Medallion M5S Guide d'installation

Taper
Guide d'installation

Ce manuel convient également à

M1B, M1M & M5S Series
Downflow, Direct Vent (Sealed Combustion)
Forced Air Gas & Oil Furnaces
For installation in:
 
     
Buildings
 

 

 




       




   


      




    


      
   
    

     

      
     


     



      


   


2




Minimum Clearances ............................................... 4
Applications ............................................................. 4
Unit Location ............................................................ 6
 6
Return Air ................................................................. 6
Supply Air ................................................................ 6

General Information ................................................. 7
Locating & Cutting Duct Openings ........................... 7
Standard Duct Connector Installation ...................... 9
Alternate Attachment Method ................................ 9
Round Duct Connector Installation .......................... 9
Installing the Furnace .............................................. 9
 
Roof Jack Selection ................................................. 10
Locating & Cutting Roof / Ceiling Openings ............ 10
Installing The Roof Jack .......................................... 11
Installation of Transit-Mode Venting System ........... 11
Before home is moved to site .................................. 11
Installation of Transit-Mode Venting System ........... 12
After home is moved to site ..................................... 12
 
Line Voltage Wiring .................................................. 13
Connecting Power Supply Wires ........................... 13
Low Voltage Wiring .................................................. 13
Connecting Thermostat Wires ............................... 13
Verifying Anticipator Setting .................................. 13
Grounding ................................................................ 14
 15
Leak Check .............................................................. 15
Flue Gas Sampling .................................................. 16
High Altitude Conversion ......................................... 16
Conversion to Propane (LP) Gas ............................. 17
Atmospheric & Direct Ignition Furnaces ................ 17
Measuring the Supply Gas Pressure.....................18
Measuring the Manifold Pressure..........................18
Oil Tank & Piping Installation ................................... 18
One-Line System .................................................. 18
Two-Line System...................................................18
Fuel line Hook-Up .................................................... 19
Fuel Line Bleeding ................................................... 19
Priming furnaces equipped with Honeywell...........19
R7184 primary control ........................................... 19
Priming furnaces equipped with Beckett 7505
primary control.......................................................19
Fuel Oil Type ........................................................... 20
 
M1M Operating Instructions ..................................... 20
How to Shut Off Gas - Direct Ignition Models........21
M1B Operating Instructions ..................................... 21
How to Shut Off Gas Gun Models ......................... 21
M5S Operating Instructions ..................................... 21
How to Shut Off Oil Gun Models ........................... 22
Verifying Input Rate ................................................. 22
Verifying & Adjusting Temperature Rise .................. 22
Burner Adjustments ................................................. 22
Gas Pressure ........................................................ 22
Combustion Air ........................................................ 22
Gas Gun (M1B Models).........................................23
Oil Gun Only (M5S Models) .................................. 23
Electrode Setting (Oil Gun Only) ............................. 23
Switching Ignition Control between Interrupted
and Intermittent Duty ............................................... 23
 
Direct Ignition Furnaces (M1M Models) ................... 23
Gas Gun Furnaces (M1B Models) ........................... 23
Oil Gun Furnaces (M5S Models) ............................. 23
 
Direct Ignition Furnaces (M1M Models) &
Gas Gun Furnaces (M1B Models) ........................... 24
Oil Gun - Honeywell R7184 or Beckett 7505
Controls Only - M5S Series ..................................... 25
 
 
Installer Information ................................................. 27
Additional Oil Furnace Maintenance ........................ 27
 
Optional Add-On Air Conditioning ............................ 27
 
Table 10. M1/M5 Furnace Specifications -
Factory Settings .................................................... 28
Table 11. A/C Blower Speed Selection Chart ....... 28
Gas Information ....................................................... 29
Table 12. Gas Flow Rates ..................................... 29
Table 13. Gas Pipe Capacities .............................. 29
Table 17. High Altitude Deration Chart for
Propane Gas ......................................... 30
Electrical Information ............................................... 31
Figure 35. Gas Direct Ignition Furnace, Heating &
A/C Ready - All M1M Models ............... 31
Figure 36. Gas and Oil Furnaces, A/C Ready -
M1B & M5S (066, 086) Models ............ 32
 
3

Safety markings are used frequently throughout this
manual to designate a degree or level of seriousness and
should not be ignored.  indicates a potentially
hazardous situation that if not avoided, could result in
personal injury or death.  indicates a potentially
hazardous situation that if not avoided, may result in minor
or moderate injury or property damage.

      
     

    
     




      





    

     
       




• This furnace must be installed in accordance with
these instructions, all applicable local building codes
and the current revision of the National Fuel Gas Code
(NFPA54/ANSI Z223.1) or the Natural Gas and Propane
Installation Code, CAN/CSA B149.1.
• Useonly with type of gas approvedforthisfurnace.
Refer to the furnace rating plate.
• Install this furnace in accordance to the minimum
clearances to combustible materials listed in Table 1,
(page 5).
• Provideadequatecombustionandventilationairtothe
furnace space as specified on page 6 and page 22.
Do not block or obstruct air openings on the furnace,
air openings to the area where the furnace is installed,
or the space around the furnace.
• Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system, as
specified on page 10.
• Never test for gas leaks with an open ame. Use
a commercially available soap solution to check all
connections. See page 15.
• Thisfurnaceisdesignedtooperatewithamaximum
externalpressureriseof0.5inchesofwatercolumn.
 The static pressure measurement should not
include the coil (if applicable). Consult Table 10, (page
28) and the rating plate for the proper circulating air
owandtemperaturerise.
 It is important that the duct system be designed
tohandlethedesiredowrateandexternalpressure
rise. An improperly designed duct system can result in
nuisance shutdowns, and comfort or noise issues.
• Whensupplyductscarryaircirculatedbythefurnace
to areas outside the space containing the furnace, the
return air shall also be handled through the front door
of the furnace. Make sure there is sufficient return air
through the door. See return air connections page 6.
• Additional information listed below is for reference
purposes only and does not necessarily have jurisdiction
over local or state codes. Always consult with local
authorities before installing any gas appliance.
Combustion & Ventilation Air
• US:NationalFuelGasCode(NFGC),AirforCombustionand
Ventilation
• CANADA: Natural Gas and Propane Installation Codes
(NSCNGPIC), Venting Systems and Air Supply for Appliances

• USandCANADA:AirConditioningContractorsAssociation
(ACCA) Manual D, Sheet Metal and Air Conditioning
Contractors National Association (SMACNA), or American
Society of Heating, Refrigeration, and Air Conditioning
Engineers (ASHRAE) Fundamentals Handbook

• US:NationalElectricalCode(NEC)ANSI/NFPA70
• CANADA:CanadianElectricalCodeCSAC22.1

• US:NFGCandNationalPlumbingCodes
• CANADA:NSCNGPIC
General Installation
• US: Currentedition of the NFGC and the NFPA90B. For
copies, contact the National Fire Protection Association Inc.,
Batterymarch Park, Quincy, MA 02269; or American Gas
Association, 400 N. Capitol, N.W., Washington DC 20001 or
www.NFPA.org
• CANADA:NSCNGPIC.Foracopy,contactStandardSales,
CSA International, 178 Rexdale Boulevard, Etobicoke
(Toronto), Ontario, M9W 1R3 Canada

• US:(NFGC)NFPA54–1999/ANSIZ223.1andtheInstallation
Standards, Warm Air Heating and Air Conditioning Systems
ANSI/NFPA 90B.
• FederalManufacturedHomeConstructions&SafetyStandard
(H.U.D. Title 24, Part 3280.707[a][2])
The Standard for Manufactured Home Installations
(Manufactured Home Sites, Communities, and Set-Ups) ANSI
A225.1 and/or CAN/CSA-2240 MH Series).
• American National Standard (ANSI-119.2/NFPA-501C) for
all recreational vehicle installations.
• CANADA:CAN/CSA-B149.1and.2–M00NationalStandard
of Canada. (NSCNGPIC)
4
The Commonwealth of Massachusetts requires
compliance with regulation 248 CMR 4.00 and 5.00 for
installationofthrough–the–wallventedgasappliances
asfollows:
1. For direct-vent appliances, mechanical-vent heating
appliances or domestic hot water equipment, where the
bottom of the vent terminal and the air intake is installed
below four feet above grade the following requirements
mustbesatised:
a.)Acarbonmonoxide(CO)detectorandalarmshallbe
placedoneachoorlevelwheretherearebedrooms.
The detector shall comply with NFPA 720 (2005
Edition) and be mounted in the living area outside
the bedroom(s).
b.) A (CO) detector shall be located in the room that
housestheapplianceorequipmentandshall:
•Be powered by the same electrical circuit as the
appliance or equipment. Only one service switch shall
power the appliance and the (CO) detector;
•Havebatteryback-uppower;
•Meet ANSI/UL 2034 Standards and comply with
NFPA 720 (2005 Edition); and Approved and listed
by a Nationally Recognized Testing Laboratory as
recognized under 527 CMR.
c.) A Product-approved vent terminal must be used, and
if applicable, a product-approved air intake must be
used. Installation shall be in strict compliance with the
manufacturer’s instructions. A copy of the installation
instructions shall remain with the appliance or
equipment at the completion of the installation.
d.) A metal or plastic identification plate shall be mounted
attheexteriorofthebuilding,4feetdirectlyabove
the location of vent terminal. The plate shall be of
sufficient size, easily read from a distance of eight
feet away, and read “Gas Vent Directly Below”.
2. For direct-vent appliances, mechanical vent heating
appliances or domestic hot water equipment where the
bottom of the vent terminal and the air intake is installed
above four feet above grade the following requirements
mustbesatised:
a.) A (CO) detector and alarm shall be placed on each
oorlevelwheretherearebedrooms.Thedetector
shall comply with NFPA 720 (2005 Edition) and be
mounted in the living area outside the bedroom(s).
b.)The(CO)detectorshall:
•Belocatedintheroomthathousestheapplianceor
equipment;
•Behard-wired,batterypoweredorboth.
•ShallcomplywithNFPA720(2005Edition).
c.) A product-approved vent terminal must be used, and
if applicable, a product-approved air intake must be
used. Installation shall be in strict compliance with the
manufacturer’s instructions. A copy of the installation
instructions shall remain with the appliance or
equipment at the completion of the installation.


 




      
     

Minimum Clearances
This heating appliance must be installed with clearances
not less than the minimums listed in Table 1, (page 5).
This furnace must be installed with ample clearance for
easy access to the air filter, blower assembly, burner
assembly, controls, and vent connections. See Figure 1,
Figure 2, and Figure 3 (page 5).
• Thedimensionsoftheroomoralcovemustbeableto
accommodate the overall size of the furnace and the
installation clearances listed in Table 1 and in Figure 4
(page 5).
• Alcove installations: minimum 18” clearance at front
of furnace shall be provided for future servicing. A
removable access panel should be installed between
top of the furnace door frame and the ceiling.
• Closetinstallationsmustusealouvereddoorhaving
a minimum free area of 235 in
2
when located 6” from
furnace or 390 in
2
for 5 ton ready M1/M5 furnaces. For
special clearance between 1” - 6”, requirements are a
louvered door with a minimum of 250 in
2
free area, with
the openings in the closet door in line with the louvered
openings in the furnace door. A fully louvered closet
door may be used. See Circulating Air Requirements
section (page 6).
• Thefurnacemustbekeptfreeandclearofinsulating
material.Examinethefurnaceareawhenthefurnaceis
installed or when insulation is added. Insulating material
may be combustible.

M1 Series gas and M5 Series oil furnaces are listed direct
vent(sealedcombustion),downowheatingappliancesfor
manufactured (mobile) homes and recreational vehicles.
The furnace must be located so that venting can be
properly achieved.
Air conditioning may be added to structures with M1/M5
series furnaces using air conditioning or conventional
units. This Installation Instruction manual includes
special requirements for incorporation of air conditioning
equipment to the M1/M5 series of furnaces. See Table
11, (page 28).
Multi-speed blower assemblies shown in Table 2, (page
5), have been certified for field installation in M1/M5
Series furnaces.
5
“A”- 56"
23 3/4"
“B”- 76"
“A” Model
w/o Coil
Cabinet
“B” Model
w/Coil
Cabinet
19 3/4”

Minimum Clearances
  
Front 6” 18”
Back 0” 0”
Sides 0” 0”
Roof Jack 0” 0”
Top 6” 6”
Top and Sides of Duct 0” 0”
Bottom of Duct
ACabinet(w/coilbox) 0” 0”
ACabinet(w/ocoilbox) 1/4” 1/4”
B Cabinet 0” 0”
Blower Assemblies




(TONS)




903413 11x8 1/2 2, 2½, 3 & 4
903890 11x8 3/4 2, 2½, 3, 4 & 5
Removable access
panel should be
installed above
furnace door frame
to access roof jack
Nearest
Wall or
Partition
18"
(457 mm)
6" (152 mm)
Top Clearance
0" Side
Clearance
to Furnace
Cabinet
6" (152 mm)
Top Clearance
0" Side
Clearance
to Furnace
Cabinet
Provide min. 235
sq. in. (1516 cm )
open free area in
front or side wall
2
or
In closet
door
located
at top,
center
or bottom
CLOSET DOOR
6" (152 mm)
Top Clearance
Provide min. 250
sq. in. (1613 cm )
open free area in
front or side wall
2
a fully
louvered
door may
be used
CLOSET DOOR
6"
(152 mm)
1"
(25 mm)
0" Side
Clearance
to Furnace
Cabinet
or
in closet
door
Closet Installation


6

• Thefurnaceshallbeappropriatelylocatedtothesupply
and return air distribution system (page 6). Sides and
back of the furnace may be enclosed by wall framing.
See Minimum Clearances section on page 4.
• Thefurnaceinstallationisonlyintendedforfreeairreturn
through the furnace door louvers. DO NOT connect a
ducted return air system directly to the furnace. Improper
installation may create a hazard and damage equipment,
as well as void all warranties.
• Furnacemaybeinstalledoncombustibleooringwhen
using manufacturer approved duct connectors. See
page 6.
• Wheninstalledinaresidentialgarage,thefurnacemust
be positioned so the burners and the source of the
ignition are located no less than 18 inches above the
oorandprotectedfromphysicaldamagebyvehicles.



      
     
     




       


   




U.S.A. home manufacturers shall comply with all of the
following conditions to have acceptable return air systems
forclosetinstalledforcedairheatingappliances:
• Thereturnairopeningintotheclosetshallnotbeless
than specified in the appliance’s listing.
• The cross-sectional area of the return duct system
leading into the closet, when located in the oor or
ceiling shall not be less than 235 in
2
(or 390 in
2
for M1/
M5 Furnaces with 5 ton blower kits).

   

• Meansshallbeprovidedthatpreventinadvertentclosure
ofatobjectsplacedoverthereturnairopeninglocated
intheoorofthecloset(versustheverticalfrontorside
wall).
• Thetotalfreeareaofopeningsintheoororceiling
registers serving the return air duct system must be at
least 235 in
2
. At least one register should be located
whereitisnotlikelytobecoveredbycarpeting,boxes
and other objects.
• Materialslocatedinthereturnductsystemmusthavea
amespreadclassicationof200orless.Thisincludes
a closet door if the furnace is in a closet.
• Noncombustiblepanshaving1”upturnedangesare
locatedbeneathopeningsinaoorductsystem.
• Wiringmaterialslocatedinthereturnductsystemshall
conform to Articles 300-22 of the National Electrical
Code (ANSI C1/NFPA-70).
• Gaspipingisnotruninorthroughthereturnductsystem.


   
      


• Testthenegativepressureintheclosetwiththeair-
circulating fan operating at high speed and the closet
closed. The negative pressure is to be no more negative
than minus 0.05 inch water column.
• Airconditioningsystemsmayrequiremoreductregister
andopenlouverareatoobtainnecessaryairow.

For proper air distribution, the supply duct system must be
designedsothatthestaticpressuremeasuredexternal
tothefurnacedoesnotexceedthelistedstaticpressure
rating shown on the furnace rating plate.
Location, size, and number of registers should be selected
on the basis of best air distribution and oor plan of
the home.        

      
Three typical distribution systems are shown in Figure 5

A Single trunk duct
B
Dual trunk duct
w/crossover connector
C
Transition duct
w/branches
7

These Installation procedures are suggested for
typical furnace installations. Since each installation is
different, the sequence of instructions may differ from
the actual installation. Only qualified HVAC technicians
should install this furnace.
The installer must be familiar with and comply with all
codes and regulations applicable to the installation of
these heating appliances and related equipment. In
the absence of local codes, the installation must be in
accordance with the current provisions of one or more of
the following standards.
• FederalManufactured Home Constructions&Safety
Standard (H.U.D. Title 24, Part 3280.707[a][2])
• AmericanNationalStandard(ANSI-119.2/NFPA-501C)
for all recreational vehicle installations.
• AmericanNationalStandard(ANSI-Z223.1/NFPA-54)
and/or CAN/CSA B149 for all gas-fired furnace models.
• American National Standard (ANSI-Z95.1/NFPA-31)
and/or CSA B139 for all oil-fired furnace models.
• AmericanNationalStandard(ANSI-C1/NFPA-70)and/or
CSA 22.1 Canadian Electric Code Part 1 for all electrical
field wiring.
• UnitshavebeencertiedunderstandardsUL307A&B,
UL727-1999, ANSI Z21.47/CSA 2.3, and CSA B140.10.

• Thefurnacemustbeleveledatinstallationandattached
to a properly installed duct system.    
       See page 6
for circulating requirements.
• The furnace must be installed so that all electrical
components are protected from water
• Thedimensionsoftheroomoralcovemustbeableto
accommodate the overall size of the furnace and the
installation clearances listed in Table 1, (page 5)
and Figure 1 (page 5)
• The furnace must be installed upstream from a
refrigeration system.
• M1 series (gas) and M5 series (oil) furnaces are
certiedforuseonwoodooringorsupports,butmust
be installed on top of a duct connector. This factory
suppliedaccessorymustbeinstalledintheoorcavity
and attached to the supply air duct before the furnace
is installed.

Floor cut-outs and fuel line holes must be carefully located
to avoid misalignment of the furnace, and vent piping.
To locate standard ducts see Figure 6. For round ducts,
see Figure 7.
1. Measure 10” from the rear wall or alcove and mark the
centerlineofthecut-outontheoor.
2. Using the centerline as a starting point, draw the rest
of the duct cut-out to the dimensions shown in Figure
6 or Figure 7.
3.Cutouttheooropening1/16”largerthantheactual
cutout drawn. This will allow some clearance when
installing the duct connector.
4.Measurefromthetopoftheoordowntothetopofthe
supplyairducttoobtainthedepthoftheoorcavity.
FLOOR CUT-OUT
FOR STANDARD
DUCT CONNECTORS
C
L
C
L
C
L
24"
23 1/4"
21 3/4"
14 1/2"
2 1/4"
2 3/4"
20"
CUT-OUT FOR
OPTIONAL
COOLING COIL
REAR WALL OF CLOSET OR ALCOVE
1 3/4"
2"
3/4"
C
L
C
L
C
L
10"
C
L
FURNACE OUTLINE
14 1/2"
ALT FUEL-LINE
ENTRY 1 1/4" Dia.
FURNACE
OUTER
DOOR
FUEL
LINE
1 3/4"
3/4"
1 7/8"
2 7/8"

Standard Duct Connectors
FLOOR
CUT-OUT FOR
ROUND DUCT
(14 1/4” DIAMETER)
C
L
C
L
C
L
C
L
24"
23 1/4"
21 3/4"
20"
CUT-OUT FOR
OPTIONAL
COOLING COIL
ALT FUEL-LINE
ENTRY 1 1/4" Dia.
FURNACE
OUTER
DOOR
REAR WALL OF CLOSET OR ALCOVE
FUEL
LINE
1 3/4"
2"
3/4"
C
L
C
L
10"
FURNACE OUTLINE
1 3/4"
10"
3/4"
1 7/8"
2 7/8"
C
L


Bend tabs
up 90°
Mounting Plate
Duct
Connector
Connector
Tabs
Supply
Air Duct
Hole for
Gas Line
Wood Floor
Standard Duct Connector Installed
8





 
7/8” / (22) 901987A 904008
2” / (51) 901988A N/A
4-1/4” / (108) 901989A 904010
6-1/4” / (159) 901990A 904011
8-1/4” / (210) 901991A 904012
10-1/4” / (260) 901992A 904013
12-1/4” / (311) 901993A 904014
 Dimensions shown as Inches / (Millimeter)

DUCT CONNECTOR
SUPPLY
AIR DUCT
BEND TABS TIGHTLY
AGAINST SUPPLY AIR DUCT
Duct Connector Tabs
OPTION 1 OPTION 2
Supply
Air Duct
Fold Flap Here
Fold Flap Here
Remove
this
Flap
Remove
this
Flap
Cut Here
Cut Here
Cut Here
Cut Here
Cut Here
Cut Here
Cut Here
Cut Here
Cut Here
Fold Flap Here
Fold Flap Here

DUCT
CONNECTOR
SCREWS
MOUNTING
PLATE
FUEL LINE
HOLE
FUEL LINE
HOLE
14” SUPPLY
CONNECTION

MTG. PLATE TABS
SLIDE FURNACE
ALL THE WAY BACK
ONTO MTG. PLATE
SUPPLY AIR DUCT
Knockout Over Holes
SECURE FURNACE
WITH 2 FASTENERS AT FRONT
CORNER HOLES

Narrow Ducts
Narrow
Duct
Narrow
Duct
Duct connector tabs
Staples or sheet metal screws
Duct
Flap
Narrow
Duct
Duct
Connector
Sheet metal
screws

“X”
FLOOR OPENING
R
SUPPLY AIR DUCT
FUEL LINE HOLES
MTG. PLATE TABS
SLIDE FURNACE
BACK AGAINST
MTG. PLATE
SECURE FURNACE
WITH 2 FASTENERS
AT FRONT CORNER HOLES
SUPPLY
AIR DUCT

9
Thedepthoftheoorcavityshownas“X”in
Figure 9 (page 8) will determine the correct duct
connector.
5. Determine which duct connector to use from Table 3,
(page 8).
6. Measure and drill gas hole and cut out for cooling coil
(if applicable). See Figure 6 or Figure 7.
Standard Duct Connector Installation
The standard duct connector is designed for use on
ducts 12” in width. Ducts narrower than 12” may not
allow sufficient clearances for this type of installation. See
Alternate Attachment Method section below.
1.Center the duct connector in the oor opening with
bottom tabs resting on top of the supply air duct.
2. Mark the cut-out area on the supply air duct by tracing
around the connector tabs of the duct connector. See
Figure 8 (page 7).
3. Remove the duct connector and cut out the marked
area of the supply air duct 1/4” larger the actual cutout
drawn.
4.Installtheductconnectorbackintheooropeningwith
thebottomtabsextendingintothesupplyairduct.
5. Install the mounting plate under the back side of the
duct connector as shown in Figure 8. Align the screw
holes in both components.
6. Secure the duct connector and the mounting plate to
thewoodoorwithappropriatesizescrews.
7. Bend the connector tabs on the bottom of the duct
connector upwards and as tight as possible against
the supply air duct.
8. Bend both tabs up 90° on the mounting plate. See
Figure 10 (page 8).
9. Seal all connections with industrial grade sealing tape
or liquid sealant.
 Requirements for sealing ductwork vary
from region to region. Consult with local codes for
requirements specific to your area.
Alternate Attachment Method
The standard duct connector is designed for use on ducts
12” in width. However if there is insufficient clearance to
bend the duct connector tabs, this alternate attachment
method may be used.
1. Score and cut the top of the supply air duct as indicated
in Option 1 or Option 2. See Figure 11 (page 8).
 If Option 1 is selected, cut out the metal from
the shaded area.
2.Foldthetwoaps(Options1or2)uptoformtheopening
for the duct connector.
3.Installtheductconnectorwiththebottomtabsextending
into the supply air duct.
4. Bend the tabs on the bottom of the duct connector
upwards and as tight as possible against the supply
air duct. See Figure 12 (page 8).
5.Form the aps (Options 1 or 2) up against the duct
connector as tight as possible.
6.Securetheductconnectorapstothesupplyairduct
withstaples(3minimum) or if a 2x block/joist is not
provided, use sheet metal screws (2 minimum).
 The duct connector tabs may be attached to
the air duct with sheet metal screws or other suitable
fasteners as long as the duct connector and the air duct
are securely attached.
7. Seal all connections with industrial grade sealing tape
or liquid sealant.
 Requirements for sealing ductwork vary
from region to region. Consult with local codes for
requirements specific to your area.

1. Apply a bead of caulking, mastic, or other approved
sealant around bottom side of connector.
2.Installandcentertheductconnectorintheooropening.
3. Install the mounting plate under the back side of the
duct connector. See Figure 13.  Align the screw
holes in both components.
4. Secure the duct connector and the mounting plate to
thewoodoorwithappropriatesizescrews.
5. Connect the round supply duct to the underside of the
duct connector and secure them with field supplied
sheet metal screws.
6. Seal all connections with industrial grade sealing tape
or liquid sealant.
 Requirements for sealing ductwork vary
from region to region. Consult with local codes for
requirements specific to your area.

Sides and back of the furnace may be enclosed by wall
framing such as in a closet or alcove. The dimensions
of the room or alcove must be able to accommodate the
overall size of the furnace shown in Figure 4 (page 5)
and the installation clearances outlined on page 4. The
furnace shall be appropriately connected to the supply
distribution system as shown in Figure 14 (page 8) &
Figure 15 (page 8).
1. Remove furnace outer door(s) and bottom fuel line
knockout.
2.Placefurnaceontoductconnectorandcenterwithoor
opening.
3. Slide onto mounting plate. (Bottom rear slots on furnace
should engage with mounting plate tabs.)
4. Secure front with one (1) fastener at each corner. See
Figure 14 & Figure 15.
 Additional fasteners may be used at rear, sides
or through door frame, as desired, to secure furnace to
closet or alcove framing.
10

ROOF JACK
CROWN
SLANT DECK
FLASHING
PITCHED
ROOF
CEILING
CEILING
CAVITY
Roof
Opening
"X" (SEE TABLE 5)
Flue Pipe
Combustion Air Pipe
56"
or
76"
Furnace
“A”
“B”
SLANT DECK
FLASHING
PITCHED
ROOF
CEILING
ROOF
OPENING
"X" (SEE TABLE 5)
CEILING
CAVITY
CEILING
OPENING
ROOF JACK
CROWN

5/12 ROOF SLOPE
2
SLANT DECK
/12
1
2
ROOF JACK WITH
2
FLASHING
/12 SLANT
1
2



Required ceiling and roof cut-out openings must be
carefully located to avoid misalignment of the furnace
and Roof Jack. Install only roof jack assemblies
listed in Table 4, (page 11) on this heating appliance.

1. Determine depth of ceiling cavity from center of roof
opening to center of ceiling opening noted as “Dimension
A” in Figure 16 (page 10).
2. Determine ceiling height and subtract height of furnace
noted as “Dimension B” in Figure 16 (page 10).
3.Adddimensions“A”&“B”(andXfromTable 5, (page
11)ifslantdeckashingisused).Thetotallengthof
[A]+[B]+[X]mustbewithintheminimumandmaximum
range of the roof jack listed in Table 4.
Application Notes
• FAW,FAWT,SAWandSAWTSeriesRoofJackswitha
5” diameter inner vent pipe may be used with all models
of M1 Series gas and M5 Series oil furnaces.
F=FlatFlashing:exesfrom0/12to1/12roofslope.
See Figure 17 (page 10).
S=SlantFlashing:2.5/12Slopeexesfrom1/12to
4/12roofslope,4/12exesfrom3/12to5/12.
See Figure 18 (page 10).
• Stainlesssteelroofjacksareavailable.
• M1/M5furnacesmaybeusedwithroofjacksystems
andextensionaccessoriesastallas170”(exceptM1M
056 & M1B 066 models, which are limited to 120”).
Aninternalroofjackextension(p/n901935-10”,p/n
903107 - 18”) can be used to increase roof jack height.
All connections inside the home must be made below
the ceiling.
• Thisfurnacemustneverbeconnectedtoachimney
ueservicingareplaceorotherappliancedesigned
to burn solid fuel.
• Iftheroofjackcrowniscoveredorblockedwithsnow,the
furnace will not operate properly. If the home is located
inregionswheresnowaccumulationexceeds7”(HUD
snowloadzones)useanexternalroofjackextension
(p/n901937).Amaximumof2extensionsperroofjacks
canbeused.Extensionsareoptionalaccessoriesand
may be purchased through your distributor.


         





 Refer to the installation instructions provided
with optional air conditioning packages when installing
furnaces with optional cooling coil cabinet or with optional
C* series indoor coils.
1. Locate center of Roof Jack opening, measure 13 1/2”
from the rear wall of closet or alcove along the center
lineoffurnaceandooropening.SeeFigure 19.
11
2.Cutceilingandroofholes:
•Ceiling=83/4”(222mm)diameter
•Roof=93/8”(238mm)diameter

1.Applycaulkingcompoundonundersideofroofashing
to form a continuous strip at least 3/8” wide around the
undersideoftheperimeteroftheashing.Foratroof,
see Figure 20 or see Figure 21 (page 12) if roof is
pitched.
2. Connect roof jack assembly to the furnace. Insert
telescoping roof jack assembly through the opening
cut on the roof.
3.Connectinneruepipetoventcollarofthefurnace.
See Figure 22 (page 12).
4. Connect combustion air pipe to furnace collar with sheet
metal screw. See Figure 22.

• Itisrecommendedthattheconnectionofthecombustion
airpipetothefurnacebemadebeforetheashingis
secured to the roof to maintain alignment of roof jack
and furnace connections.
• Forreplacementfurnaces,besuretheinneruepipe
connects over the furnace vent collar. DO NOT use a



5.Attach roof ashing. If necessary, shift roof ashing
slightly in the roof opening so that assembly is in
alignment with furnace.
 If ashingismountedon12degreeangle,it
may be necessary to adjust the angle to match the roof
pitch;(1/12-4/12maximum).
6.Pressdownrmlyonroofashing(overcaulking)to
make the seal with roof water tight.
7.Secureashingwithappropriatefasteners. For
addedprotectionagainstleaks,coattheashingplate
and fasteners with approved roofing compound.
 Upper roof jack crown to be stored in a
prominent location inside manufactured home until
on-site installation.
   

 For transit purposes, the transit kit (P/N 903838)
should be installed before home is moved to site.
1. Furnace must be installed in accordance to furnace
installation manual.
2. Select appropriate roof jack from Table 4, (page 11)
3. Roof jack (less upper roof jack crown), with weather
cap to be installed as described in Installing The Roof
Jack section.
4. Install the four warning tags (factory supplied) on these
items:
•Weathercap
•Fuellineconnectionpoint(Gas)orfurnaceburner(Oil)
•Furnaceameobservationdoor(GasorOil)
•Furnacewallthermostat

SSAW
27
47 - 2
AW= ALL WEATHER
FLASHING
PITCH/12" RISE
0=FLAT
2=2.5/12
4=4/12
MIN. ADJ.
LENGTH
F = FLAT FLASHING
S = SLANT FLASHING
MAX. ADJ.
LENGTH
FLUE STEEL TYPE
A= ALUMINIZED
S=STAINLESS



(F,S)AW1523-(0,2,4)(A,S) 15” - 23”
(F,S)AW2135-(0,2,4)(A,S) 21” - 35”
(F,S)AW2747-(0,2,4)(A,S) 27” - 47”
(F,S)AW3563-(0,2,4)(A,S) 35” - 63”
(F,S)AW5195-(0,2,4)(A,S) 51” - 95”
 Not all models are available. Check with your local distributor
for available models.


CEILING
CUT-OUT FOR
FLUE AND
ROOF JACK
C
L
C
L
24"
20"
13 1/2"
REAR WALL OF CLOSET OR ALCOVE
10"
FURNACE
OUTER
DOOR
FURNACE OUTLINE









“F Series
2” in 12” 903893 (2.5/12) 2-1/8”
2-1/2” in 12” 903893 (2.5/12) 2-1/2”
3” in 12” 903894 (3/12) 2-7/8”
3-1/2” in 12” 903894 (3/12) 3-1/4”
4” in 12” 903895 (4/12) 3-5/8”
“S” Series
(2.5 / 12 Pitch only)
4-1/2” in 12” 903895 (2.5/12) 2-1/8”
5” in 12” 903895 (2.5/12) 2-1/2”
5-1/2” in 12” 903894 (3/12) 2-7/8”
6” in 12” 903894 (3/12) 3-1/4”
6-1/2” in 12” 903895 (4/12) 3-5/8”
Optionaldeckashingsforatand2.5/12pitchroofjacks.
4/12 pitch roof jacks not applicable.
12



       
       

1. Transit-mode weather cap to be removed and upper
roof jack crown installed. .
See Figure 23.
2.Placeupperroofjack(crown)ontheuepipeassembly.
Makesureinsideuepipeattachesoverinner
uepipeandouterRoofJackpipetsoverouterpipe.
3. Secure in place using three sheet metal screws (#10
x1/2”)removedinstep1.Donotusethesameholes
which secured the rain cap in place.
4. Remove and discard all 4 venting system warning tags.

Secure roof jack with
appropriate fasteners
after connecting to
furnace
Caulk under roof
flashing to prevent
water leakage
Roof
Ceiling
Optional 2-piece ceiling
ring #902521
Upper Roof Jack Section
Secure lower roof
jack section with
no. 10 S.M. screws
Caulk under roof
ashing to prevent
water leakage
Optional Slant
Deck Flashing
Secure ashing
with appropriate
fasteners
Ceiling

CONNECT OUTER
FLUE SHIELD
INNER FLUE PIPE
VENT COLLAR
MOUNTING
FLANGE

SCREWS
COMPLETED
ASSEMBLY
TO FURNACE
UPPER ROOF
JACK (CROWN)
INNER FLUE PIPE
FLUE ASSEMBLY
OUTER PIPE
FLASHING
WEATHER CAP


On-Off
Switch
Blower
Plug
Power
Entry
On-Auto Switch
(Heating Models Only)
Thermostat Wires
Furnace
Control Box
To combustion
Blower or Flame
Roll-out Switch
To Gas Valve
or Burner
13







     

     

 

 
Line Voltage Wiring





• Electricalconnectionsmustbeincompliancewithall
applicable local codes with the current revision of the
National Electric Code (ANSI/NFPA 70).
• For Canadian installations the electricalconnections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
It is recommended that 115VAC line voltage be supplied
to the furnace from a dedicated branch circuit containing
the correct fuse or circuit breaker for the furnace as listed
in Table 6, (page 14).

      
  Figure 35 (page 31) & Figure 36 (page 32)

      


      
     



      
       



 
)
For installation of A-size Cabinet furnaces, allow sufficient
slack in the wiring if an optional cooling coil cabinet is
added at a later time.     

Connecting Power Supply Wires
1. Remove the furnace control panel cover.
2. Route wires (115 VAC) through the strain relief on the
leftsideofthefurnacecontrolbox.SeeFigure 24 (page
12).
3. Connect the  wire to the  pigtail lead, and
the neutral wire to the  pigtail lead. Secure all
connections with suitable wire nuts.
4. Connect the ground wire to the grounding screw.
5. Reinstall the control panel cover and secure with the
original mounting screws.
Low Voltage Wiring
• Thefurnaceisdesignedtobecontrolledbya24VAC
thermostat. The thermostat’s wiring must comply with
the current provisions of the NEC (ANSI/NFPA 70) and
with applicable local codes having jurisdiction.
• The thermostat must be installed according to the
instructions supplied by the thermostat manufacturer.
Low voltage connections (24 VAC) from the thermostat
are wired to the terminal strip on the integrated control
in the furnace.
• Thethermostatshouldbemountedabout5feetabove
theooronaninsidewall.DONOTinstallthethermostat
on an outside wall or any other location where its
operation may be adversely affected by radiant heat from
replaces,sunlight,orlightingxtures,andconvective
heat from warm air registers or electrical appliances.
Refer to the thermostat manufacturer’s instruction sheet
for detailed mounting information.
• The nominal anticipator setting is 0.4. Refer to the
thermostat literature for additional information.
• Five-conductorthermostatwireisrecommendedfor24
volt low-voltage circuit (2-wire is required for furnace
only; 5-wire for heating and optional cooling systems).
Refer to Table 6 for thermostat wire information.
Connecting Thermostat Wires
1. Insert 24 volt wires through the plastic grommet just
above the control panel.
2. Connect the thermostat wires to the furnace low voltage
pigtails (dependent on the installation application). See
Figure 25 (page 14).
•For M1 models: from the furnace is not connected;
 of the furnace connects to the thermostat.
•For M5 models:ToconnectanM5toathermostat
without an  &  connection, please refer to the
wiring diagram and the installation instructions
supplied in the kit [P/N 1018453]. Units installed with kit
[P/N 1018453] will not use the  connection from the
furnace,  on the furnace connects to the thermostat.
3. Connect low-voltage circuit to the wall thermostat.
14
4. A hole may be made in the furnace cabinet to ease
thermostat wiring. Make sure that the wiring is protected
from the sharp edge of the added hole.
Verifying Anticipator Setting
After the furnace is installed, check the thermostat
anticipator against the nominal setting of 0.4.
1. Connect the milliamp meter in series with one of the
gas valve’s low voltage terminals.
2. Energize the gas valve.
3. Read the value of the milliamps.
4. Adjust the heat anticipator of the thermostat to the
value on the milliamp meter. If the heat anticipator is
set too high, the furnace may delay turning on. If set too
low, the furnace may cycle frequently and not provide
comfort to the homeowner.
Grounding





     
       












NOMINAL

















1



M1MB 056 56,000 19 3/4 115-1-60 103 127 7.0 15 8.5 14.5
M1MB 070 70,000 19 3/4 115-1-60 103 127 7.0 15 8.5 14.5
M1MB 077 77,000 19 3/4 115-1-60 103 127 7.0 15 8.5 14.5
M1MB 090 90,000 19 3/4 115-1-60 103 127 7.0 15 8.5 14.5
M1BB 066 66,000 19 3/4 115-1-60 103 127 6.8 15 8.3 14.3
M1BB 086 86,000 19 3/4 115-1-60 103 127 6.8 15 8.3 14.3
M1MC 056 56,000 19 3/4 115-1-60 103 127 8.9 15 10.9 18.8
M1MC 070 70,000 19 3/4 115-1-60 103 127 8.9 15 10.9 18.8
M1MC 077 77,000 19 3/4 115-1-60 103 127 8.9 15 10.9 18.8
M1MC 090 90,000 19 3/4 115-1-60 103 127 8.9 15 10.9 18.8
M1BC 066 66,000 19 3/4 115-1-60 103 127 8.7 15 10.7 18.6
M1BC 086 86,000 19 3/4 115-1-60 103 127 8.7 15 10.7 18.6
Minimumwiregaugeandmaximumfuse/circuitbreakeramperagearebasedonMCA
1
and MOP
2
calculations. This furnace is approved
for installation with a 15 or 20 amp fuse/circuit breaker however wiring sizing must adhere to current version of the NEC and/or applicable local
codes depending upon the overcurrent protection.
* Time-delay fuses or circuit breakers are required.


 
24 55 ft. 25 ft.
22 90 ft. 45 ft.
20 140 ft. 70 ft.
18 225 ft. 110 ft.
Total wire length includes wire from furnace to the thermostat, from thermostat to outdoor unit, & from outdoor unit back to the furnace.
Rc
R
H
W
G
Y
Red
White
Green
Yellow
Red
White
Green
Grey
Thermostat
M1 Furnace
To AC Contactor
Rc
R
H
W
G
Y
Red
White
Green
Yellow
Red
White
Green
Grey
Thermostat
M5 Furnace
To AC Contactor
Red Red
TR
TW
Oil Burner
15



 




       




     


      











This furnace may be installed with left, right, or bottom gas
entry. When connecting the gas supply, provide clearance
between the gas supply line and the entry hole in the
furnace casing to avoid unwanted noise and/or damage
to the furnace. Typical gas service hookup for this furnace
is shown in Figure 26 (page 16).
Table 13, (page 29)listsgasowcapacitiesforstandard
pipe sizes as a function of length in typical applications
based on nominal pressure drop in the line.

 

      16)

     



 

 
       

 


 
    


 

 

 
     16) &   
)       



 

       
Figure
)
 Optional fuel inlet lines are available for all gas
furnace models to permit the addition of a 1/2” F.P.T.
shut-offvalveabovetheoor.
The gas supply to your home will either be Natural Gas
or L.P. Your furnace is factory equipped to operate on
Natural Gas. If your gas supply is L.P., you must contact
a qualified serviceman or gas supplier to convert the
furnace. Instructions for conversion to propane are shown
on page 17. Factory installed orifice sizes are listed in
Table 10, (page 28).
Fornaturalgasoperation,themaximuminletpressure
for the valve is 7” W.C and the minimum inlet pressure
is 4.5” W.C. Pressure is reduced to 3 1/2” W.C. by the
pressure regulator in the gas valve.
For LP gas, pressure to the gas valve must be more than
11” W.C. but not more than 13” W.C. Pressure is reduced
to 10” W.C. by the pressure regulator in the gas valve.











16
1. Turn off all electric power to the appliance.
2. Remove the black plastic cap located above the blower.
Do not discard cap.
3. Drill a hole through the top of the blower compartment.
Hole diameter should be same size as sampling
tube.
4. Insert sampling tube through the drilled hole and into
theheatexchanger.
5. After a complete check and adjustment of furnace
performance, seal the drilled hole with a screw larger
than the hole.  Seal the screw threads with silicon
sealant - rated at least 500° F.
6. Plug the outside hole with the plastic cap removed in
step 3.






     

High altitude conversion with this furnace depends on
the installation altitude and the heating value of the gas.
The installation of this furnace at altitudes above 2,000
feet must meet the requirements of the National Fuel Gas
Code or local jurisdiction. In Canada, the requirements for
high altitude are different and governed by CSA B149.1.
Always consult your local code authority.
This furnace is shipped from the factory with orifices and
gas regulator settings for natural gas operation at sea
level altitudes. At 2000 feet, the NFGC requires that this
appliance be derated 4% for each 1000 feet of altitude. For
example,theinputneedstobereduced8%at2,000feet,
12% at 3,000 feet and etc. This deration is in reference to
the input rate and gas heating value at sea level.
To derate the furnace requires knowing the heating value of
the gas at the installation site. Heating values at particular
jobsitesvaryfortworeasons:
1.Thechemicalmixtureofthegasvariesfromregionto
regionandisexpressedasthe“sealevelheatingvalue”.
2. The heating value varies by altitude. For this reason,
especially in high altitude areas, the local gas utility
specifies the heating value at the residence’s gas meter
as the “local value”.
Foraddedexibility,twotableshavebeenprovidedfor
natural gas installations with high or low heating values
at sea level. Table 15, (page 30) & Table 16, (page
30) contain the manifold pressure and orifice sizes to
use at various altitudes. Table 15 (HIGH) is for natural
gas installations with a heating value of more than 1,000
Btu per cubic foot and Table 16 (LOW) is for less than
1,000Btupercubicfoot.Todeterminewhichtabletouse:
1. Consult the local utility for the local heating value at
your installation site.
Floor
Control
Panel
On-Off-Fan
Switch
Alt. Fuel
Line Entry
Floor Cavity
Some codes may require installation of a manual main shut-off
valve and ground joint union external to the furnace. The shut-off
valve should be readily accessible for service and/or emergency
use. Consult the local utility or gas supplier for additional
requirements regarding placement of the manual main gas shut-off.
To Gas Supply

After the gas piping to the furnace is complete, all
connections must be tested for gas leaks. This includes all
fittings, pipe connections at the main gas valve, emergency
shutoffvalve,andexiblegasconnectors(ifapplicable).
The soap and water solution can be applied on each
joint or union using a small paintbrush. If any bubbling is
observed, the connection is not sealed adequately and
must be retightened. Repeat the tightening and soap
check process until bubbling ceases.

      







Itmaybenecessarytotakeuegassamplingfromoil
and gas furnaces (M5S and M1B Series Models) in order
to check the performance after furnace installation. A
uegassamplemaybetakenfromtheheatexchanger,
which is located behind the hole of the top-front of blower
compartment.
17
2. From Table 14, (page 30), find your local heating
value as supplied by the utility company. Follow down
the column and stop at your altitude level.
3. If your sea level heating value is HIGH, use Table 15
or if it’s LOW, use Table 16. See Example.
After changing the orifices, it is required that you measure
the gas input rate. This may be accomplished in the usual
way, by clocking the gas meter and using the local gas
heating value. See Verifying Input Rate (page 22).



LP Gas
Configuration
Black Cover
Red
Ring
Natural Gas
Configuration
Gas Control
Lever


PRESSURE
REGULATOR
CAP
N
A
T
N
A
T
N
A
T
N
A
T
L
P
L
P
OR
OTHER SIDE
OF CAP
OUTLET PRESSURE
TAP (1/8 NPT)
INLET PRESSURE
TAP (1/8 NPT)

 ...................................................5,000 feet
 ............................................ Natural Gas
 ...............................750
Determine which natural gas table to use. From Table
14, (page 30), find 750 and follow down the column,
stop at the 5,000 feet row. The heating value listed is
LOW. Table 16, (page 30) will be used to determine
orifice size and verify manifold pressure.


      


    
      















This furnace can be converted from factory-equipped
natural gas to liquid propane gas. Conversion of this valve
requiresreplacementoftheburneroriceandippingthe
regulator cap to the side marked LP. The orifice required
for conversion is supplied with the furnace. See Figure 27.
For altitudes between 0 and 1,999 feet, use the factory
supplied LP orifice as shown in Table 10, (page 28).
Altitudes between 2,000 and 10,000 feet require the orifice
to be changed. Table 17, (page 30) lists the correct
orifice size and manifold pressure at different altitudes.
Atmospheric & Direct Ignition Furnaces
1. Follow the instructions in “How to Shut Off Gas - Direct
Ignition” on page 21.
2. Disconnect the gas pipe union and the electrical wires
connected to the gas valve.
3.Removethegasvalveassembly:
a. Remove screw(s) from gas valve bracket. Gas valve
and spud may be removed. Orifice is located at the
end of the spud (M1M Models)
b. Remove three (3) bolts from U-shaped manifold plate
and orifice assembly (M1B Models).
5. Replace the main orifice with the L.P. gas orifice supplied
in the envelope located by the gas valve. Verify the
orifice size matches the nameplate or Table 10, (page
28).
18
6. ForHoneywellgasvalveswiththeregulatorconverter:
a. Unscrew the pressure regulator cap and check for
the letters NAT or LP. See Figure 27 (page 17).
b. Invert the cap and tighten until snug.
7. ForRobertshawgasvalveswiththeregulatorconverter:
a. Remove the black cover and unscrew the converter
located on top of the gas valve. See Figure 28 (page
17).
b. Invert the converter. For LP, the red ring will be located
at the bottom and the LP stamping on the converter
will appear right side up.
c. Screw converter back into the regulator, hand tight
plus 1/8 turn. Replace the black cover on the converter
top to protect the threads.
8. Reassemble the burner assembly into the furnace.
9. Reconnect the gas piping and electrical wires to the
gas valve.
10. Open the manual shut-off valve and follow the M1M
Operating Instructions on page 20
Measuring the Supply Gas Pressure

      

1. Remove the inlet pressure plug from the INLET side
of the gas valve with a 3/16 Allen wrench. See Figure
27 (page 17).
2. Install a 1/8 NPT fitting, which is compatible with a
manometer or similar pressure gauge.
3. Connect the manometer or pressure gauge to the inlet
pressure tap.
4. Turn on all electrical power to the furnace.
5. Turn the main gas supply valve (on the outside of the
unit) to the ON position.
6. Start the furnace by adjusting the thermostat to it’s
highest setting. Allow the furnace to run for 10 minutes.
7. Check the incoming gas line pressure. Propane gas
furnaces must be between 11.0”-14.0” W.C. Natural
gas installations must be between 4.5”-10.0” W.C. If
the pressure is not between these specified ranges,
contact your local gas supplier for adjustment.
8. Adjust the thermostat to it’s lowest setting and allow
the unit to cycle off.
9. Turn the main gas supply valve (on the outside of the
unit) to the OFF position.
10. Turn off all electrical power to the furnace.
11. Disconnect the manometer or pressure gauge.
12. Remove the NPT fitting and reinstall the inlet pressure
plug. To prevent cross threading, hand tighten
the plug first, then tighten with 3/16 Allen wrench.
Measuring the Manifold Pressure
The manifold pressure must be measured by installing a
pressure gauge (Manometer, Magnehelic Meter, etc.) to
the outlet end of the gas valve.
1. Remove the manifold pressure plug from the outlet side
of the gas valve with a 3/16 Allen wrench.See Figure
27 (page 17).
2. Install a 1/8 NPT fitting, which is compatible with a
Manometer or similar pressure gauge.
3. Connect the manometer or pressure gauge to the pipe
thread fitting.
4. Start the furnace by adjusting the thermostat 5 degrees
above room temperature. Allow the furnace to operate
for 3 minutes.
5. Measure the manifold pressure on the manometer or
pressure gauge. Compare the measured value to the
value in Table 15, (page 30), Table 16, (page 30),
or Table 17, (page 30).
6. Replace the cap so that the letters facing up represent
the type of gas being used for the furnace. See Figure
27 (page 17).
7. Adjust the thermostat to its lowest setting.
8. Turn off the main gas supply to the unit at the manual
shut-off valve, which is located outside of the unit.
9. Turn off all of the electrical power to the furnace.
10. Disconnect the manometer or pressure gauge.
11. Remove the 1/8 NPT fitting and reinstall the manifold
pressure plug.  To prevent cross threading,
hand tighten the plug first then tighten with 3/16 Allen
wrench.

The following procedures are recommended as good
practice. However, requirements of local codes and
ordinances, H.U.D. Manufactured Home and Safety
Standards or National Fire Protection Association must be
satisfied, where they apply, for an approved installation.
• Useatankcapacitysuitablefortheapplicationwitha
weatherproof, capped fill opening and a shielded vent
to let in air as fuel is used.
• Theinsideofthetankmustbecleanbeforelling.All
water,rust,sediment,anddebrismustbeushedout.
• Afuelortankgaugeisrecommendedforeasychecking
of the fuel level. Check the gauge reading with a dipstick.
See Figure 29 (page 19).
• Locatethestoragetankconvenientlynearthehome.
If the fuel tank is installed above ground, the tank may
rest 3 to 4 inches off the ground. Fuel tanks may also
be buried if properly coated to resist corrosion. The
vertical dimension from the bottom of the fuel tank to
thefuelpumpmustnotexceed10feet.
• Keepthetanklled,especiallyinthesummertoreduce
the accumulation of condensation.
One-Line System
The One-Line System is highly recommended where
vertical lift, from bottom of tank to pump, is less than 8
feet. See Figure 29 (page 19). A single line hookup
has the advantage of lower cost and quieter operation.
Two-Line System
If a Two-Line system is used or if oil is taken from the
bottom of the tank, a filter is recommended. A Two-Line
systemshouldonlybeusedifverticalliftexceeds8feet.
1. Install the oil feed line as outlined in steps 1 - 6 below.
2. Install the oil pump bypass plug in the bottom return
port.
3. Route the return line up through the furnace base to
the return port of the pump. Route the other end of the
line to the tank, using 3/8” O.D. copper tubing or 1/4”
pipe with the ends capped.
19
4. Insert the return line through the second opening in the
duplexbushing.Ifthebottomofthetankislowerthan
the pump intake, the tube should be inserted three or
four inches from the tank bottom. If the bottom of the
tank is higher than the pump intake, the return line
shouldextendnotmorethan8”insidethetank.

1. Use a 3/8” O.D. copper tubing for the fuel line.
 Cap the end with tape to keep out dirt while the
line is being routed.
2.Installduplexbushingfortwo3/8”linesinthetoptting
of the tank. See Figure 29.
3.Insertoneendofthetubingthroughtheduplexbushing
until it is three to five inches from the bottom drain.
Tighten the bushing.
4. Route the line where it will not incur any damage. Make
bends gradual and avoid kinks which might restrict oil
ow.
5. Open the furnace door and connect the oil line to the
intake port on the pump. Tighten other port plugs on
the pump.  Verify the oil line is airtight! Air leaks
can cause the pump to lose prime and will create other
problems such as nozzle failure, odors, rumbling noise,
and false safety shutdown.
6. Insert the short length of the copper tube level with the
bottomoftheduplexbushing.Formthetubeintoan
inverted “U” to serve as a vent.
Fuel Line Bleeding
To eliminate problems caused by air in the oil line, all
connections in the oil supply line and all plugs, nuts,
and fittings on the pump must be airtight.  This
includes the nut that covers the pressure adjustment. It
is important that the hook-up be done carefully and with
agoodaringtool.
Prepare the burner for priming by attaching a clear plastic
hose over the bleed port fitting and fully opening the pump
bleed port. Use a suitable container to collect purged oil.
To ensure continuous operation, use a wire to jump
terminals T-T (or F-F) on the primary control while burner
is running.
Priming furnaces equipped with Honeywell
R7184primarycontrol:
1. While the ignition is on, press for 1/2 second (or less),
and release the reset button. The lockout time will be
extendedto4minutes.
2. If prime is not established within the 4 minutes, the
control will lock out. Press the reset button to reset the
control.
3. Repeat steps 1 & 2 (if needed) until the oil pump is fully
primed.
Priming furnaces equipped with Beckett 7505
primary control
1. After the burner starts, press and hold the reset button
until the yellow LED turns on (15 seconds). This indicates
that the button has been held long enough.
2. Release the reset button. The yellow LED will turn off
and the burner will start up again.
3. At burner start up, click the reset button while the igniter
is still on. This transitions the control to a dedicated pump
prime mode, during which the motor, igniter and valve
are powered for 4 minutes. The yellow LED will be on.
 If prime is not established during the four minute
pump prime mode, repeat step 3 until the oil pump is
fully primed.
4.When oilow is clearand free ofair bubbles,close
air-bleed valve and tighten.  Air bleed out time
will varies depending on length of oil line, number of
bends, etc.

Top of Tank
8 ft.
Shut-off
Valve
Optional
Fuel
Filter
Alternate
Fuel Line
Entry
Control
Panel
Oil
Furnace
On-Off-Fan
Switch
Floor Cavity
Oil-Gun
Burner
Floor
Flue Gas
Sampling
Hole
Drain
End of Oil Supply Line
3" to 5" Above Bottom Drain
Guide
Pipe
Gauge
Vent with cap
2" Duplex
Bushing
2" Fill
3/8" Oil Supply Line
NOTE: Additional venting may be
required if tank is filled rapidly.
4 GPH 100-150 PSI 3450 RPM
3 GPH 150-200 PSI 3450 RPM
VALVE ON DELAY
NO. 2 & LIGHTER FUEL
USE ONLY WITH
INLET
BY-PASS
Exclusively for Beckett
Made by Suntec
INLET
NO. 2 FUEL
A2EA-6520
Becket
t
Nozzle Port
3/16 Flare Fitting
Bypass Solenoid Valve
Cordset
Inlet Port
1/4 NPTF
Bleed & Gauge Port
Pressure
Adjustment
Screw
Inlet Port
1/4 NPTF
Return Port - Install 1/6” Bypass Pipe
Plug for 2-pipe System Only.
(Use 5/32” Allen Wrench)
If fuel pump fails to lift oil, check for air
leaks and tighten all fuel fittings.
Reprime fuel pump by injecting fuel oil into
optional (top) return port. Replace return
port plug and repeat priming procedure.
Some codes may require installation of a manual main shut-off
valve and ground joint union external to the furnace. The shut-off
valve should be readily accessible for service and/or emergency
use. Consult the local utility or gas supplier for additional
requirements regarding placement of the manual main gas shut-off.
20


      

     



Do not use fuel oil heavier than Grade No. 2. In areas
where the oil supply is subject to low temperatures, Grade
No. 1 may be used.





 




       




     


      












• 
       

• BEFORESTARTUP:Smellallaroundthefurnacefor
gasandnexttotheoor.Somegasisheavierthanair
andmaysettleontheoor.
• M1BUnitsOnly:Useonlyyourhandtopushinthegas
control lever. Never use tools. If the lever will not push
in by hand, don’t try to repair it. Force or attempted
repairmayresultinareorexplosion.Callaqualied
service technician.
• Do not use this furnace if any part has been under
water. Immediately call a service technician to inspect
the furnace and to replace any part of the gas valve or
control system which has been under water.


        







(Direct Ignition Furnaces)
Direct ignition furnaces do not have a pilot. Ignition is
accomplished by a hot surface ignitor. A circuit board
takes care of all timing functions. After lighting, the circuit
boardusestheignitorasaamesensor,shuttingoffgas
shouldtheamegoout.Therearenoexternalrelaysor
timing devices. 

1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance.
3.Removethefurnacedoorandturnoffthegasvalve:
• Honeywell: push in and turn the gas control knob
clockwise to OFF. See Figure 30.
• Robertshaw:pushthegascontrollever
to the OFF position. See Figure 28, (page 17).
4. Wait ten (10) minutes to clear out any gas. If you smell
gas,  and follow the Safety Information. If you
do not smell gas, proceed to step 5.
5. Set the thermostat MODE the ON position.

GAS CONTROL KNOB
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68

Medallion M5S Guide d'installation

Taper
Guide d'installation
Ce manuel convient également à

dans d''autres langues