2
S19-120, S19-120A Installation
5/30/2012
"RADLEYs
215-148 Rev. Y; ECN 12-05-016A
WARNING
Read this installation manual completely to ensure proper installation, then file it
with the owner or maintenance department. Compliance and conformity to drain
requirements and other local codes and ordinances is the responsibility of the installer.
Separate parts from packaging and make sure all parts are accounted for before
discarding any packaging material. If any parts are missing, do not begin installation
until you obtain the missing parts.
Flush the water supply lines before beginning installation and after installation is
complete. Test the unit for leaks and adequate water flow. Main water supply to the
eyewash should be “ON” at all times. Provisions shall be made to prevent unauthorized
shutoff.
The ANSI Z358.1 standard requires an uninterruptible supply of flushing fluid at a
minimum 30 PSI (0.21 MPa) flowing pressure. Flushing fluid should be tepid per ANSI
Z358.1.
The inspection and testing results of this equipment should be recorded weekly
to verify proper operation. This equipment should be inspected annually to ensure
compliance with ANSI Z358.1.
Workers who may come in contact with potentially hazardous materials should be
trained regarding the placement and proper operation of emergency equipment per
ANSI Z358.1.
For questions regarding the operation or installation of this product, visit www.
bradleycorp.com or call 1-800-BRADLEY.
Product warranties and service parts information may also be found under ”Products”
on our web site at www.bradleycorp.com.
Installation
THIS
SIDE
UP
Packing List
P.O. Box 309, Menomonee F
alls,
WI 53051
R
TES
T
THIS
U
N
IT EACH
WEEK
Test-operate valve(s) each week and sign
below.
Report an
y malfunctions im
m
ediatel
y.
Ventil(e) wöc
hentlich im
Tes
tbetrieb prüfen, bestätigt
durch Unterschrift. J
egliche Störung sofort melde
n.
Date
Datum
Date
Signed
Unterschrift
Signe
Date
Date
Date Signed
Signed
Signed
D
IE
S
ES GERÄT 1ST
WÖCHEN
TLICH ZU
PRÜ
FEN.
ESSAI HEBDOMADAIRE
Test le fonctionnement des v
alves chaque semaine et
signe en bas. S'il y à quelqu
e chose qui ne v
a pas fait
un rapport immédiateme
nt.
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA
TEL: 1-800-BRADLEY FAX: (262-251-5817)
http://www.bradleycorp.com
114-051