CREE LIGHTING CR-B Wireless (SC1_VDO_VRF) Guide d'installation

Taper
Guide d'installation
CR-B Series with Wireless Technology
LED Architectural Troffer
Includes: CR14-B-(SC1,VDO/VRF), CR22-B-(SC1,VDO/VRF), CR24-B-(SC1,VDO/VRF)
1x4, 2x2, 2x4 Luminaires
1 of 3 LPN05500X0003A0_A
INSTALLATION INSTRUCTIONS
INSTRUCTIONS D’INSTALLATION
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions
should always be followed including the following:
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
1. DANGER- Risk of shock- Disconnect power before
installation.
DANGER – Risque de choc – Couper l’alimentation avant
l’installation.
2. This luminaire must be installed in accordance with the
NEC or your local electrical code. If you are not familiar
with these codes and requirements, consult a qualied
electrician.
Ce produit doit être installé conformément à NEC ou votre
code électrique local. Si vous n’êtes pas familier avec ces
codes et ces exigences, veuillez contacter un électricien
qualié.
3. Do not handle energized module with wet hands or when
standing on wet or damp surfaces, or in water.
4. Suitable for damp locations.
Convient aux emplacements humides.
5. Access above ceiling required. Do not install insulation within
3" (76mm) of any part of the luminaire.
Accès requis au-dessus du plafond. Ne pas mettre l’isolant à
moins de 76 mm (3 po) de toute partie du luminaire.
6. Suitable for suspended ceilings.
SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE
TO INSTALL:
LUMINAIRE INSTALLATION
STEP 1:
Unpack the CR-B troffer from its
shipping container.
STEP 2:
For units without power whip option,
proceed to STEP 3.
For units equipped with power whip, install
access plate cover attached to power whip
onto luminaire using screw provided.
STEP 3:
Install the (4) T-Bar clips included with
the luminaire (located in
pre-pack fastened to luminaire junction
box). See Figure 1.
1
The CR-B Series of recessed troffers is for non-insulated ceiling applications using T-Bar ceiling grid , drywall grid adapters, and surface mount
accessory kits.
Designed for use in 120-277V 60 Hertz protected circuit (fuse box, circuit breaker). Supply wire sized as per NEC or governing code(s), 90° C
rated.
NOTE: SmartCast luminaires must be installed on unswitched AC power. Constant power is required to maintain all luminaires on the
SmartCast network. If wall control or manual dimming is required, a SmartCast wall control dimmer must be used for manual on, off, and
dimming.
CR14-B-SC1
CR14-B-VDO/VRF
CR24-B-SC1
CR24-B-VDO/VRF
CR22-B-SC1
CR22-B-VDO/VRF
2 of 3 LPN05500X0003A0_A
STEP 4:
Place the CR-B troffer into the T-Bar Ceiling panel.
Ensure T-Bar clips are attached to the T-Bar. See
Figure 2.
SETUP
OPTION: Power whip (if installed) skip Steps 1-3 and
refer directly to the Electrical Connections section
and wire flying leads.
STEP 1:
Disconnect power to circuit by turning circuit breaker
OFF before installation.
STEP 2:
Loosen access plate cover screw and remove cover
to expose wiring chamber. Bring conduit into wiring
chamber using one of the knockouts. See Figure 3.
STEP 3:
Wire luminaire per “Electrical Connections” section
and push all leads into the junction box. Close
junction box cover that was removed in Step 2 and
retighten screw. Make sure no wires are pinched.
STEP 4:
Switch the circuit breaker on.
STEP 5:
Luminaires ordered with SC1 are provided with
factory installed integrated Cree Lighting SmartCast®
Wireless fixture control with occupancy and Daylight
sensor. Make sure the blue LED has a two-blink
sequence. If not, please proceed to Troubleshooting
section. Otherwise proceed to commissioning as per
SmartCast® Technology Deployment guide. Please
refer to the SmartCast® documentation for details.
See Figure 4.
STEP 6:
Luminaires ordered with VD0/VRF are provided with
factory installed Lutron Vive Wireless fixture control.
For set-up programming, troubleshooting with a
Lutron Vive system, please refer to the installation
instructions included with Vive or at www.lutron.com.
See Figure 4.
EXPANDED JBOX ASSEMBLY OPTION:
In the case of through wiring with conductors larger
than 14 gauge, it is recommended to utilize the EJBCR-
5PK accessory to expand the junction box volume,
thereby allowing for additional space for wiring and
wiring fasteners. EJBCR-5PK is supplied separately
and attaches to existing J-Box assembly. It is sold in
minimum quantities of five. See Figure 5.
SMARTCAST® RESET
STEP 1:
Actuate RESET button through the access hole. Press
and hold Reset button until the blue LED flashes fast
(approximately 5 seconds). See Figure 4.
STEP 2:
Release the Reset button for 1 second (Fast flashing
continues). Press and hold Reset for 1 second until
fast flashing stops. If the blue LED does not respond
with the two-blink sequence, please repeat the RESET
procedure.
3Access Plate
2
4
LUTRON VIVE SENSOR
(VDO/VRF)
Ambient Light Sensor /
Blue LED indicator
Motion
Sensor
Reset
Button
Ambient Light Sensor /
Blue LED indicator
Motion
Sensor
Reset
Button
SmartCast® SENSOR
(SC1)
5
Optional Power
Whip
(if installed)
3 of 3 LPN05500X0003A0_A
www.creelighting.com
© 2023 Cree Lighting, A company of IDEAL INDUSTRIES. All rights reserved. For informational purposes only. Content
is subject to change. See www.creelighting.com/warranty for warranty and specifications. Cree® and the Cree Lighting
logo are registered trademarks of Cree, Inc. SmartCast® is a registered trademark, and CR14™, CR22™ and CR24™ are
trademarks of Cree Lighting, A company of IDEAL INDUSTRIES.
TROUBLESHOOTING:
Out of the box, if the light does not turn on when power is applied:
Check Wiring with power off
If wired correctly for SC1:
Check to see if blue LED has a two-blink sequence. If not,
please proceed to RESET procedure.
If you have done a RESET, and the light is still off, call
Cree Lighting Customer Service.
If blue LED is on solid or off, call Cree Lighting Customer
Service.
If light is unresponsive, use Cree Lighting Configuration
Tool to verify configuration.
If wired correctly for VD0/VRF:
Refer to the installation instructions included with Lutron
Vive or at www.lutron.com.
FCC NOTICE
To comply with the FCC RF exposure compliance requirements,
this device and its antenna must not be co-located or operating to
conjunction with any other antenna or transmitter.
This equipment should be installed and operated with minimum
distance 5cm between the radiator & your body.
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved could void
your authority to use this equipment.
This device complies with Part 15 of the FCC Rules. Operation to
the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation
This device has been tested and found to comply with the limits for
a Class A digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference when the device is operated in a commercial environment.
This device generates, uses, and can radiate radio frequency energy
and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of
this device in a residential area is likely to cause harmful interference
in which case the user will be required to correct the interference at his
own expense.
The LED in the front of this device operates within Risk Group 1 levels
per IEC 62471.
INDUSTRY CANADA STATEMENT
This device complies with Industry Canada licence-exempt RSS
standard(s). Operation is subject to the following two conditions: (1) this
device may not cause interference, and (2) this device must accept any
interference, including interference that may cause undesired operation
of the device. In addition, this device complies with ICES-003 of the
Industry Canada (IC) Regulations.
Le présent appareil est conforme aux CNR d’Industrie Canada
applicables aux appareils radio exempts de licence. L’exploitation est
autorisée aux deux conditions suivantes : (1) l’appareil ne doit pas
produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout
brouillage radioélectrique subi, même si le brouillage est susceptible
d’en compromettre le fonctionnement.
ELECTRICAL CONNECTIONS
STEP 1:
Make the following Electrical Connections::
a. Connect the black fixture lead to the line or Hot 1.
b. Connect the white fixture lead to the neutral or Hot 2.
c. Connect the green or green/yellow ground lead to ground.
LINE
OR HOT 1
GREEN
LINE-BLACK
GROUND-GREEN
NEUTRAL-WHITE
NEUTRAL
OR HOT 2
SUPPLY WIRING
LUMINAIRE
  • Page 1 1
  • Page 2 2
  • Page 3 3

CREE LIGHTING CR-B Wireless (SC1_VDO_VRF) Guide d'installation

Taper
Guide d'installation