Middle Atlantic Products UPS-1000R Manuel utilisateur

Catégorie
Alimentations sans interruption (UPS)
Taper
Manuel utilisateur
I-00350 Rev D
UPS-RBP Series
Replacement Batteries
UPS-1000R | UPS-2200R
User Manual
• Replace batteries in your UPS-RBP Series Battery Pack.
THANK YOU
PRODUCT FEATURES
Thank you for purchasing the UPS-RBP. The UPS-RBP is a hot-swappable (for qualified service
personnel) replacement battery pack for the UPS-1000R and UPS-2200R Series Rackmount UPS.
Please read this manual thoroughly before installing this product.
Page 2
BATTERY REPLACEMENT
Safety Precautions
CAUTION! Make sure everything is turned off and AC power is disconnected completely before
conducting any maintenance, battery replacement, repairs, or shipment.
CAUTION! Only use replacement batteries which are certified by Middle Atlantic Products. Use of
incorrect battery type is an electrical hazard that could lead to explosion, fire, electric shock, or short
circuit.
CAUTION! Batteries contain an electrical charge that can cause severe burns. Before servicing
batteries, please remove any conductive materials such as jewelry, chains, wrist watches, and rings.
CAUTION! Do not open or mutilate the batteries. Electrolyte fluid is harmful to the skin/eyes and may
be toxic.
CAUTION! To avoid electric shock, turn off and unplug the UPS from the wall receptacle before
servicing the battery.
CAUTION! Only use tools with insulated handles. Do not lay tools or metal parts on top of the UPS or
battery terminals.
Précautions de Sécurité
ATTENTION! Assurez-vous que tout est éteint et alimentation secteur est débranchée complètement
avant de procéder à tout entretien, le remplacement de la batterie, reparations, ou l'expédition.
ATTENTION: La batterie est lourd. Soyez prudent lorsque vous retirez.
CAUTION: The battery is heavy. Use caution when removing.
IMPORTANT SAFETY INSTRUCTIONS
UPS-2200R
UPS-1000R
UPS-RBP (4x) 12V, 8AH, 26.4 lbs. (11.97 KG)
MODEL
SPECIFICATIONS
REPLACEMENT BATTERY
PART NUMBER
CONSIGNES DE SÉCURITÉ IMPORTANTES
CAUTION: Risk of explosion if battery is replaced by an incorrect type. See the specification table for more
information.
CAUTION: Risk of Energy Hazard, 48 V, maximum 8 Ampere-hour batteries. Before replacing batteries,
remove conductive jewelry such as chains, wrist watches, and rings. High energy through conductive
materials could cause severe burns.
ATTENTION: Risque d’explosion si la batterie de replacement par un type incorrect.
ATTENTION: Risques d'énergie danger, 48 V, maximaux 8 ampère-heure batterie. Avant de remplacer
des batteries, enlever conducteur bijoux tels que des chaînes, des montres-bracelet et des anneaux. La
haute énergie par les matériaux conducteurs a pu causer les brûlures graves.
Page 3
BATTERY REPLACEMENT (CONTINUED)
ATTENTION! Utilisez uniquement des batteries de remplacement qui sont certifiés par Middle Atlantic Products.
L'utilisation de batterie de type incorrect est un danger électrique qui pourrait provoquer une explosion, un
incendie, un choc électrique ou un court-circuit.
ATTENTION! Les piles contiennent une charge électrique qui peut causer de graves brûlures. Avant
batteries desservant, s'il vous plaît supprimer tous les matériaux conducteurs comme des bijoux, chaînes,
montres-bracelets, et bagues.
ATTENTION! Ne pas ouvrir ni mutiler la batterie, l'électrolyte libéré est nocif pour la peau et les yeux.
ATTENTION! Pour éviter un choc électrique, éteindre et de débrancher l'onduleur de la prise murale avant de
réparer la batterie.
ATTENTION! Utilisez uniquement des outils avec des poignées isolées. Ne posez pas d'outils ou de pièces
métalliques sur le dessus de l'onduleur ou bornes de la batterie.
Please read and follow the Safety Precautions before servicing the battery. Battery replacement should be
performed by trained personnel who are familiar with the procedures and safety precautions. Make a note of
the replacement Battery tray number.
After the product is removed from its shipping carton, inspect the Battery Pack before installing and
operating. The shipping carton should contain the following items:
UPS Battery Pack, Installation Instructions, and (3x) M3 x 6 Battery Retainer Screws
NOTE:
• Batteries are considered hazardous waste and must be disposed of properly. Contact your local
government for more information about proper disposal and recycling of batteries. Do not dispose of
batteries in fire.
• Middle Atlantic Products encourages environmentally sound methods for disposal and recycling of
its UPS products. Please dispose and/or recycle your UPS and batteries in accordance to the local
regulations of your state.
• Contact technical support at 1-800-266-7225 for more information about Middle Atlantic Product’s
Battery Replacement Program.
• Both UPS-1000R Series and UPS-2200R Series contain hot-swappable battery packs. Hot-swappable
is the ability to replace a battery pack without switching line power off.
• Do not replace battery when UPS is working in battery mode, as this will cause power to be lost and
may cause damage to connected equipment.
To check if UPS is in battery mode, look at the display. If the UPS is operating in battery mode the
“BATTERY” icon appears in the LCD window. See the following circled example.
Page 4
REMOVE CABLE PROTECTION COVER
BATTERY REPLACEMENT (CONTINUED)
2. Remove the UPS front panel by removing the six screws and pulling it away from the unit.
1. Power off the unit and disconnect it from its AC power source.
3. Remove the retaining screws securing the cable protection cover to the UPS and remove the cover.
NOTE: For qualified service personnel, the battery is hot swappable. Non-qualified service person-
nel are strongly urged to follow the first step to power off the unit and disconnect it from its AC
power source.
4. Disconnect the cable connectors from each other.
Page 5
DISCONNECT CABLE CONNECTORS
BATTERY REPLACEMENT (CONTINUED)
5. Remove three battery retaining screws (2 on left side, and 1 on the right side) and pull the
battery out using the handle while supporting battery pack from underneath to prevent battery from
falling. (The battery pack is heavy and caution should be taken when removing and replacing it.)
6. Insert replacement battery and perform steps in reverse using (3) replacement screws
supplied with battery pack. Recharge battery for 4-8 hours to ensure UPS performs expected runtime.
REMOVE 2 SCREWS
Page 6
HANDLE
REMOVE 1 SCREW
BATTERY REPLACEMENT (CONTINUED)
OPTIONAL EXTERNAL BATTERY CONNECTION
Both UPS-1000R and UPS-2200R Series models feature a connector that accepts an optional
external battery pack (part number: UPS-EBPR, sold separately) that provides additional runtime.
The external battery packs can be series connected up to a maximum of 10 battery packs in order to
provide additional UPS runtime.
Page 7
WARRANTY
For warranty information, refer to www.middleatlantic.com/terms.
Corporate Headquarters
Corporate Voice: 973-839-1011 - Fax: 973-839-1976 / International Voice: +1 973-839-8821 - Fax: +1
973-839-4982
www.middleatlantic.com - [email protected]
Middle Atlantic Canada
Voice: 613-836-2501 - Fax: 613-836-2690 / www.middleatlantic.ca - customerservicecanada@middleat-
lantic.ca
Factory Distribution
USA: NJ - CA - IL Canada: ON - BC
At Middle Atlantic Products we are always listening. Your comments are welcome.
Middle Atlantic Products is an ISO 9001 and ISO 14001 Registered Company.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Middle Atlantic Products UPS-1000R Manuel utilisateur

Catégorie
Alimentations sans interruption (UPS)
Taper
Manuel utilisateur

dans d''autres langues