Whirlpool CED9150GW Guide d'installation

Catégorie
Sèche-linge électriques
Taper
Guide d'installation

Ce manuel convient également à

INSTALLATION INSTRUCTIONS
Commercial Dryer Gas or Electric
www.whirlpoolcommerciallaundry.com
W10919522A
W10919523A—SP
INSTRUCTIONS D’INSTALLATION
Sécheuse à usage commercial
à gaz ou électrique
2
DRYER SAFETY
It is recommended that the owner post, in a prominent location, instructions for the customer’s use in the event the customer
smells gas. This information should be obtained from your gas supplier.
Post the following warning in a prominent location.
TABLE OF CONTENTS
Page
DRYER SAFETY ....................................................................... 2
INSTALLATION REQUIREMENTS ........................................... 5
Tools and Parts .................................................................... 5
Dimensions/Clearances ...................................................... 6
Venting Requirements ........................................................ 7
Gas Dryer Installation Requirements ................................ 10
Electric Dryer Installation Requirements ........................... 14
INSTALLING LEVELING LEGS, COIN SLIDE,
AND COIN BOX ..................................................................... 17
INSTALLATION INSTRUCTIONS – GAS DRYER .................. 18
Make Gas Connection ...................................................... 18
INSTALLATION INSTRUCTIONS – ELECTRIC DRYER ....... 19
Electric Dryer Electrical Connections ............................... 19
LEVELING .............................................................................. 24
COMPLETE INSTALLATION ................................................. 24
REVERSING DRYER DOOR SWING .................................... 25
MAINTENANCE INSTRUCTIONS ......................................... 27
IF YOU NEED ASSISTANCE ................................................. 27
ELECTRONIC CONTROL SETUP INSTRUCTIONS ........... 28
WARRANTY .......................................................................... 34
TABLE DES MATIÈRES
Page
SÉCURITÉ DE LA SÉCHEUSE .............................................. 35
EXIGENCES D’INSTALLATION ............................................. 38
Outils et pièces .................................................................. 38
Dimensions/Distances de dégagement ............................. 39
Exigences concernant l’évacuation ................................... 40
Exigences d’installation pour la sécheuse à gaz ................ 43
Exigences d’installation pour la sécheuse électrique ........ 47
INSTALLATION DES PIEDS DE NIVELLEMENT,
DE LA GLISSIÈRE À MONNAIE ET DE LA CAISSE
À MONNAIE ........................................................................... 49
INSTRUCTIONS D’INSTALLATION
POUR LA SÉCHEUSE À GAZ ................................................ 50
Raccordement à la canalisation de gaz ............................. 50
NIVELLEMENT .......................................................................51
ACHEVER L’INSTALLATION ................................................. 52
INVERSION DU SENS D’OUVERTURE
DE LA PORTE DE LA SÉCHEUSE ........................................53
INSTRUCTIONS D’ENTRETIEN ............................................55
SI VOUS AVEZ BESOIN D’ASSISTANCE .............................. 55
INSTRUCTIONS DE RÉGLAGE DU TABLEAU
DE COMMANDE ÉLECTRONIQUE ...................................... 56
GARANTIE ............................................................................. 63
3
DRYER SAFETY
4
DRYER SAFETY
5
Tools Needed:
8" (200 mm) 8" (200 mm) or 10" (250 mm) Flat-Blade Screwdriver Phillips Screwdriver
or 10" (250 mm) Adjustable Wrench
Pipe Wrench that opens to 1" (25 mm)
TORX
®
T-20
®†
Security 1" (25 mm) Hex-Head 1⁄4" Socket Wrench Pliers (that open to
Screwdriver or Bit Socket Wrench 1
9
/
16
" [39 mm])
Level Utility Knife 1/4" (6 mm) Nut Driver 27" (686 mm)
Wood Block
Caulk Gun and Caulk Vent Clamps Pipe-Joint Compound Putty Knife
(for installing new exhaust vent) suitable for gas type
Flashlight (optional) 1" (25 mm) Ruler or Measuring Tape
Open-End Wrenches
INSTALLATION REQUIREMENTS
†®TORX and T20 are registered trademarks of Acument Intellectual Properties, LLC.
Parts Supplied:
Foot Boots (4) Leveling Legs (4)
Tools and Parts
6
INSTALLATION REQUIREMENTS
Front View Side View Back View
Dimensions
Clearances
Recessed Front View Closet Side View
Bottom Exhaust
Dimensions/Clearances
7
INSTALLATION REQUIREMENTS
WARNING: To reduce the risk of re, this dryer MUST BE
EXHAUSTED OUTDOORS.
IMPORTANT: Observe all governing codes and ordinances.
Dryer exhaust must not be connected into any gas vent,
chimney, wall, ceiling, attic, crawlspace, or a concealed space
of a building. Only rigid or exible metal vent shall be used for
exhausting.
Only a 4" (102 mm) heavy, metal exhaust vent and clamps
may be used.
Do not use plastic or metal foil vent.
Rigid metal vent:
Recommended for best drying performance and to avoid
crushing and kinking.
Flexible metal vent: (Acceptable only if accessible to clean)
Must be fully extended and supported in nal dryer location.
Remove excess to avoid sagging and kinking that may result
in reduced airow and poor performance.
Do not install in enclosed walls, ceilings, or oors.
The total length should not exceed 7
3
4
ft. (2.4 m).
NOTE: If using an existing vent system, clean lint from entire
length of the system and make sure exhaust hood is not
plugged with lint. Replace plastic or metal foil vents with rigid
metal or exible metal vents. Review “Vent System Chart” and
if necessary, modify existing vent system to achieve best drying
performance.
NOTE: Although each single-load dryer should typically have
an unobstructed outdoor air opening of 24" (154 cm) (based
on 1" [6.5 cm] per 1,000 Btu [252 kcal]), common make-up air
openings are also acceptable.
Set up common openings so the make-up air is distributed
equally to all dryers. Coverage area must be increased by 33%
to account for the use of registers or louvers.
Make-up air openings should not be installed near the building
exits for exhaust vents.
4"
(102 mm)
4" (102 mm) heavy, metal exhaust vent
Elbows:
45° elbows provide better airow than 90° elbows.
Clamps:
Use clamps to seal all joints.
Exhaust vent must not be connected or secured with screws
or other fastening devices that extend into interior of duct
and catch lint. Do not use duct tape.
Improper venting can cause moisture and lint to collect
indoors, which may result in:
Moisture damage to woodwork, furniture, paint, wallpaper,
carpets, etc.
Housecleaning problems and health problems.
Better
Good
Venting Requirements
8
4" (102 mm) Diameter Exhaust Hoods
Box Hood Louvered Hood Angled Hood
Vent Hoods
INSTALLATION REQUIREMENTS
Exhaust hood must be at least 12" (305 mm) from the ground
or any object that may be in the path of the exhaust (such as
owers, rocks, bushes, or snow).
Maximum Vent Length/Vent Connection
Maximum length of vent system depends upon the type of vent
used, number of elbows, and type of exhaust hood.
For vent systems not covered by the vent specication chart,
see your parts distributor.
Provision must be made for enough air for combustion
and ventilation. (Check governing codes and ordinances.)
See “Recessed Area and Closet Installation Instructions”
in the “Location Requirements” sections.
A 4" (102 mm) outlet hood is preferred. However, a 2
1
2
"
(64 mm) outlet exhaust hood may be used. A 2
1
2
" (64 mm)
outlet creates greater back pressure than other hood types.
For permanent installation, a stationary vent system is required.
Connect Vent
1. If connecting to existing vent, make sure the vent is clean.
2. Using a 4" (102 mm) clamp, connect vent to exhaust outlet
in dryer.
NOTE: Do not remove vent collar.
Vent System Length
3. Tighten hose clamp with Phillips screwdriver.
4. Make sure the vent is secured to exhaust hood with
a 4" (102 mm) clamp.
5. Move dryer into nal position. Do not crush or kink vent.
Make sure dryer is level.
12" min.
(305 mm)
Vent collar
Vent System Chart (Rigid Metal Vent)
No. of
90˚ Turns
Box and
Louvered Hood
Angled Hood
0 130 ft. (39.6 m) 129 ft. (39.3 m)
1 125 ft. (38.1 m) 119 ft. (36.3 m)
2 115 ft. (35.1 m) 109 ft. (33.2 m)
3 106 ft. (32.3 m) 100 ft. (30.5 m)
4 98 ft. (29.9 m) 92 ft. (28.0 m)
9
The outside end of main vent should have a sweep elbow
directed downward.
If main vent travels vertically through the roof, rather than
through wall, install a 180° sweep elbow on end of vent at least
2 ft. (610 mm) above surface of roof.
The opening in wall or roof shall have a diameter 1/2" (13 mm)
larger than vent diameter. Vent should be centered in opening.
Do not install screening over end of vent for best performance.
12" min.
(305 mm)*
A main vent can be used for venting a group of dryers. The
main vent should be sized to remove 5663 l/min. (200 CFM)
of air per dryer. Large-capacity lint screens of proper design
may be used in main vent if checked and cleaned frequently.
The room where the dryers are located should have make-up
air equal to or greater than CFM of all the dryers in the room.
Back-draft Damper Kit is available from your distributor and
should be installed in the vent of each dryer to keep exhausted
air from returning into dryers and to keep exhaust in balance
within main vent. Unobstructed return air openings are required.
Each vent should enter the main vent at an angle pointing in
the direction of the airow. Vents entering from the opposite
side should be staggered to reduce the exhausted air from
interfering with the other vents.
The maximum angle of each vent entering the main vent should
be no more than 30°.
Keep air openings free of dry cleaning uid fumes. Fumes
create acids which, when drawn through the dryer heating
units, can damage dryers and items being dried.
A clean-out cover should be located on the main vent
for periodic cleaning of the vent system.
If an Exhaust Hood Cannot be Used Multiple Dryer Venting
INSTALLATION REQUIREMENTS
24" min.
(610 mm)
* Minimum clearance above
any accumulation of snow,
ice, or debris such as leaves
30˚ max.
Air ow
Air Flow
10
Your dryer can be installed in a basement, laundry room,
or recessed area.
This dryer is not intended for installation in a mobile home.
Companion appliance location requirements should also be
considered.
IMPORTANT: Do not install or store the dryer where it will be
exposed to water and/or the weather. Proper installation is your
responsibility.
You will need:
A grounded electrical outlet located within 6 ft. (1.8 m) of
where the power cord is attached to the back of the dryer.
See “Electrical Requirements.”
A level oor with a maximum slope of 1" (25 mm) under
entire dryer. Installing the dryer on soft oor surfaces,
such as carpets or surfaces with foam backing, is not
recommended.
Gas dryer installation clearances
The location must be large enough to allow the dryer door
to be fully opened.
Additional spacing should be considered for ease of
installation and servicing. The door opens more than 180°.
Additional clearances might be required for wall, door,
and oor moldings.
Additional spacing of 1" (25 mm) on all sides of the dryer
is recommended to reduce noise transfer.
When installing a gas dryer:
IMPORTANT: Observe all governing codes and ordinances.
Check code requirements: Some codes limit or do not
permit installation of clothes dryers in garages, closets,
or sleeping quarters. Contact your local building inspector.
Make sure that lower edges of the cabinet, plus the back
and bottom sides of the dryer, are free of obstructions to
permit adequate clearance of air openings for combustion
air. See “Recessed Area and Closet Installation Instructions”
below for minimum spacing requirements.
Location Requirements
INSTALLATION REQUIREMENTS
Recessed Area and Closet Installation Instructions
This dryer may be installed in a recessed area or closet. For
recessed area and closet installations, minimum clearances
can be found on the warning label on the rear of the dryer
or in “Dimensions/Clearances.”
The installation spacing is in inches and is the minimum
allowable. Additional spacing should be considered for ease
of installation, servicing, and compliance with local codes
and ordinances.
If closet door is installed, the minimum unobstructed air
opening in the top and bottom is required. Louvered doors
with equivalent air openings are acceptable.
The dryer must be exhausted outdoors.
No other fuel-burning appliance may be installed in the same
closet as the dryer.
24 in.
2
(155 cm
2
)
48 in.
2
(310 cm
2
)
3"
(76 mm)
3"
(76 mm)
Closet
door
Front
View
Closet
Door
Front
View
Gas Dryer Installation Requirements
11
Gas Dryer Grounding
IMPORTANT: The dryer must be electrically grounded in
accordance with local codes and ordinances or, in the absence
of local codes, with the National Electrical Code, ANSI/NFPA
70, latest edition, or Canadian Electrical Code, CSA C22.1.
If codes permit and a separate ground wire is used, it is
recommended that a qualied electrical installer determine
that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
Do not ground to a gas pipe.
Do not have a fuse in the neutral or ground circuit.
A 120-volt, 60 Hz, AC-only, 15- or 20-amp, fused electrical
circuit is required. A time-delay fuse or circuit breaker is also
recommended. It is recommended that a separate circuit
serving only this dryer be provided.
This dryer is equipped with a power supply cord having
a 3-prong grounding plug.
To minimize the possibility of shock, the cord must be
plugged into a mating, 3 prong, grounding-type outlet,
grounded in accordance with local codes and ordinances.
If a mating outlet is not available, it is the personal
responsibility and obligation of the customer to have the
properly grounded outlet installed by a qualied electrician.
If codes permit and a separate ground wire is used, it is
recommended that a qualied electrician determine that
the ground path is adequate.
Check with a qualied electrician if you are not sure
the dryer is properly grounded.
INSTALLATION REQUIREMENTS
Electrical Requirements
GROUNDING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipment-
grounding conductor and a grounding plug. The plug must
be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes
and ordinances.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualied electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with
the dryer: if it will not t the outlet, have a proper outlet
installed by a qualied electrician.
12
IMPORTANT: Observe all governing codes and ordinances.
This installation must conform with all local codes and
ordinances. In the absence of local codes, installation must
conform with American National Standard, National Fuel Gas
Code ANSI Z223.1/NFPA 54 or CAN/CSA B149.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, Ohio 44131-5575
The design of this dryer has been certied by CSA International
for use at altitudes up to 10,000 feet (3048 m) above sea level
at the B.T.U. rating indicated on the model/serial plate. Burner
input adjustments are not required when the dryer is operated
up to this elevation.
Gas Supply
INSTALLATION REQUIREMENTS
When installed above 10,000 feet (3048 m), a four percent
(4%) reduction of the burner B.T.U. rating shown on the model/
serial plate is required for each 1,000 foot (305 m) increase in
elevation. For assistance when converting to other gas types
and/or installing above 10,000 feet (3048 m) elevation, contact
your local service company.
Gas supply pressure required to operate this dryer is
a minimum of 5.2" wc (1.30 kPa) and a maximum of
10.5" wc (2.62 kPa).
13
This dryer is equipped for use with natural gas. It is design-
certied by CSA International for LP (propane and butane)
gases with appropriate conversion. No attempt shall be made
to convert dryer from gas specied on serial/rating plate for use
with a different gas without consulting the serving gas supplier.
Conversion must be done by a qualied service technician.
Gas conversion kit part number is W10402145. This number
can also be found on a label on the gas valve burner base.
Type of Gas
INSTALLATION REQUIREMENTS
Recommended Method
Provide a gas supply line of 1⁄2" (13 mm) rigid (IPS) pipe to
dryer location. Pipe joint compounds that resist action of LP
gas must be used. Do not use TEFLON
®†
tape. With LP gas,
piping or tubing size can be 1⁄2" (13 mm) minimum. Usually, LP
gas suppliers determine size and materials used in the system.
Gas Supply Pressure Testing
A 1/8" NPT minimum plugged tapping, accessible for gauge
testing, must be installed immediately downstream of the
installed shut-off valve to the dryer (as shown above). The
dryer must be disconnected from the gas supply piping system
during any pressure testing of the system at test pressures in
excess of 1/2" psig (352 kg/m
2
).
Expected Pressures For Gas Supply
Minimum
Inches of Water
Maximum
Inches of Water
Natural Gas 5.2 10.5
LP Gas 8.0 13.0
Alternate Method
The gas supply may also be connected using 38" (10 mm)
approved copper or aluminum tubing. If the total length of
the supply line is more than 20 ft. (6.1 m), larger tubing will
be required.
If using natural gas, do not use copper tubing. Pipe joint
compounds that resist action of type of gas supplied must
be used.
Shut-off valve required
The supply line must be equipped with a manual shut-off
valve installed within 6 ft. (1.8 m) of dryer in accordance
with National Fuel Gas Code, ANSI Z223.1. This valve should
be located in same room as dryer. It should be in a location
that allows ease of opening and closing. Do not block access
to shut-off valve. In Canada, an individual manual shut-off
valve must be installed in accordance with the B149 installation
codes CAN/CGA B149.1 and CAN/CGA B149.2.
Gas Supply Line
Flexible Metal Appliance Connector
It is recommended that a new exible stainless steel gas line,
design-certied by CSA International, be used for connecting
the dryer to the gas supply line. (The gas pipe which extends
through the lower rear of the dryer is provided with 38"
male pipe thread.)
NOTE: Do not kink or damage the exible stainless steel gas
line when moving the dryer.
Rigid Pipe Connection
The rigid pipe connection requires a combination of pipe ttings
to obtain an in-line connection to the dryer.
†®TEFLON is a registered trademark of Chemours.
14
Your dryer can be installed in a basement, laundry room,
or recessed area.
This dryer is not intended for installation in a mobile home.
Companion appliance location requirements should also be
considered.
IMPORTANT: Do not install or store the dryer where it will be
exposed to water and/or the weather. Proper installation is your
responsibility.
You will need:
A grounded electrical outlet located within 6 ft. (1.8 m) of
where the power cord is attached to the back of the dryer.
See “Electrical Requirements.”
A level oor with a maximum slope of 1" (25 mm) under
entire dryer. Installing the dryer on soft oor surfaces,
such as carpets or surfaces with foam backing, is not
recommended.
Electric dryer installation clearances
The location must be large enough to allow the dryer door
to be fully opened.
Additional spacing should be considered for ease of
installation and servicing. The door opens more than 180°.
Additional clearances might be required for wall, door,
and oor moldings.
Additional spacing of 1" (25 mm) on all sides of the dryer
is recommended to reduce noise transfer.
Recessed Area and Closet Installation Instructions
This dryer may be installed in a recessed area or closet. For
recessed area and closet installations, minimum clearances
can be found on the warning label on the rear of the dryer
or in “Dimensions/Clearances.”
The installation spacing is in inches and is the minimum
allowable. Additional spacing should be considered for ease
of installation, servicing, and compliance with local codes
and ordinances.
If closet door is installed, the minimum unobstructed air
opening in the top and bottom is required. Louvered doors
with equivalent air openings are acceptable.
Location Requirements
The dryer must be exhausted outdoors.
24 in.
2
(155 cm
2
)
48 in.
2
(310 cm
2
)
3"
(76 mm)
3"
(76 mm
)
Closet
door
Front
View
INSTALLATION REQUIREMENTS
Closet
Door
Front
View
Electrical Requirements – U.S.A. only
It is your responsibility:
To contact a qualied electrical installer.
To be sure that the electrical connection is adequate and in
conformance with the National Electrical Code, ANSI/NFPA
70-latest edition and all local codes and ordinances.
The National Electrical Code requires a 4-wire power supply
connection for homes built after 1996, dryer circuits involved
in remodeling after 1996, and all mobile home installations.
A copy of the above code standards can be obtained from:
National Fire Protection Association, One Batterymarch
Park, Quincy, MA 02269.
To supply the required 3- or 4-wire, single-phase, 120/240
volt, 60 Hz., AC-only electrical supply (or 3- or 4-wire,
120/208 volt electrical supply, if specied on the serial/
rating plate) on a separate 30-amp circuit, fused on both
sides of the line. A time delay fuse or circuit breaker is
recommended. Connect to an individual branch circuit.
Do not have a fuse in the neutral or grounding circuit.
Do not use an extension cord.
If codes permit and a separate ground wire is used, it is
recommended that a qualied electrician determine that
the ground path is adequate.
Electric Dryer Installation Requirements
15
Electrical Requirements – U.S.A. only (cont.)
Electrical Connection
To properly install your dryer, you must determine the type
of electrical connection you will be using and follow the
instructions provided for it here.
This dryer is manufactured ready to install with a 3-wire
electrical supply connection. The neutral ground conductor
is permanently connected to the neutral conductor (white
wire) within the dryer. If the dryer is installed with a 4-wire
electrical supply connection, the neutral ground conductor
must be removed from the external ground connector
(green screw), and secured under the neutral terminal
(center or white wire) of the terminal block. When the neutral
ground conductor is secured under the neutral terminal
(center or white wire) of the terminal block, the dryer cabinet
is isolated from the neutral conductor.
If local codes do not permit the connection of a neutral
ground wire to the neutral wire, see “Optional 3-wire
connection” section.
A 4-wire power supply connection must be used when the
appliance is installed in a location where grounding through
the neutral conductor is prohibited. Grounding through the
neutral is prohibited for (1) new branch-circuit installations
and (2) areas where local codes prohibit grounding through
the neutral conductor.
Electric Dryer Power Supply Cord
If using a power supply cord:
Use a UL-listed power supply cord kit marked for use with
clothes dryers. The kit should contain:
A UL-listed 30-amp power supply cord, rated 120/240 volt
minimum. The cord should be type SRD or SRDT and be at
least 4 ft. (1.22 m) long. The wires that connect to the dryer
must end in ring terminals or “U”-shaped spade terminals
with upturned ends.
A UL-listed strain relief.
If your outlet looks like this:
4-wire
receptacle
(14-30R)
3-wire
receptacle
(10-30R)
Then choose a 4-wire power supply cord with ring
or spade terminals and UL-listed strain relief. The
4-wire power supply cord, at least 4 ft. (1.22 m)
long, must have four 10-gauge copper wires and
match a 4-wire receptacle of NEMA Type 14-30R.
The ground wire (ground conductor) may be either
green or bare. The neutral conductor must be
identied by a white cover.
Then choose a 3-wire power supply cord with ring
or spade terminals and UL-listed strain relief. The
3-wire power supply cord, at least 4 ft. (1.22 m)
long, must have three 10-gauge copper wires and
match a 3-wire receptacle of NEMA Type 10-30R.
If your outlet looks like this:
INSTALLATION REQUIREMENTS
Electric Dryer Grounding
16
Direct Wire
If connecting by direct wire:
Power supply cable must match power supply (4-wire or 3-wire)
and be:
Flexible armored cable or nonmetallic sheathed copper
cable (with ground wire), covered with exible metallic
conduit. All current-carrying wires must be insulated.
10-gauge solid copper wire (do not use aluminum).
At least 5 ft. (1.52 m) long.
INSTALLATION REQUIREMENTS
Electrical Requirements – Canada only
It is your responsibility:
To contact a qualied electrical installer.
To be sure that the electrical connection is adequate
and in conformance with the Canadian Electrical Code,
C22.1 – latest edition and all local codes. A copy of the
above codes standard may be obtained from: Canadian
Standards Association, 178 Rexdale Blvd., Toronto, ON
M9W 1R3 CANADA.
To supply the required 4 wire, single phase, 120/240 volt,
60 Hz., AC-only electrical supply on a separate 30-amp
circuit, fused on both sides of the line. A time-delay fuse
or circuit breaker is recommended. Connect to an individual
branch circuit.
This dryer is equipped with a CSA International
Certied Power Cord intended to be plugged into
a standard 14-30R wall receptacle. The cord is
5 ft (1.52 m) in length. Be sure wall receptacle is
within reach of dryer’s nal location.
Do not use an extension cord.
If you are using a replacement power supply cord,
it is recommended that you use Power Supply Cord
Replacement Part Number 8579325. For further information,
please reference the service numbers located in the
“Assistance or Service” section.
4-wire
receptacle
(14-30R)
GROUNDING INSTRUCTIONS
SAVE THESE INSTRUCTIONS
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipment-
grounding conductor and a grounding plug. The plug must
be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes
and ordinances.
WARNING: Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualied electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with
the dryer: if it will not t the outlet, have a proper outlet
installed by a qualied electrician.
17
INSTALLING LEVELING LEGS, COIN SLIDE, AND COIN BOX
The coin slide mechanism, control panel lock and key, and
coin box lock and key are not included and are available from
usual industry sources. A special coin slide extension must be
used on this model and can be purchased from the coin slide
distributor.
1. Prepare dryer for leveling legs
NOTE: Slide dryer onto cardboard or hardboard before moving
to avoid damaging oor covering.
Using two or more people, move dryer to desired installation
location.
Take tape off front corners of dryer. Open dryer and remove
the literature and parts packages. Wipe drum interior with damp
cloth to remove any dust.
Take two cardboard corners from the dryer carton and place
them on the oor in back of the dryer. Firmly grasp body of
the dryer and gently lay it on its back on the cardboard corners.
2. Screw in leveling legs
Examine leveling legs and nd diamond
marking. Screw legs into leg holes by
hand. Use an adjustable wrench or 1"
(25 mm) hex-head socket wrench to
nish turning legs until diamond marking
is no longer visible. Then t a covered foot
boot over each leg foot. For oors with
greater slopes, a longer leveling foot
(part no. 279810) is available.
To protect the oor, use a large piece of cardboard from the
dryer carton. Stand dryer up on the cardboard. Slide the dryer
until it is close to its nal location. Leave enough room for
electrical connection and to connect the exhaust vent.
On some models: The meter case houses the factory-installed
coin slide mechanism, service lock and key, and coin box lock
and key.
3. Install coin slide and coin box
Remove the service door of the meter case by lifting
it up at the back. Install the money-accepting device.
(Refer to manufacturer’s instructions for proper installation.)
Replace the meter case service door. Put the coin vault with
lock and key in the meter case opening.
Remove cardboard or hardboard from under dryer. Adjust
the legs of the dryer up or down until the dryer is level.
Foot
Diamond
Marking
18
1. Remove red cap from gas pipe on back of dryer.
2. Connect gas supply to dryer. Use a pipe thread compound
approved for the type of gas supplied. If exible metal
tubing is used, be certain there are no kinks.
If necessary for service, open the front lower service panel
by using a 1/4" nutdriver to remove the 2 hex-head screws
from the bottom of the panel. Then lift up on the panel while
pulling the bottom of the panel away from the dryer.
3. Open the shut-off valve in the gas supply line and make sure
the dryer has its own gas supply opened.
4. Test all connections by brushing on an approved
noncorrosive leak-detection solution. Bubbles will show
a leak. Correct any leaks found.
Make Gas Connection
INSTALLATION INSTRUCTIONS – GAS DRYER
19
Power Supply Cord Strain Relief
1. Insert strain relief.
2. Insert power cord into strain relief.
Remove Terminal Block Cover
Strain Relief
INSTALLATION INSTRUCTIONS – ELECTRIC DRYER
Direct Wire Strain Relief
1. Insert strain relief.
2. Insert conduit into strain relief and tighten clamp.
Electric Dryer Electrical Connections
20
INSTALLATION INSTRUCTIONS – ELECTRIC DRYER
Power Cord
4-wire receptacle (NEMA Type 14-30R)
3-wire receptacle (NEMA Type 10-30R)
Standard Power Supply Cord Connectors
Flanged Spade Connector Ring Connector
Connecting Ground and Neutral Wires
1. Remove center terminal block screw and the ground wire
by removing the external ground connector screw.
2. Connect ground and neutral wire to center terminal block.
Connection Options
Connecting 4-Wire Connection: Power Supply Cord
IMPORTANT: A 4-wire connection is required for mobile
homes and where local codes do not permit the use of 3-wire
connections.
Direct Wire
4-wire direct
3-wire direct
1"
(25 mm)
5"
(127 mm)
Connecting Power Cord Ground Wire
3. Connect ground wire (green or bare) with external ground
connector screw.
Connecting Remaining Wires
4. Connect remaining wires with outer terminal block screws.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Whirlpool CED9150GW Guide d'installation

Catégorie
Sèche-linge électriques
Taper
Guide d'installation
Ce manuel convient également à

dans d''autres langues