Legrand HPSA Outdoor Analog Photocell Sensor for the Lighting Integrator Panel Guide d'installation

Taper
Guide d'installation
Wattstopper
®
Outdoor Analog Photocell Sensor for the Lighting Integrator Panel
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 25267 – 11/16 rev. 1
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: HPSA/HPSA-X
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
800.879.8585
www.legrand.us/wattstopper
No. 25267 – 11/16 rev. 1
© Copyright 2016 Legrand All Rights Reserved.
© Copyright 2016 Tous droits réservés Legrand.
© Copyright 2016 Legrand Todos los derechos reservados.
Wattstopper warranties its products to be free
of defects in materials and workmanship for a
period of five (5) years. There are no obligations
or liabilities on the part of Wattstopper for
consequential damages arising out of, or in
connection with, the use or performance of this
product or other indirect damages with respect
to loss of property, revenue or profit, or cost of
removal, installation or reinstallation.
Wattstopper garantit que ses produits sont
exempts de défauts de matériaux et de fabrication
pour une période de cinq (5) ans. Wattstopper
ne peut être tenu responsable de tout dommage
consécutif causé par ou lié à l’utilisation ou
à la performance de ce produit ou tout autre
dommage indirect lié à la perte de propriété, de
revenus, ou de profits, ou aux coûts d’enlèvement,
d’installation ou de réinstallation.
Wattstopper garantiza que sus productos
están libres de defectos en materiales y mano
de obra por un período de cinco (5) años. No
existen obligaciones ni responsabilidades por
parte de Wattstopper por daños consecuentes
que se deriven o estén relacionados con el
uso o el rendimiento de este producto u otros
daños indirectos con respecto a la pérdida
de propiedad, renta o ganancias, o al costo
de extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
SPECIFICATIONS
Footcandle range
HPSA .............................................................................. 0 - 200 fc
HPSA-X ..................................... Custom range, see product label
Calibration ...................................None, controlled by system software
Input voltage .............................................................................. 12VDC
Sensor output ...................................................................... 0 - 4.4VDC
Peak current .............................................................. 4.5 mA Maximum
Slew rate ...................................1 minute full scale response time filter
Operating temperature ..........................-40�F to 140�F (-40�C to 60�C)
Wire color code
Red ........................................................................+12 VDC input
Black ..................................................0 - 4.4VDC signal to panel
White ........................................................................ DC common
Housing ................. Watertight, UV stabilized plastic with integral hood
Mounting .................................................................½” NPT x .69” stem
Overall dimensions ............................................... 2.55”L x 1.28”D
DESCRIPTION
The HPSA is a daylight sensor specifically designed to be used
in conjunction with a Lighting Integrator Complete Control level
panel and WinControl user software only. Consult the factory for
information on photocell sensors to be used with other Legrand/
Wattstopper lighting control panels.
INSTALLATION
Install the sensor on the roof of the building facing north. The sensor
housing is equipped with a ½” NPT nipple and will thread into any
suitable watertight box or fitting. Orient the housing so that the hood
is above the lens to provide shielding.
Wiring
Connect the sensor to the lighting control panel as shown, making
sure to maintain the color code of the conductors between the
sensor pigtails and the color coded connector within the panel. The
sensor can be connected to any of the available terminals on the
panel’s group switching card (see panel installation instructions for
the location of these terminals). However, if factory documentation
was supplied with the system, the sensor must be connected to the
specified terminal in order for the programming to work correctly.
For an overview of the entire system, refer to the Lighting
Integrator Installation and Operation Manual.
If you have any questions, call our Service Team at:
800.879.8585.
Group Switching Card inside LI Panel
Wiring Terminals
$%&'()*+
5
%
<
:
5
%
<
:
5
%
<
:
5
%
<
:
5
%
<
:
5
%
<
:
5
%
<
:
5
%
<
:
#20 AWG up to 250 feet
#18 AWG up to 1000 feet
Class 2 wiring
HPSA
Sensor
Watertight J Box
North
Sensor Hood
  • Page 1 1

Legrand HPSA Outdoor Analog Photocell Sensor for the Lighting Integrator Panel Guide d'installation

Taper
Guide d'installation