operated outdoors.
This exhaust system must be properly main-
tained. Do nothing that might render the
exhaust system unsafe or in noncompliance
with any local codes and/or standards.
Always use a battery operated carbon monox-
ide alarm indoors, installed according to the
manufacturer's instructions.
3.1.1 — Grounding The Generator When
Used As A Portable
This generator has an equipment ground that connects
the generator frame components to the ground terminals
on the AC output receptacles (see NEC 250.34 (A) for
explanation). This allows the generator to be used as a
portable without grounding the frame of the generator as
specified in NEC 250.34.
Figure 3-1. Grounding the Generator
3.1.1.1 — Special Requirements
There may be Federal or State Occupational Safety and
Health Administration (OSHA) regulations, local codes,
or ordinances that apply to the intended use of the gener-
ator.
Please consult a qualified electrician, electrical inspector,
or the local agency having jurisdiction:
In some areas, generators are required to be regis-
tered with local utility companies.
If the generator is used at a construction site, there
may be additional regulations which must be
observed.
*
*
*
*
*
Section 3 Operation
14 RS5500 / RS7000E PowerDial Series Portable Generators
3.1.2 — Connecting The Generator To A
Building’s Electrical System
When connecting directly to a building’s electrical sys-
tem, it is recommended that a manual transfer switch is
used. Connections for a portable generator to a building’s
electrical system must be made by a qualified electrician
and in strict compliance with all national and local electri-
cal codes and laws.
3.2 — GENERATOR LOADS
Overloading a generator in excess of its rated wattage
capacity can result in damage to the generator and to
connected electrical devices. Observe the following to
prevent overloading the unit:
Add up the total wattage of all electrical devices to be
connected at one time. This total should NOT be
greater than the generator's wattage capacity.
The rated wattage of lights can be taken from light
bulbs. The rated wattage of tools, appliances and
motors can usually be found on a data label or decal
affixed to the device.
If the appliance, tool or motor does not give wattage,
multiply volts times ampere rating to determine watts
(volts x amps = watts).
Some electric motors, such as induction types, require
about three times more watts of power for starting
than for running. This surge of power lasts only a few
seconds when starting such motors. Make sure to
allow for high starting wattage when selecting electri-
cal devices to connect to the generator:
1. Figure the watts needed to start the largest motor.
2. Add to that figure the running watts of all other con-
nected loads.
The Wattage Reference Guide is provided to assist in
determining how many items the generator can operate
at one time.
NOTE:
All figures are approximate. See data label on appli-
ance for wattage requirements.
3.3 — WATTAGE REFERENCE GUIDE
Device . . . . . . . . . . . . . . . . . . . . . . . . . . . Running Watts
*Air Conditioner (12,000 Btu) . . . . . . . . . . . . . . . . .1700
*Air Conditioner (24,000 Btu) . . . . . . . . . . . . . . . . .3800
*Air Conditioner (40,000 Btu) . . . . . . . . . . . . . . . . .6000
Battery Charger (20 Amp). . . . . . . . . . . . . . . . . . . . .500
Belt Sander (3"). . . . . . . . . . . . . . . . . . . . . . . . . . . .1000
Chain Saw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Circular Saw (6-1/2"). . . . . . . . . . . . . . . . . . 800 to 1000
*Clothes Dryer (Electric) . . . . . . . . . . . . . . . . . . . . .5750
*Clothes Dryer (Gas). . . . . . . . . . . . . . . . . . . . . . . . .700
*Clothes Washer . . . . . . . . . . . . . . . . . . . . . . . . . . .1150
Coffee Maker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1750
*Compressor (1 HP) . . . . . . . . . . . . . . . . . . . . . . . .2000
*Compressor (3/4 HP). . . . . . . . . . . . . . . . . . . . . . .1800
*Compressor (1/2 HP). . . . . . . . . . . . . . . . . . . . . . .1400
Curling Iron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
*Dehumidifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .650
Disc Sander (9") . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Edge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500
Electric Blanket . . . . . . . . . . . . . . . . . . . . . . . . . . . . .400
Electric Nail Gun . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Electric Range (per element). . . . . . . . . . . . . . . . . .1500
Electric Skillet . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1250
*Freezer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
*Furnace Fan (3/5 HP) . . . . . . . . . . . . . . . . . . . . . . .875
*Garage Door Opener. . . . . . . . . . . . . . . . . . 500 to 750
Hair Dryer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Hand Drill. . . . . . . . . . . . . . . . . . . . . . . . . . . 250 to 1100
Hedge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . .450
Impact Wrench . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500
Iron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
*Jet Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .800
Lawn Mower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
Light Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Microwave Oven . . . . . . . . . . . . . . . . . . . . . 700 to 1000
*Milk Cooler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1100
Oil Burner on Furnace. . . . . . . . . . . . . . . . . . . . . . . .300
Oil Fired Space Heater (140,000 Btu). . . . . . . . . . . .400
Oil Fired Space Heater (85,000 Btu). . . . . . . . . . . . .225
Oil Fired Space Heater (30,000 Btu). . . . . . . . . . . . .150
*Paint Sprayer, Airless (1/3 HP) . . . . . . . . . . . . . . . .600
Paint Sprayer, Airless (hand-held). . . . . . . . . . . . . . .150
Radio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 to 200
*Refrigerator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
Slow Cooker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200
*Submersible Pump (1-1/2 HP). . . . . . . . . . . . . . . .2800
*Submersible Pump (1 HP). . . . . . . . . . . . . . . . . . .2000
*Submersible Pump (1/2 HP) . . . . . . . . . . . . . . . . .1500
*Sump Pump. . . . . . . . . . . . . . . . . . . . . . . . 800 to 1050
*Table Saw (10") . . . . . . . . . . . . . . . . . . . . 1750 to 2000
Television. . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 to 500
Toaster. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000 to 1650
Weed Trimmer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500
* Allow 3 times the listed watts for starting these devices.
RS5500 / RS7000E PowerDial Series Portable Generators 15
3.4 — STARTING THE GENERATOR
(ELECTRIC START) - 7.0 KW ONLY
Never start or stop engine with electrical
devices plugged into the receptacles AND
devices turned on.
1. To start the engine, turn the PowerDial to the START
position (Figure 3-2). This opens the fuel valve and
activates (closes) the choke.
2. Press and momentarily hold the PowerDial in the
START position. The engine will crank and attempt to
start. When the engine starts, release the switch.
3. See Figure 3-3. When the engine starts, rotate the
PowerDial gradually clockwise, until the engine runs
smoothly, and then fully to the RUN position. Choke
operation is reduced as the Power Dial is rotated
towards the RUN position. If engine falters, rotate the
PowerDial counterclockwise to the START position,
to increase the choke, until the engine runs smoothly
and then rotate it to the RUN position.
NOTE
In the RUN position, the choke is completely turned OFF and fuel
flow is ON.
4. Both generators are also equipped with a manual
recoil starter which may be used if the battery is dis-
charged.
Figure 3-2. PowerDial START Position
Figure 3-3. PowerDial RUN Position
3.5 — STARTING THE GENERATOR
(MANUAL/RECOIL) STARTING
Never start or stop engine with electrical
devices plugged into the receptacles AND
devices turned on.
1. See Figure 3-2. To start the generator, rotate the
PowerDial to the START position.
2. Firmly grasp the recoil handle and pull slowly until
increased resistance is felt. Pull rapidly up and away
to start engine.
3. See Figure 3-3. When the engine starts, rotate the
PowerDial gradually clockwise, until the engine runs
smoothly, and then fully to the RUN position. Choke
operation is reduced as the PowerDial is rotated
towards the RUN poistion. If engine falters, rotate the
PowerDial counterclockwise to the START position,
to increase the choke, until the engine runs smoothly
and then rotate it to the RUN position.
NOTE
If engine fires, but does not continue to run, rotate
the PowerDial to “START” and repeat starting
instructions.
+
+
16 RS5500 / RS7000E PowerDial Series Portable Generators
IMPORTANT: Do not overload the generator. Also, do
not overload individual panel receptacles. These outlets
are protected against overload with push-to-reset or tog-
gle type circuit breakers. If amperage rating of any circuit
breaker is exceeded, that breaker opens and electrical
output to that receptacle is lost. Read “Generator Loads”
carefully.
3.6 — STOPPING THE GENERATOR
NOTE
NEVER start or stop the engine with electrical
devices plugged in and turned on.
1. Shut off all loads, then unplug the electrical loads
from the generator’s panel receptacles or extension
cord.
2. Let the engine run at no-load for several minutes to
stabilize the internal temperatures of the engine and
generator.
3. See Figure 3-4. Rotate the PowerDial clockwise to
the STOP position. This will shut down the engine
and turn off the fuel flow by closing the fuel valve.
Figure 3-4. PowerDial STOP position
3.7 — RESTARTING THE GENERATOR
If the generator has cooled completely, use the starting procedures
outlined in 3.4 or 3.5. However, if the generator is at or near operating
temperature, use the following steps when restarting the unit.
.Never start or stop engine with electrical devices
plugged into the receptacles AND devices turned on.
NOTE
The generator is shut off and the PowerDial is turned to the
STOP position. Turning the PowerDial counterclockwise, past
the RUN position, turns on the fuel again and permits use of the
electric starter. The PowerDial MUST be turned from the STOP
position to just past the RUN position to restart the fuel flow.
Do not turn far. The choke is not required if the engine is hot.
Figure 3-5. PowerDial in the hot restart position
1. See Figure 3-5. To restart a hot generator, turn the
PowerDial counterclockwise, from the STOP posi-
tion, until it is just past the RUN position. This will
reopen the fuel valve and permit electric start or
recoil starting.
2. Press the PowerDial button in this position to electric
start. (7.0 kW only) or firmly grasp the recoil handle
and pull slowly until increased resistance is felt. Pull
rapidly up and away to pull start engine.
3. Then turn the PowerDial clockwise to the RUN posi-
tion.
3.8 — LOW OIL LEVEL SHUTDOWN
S
YSTEM
The engine is equipped with a low oil level sensor that
shuts down the engine automatically when the oil level
drops below a specified level. If the engine shuts down by
itself and the fuel tank has sufficient fuel, check engine oil
level.
+
+
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96

Generac RS7000E G0066751 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur