NOTE: Simply shorting the two wires together
will cause the light to shut off.
WARNING: Improper installation, operation,
or maintenance of this luminaire may result in
the invalidation of the warranty, certificate,
or declaration of conformity.
DALI Control (If Applicable)
DALI is used to control/schedule and group
the luminaire. A DALI controller is to be
provided by the installer. The luminaire will not
provide a bus signal. A Bus power supply
should be used to provide a Bus signal
according to the DALI standard.
WARNING: Never connect the DALI wires to
the Hot/Live or Neutral supply wires.
WARNING: Do not connect the DALI wires to
the dimming wires.
For luminaires containing one power supply
[F1U*********** & F2U****(F/H)******], only one
DALI address will be assigned by the DALI
controller.
For luminaires containing two power supplies
[F2U****(L/N)******], two DALI addresses will
be assigned by the DALI controller.
NOTE: The DALI circuit in two power supply
luminaires are already internally wired as a
daisy chain to allow for commissioning and
discovery. The Bus wire needs to be
connected to the DALI terminal block
positions in the wiring compartment.
NOTE: Make sure luminaires containing two
power supplies are grouped and scheduled
together for the luminaire to function in the
correct manner.
WARNING: Improper installation, operation,
or maintenance of this luminaire may result in
the invalidation of the warranty, certificate,
or declaration of conformity.
Maintenance / Inspection
This LED luminaire should require a minimum
amount of maintenance. If any unforeseen
repairs are required, please contact Dialight
or its authorized representative.
Within the scope of maintenance or
inspection routine the following should be
included:
Protective hoses should be covering the
connection cables.
Cable entries must be free of corrosion.
The lens should be cleaned periodically as
needed to ensure continued photometric
performance. Clean the lens with a damp,
non-abrasive, lint free cloth. If not
sufficient, use mild soap or a liquid cleaner.
Inspect the luminaire to ensure that it is free
of any obstructions or contamination (i.e.
excessive dust build up). Clean with a non-
abrasive cloth if needed.
Perform visual mechanical and electrical
inspections on
a regular basis.
We
recommend routine checks to be made
on a yearly basis. Frequency of use and
environment should determine this.
It is recommended to follow an Electrical
Preventive Maintenance Program as
described in NFPA 70B: Recommended
Practice for Electrical Equipment.
Repairs / Overhaul / Modification
The equipment must be operated according
to the intended purpose in a perfect and
undamaged condition.
NOTE: Should the luminaire enclosure be
damaged, only a full luminaire replacement
will be permitted. In case of doubt, the
equipment should be returned to Dialight for
inspection/repair.
Disposal & Recycling
When the apparatus is disposed of, the
respective national regulations on waste
disposal should be observed.
Secondary Retention Cable
1. Read and follow all instructions in the
installation manual provided with the
secondary retention cable.
2. Connect the safety cable to one of the
retention brackets on the luminaire.
3. When using a safety cable for secondary
retention, ensure minimum slack in the
cable installation. The slack should be no
greater than 1 ft. [0.3 m]
NOTE: Cable type, size, material, and
attachment method to meet customer
application and to be appropriate with all
local and regional regulations.