DESCRIPTION
The LCVR series 8/24/48 is the standard cover for a Wattstopper
Lighting Integrator (LI) Lighting Control Panel.
A complete panel assembly includes one each of the following:
• Enclosure (LTUB series)
• Interior with relays and power supply
• Cover to match the Enclosure (LCVR Series)
Features
• Key-hole screw attachment allows temporary hanging of the
cover during installation.
• Locking door with 2 keys supplied per cover.
• Door exposes Class 2 section of panel only, meets NEC Article
409.
• Clear display pocket provided on inside of door for circuit
schedule and other documentation.
Cover and Tub Compatibility
LCVR8S, LCVR8F LTUB8
LCVR24S, LCVR24F LTUB24
LCVR24PS, LCVR24PF LTUB24
LCVR48S, LCVR48F LTUB48
LCVR48S-24, LCVR48F-24 LTUB48
Refer to LTUB Panel Enclosure Installation and Setup for
assembly instructions that will preceed the installation of the
LCVR Panel Cover.
INSTALLATION
1. Drive the supplied cover mounting screws into the threaded
holes until approximately 3/8” of the thread is still exposed.
2. Hang the cover on the screws by aligning the screw heads with
the keyholes.
3. Tighten the screws to complete the installation.
4. Insert completed relay and circuit schedules and the Lighting
Control Panel Interior Instructions in the plastic sleeve affixed to
the inside of the cover to complete the panel installation.
Refer to the Dimensions section for panel enclosure and cover
dimensions.
DIMENSIONS
LTUB8y Enclosure, LI panel
8 relay capacity
15.08” x 16.5” x 4.5”
LTUB24y Enclosure, LI panel
24 relay capacity
31.38” x 23.88” x 4.5”
LTUB48y Enclosure, LI panel
48 relay capacity
43.88 “x 23.88” x 4.5”
LCVR8S NEMA 1 surface cover, LI
panel
8 relay capacity
15.36” x 16.84” x .75”
LCVR8F NEMA 1 flush cover, LI
panel
8 relay capacity
17.06” x 18.48” .75”
LCVR24S NEMA 1 surface cover, LI
panel
24 relay capacity
31.66” x 24.16” x .75”
LCVR24F NEMA 1 flush cover, LI
panel
24 relay capacity
33.35” x 25.85” .75”
LCVR48S NEMA 1 surface cover, LI
panel
48 relay capacity
44.90” x 24.19” x .75”
LCVR48F NEMA 1 flush cover, LI
panel
48 relay capacity
45.85” x 25.85” .75”
y = blank (NEMA 1 (default), S3R (NEMA 3R - not available for
LTUB8), S4 (NEMA 4)
NOTE: Dimensions given for NEMA1 Enclosures only.
WARNING: DO NOT INSTALL OR
REMOVE COVER WITH POWER
APPLIED TO THE LIGHTING CONTROL
PANEL. DANGER OF ELECTRIC SHOCK.