Mammoth P7TQ Guide d'installation

Taper
Guide d'installation
P7TQ- 072 / 090 / 120 Series
Single Package Heating / Electric Cooling Rooftop Units
INSTALLATION INSTRUCTIONS
IMPORTANT
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer. This includes being
able to install the product according to strict safety guidelines and instructing the customer on
how to operate and maintain the equipment for the life of the product. Safety should always be
the deciding factor when installing this product and using common sense plays an important
role as well. Pay attention to all safety warnings and any other special notes highlighted in the
manual. Improper installation of the furnace or failure to follow safety warnings could result in
serious injury, death, or property damage.
These instructions are primarily intended to assist qualified individuals experienced in the proper
installation of this appliance. Some local codes require licensed installation/service personnel
for this type of equipment. Please read all instructions carefully before starting the installation.
Return these instructions to the customer’s package for future reference.
DO NOT DESTROY. PLEASE READ CAREFULLY & KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
2
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION .....................3
REQUIREMENTS & CODES .....................................4
GENERAL INFORMATION ........................................4
About the Rooftop Unit ..................................................... 4
Before You Install this Equipment .................................... 4
Locating the Unit .............................................................. 4
Heating Load .................................................................... 5
CIRCULATING AIR SUPPLY .....................................5
Unconditioned Spaces ..................................................... 5
Acoustical Ductwork ......................................................... 5
Air Filter Requirements .................................................... 5
UNIT INSTALLATION ................................................6
Packaging Removal ......................................................... 6
Rigging & Hoisting ........................................................... 6
Minimum Clearance Requirements .................................. 6
Vertical to Horizontal Conversion ..................................... 6
Rooftop Mounting ............................................................. 7
Ground Level ................................................................... 7
Condensate Drain ............................................................ 7
ELECTRICAL WIRING ............................................... 8
Pre-Electrical Checklist .................................................... 8
Line Voltage ..................................................................... 8
Grounding ........................................................................ 8
Unbalanced 3-Phase Supply Voltage .............................. 8
Thermostat / Low Voltage Connections ........................... 9
Heat Anticipator ............................................................... 9
Blower Speed ................................................................... 9
STARTUP & ADJUSTMENTS ...................................10
Pre-Start Check List ........................................................ 10
Startup Procedures .......................................................... 10
Air Circulation ................................................................... 10
System Cooling ................................................................ 10
System Heating - Field Installed Electric Heat ................. 10
Verifying Temperature Rise ............................................. 10
Verifying Operation of Over-Temperature Limit Control
(Field Installed Electric Heat) ........................................... 10
OPERATING SEQUENCE .........................................11
Cooling Mode ................................................................... 11
Heating Mode (Optional Electric Heat) ............................ 11
Blower Mode .................................................................... 11
Unit Fails to Operate ........................................................ 11
TROUBLESHOOTING ...............................................11
REFRIGERANT CHARGING .....................................11
Table 2. Heat Rise and Range ..................................... 11
Charging Charts & Application Notes .............................. 12
Table 3. Refrigerant Charge Table ............................... 12
Figure 9. P7TQ-072 Charging Chart (6-Ton) ............... 12
Figure 10. P7TQ-090 Charging Chart (7.5-Ton) .......... 13
Figure 11. P7TQ-120 Charging Chart (10-Ton) ........... 13
UNIT MAINTENANCE ................................................14
Routine Maintenance ....................................................... 14
Air Filters ...................................................................... 14
Blower Compartment .................................................... 14
Condensate Drain & Outdoor Coil ................................ 14
Electrical ....................................................................... 14
Motor / Bearing Lubrication .......................................... 14
FIGURES & TABLES .................................................16
Figure 13. Physical Dimensions for P7TQ Units .......... 16
Table 4. Center of Gravity & Unit Shipping Weights .... 17
Blower Performance Data ................................................ 18
Table 5. P7TQ-072 C/D/N Series -
Downflow Models ........................................... 19
Table 6. P7TQ-072 C/D/N Series -
Horizontal Models .......................................... 20
Table 7. P7TQ-090 C/D/N* Series -
Downflow Models ........................................... 21
Table 8. P7TQ-090 C/D/N* Series -
Horizontal Models .......................................... 22
Table 9. P7TQ-120 C/D/N* Series -
Downflow Models ........................................... 23
Table 10. P7TQ-120 C/D/N*Series -
Horizontal Models ........................................ 24
Table 11. P7TQ-090C/D/N* Series High Static Drive ... 25
Table 12. P7TQ-120C/D/N* Series High Static Drive ... 25
Electrical Data & Diagrams .............................................. 26
Figure 14. Wiring Diagram for 6 Ton Models
(208/230 V, 2 Speed, 2 HP Motor) .............. 26
Figure 15. Wiring diagram for 6 Ton Models
(460 V, 2 Speed, 2 HP Motor) ..................... 28
Figure 16. Wiring diagram for 6 Ton Models
(575 V, 2 Speed, 2 HP Motor) ..................... 30
Figure 17. Wiring diagram for 6 Ton Models
(208/230 V, 5 Speed, 3 HP ECM Motor) ..... 32
Figure 18. Wiring diagram for 6 Ton Models
(460 V, 5 Speed, 3 HP ECM Motor) ............ 34
Figure 19. Wiring diagram for 6 Ton Models
(575 V, 5 Speed, 3 HP ECM Motor) ............ 36
Figure 20. Wiring diagram for 7.5 & 10 Ton Models
(208/230 V, 2 Speed, 2 HP Motor) .............. 38
Figure 21. Wiring diagram for 7.5 & 10 Ton Models
(460 V, 2 Speed, 2 HP Motor) ..................... 40
Figure 22. Wiring diagram for 7.5 & 10 Ton Models
(575 V, 2 Speed, 2 HP Motor) ..................... 42
Figure 23. Wiring diagram for 7.5 & 10 Ton Models
(208/230 V, 5 Speed, 3 HP ECM Motor) ..... 44
Figure 24. Wiring diagram for 7.5 & 10 Ton Models
(460V, 5 Speed, 3 HP ECM Motor) ............. 46
Figure 25. Wiring diagram for 7.5 & 10 Ton Models
(575 V, 5 Speed, 3 HP ECM Motor) ............ 48
Table 13. MCA / MOP Data (Single Circuit) ................. 50
Table 14. MCA / MOP Data (Multiple Circuit) ............... 51
INSTALLATION CHECKLIST ............................................. 54
3
IMPORTANT SAFETY INFORMATION
Please read all instructions before servicing this equipment.
Pay attention to all safety warnings and any other special
notes highlighted in the manual. Safety markings are used
frequently throughout this manual to designate a degree or
level of seriousness and should not be ignored.
WARNING indicates a potentially hazardous situation that if
not avoided, could result in personal injury or death.
CAUTION indicates a potentially hazardous situation that
if not avoided, may result in minor or moderate injury or
property damage.
WARNING:
Improper installation, service, adjustment, or
maintenance may cause explosion, fire, electrical
shock or other hazardous conditions which may
result in personal injury or property damage.
Unless otherwise noted in these instructions,
only factory authorized kits or accessories may
be used with this product.
WARNING:
Do not place combustible material on or against
the unit cabinet. Do not place combustible
materials, including gasoline and any other
flammable vapors and liquids, in the vicinity of
the unit.
WARNING:
PROPOSITION 65 WARNING: This product
contains fiberglass insulation. Disturbing the
insulation of this product during installation,
maintenance, or repair may expose you to
fiberglass insulation.
• Breathingthismaterialmaycauserespiratory
irritations.
• Fiberglass insulation may also cause eye
irritation, skin sensitization, or other allergic
responses in susceptible individuals.
• Always wear goggles, disposable gloves,
long sleeved shirt, and appropriate breathing
protection when working near this insulation.
If contact with skin occurs, wash immediately
with soap and water. In case of contact with
eyes, flush immediately with water for at least
15 minutes. Contact a physician if needed.
WARNING:
Rooftop installations with vertical ducts must be
provided with a 90 degree elbow installed in the
supply duct to comply with U.L. (Underwriters
Laboratories) codes for use with electric heat
so the elements are not directly over a supply
grille.
WARNING:
The information listed below and must be followed
during the installation, service, and operation
of this unit. Unqualified individuals should
not attempt to interpret these instructions or
install this equipment. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious personal
injury or death.
• Thisequipmentcontainsliquidandgaseousrefrigerant
under high pressure. Installation or servicing should only
be performed by qualified trained personnel thoroughly
familiar with this type equipment.
• Beforebeginningtheinstallation,verifythattheunitmodel
is correct for the job. The unit model number is printed on
the data label.
• Followallprecautionsintheliterature,ontags,andon
labels provided with the equipment. Read and thoroughly
understand the instructions provided with the equipment
prior to performing the installation and operational checkout
of the equipment.
• This unit is designed only for outdoor installations and
should be located with consideration of minimizing the
length of the supply and return ducts.
• Theinstallershouldbecomefamiliarwiththeunit’swiring
diagram before making any electrical connections to the
unit. See the unit wiring label or
Figure 14 (page 26), Figure
15 (page 28)
, Figure 16 (page 30), Figure 17 (page 32),
Figure 18 (page 34)
, Figure 19 (page 36), Figure 20 (page
38)
, Figure 21 (page 40), Figure 22 (page 42), Figure 23
(page 44) Figure 24 (page 46)
, & Figure 25 (page 48).
• Use caution when handling thisapplianceorremoving
components. Personal injury can occur from sharp metal
edges present in all sheet metal constructed equipment.
4
REQUIREMENTS & CODES
• Thisequipmentmustbeinstalledinaccordancewith
instructions outlined in this manual and all applicable
local building codes.
• Allelectricalwiringmustbecompletedinaccordancewith
local, state and national codes and regulations and with
the National Electric Code (ANSI/NFPA 70) or in Canada
the Canadian Electric Code Part 1 CSA C.22.1.
• The installer must comply with all local codes and
regulations which govern the installation of this type of
equipment. Local codes and regulations take precedence
over any recommendations contained in these instructions.
Consult local building codes and the National Electrical
Code (ANSI CI) for special installation requirements.
• AirDuctsmustbeinstalledinaccordancewiththestandards
of the National Fire Protection Association “Standards for
Installation of Air Conditioning and Ventilation Systems”
(NFPA 90A), “Standard for Installation of Residence Type
Warm Air Heating and Air Conditioning Systems” (NFPA
90B), these instructions, and all applicable local codes.
• Consult
Table 2 (page 11), and the rating plate for the proper
circulating air flow and temperature rise. It is important that
the duct system be designed to provide the correct flow
rates and external pressure rise. An improperly designed
duct system can result in nuisance shutdowns, and comfort
or noise issues.
• This unitis designedforoutdoor installations only and
should be located as described on
page 4.
• Theinformationlistedbelowisforreferencepurposesonly
and does not necessarily have jurisdiction over local or
state codes. Always consult with local authorities before
installing this appliance.
Duct Systems
• USandCANADA:AirConditioningContractorsAssociation
(ACCA) Manual D, Sheet Metal and Air Conditioning
Contractors National Association (SMACNA), or American
Society of Heating, Refrigeration, and Air Conditioning
Engineers (ASHRAE) Fundamentals Handbook
Electrical Connections
• US:NationalElectricalCode(NEC)ANSI/NFPA70
• CANADA:CanadianElectricalCodeCSAC22.1
General Installation
• US:CurrenteditionoftheNFPA90B.Forcopies,contact
the National Fire Protection Association Inc., Batterymarch
Park, Quincy, MA 02269; or American Gas Association,
400 N. Capitol, N.W., Washington DC 20001 or www.
NFPA.org
• CANADA:NSCNGPIC.Foracopy,contactStandardSales,
CSA International, 178 Rexdale Boulevard, Etobicoke
(Toronto), Ontario, M9W 1R3 Canada
Safety
US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the
Installation Standards, Warm Air Heating and Air
Conditioning Systems ANSI/NFPA 90B.
CANADA: CAN/CSA-B149.1 and .2–M00 National
Standard of Canada. (NSCNGPIC)
GENERAL INFORMATION
About the Rooftop Unit
Single Package Electric Cooling Rooftop Units are designed
only for outdoor rooftop or ground level installations and can
be readily connected to the duct system of a building.
This unit has been tested for capacity and efficiency in
accordance with AHRI Standards and will provide many
years of safe and dependable comfort, providing it is properly
installed and maintained. With regular maintenance, this unit
will operate satisfactorily year after year. Abuse, improper
use, and/or improper maintenance can shorten the life of
the appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment
failure, it is recommended that periodic maintenance be
performed on this unit. The ability to properly perform
maintenance on this equipment requires certain tools and
mechanical skills.
Before You Install this Equipment
The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected.
It is recommended that the area to be conditioned be
completely insulated and vapor sealed.
Check the electrical supply and verify the power supply
is adequate for unit operation. Consideration should be
given to availability of electric power, service access, noise,
and shade. If there is any question concerning the power
supply, contact the local power company.
All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage prior
to installing the equipment at the job site. Verify coil fins
are straight. If necessary, comb fins to remove flattened
or bent fins. Claims for damage (apparent or concealed)
should be filed immediately with the carrier.
Please consult your dealer for maintenance information and
availability of maintenance contracts. Read all instructions
before installing the unit.
Locating the Unit
• Surveythejobsitetodeterminethebestlocationforthe
packaged unit. The unit should be located with consideration
of minimizing the length of the supply and return ducts.
If practical, place the equipment and its ducts in an area
where they will be shaded from the afternoon sun, when
the heat load is greatest.
• ForHorizontalinstallations:selectasolid,levelposition,
preferably on a concrete slab, slightly above the grade
level, and parallel to the building.
• Overheadobstructions,poorlyventilatedareas,andareas
subject to accumulation of debris should be avoided. Do
not place the unit in a confined space or recessed area
where discharge air from the unit could re-circulate back
through the condenser coil.
• Sufcientclearanceforunobstructedairowthroughthe
louvered control access panel and outdoor coil must be
maintained in order to achieve rated performance. See
Figure 1 (page 5) for minimum clearance requirements.
• If minimum clearances to combustibles are greater
than recommended serviceability clearances, then
clearances to combustibles must take precedence.
5
Heating Load
This unit should be sized to provide the design heating
load requirement. Heating load estimates can be made
using approved methods available from Air Conditioning
Contractors of America (Manual N); American Society of
Heating, Refrigerating, and Air Conditioning Engineers; or
other approved engineering methods.
CIRCULATING AIR SUPPLY
WARNING:
Do not allow combustion products from other
equipment or building vents to enter the return
air ductwork or the circulating air supply. Failure
to prevent products of combustion from being
circulated into the living space can create
potentially hazardous conditions including
carbon monoxide poisoning that could result in
personal injury or death.
All return ductwork must be adequately sealed,
all joints must be taped, and the ductwork must
be secured to the unit with sheet metal screws.
When return air is provided through the bottom
of the unit, the joint between the unit and the
return air plenum must be air tight.
The roof curb or cement pad that the unit is
mounted to must provide sound physical support
of the unit with no gaps, cracks, or sagging
between the unit and pad.
Return air and circulating air ductwork must not
be connected to any other heat producing device
such as a fireplace insert, stove, etc. Doing so
may result in fire, explosion, carbon monoxide
poisoning, personal injury, or property damage.
This unit is designed only for use with a supply and return
duct. Air ducts should be installed in accordance with
the standards of the National Fire Protection Association
“Standard for Installation of Air Conditioning Systems” (NFPA
Figure 1. Unit Clearance Requirements
Top of unit
to be
unobstructed
Recommended Clearances
for Service or Accesories
Minimum Required
Clearances to Combustibles
36"
36"
36"
36"
48"
48"
60"
48"
90A), “Standard for Installation of Residence Type Warm Air
Heating and Air Conditioning Systems” (NFPA 90B), and all
applicable local codes. NFPA publications are available by
writingto:NationalFireProtectionAssociation,Batterymarch
Park,Quincy,ME02269orvisittheirwebsite:www.NFPA.org.
• DesigntheductworkaccordingtoManualQbytheAir
Conditioning Contractors of America (ACCA) or similar
commercial methods.
• Ifroofcurbisinstalled,theductsmustbeattachedtothe
curb hangers, not the unit.
• Ductworkshouldbeattacheddirectlytotheunitendpanel
for horizontal applications.
• Ifacombinationofindoorandoutdoorairisused,theducts
and damper system must be designed so that the return
air supply to the furnace is equal to the return air supply
under normal, indoor return air applications.
• Thisunitisshippedreadyforverticalductconnections
and is easily converted for horizontal duct connections.
Unconditioned Spaces
All ductwork passing through unconditioned space must be
properly insulated to prevent condensation and minimize duct
losses. Use insulation with an outer vapor barrier. Refer to
local codes for insulation material requirements.
Acoustical Ductwork
Certain installations may require the use of acoustical lining
inside the supply duct work.
• Acoustical insulation must be in accordance with the
current revision of the Sheet Metal and Air Conditioning
Contractors National Association (SMACNA) application
standard for duct liners.
• DuctliningmustbeULclassiedbattsorblanketswitha
fire hazard classification of FHC-25/50 or less.
• Fiberductworkmaybeusedinplaceofinternalductliners
if the fiber duct work is in accordance with the current
revision of the SMACNA construction standard on fibrous
glass ducts. Fibrous duct work and internal acoustical
lining must be NFPA Class 1 air ducts when tested per
UL Standard 181 for Class 1 ducts.
Air Filter Requirements
WARNING:
Never operate the unit without a filter in place.
Dust and lint could accumulate on internal parts,
resulting in loss of efficiency, equipment damage
and possible fire.
All return air must pass through the filters before entering the
unit. It is important that all filters be kept clean and replaced
frequently to ensure proper operation of unit. Dirty or clogged
filters will reduce the efficiency of the unit and result in unit
shutdowns. Air filter pressure drop must not exceed 0.08
inches WC. When replacing the air filters, a suitable air filter
must be installed ahead of the evaporator coil of the return
air system. Refer to
Table 1 for recommended filter sizes.
Table 1. Filter Sizes & Quantities
UNIT
FACTORY
FILTER SIZE
QTY
P7TQ-072 20 x 20 x 2 4
P7TQ-090 20 x 20 x 2 4
P7TQ-120 20 x 20 x 2 4
6
UNIT INSTALLATION
Packaging Removal
All units have been securely packaged at the point of shipment.
After unpacking the unit, carefully inspect for apparent and
concealed damage. Claims for damage should be filed with
the carrier by the consignee.
1. Remove any shipping brackets. DO NOT remove base
rails from unit.
2. Inspect unit thoroughly for shipping damage.
3. Carefully lower and position unit to its permanent location.
Rigging & Hoisting
WARNING:
To avoid the risk of property damage, personal
injury, or death, it is the rigger’s responsibility
to ensure that whatever means are used to hoist
the unit are safe and adequate:
• Theliftingequipmentmustbeadequateforthe
load. Refer to
Table 4 (page 17) for unit weights.
• Theunit must beliftedfrom the holesinthe
base rails using cables or chains.
• Spreaderbarsarerequiredtoprotecttheunit
and ensure even loading. See
Figure 2.
• Keeptheunitinanuprightpositionatalltimes.
The rigging must be located outside the unit’s
center of gravity. Refer to
Table 4 (page 17) for
locating the center of gravity.
• All panels must be securely in place during
rigging and hoisting.
Minimum Clearance Requirements
P7TQ units are certified as combination heating and cooling
equipment for outdoor installation only.
Figure 1 (page 5)
displays the minimum clearances to combustible materials
for both Downflow and Horizontal discharge.
P7TQ units may be installed on non-combustible surfaces
when used with bottom supply and return air ducts. Units
may be installed on wood flooring or on Class A, B, or C
roof covering material as long as the following requirements
aremet:
• Ifusingsidesupplywithreturnairducts,theunitmustbe
converted for horizontal connections. Refer to Vertical to
Horizontal section below. NOTE: This must be converted
prior to unit installation.
• Ifusingverticaldischargeandreturnairductsaroofcurb
must be installed prior to unit installation. See Rigging and
Hoisting section
(page 6) for setting of the unit.
Vertical to Horizontal Conversion
The unit is shipped ready for downflow duct connections.
If horizontal ducts are required, the unit must be converted
prior to attaching duct work to unit.
1. Remove both return and supply horizontal duct covers.
Do not discard the screws or covers. These will be used
to cover the openings in the bottom of the unit. See
Figure
3
.
2. Cut both return and supply openings following along the
tabbed cutouts. NOTE: There are tabs on the inside and
the outside of the panels. Discard the cut sections when
done. These will not be needed.
Figure 4.
IMPORTANT NOTE:
Use caution when cutting left vertical side of return air
panel. The filter rack is in close proximity to opening
3. Install the duct covers (removed in step 1) over the openings
in the bottom of the unit. NOTE: Apply adhesive around
the perimeter of both openings before setting the duct
covers into position.
4. Align the predrilled locating holes and secure the duct
covers with screws removed in step 1.
Figure 2. Rigging & Hoisting
LIFTING
BEAM
CABLE OR CHAIN
SPREADER
BAR
SPREADER
BAR
BASE
RAIL
BASE
RAIL
Figure 3. Vertical to Horizontal conversion
(Right side view)
Covers removed
Exposing area for
cutouts-connecting tabs
Figure 4. Cutouts removed
(Right Side view)
7
Rooftop Mounting
Rooftop installations must be located according to local
buildingcodesorordinancesandtheserequirements:
• Theroofmustbecapableofhandlingtheweightofthe
unit. For unit weights, see
Table 4 (page 17). Reinforce
the roof if necessary.
• The appropriate accessory roof curb
Figure 5 (page 7)
must be installed prior to unit installation. The roof curb
must be square and level to ensure proper condensate
drainage. Please follow all instructions provided with
the kit.
WARNING:
Never drill or punch holes in unit base when
installing downflow units. Leakage may occur if
bottom pan is punctured.
• Onbottomdischargeapplications,thesupplyandreturn
air ducts must be attached to the roof curb duct supports,
not the unit. Install all ductwork before setting unit on curb
or frame.
• Framesupportmustbeconstructedusingnoncombustible
materials. Full perimeter support is required under the
unit. Supports must be made of steel or weather resistant
wooden materials. The unit must be square and level to
ensure proper condensate drainage.
• The frame must be high enough to ensure prevention
of any moisture from entering the unit. Recommended
height to unit base is 8” for both downflow and horizontal
installations.
• Secure roof curb or frame to roof using acceptable
mechanical methods per local codes.
Ground Level
Ground level installations must be located according to local
buildingcodesorordinancesandtheserequirements:
• Clearancesmustbeinaccordancewiththoseshownin
Figure 1 (page 5).
• Amountingpad
Figure 6 (page 7) must be provided and
separate from the building foundation. The pad must be
level to ensure proper condensate disposal and strong
enoughtosupporttheunit’sweight.Theslabheightmust
be a minimum of 3” (8 cm) above grade and with adequate
drainage.
• Whenusinghorizontalsupplywithreturnairducts,theunit
must be converted for horizontal connections prior to unit
installation. Refer to the Vertical to Horizontal Conversion
section on
page 6.
Condensate Drain
The method for disposing of condensate varies according
to local codes. Consult your local code or authority having
jurisdiction.
Condensate is drained from the unit through a 3/4” (19 mm)
PVC pipe located on end of the unit (
Figure 7). For proper
drainage, install a 3” (8 cm) Min. trap between the drain
line and an open vent of the same size. Avoid areas where
condensate drainage may cause problems.
The condensate drain line must be J-trapped using field
supplied parts and may be combined with other drain lines
when routed to the drain.
When connecting rigid drain line, hold any fittings with a
wrench to prevent twisting. Do not overtighten!
Figure 5. Roof Curb
See Table
3
Roof Curb
Figure 6. Mounting Pad
3”
Condensate
Drain
Figure 7. Condensate Drain
8
• Useonlycopperwireforthelinevoltagepowersupply
to this unit. Use proper code agency listed conduit and
connector for connecting the supply wires. Use of rain
tight conduit is recommended.
• Unitsareshippedfromthefactorywiredfor230or460volt
operation. On 208-230V units being placed into 208 volt
operation, remove the lead from the transformer terminal
marked 240V and connect it to the terminal marked 208V.
• Overcurrent protection mustbeprovidedat the branch
circuit distribution panel and sized as shown on the unit
rating label and according to the National Electric Code
and applicable local codes. NOTE: See the unit rating plate
for maximum circuit ampacity and maximum overcurrent
protection limits.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground
!
This unit must be electrically grounded in accordance with
local codes or, in the absence of local codes, with the National
Electrical Code (ANSI/NFPA 70) or the CSA C22.1 Electrical
Code. Use the grounding lug provided in the control box for
grounding the unit.
Unbalanced 3-Phase Supply Voltage
Voltage unbalance occurs when the voltages of all phases
of a 3-phase power supply are no longer equal. This
unbalance reduces motor efficiency and performance. Some
underlyingcausesofvoltageunbalancemayinclude:Lack
of symmetry in transmission lines, large single-phase loads,
and unbalanced or overloaded transformers. A motor should
never be operated when a phase imbalance in supply is
greater than 2%.
Perform the following steps to determine the percentage of
voltageimbalance:
1. Measure the line voltages
of your 3-phase power
supply where it enters the
building and at a location
that will only be dedicated
to the unit installation. (at
the units circuit protection
or disconnect).
EXAMPLE:
AB = 451V
BC = 460V
AC = 453V
2. Determine the average voltage in the power supply.
In this example, the measured line voltages were 451, 460,
and 453. The average would be 454 volts (451 + 460 +
453 = 1,364 / 3 = 454).
ELECTRICAL WIRING
WARNING:
ELECTRICAL SHOCK, FIRE OR
EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical
power to furnace.
• Whenservicingcontrols,labelallwiresprior
to disconnecting. Reconnect wires correctly.
• Verifyproperoperationafterservicing.
Pre-Electrical Checklist
Verify that the voltage, frequency, and phase of the supply
source match the specifications on the unit rating plate.
Verify that the service provided by the utility is sufficient
to handle the additional load imposed by this equipment.
For proper MCA / MOP data see the unit wiring label or
Table 13 (page 50) or Table 14 (page 51).
Verify factory wiring is in accordance with the unit wiring
diagram. Inspect for loose connections.
For 3 phase units always check the phase balance. See
page 8.
Line Voltage
• Electrical connections must be in compliance with all
applicable local codes and ordinances, and with the current
revision of the National Electric Code (ANSI/NFPA 70).
For Canadian installations the electrical connections and
grounding shall comply with the current Canadian Electrical
Code (CSA C22.1 and/or local codes).
• Providepowersupplyfortheunitinaccordancewiththe
unit wiring diagram and the unit rating plate. The line
voltage to the unit should be supplied from a dedicated
branch circuit containing the correct fuse or circuit breaker
for the unit.
• An electrical disconnect must be located within sight
of and readily accessible to the unit. This switch shall
be capable of electrically de-energizing the outdoor unit.
See unit data label for proper incoming field wiring. Any
other wiring methods must be acceptable to authority
having jurisdiction.
• Awiringdiagramislocatedontheinsidecoverofthecontrol
access panel of the outdoor unit. The installer should
become familiar with the wiring diagrams before making
any electrical connections to the outdoor unit. See
Figure
14 (page 26)
, Figure 15 (page 28), Figure 16 (page 30),
Figure 17 (page 32), Figure 18 (page 34), Figure 19 (page
36)
, Figure 20 (page 38), Figure 21 (page 40), Figure
22 (page 42)
, Figure 23 (page 44), Figure 24 (page 46),
&
Figure 25 (page 48).
• Ifanyoftheoriginalwiressuppliedwiththeunitmustbe
replaced, they must be replaced with material of the same
voltage, gauge, and temperature rating.
• Connect the line-voltageleads to the terminals on the
3-pole terminal block (inside the control compartment).
9
3.Determinethemaximumdeviation:
EXAMPLE
From the values given in step 1, the BC voltage (460V) is
thegreatestdifferenceinvaluefromtheaverage:
460 - 454 = 6
454 - 451 = 3
454 - 453 = 1
4. Determine percent of
voltage imbalance by
using the results from
steps 2 & 3 in the following
equation.
6
454
100 x
= 1.32%
EXAMPLE
maxvoltage deviation
fromaverage voltage
=100 x
averagevoltage
% Voltage
Imbalance
The amount of phase imbalance (1.32%) is satisfactory
since the amount is lower than the maximum allowable 2%.
Please contact your local electric utility company if your
voltage imbalance is more than 2%.
Thermostat / Low Voltage Connections
• SinglePackageElectricHeating/ElectricCoolingRooftop
Units are designed to operate with a 24 VAC Class II
control circuit. The control circuit wiring must comply with
the current provisions of the NEC (ANSI/NFPA 70) and
with applicable local codes having jurisdiction. Thermostat
connections should be made in accordance with the
instructions supplied with the thermostat.
• Atwo-stagecoolingthermostatisrequiredforP7TQseries
units. Select a thermostat which operates in conjunction
with the installed accessories. See Figure 10 for proper
wire gauge and their recommended lengths for typical
thermostat connections.
• Thelowvoltagewiresmustbeproperlyconnectedtothe
units low voltage terminal block. Route 24V control wires
through the side of the unit. Recommended wire gauge
and wire lengths for typical thermostat connections are
shown in
Figure 8.
• Thethermostatshouldbemountedabout5feetabovethe
floor on an inside wall. DO NOT install the thermostat on
an outside wall or any other location where its operation
may be adversely affected by radiant heat from fireplaces,
sunlight, or lighting fixtures, and convective heat from
warm air registers or electrical appliances. Refer to the
thermostatmanufacturer’sinstructionsheetfordetailed
mounting information.
Heat Anticipator
Verify if the thermostat being used for the installation has a
heat anticipator setting. This function allows the thermostat to
anticipate the space heating rate and time the burner to shutoff
accordingly.Alwaysrefertothethermostatmanufacturer’s
instructions for the correct settings.
Blower Speed
The blower speed is preset at the factory but must be verified
at each installation. For optimum system performance and
comfort, it may be necessary to change the factory set speed.
Refer to
Table 5 (page 19), Table 6 (page 20), Table 7 (page
21)
, Table 8 (page 22), Table 9 (page 23), Table 10 (page
24)
, Table 11 (page 25), & Table 12 (page 25) for proper
blower performance data. Always ensure drive belt is secure
and tensioned properly. Also inspect variable pitch sheaves
for proper tightness of the set screws
CAUTION:
To avoid personal injury or property damage,
make certain that the motor leads do not make
contact with any uninsulated metal components
of the unit.
Tochangetheblowerspeed:
1. Disconnect all electrical power to the unit and open
the blower access door.
2. Loosen the motor mounting nuts and mounting plate
adjustment bolt to allow removal of the blower belt from
the motor sheave.
3. Loosen top set screw on motor sheave and turn clockwise
to close (increases blower speed), or counterclockwise to
open (decreases blower speed).
4. Replace belt on pulleys and position motor mounting plate
to correct position for proper belt tension.
5. Tighten motor nuts.
Figure 8. Typical 2 - Stage Heat/Cool
Thermostat Connection
T-Stat Wire
Gauge
Recommended T-Stat Wire
Length - Ft. (Unit to T-Stat)
18 Ga. 0 - 60
16 Ga. 61 - 130
Field Supplied Wiring - - - - - Use Solid Class II Copper Wire
Y1
Y2
W2
W1
G
RH
RC
Y1
Y2
W2
W1
G
R
Indoor
Thermostat
Sub-Base
Unit Low Voltage
Terminal
A1
Economizer
OCC/UNOCC
Stage 1 Cool
Stage 2 Cool
Stage 1 Heat
Blower
24V Hot
10
STARTUP & ADJUSTMENTS
Pre-Start Check List
Verify unit is properly supported.
Verify unit is level for proper condensate drainage.
Verify all clearance requirements are met. Airflow to and
from the outdoor coil must be unrestricted.
Verify the ductwork is adequately sealed to prevent air
leakage. Insulate if necessary.
Verify the line voltage power leads are securely connected
and the unit is properly grounded.
Verify low voltage wires are securely connected to the
correct leads in the low voltage area of the control box.
Verify the indoor blower is properly set for the installation.
Verify the outdoor fan turns freely.
Verify the power supply branch circuit overcurrent protection
is properly sized.
Verify all exterior panels have been reinstalled and securely
fastened.
Verify the thermostat is wired correctly and preset for initial
operation. Set the thermostat system switch to OFF and
the fan switch to AUTO.
Startup Procedures
WARNING:
This unit is equipped with crankcase heaters.
Allow 24 hrs for heating of the refrigerant
compressor crankcase prior to start up and
anytime the power has been removed for more
than 12 hrs. Failure to comply may result in
damage or cause premature failure of the system.
IMPORTANT NOTE:
Failure to follow the crankcase heater instructions for
units equipped with microchannel coils may lead to a
discharge pressure spikes which could cause the unit
high pressure switch to trip. If this occurs, wait for unit
pressures to equalize before depressing the manual
reset switch and re-start the unit again.
• Checkallelectricalwiringforlooseconnectionsandtighten
as required.
• Checkunitforreturnairltersandcondensatetrap.
• Closeallelectricaldisconnectstoenergizethesystem.
Air Circulation
1. Set thermostat system switch to OFF and the fan switch
to ON.
2. Verify the blower motor runs continuously. Check for
air delivery at the register(s). Ensure that there are no
obstructions at the registers or in the ductwork.
3. Set thermostat fan switch to AUTO and verify the blower
shuts down immediately.
NOTE: If blower is turning opposite of arrow direction, shut
off main power to the unit and switch any two field wires at
the disconnect. DO NOT alter unit wiring.
System Cooling
1. Set the thermostat system switch to COOL and the fan
switch to AUTO.
2. Lower the thermostat temperature switch below room
temperature and observe that the blower, both compressors
and fans) energize.
3. Verify blower is turning in direction indicated by arrow
and air discharged at the register is cooler than room
temperature.
4. Verify HI and LO refrigerant pressures.
NOTE: If refrigerant pressures are abnormal and blower
is rotating in the opposite direction of the arrow, shut off
main power to the unit and switch any two field wires at the
disconnect. Ensure proper rotation of the blower. DO NOT
alter unit wiring. Listen for any unusual noises. Locate the
source and correct as needed.
5. Allow the unit to run for several minutes. Set the temperature
selector above room temperature and verify that the fan,
blower, and compressors cycle off with the thermostat.
System Heating - Field Installed Electric Heat
This packaged air conditioner is designed to allow an optional
electric heat kit to be field installed as required by the
building’sparticularheatingload.Theoptionsavailablefor
each unit are shown in the heater kit installation instructions
orunit’sTechnicalServiceLiterature.Installtheheaterkitsas
directed by the instruction manual provided with the heater
kit. Follow all cautions and warnings as directed. Use only
factory authorized heater kits.
WARNING:
Uninsulated live components are exposed when
control access panel is removed.
1. Set the thermostat to above room temperature.
2. Verify that the compressor and outdoor fan motor are not
energized and the electric heat is energized.
3. After the unit has run for approximately five minutes, set
the thermostat below room temperature and verify that
the electric heat has de-energized.
Verifying Temperature Rise
1. Place thermometers in the return and supply air stream
as close to the unit as possible. The thermometer on the
supply air side must be shielded against direct radiation
from the electric heat elements to avoid false readings.
2. Adjust all registers and duct dampers to the desired
position. Run the unit for 10 to 15 minutes before taking
any temperature readings. The temperature rise is the
difference between the supply and return air temperatures.
NOTE: For typical duct systems, the temperature rise will fall
near the value specified in the temperature rise table (with
the blower speed at the factory recommended setting). See
Table 2 (page 11). If the measured temperature rise falls
outside the specified rise, it may be necessary to change
the blower speed. Lowering the blower speed increases
the temperature rise and a higher speed decreases the
temperature rise.
Verifying Operation of Over-Temperature Limit
Control (Field Installed Electric Heat)
To verify operation of the over-temperature limit control, make
sure the louvered control access panel is in place and that
there is power to the unit.
1. Block the return airflow to the unit by installing a close-off
plate in place of or upstream of the filter.
2. Set the thermostat above room temperature and verify the
unit operates with the correct sequence of operation. See
Operating Sequence (
page 11).
11
TROUBLESHOOTING
If the unit does not operate properly in the cooling mode,
checkthefollowing:
• Thethermostatisoperatingproperly.
• Electricalpowertotheunitisturnedon.
• Allsafetyswitchesareclosed.
• Theservicedoorsareinplace.
• Transformercircuitbreakerisreset.
If the unit does not operate properly in the heating mode,
checkthefollowing:
• Thethermostatisoperatingproperly.
• Electricalpowertotheunitisturnedon.
• Allsafetyswitchesareclosed.
• Theservicedoorsareinplace.
• Transformercircuitbreakerisreset.
REFRIGERANT CHARGING
WARNING:
If repairs make it necessary for evacuation and
charging, it should only be done by qualified,
trained personnel thoroughly familiar with this
equipment. Some local codes require licensed
installation/service personnel to service this type
of equipment. Under no circumstances should
the owner attempt to install and/or service this
equipment.
Failure to comply with this warning could result
in property damage, personal injury, or death.
The P7TQ Series packaged electric units are fully charged
at the factory and when installed accordingly, no charging
is required. The refrigerant charge can be checked and
adjusted through the service ports provided on the units.
Use only gauge lines which have a “Schrader” depression
device present to actuate the valve.
Refrigerant charging must be done by qualified personnel
familiar with safe and environmentally responsible refrigerant
handling procedures. See Unit Rating Plate for the proper
type and amount of refrigerant.
NOTE: The over-temperature limit control should function
to turn off the electric heat within approximately 1-2 minutes
(exact time depends on the efficiency of the close-off when
blocking the return air). The circulating air blowers should
continue to run when the over-temperature limit control
switch opens.
3. Remove the close-off plate immediately after the over-
temperature limit control opens. If the unit operates for
more than four minutes with no return air, set the thermostat
below room temperature, shut off power to the unit, and
replace the over-temperature limit control.
OPERATING SEQUENCE
The operating sequences for the heating, cooling, and fan
modesaredescribedbelow.Refertothewiringdiagrams:
Figure 14 (page 26), Figure 15 (page 28), Figure 16 (page
30)
, Figure 17 (page 32), Figure 18 (page 34), Figure 19
(page 36)
, Figure 20 (page 38), Figure 21 (page 40), Figure
22 (page 42)
, Figure 23 (page 44) Figure 24 (page 46), &
Figure 25 (page 48).
Cooling Mode
1. On a call for cooling the thermostat closes, applying 24
VAC to Y1, G, & Y2 if Stage 2 cooling is calling.
2. G applies 24VAC to the main circulating blower circuit.
3. Y1 & Y2 apply 24VAC through all safety switches before
energizing their respective contactors.
4. When the thermostat is satisfied the contactors are de-
energized.
5. The circulating blower motor de-energizes immediately.
Heating Mode (Optional Electric Heat)
1. On a call for heat, the thermostat closes, applying 24 VAC
to the W1 terminal and the circulating blower circuit.
2. When the thermostat is satisfied the contactors are de-
energized.
3. The circulating blower motor de-energizes immediately.
Blower Mode
1. On a call for fan operation, the thermostat applies 24 VAC
directly to the blower contactor.
2. The circulating blower is energized immediately.
Unit Fails to Operate
If the unit does not operate properly in either the heating or
coolingmode,becertaintocheckthefollowing:
1. The thermostat is operating properly.
2. Electrical power to the unit is turned on.
3. All safety switches are closed.
4. The service doors are in place.
5. Transformer circuit breaker is reset.
Table 2. Heat Rise and Range
MODEL
NUMBER
NOMINAL
RATED CFM
* TEMPERATURE RISE °F (°C)
9 KW 18 KW 30 KW 35 KW
P7TQ072-* 2550 11° F (6° C) 22° F (12° C) 37° F (21° C) 43° F (24° C)
P7TQ090-* 3150 9° F (5° C) 18° F (10° C) 30° F (17° C) 35° F (19° C)
P7TQ120-* 3450 8° F (4° C) 16° F (9° C) 27° F (15° C) 32° F (18° C)
* Temperature Rise calculation = Rise (°F) = (kW*3413) / 1.08 / Nominal CFM.
NOTE: For 208-230V electric heat kits operating @ 208 Volts, the Kw rating is derated 25%, therefore temperature rise will be lower than the
values in the table.
12
NOMINAL TONNAGE STAGE 1 CHARGE LEVEL STAGE 2 CHARGE LEVEL
6 128 Oz. N/A
7 1/2 93 Oz. 94 Oz.
10 97 Oz. 94 Oz.
NOTE: If unit is unable to operate within above guidelines and equipped with an adjustable TXV, the TXV can be adjusted (not
recommended) by turning CW to close (increase sub-cooling) and CCW to open (lower sub-cooling).
Table 3. Refrigerant Charge Table
Charging Charts & Application Notes
Thisequipment’scoolingsystemscontainrefrigerantunder
high pressure, always use safe practices when servicing the
unit. Always review the factory literature and safety warnings
prior to servicing.
All P7TQ units are shipped from the factory with the proper
amount and type of refrigerant. Always inspect the unit rating
labeltodeterminetheunit’sinformationpriortoworkingon
the system. Do not mix different refrigerants or charge the
unit with a refrigerant not listed on the unit rating label.
The charging charts are valid for a variety of indoor, return
air conditions and are most highly influenced by the outdoor
ambient temperature, outdoor fan operation and the unit
operating voltage. Before referencing the charts, always
ensure that all compressor circuits are energized and have
stable operation. As can be seen in the charging charts, the
ideal system sub-cooling can vary over the range of operation.
Always reference the charts to determine the ideal amount of
sub-cooling for a given liquid pressure. See
Figure 9, Figure
10
, & Figure 11 (page 13). Units charged to other values will
not perform at the rated unit efficiency (EER). See
Table 3.
To inspect a systems operation, using quality instruments,
match the measured liquid temperature to the units chart.
The measured liquid pressure reading should be within 3%
of the value shown for most installations. For two stage
systems, the charts are valid for both compressor stages.
Do not utilize the charts for two stage systems operating
only under a single stage call for cooling.
Do not utilize the charts in systems that do not have all the
outdoor fans energized, or have the fans cycling under a
low-ambient control. Refer to the low-ambient kit instructions
for more information, if applicable.
For systems that are operating with more than a 5% deviation,
inspect the unit for leaks first and see Note in
Table 3. Always
use safe and environmentally sound methods for refrigerant
handling. When repairing system leakages, always utilize
a nitrogen (inert) gas to protect the refrigerant system and
pressure check the repair before re-charging. Always replace
the filter-dryers when performing any repair to the refrigeration
system. After completing the repairs, evacuate the system to
350-500 microns and weight in the refrigerant to the amount
specified on the unit rating label.
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
500
520
540
560
50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125
130
Liquid Pressure (PSIG)
Liquid Temperature (Deg. F)
P7TQ-072 Charging Chart - Cooling
(Both stages operating)
High Speed
Remove refrigerant when above curve
Add refrigerant when below curve
Figure 9. P7TQ-072 Charging Chart (6-Ton)
13
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
500
520
540
560
50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125
130
Liquid Pressure (PSIG)
Liquid Temperature (Deg. F)
P7TQ-090 Charging Chart - Cooling
(Both stages operating)
Remove refrigerant when above curve
Add refrigerant when below curve
Stage 1
Stage 2
Figure 10. P7TQ-090 Charging Chart (7.5-Ton)
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
500
520
540
560
50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125
130
Liquid Pressure (PSIG)
Liquid Temperature (Deg. F)
P7TQ-120 Charging Chart - Cooling
(Both stages operating)
Add refrigerant when below curve
Remove refrigerant when above curve
Stage 2
Stage 1
Figure 11. P7TQ-120 Charging Chart (10-Ton)
14
UNIT MAINTENANCE
WARNING:
ELECTRICAL SHOCK, FIRE OR
EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical
power to furnace.
• Whenservicingcontrols,labelallwiresprior
to disconnecting. Reconnect wires correctly.
• Verifyproperoperationafterservicing.
NOTE: These maintenance instructions are primarily intended
to assist qualified technicians experienced in the proper
maintenance and operation of this appliance.
To achieve optimum performance from the air conditioner
and minimize equipment failure, it is recommended that
periodic maintenance be performed on this unit. The ability
to properly perform maintenance on this equipment requires
certain mechanical skills and tools. Please consult your dealer
for maintenance information and availability of maintenance
contracts.
Routine Maintenance
Please consult your dealer for maintenance information and
availability of maintenance contracts. At a minimum, routine
maintenanceshouldincludethefollowingitems:
CAUTION:
Use care when removing parts from this unit.
Personal injury can result from sharp metal
edges present in all equipment of sheet metal
construction.
Air Filters
WARNING:
Never operate the unit without filters in place. Dust
and lint in the return air can build up on internal
components, resulting in loss of efficiency,
equipment damage, and possible fire.
It is recommended that the air filters be inspected and cleaned
or replaced every three to four weeks using filters of like size
and kind.
Table 1 (page 5) lists the factory installed filter
sizes and quantities for each unit. NOTE: P7TQ units are
equipped with 2” pleated disposable filters.
Blower Compartment
Buildup of dirt and lint on the blower and motor can create
excessive loads on the motor resulting in higher than normal
operating temperatures and possible shortened service life.
It is recommended that the blower compartment be cleaned
monthly during heating and cooling seasons to remove any
dirt and lint that may have accumulated in the compartment
or on the blower and motor. Inspect the blower drive belt for
cracks, excessive wear and proper tension after cleaning
the compartment.
Condensate Drain & Outdoor Coil
Inspect the condensate drain and outdoor coil at the begin-
ning of each cooling season. Remove any debris. Clean the
outdoor coil and hail guard louvers (optional) as necessary
using a mild detergent and water. Rinse thoroughly with water.
Electrical
WARNING:
This unit may have more than one electrical
supply. To avoid risk of electrical shock, personal
injury, or death, disconnect all electrical power
to the unit before performing any maintenance
or service.
CAUTION:
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation.
Inspect the electrical connections for tightness at the
beginning of each heating and cooling season. Service as
necessary.
Motor / Bearing Lubrication
WARNING:
Lubrication of the motors in this unit is not
required. Do not lubricate any motor in this
product.
• Theblowerassemblyinthisunitisequippedwithtwosupport
bearings. The support bearings are sealed cartridge units
and require no further lubrication.
• Theindoorblowermotorispre-lubricatedatthefactory
and does not require additional lubrication.
• Theoutdoorfanmotorsareequippedwithpre-lubricated
sealed ball bearings. No further oiling is required for the
life of this product
15
COMPONENT FUNCTIONS
The descriptions below are various functional components that affect the operation and shutting down of this unit. Some
of these components and their locations are shown in
Figure 12. If any component on this unit must be replaced, use only
factory authorized replacement parts specified in the Replacement Parts List provided online.
High Pressure Switch - This factory installed switch is designed to de-energize the unit when excessive pressure occurs
due to abnormal conditions. Under normal conditions, the switch is closed. If the discharge pressure rises above 650 psig,
then the switch will open and de-energize the outdoor unit. The switch is a manually reset type and will remain open until
the button on top of the switch is depressed.
Over-Temperature Limit Control (Optional Electric Heat)-The over-temperature limit control acts to prevent the air
temperature leaving the unit from exceeding the maximum outlet air temperature. If the limit opens, the blower limit relay
will energize. The circulating air blower will continue to operate if the over-temperature limit control opens.
Figure 12. Location of Unit Components
Electrical Control Panel
Single Point
Electrical Connection
Compressor(s)
Fuel Line Inlet
Blower
Return Air
Supply Air
Condensate Drain
Condenser
Fans
Exhaust
Vent
Base
Rails
Electric Heat
Inspection Cover
16
FIGURES & TABLES
Top View
Figure 13. Physical Dimensions for P7TQ Units
Rear View
Corner “B”
59 3/4”
54”
Lifting Fork Pockets
Front View
Return Air
36 3/8”
Supply Air
28 3/4”
14”
12 5/8”
Corner “D”
Corner “C”
Corner “A”
Corner “B”
Bottom Power Entry
8 1/8”
11 3/8”
6 1/4”27 3/16”
Bottom
Pan
(Top View)
17
Side View
Corners C & D
Corner “D” Corner “C”
96 1/4”
103 7/8”
P7TQ With Optional Hoods Installed
40 5/8”
40 3/8”
15”
15 1/8”
43 1/8”
36”
60 1/4”
A
B
CG
Figure 13. Continued
Corner “B”
Corner “A”
13 3/4”
30 1/2”
Lifting Fork Pockets
12 5/8”
12 5/8”
5 3/16”
7 5/8”
Side View
Corners A & B
MODEL
NUMBER
UNIT
WEIGHT ‡
SHIPPING
WEIGHT
CENTER OF
GRAVITY
INCHES (MM)
CORNER WEIGHTS UNIT HEIGHT**
A B C D
HORIZONTAL
DUCT
APPLICATIONS
VERTICAL
DUCT
APPLICATIONS
LBS. KG. LBS. KG A B LBS. KG. LBS. KG. LBS. KG. LBS. KG.
P7TQ-072 1017 462 1139 517 50.5” 27.0” 232 105 362 164 302 137 199 90 54” 48.5”
P7TQ-090 1141 518 1263 574 46.5” 24.5” 291 132 346 157 298 135 249 113 54” 48.5”
P7TQ-120 1155 525 1277 580 46.5” 24.0” 275 125 347 157 319 145 246 112 54” 48.5”
**Baserails are not intended to be removed. Information provided is total unit height for horizontal duct applications or height dimension added to selected roof
curb height for vertical duct applications.
‡ Unit weight without packaging or field installed accessories.
Table 4. Center of Gravity & Unit Shipping Weights
18
Blower Performance Data
This equipment is outfitted with a belt driven blower assembly in order to accommodate a large variety of duct configurations
and airflow selections. The blower has been factory inspected for proper alignment, operation and rotational direction prior
to the drive motor being situated in the shipping position. The blower drive belt is located with these instructions and must
be installed by the service technician.
The factory standard drive installed in these units has been set to deliver 350-400 Cfm/ton at an External Static Pressure
(ESP) of 0.25-0.30 in-Wg.
Table 5 (page 19), Table 6 (page 20), Table 7 (page 21), Table 8 (page 22), Table 9 (page 23),
Table 10 (page 24), Table 11 (page 25), & Table 12 (page 25) show the full blower curves of these drive configurations
and can be utilized to easily set the adjustable motor sheave for alternate configurations. Refer to the Legend below for a
description of the table information. After a sheave setting has been made, always inspect the blower amp draw to ensure
that it is less than the service factor amps listed on the motor.
For units being placed into service configured for horizontal flow operation, make sure to note any required blower drive
belt or pulley changes.
3493
Factory Low Static Setting: Recommended operational point1017
2.07
3862
Medium Static Setting (Optional): Recommended operational point
1159
3.03
2946
Italic font Indicates an allowable setting that is not recommended for unit operation.
These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
741
0.85
Indicates a setting that is not permitted for unit operation
19
Table 5. P7TQ-072 C/D/N Series - Downflow Models
P7TQ072-C/D/N SERIES
2 HP, 2 SPEED DOWNFLOW BLOWER DATA
Factory Standard & Medium Static Drive
HIGH SPEED OPERATION
EXTERNAL
UNIT STATIC
(“ WC)
OPERATING @
230V, 460V, OR
575V
ADJUSTABLE MOTOR SHEAVE SETTING
FULLY
CLOSED
0.5 TURN
OPEN
1 TURN
OPEN
1.5 TURNS
OPEN
2 TURNS
OPEN*
2.5 TURNS
OPEN
3 TURNS
OPEN
3.5 TURNS
OPEN
4 TURNS
OPEN
4.5 TURNS
OPEN
5 TURNS
OPEN
0.1
CFM
2780
2703 2626 2538 2460 2455 2450
RPM 887 866 845 821 869 848 826
kW
1.27
1.17 1.07
1.08 1.31 1.15 0.98
0.2
CFM 2728 2640 2545 2450
2555 2330 2310 2290
RPM 907 888 867 846
895 870 849 827
kW 1.40 1.27 1.20 1.14
1.20 1.19 1.13 1.07
0.3
CFM 2720 2670 2620 2535 2450 2380 2310
2420 2170 2145 2120
RPM 978 952 926 908 889 868 847
896 871 850 828
kW 1.39 1.38 1.36 1.29 1.23 1.17
1.11
1.26 1.20 1.09 0.98
0.4
CFM 2560 2525 2490 2390 2290 2230
2460 2300
RPM 980 954 927 909 890 869
921 897
kW 1.32 1.31 1.30 1.24
1.19 1.12
1.15 1.14
0.5
CFM 2460 2355 2250 2236
2570 2460 2350
RPM 982 955 928 910
966 945 924
kW 1.25
1.22 1.21 1.21
1.33 1.26 1.19
0.6
CFM 2260
2670 2575 2488 2400 2300 2200
RPM 963
1026 1005 987 968 947 925
kW
1.23
1.52 1.46 1.33 1.21 1.11 1.01
0.7
CFM
2620 2530 2440 2335 2230 2120 2010
RPM
1048 1027 1006 988 969 948 926
kW
1.48 1.47 1.45 1.33 1.20 1.10 0.99
0.8
CFM
2510 2400 2290 2185 2080
RPM
1049 1028 1007 989 970
kW
1.42 1.36 1.29 1.20 1.11
0.9
CFM
2310 2225 2140
RPM
1051 1030 1008
kW
1.41 1.34 1.28
1.0
CFM
2210
RPM
1052
kW
1.40
LOW SPEED OPERATION - FOR REFERENCE ONLY
Low Static
0.1
CFM 1915 1828 1740 1715 1690 1619 1548 1486
RPM 657 639 620 585 550 556 561 547
kW 0.59 0.59 0.58 0.56 0.55 0.51 0.47 0.47
0.2
CFM 1680 1605 1530 1480 1430 1366 1302
RPM 658 640 621 589 556 559 562
kW 0.53 0.58 0.63 0.57 0.51 0.48 0.46
0.3
CFM 1440
RPM 659
kW 0.48
Medium Static
0.2
CFM
1920 1855 1790 1670 1550 1500 1450
RPM
647 632 616 599 582 566.5 551
kW
0.53 0.49 0.45 0.49 0.53 0.51 0.50
0.3
CFM
1910 1855 1800 1780 1760 1660 1560
RPM
701 687 672 660 648 633 617
kW
0.65 0.63 0.61 0.56 0.51 0.52 0.53
0.4
CFM
1705 1653 1600 1560 1520
RPM
703 689 675 663 650
kW
0.59 0.59 0.58 0.53 0.49
0.5
CFM
1510
RPM
705
kW
0.58
NOTES:
* Denotes Recommended Sheave Setting.
- Boldface type indicates factory recommended blower operating range.
- Values include losses for 2” standard air filters, unit casing, and dry evaporator coil.
- For 208V operation deduct approximately 0.5% from CFM shown.
- See Accessory Performance Data table for additional static pressure information.
FACTORY STANDARD DRIVE CONSISTS OF:
12” x 12” FC Blower, 2 HP / 2 Speed Motor
1VP40 Sheave, BK77 Pulley Belt & B57 Belt
MEDIUM STATIC DRIVE CONSISTS OF:
Same except uses 1VP44 Motor Sheave.
20
P7TQ-072C/D/N SERIES
2 HP, 2 SPEED, HORIZONTAL BLOWER DATA
Factory Standard & Medium Static Drive
HIGH SPEED OPERATION
EXTERNAL
UNIT STATIC
(IN WC)
OPERATING
@ 230V, 460V,
OR 575V
ADJUSTABLE MOTOR SHEAVE SETTING
FULLY
CLOSED
0.5
TURN
OPEN
1
TURN
OPEN
1.5
TURNS
OPEN
2
TURNS
OPEN
2.5
TURNS
OPEN
3
TURNS
OPEN
3.5
TURNS
OPEN
4
TURNS
OPEN
4.5
TURNS
OPEN*
5
TURNS
OPEN
0.1
CFM
RPM
kW
0.2
CFM
2800
RPM 740
kW
0.81
0.3
CFM 2700 2650 2600
RPM 765 754 742
kW 0.85 0.84 0.82
0.4
CFM 2735 2520 2460 2400
RPM 802 767 756 744
kW 0.88 0.86 0.85 0.83
0.5
CFM 2780 2525 2270 2205 2140
RPM 838 804 769 758 746
kW 0.90 0.89 0.87 0.86 0.84
0.6
CFM
2830
2685 2540 2255 1970 1880 1790
RPM 880 860 839 804.5 770 759 747
kW
0.89
0.90 0.91 0.89 0.87 0.86 0.85
0.7
CFM 2735 2600 2435 2270
RPM 904 882 862 841
kW 0.91 0.89 0.90 0.91
0.8
CFM
2805
2680 2505 2330 2140 1950
RPM 945 931 908 884 865 845
kW
0.90
0.92 0.91 0.90 0.90 0.90
0.9
CFM 2680 2545 2410 2220 2030
RPM 963 948 932 910 887
kW 0.87 0.91 0.94 0.93 0.91
1.0
CFM 2410 2265 2120
RPM 963 949 934
kW 0.87 0.91 0.95
LOW SPEED OPERATION (FOR REFERENCE ONLY)
0.1
CFM 2460 2405 2350 2278 2205 2133 2060 1955 1850 1825 1800
RPM 639 629 618 604 589 575 560 537 514 509 503
kW 0.70 0.74 0.78 0.77 0.76 0.75 0.74 0.73 0.71 0.73 0.75
0.2
CFM 2240 2200 2160 2070 1980 1890 1800 1675 1550 1500 1450
RPM 637 628 619 605 591 576 562 538 514 510 505
kW 0.71 0.74 0.78 0.77 0.76 0.75 0.75 0.73 0.72 0.74 0.76
0.3
CFM 2000 1940 1880 1775 1670 1565 1460 1318 1175
RPM 639 630 621 607 592 578 563 539 515
kW 0.72 0.74 0.76 0.76 0.76 0.75 0.75 0.74 0.73
0.4
CFM 1690 1610 1530
RPM 643 633 623
kW 0.72 0.74 0.77
NOTES:
- Boldface type indicates factory recommended blower operating range.
- Values include losses for 2” standard air filters, unit casing, and dry evaporator coil.
- For 208V operation deduct approximately 0.5% from CFM shown.
- See Accessory Performance Data table for additional static pressure information.
FACTORY DRIVE CONSISTS OF:
12” x 12” FC Blower, 2 HP / 2 Speed Motor
1VP40 Sheave, BK77 Pulley, and B57 Belt.
Table 6. P7TQ-072 C/D/N Series - Horizontal Models
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104

Mammoth P7TQ Guide d'installation

Taper
Guide d'installation

dans d''autres langues