wattstopper LENC Series Lighting Integrator Panel Enclosures Guide d'installation

Taper
Guide d'installation

Ce manuel convient également à

Wattstopper
®
Panel Enclosures
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 31198 – 03/21 rev. 1
Catalog Numbers • Les Numéros de Catalogue • Los Números de Catálogo: LENCxxS, LENCxxF
Country of Origin: Made in United States • Pays d’origine: Fabriqué en États-Unis • País de origen: Hecho en Estados Unidos
All models are BAA and TAA compliant
DESCRIPTION
LENC panel enclosures are designed specifically to work with all configurations of
LMCP panel interiors containing 8 to 48 relays. The enclosures are provided with
integral mounting studs that are configured to accept the panel interior making the
installation quick and easy. Covers are secured to the tubs with screws and have
keyhole style mounting. This allows the cover to be temporarily hung on the tub during
the construction phase of the project. All covers have hinged doors that expose only the
low voltage (Class 2) section of the panel and are equipped with key locks and two keys
each. All LENC enclosures are NEMA 1 rated.
A complete panel assembly includes:
An enclosure
A matching cover
An interior with relays/contactors and a power supply.
The enclosure can be mounted early to allow conduit installation and rough-in wiring.
Covers are designed for flush mounting or surface mounting.
Enclosures rated for 24 or 48 relay capacity have space provided at the bottom for
optional mounting plates (DMP) to accept DIN rail mounted accessories such as multi-
pole contactors and ELCU-100 Emergency Lighting Control Units. Standard LENC24
and LENC48 enclosures will accommodate up to six four pole contactors (requires DMP
mounting plate) or four ELCU-100 units (requires DMP-1EM mounting plate). LENC8-24
and LENC24-48 enclosures have additional space provided and will accommodate up
to twelve four pole contactors (requires DMP-2 mounting plate) or 12 ELCU-100 units
(requires DMP-3EM mounting plate).
Environment
Mount in indoor area
32° to 131°F (0° to 50°C)
10 to 95% relative humidity, non-condensing
15 volts/meter, 10 KHz to 2 GHz maximum RFI
Catalog # Description
LENC8S 8 relay capacity, surface mount
LENC8F 8 relay capacity, flush mount
LENC8-24S 8 relay capacity with 24 size tub, surface mount
LENC24S 24 relay capacity, surface mount
LENC24F 24 relay capacity, flush mount
LENC24-48S 24 relay capacity with 48 size tub, surface mount
LENC48S 48 relay capacity, surface mount
LENC48F 48 relay capacity, flush mount
DMP Mounting Plate, one DIN rail for up to 6 contactors
DMP-2 Mounting Plate, one DIN rail for up to 12 contactors
DMP-1EM Mounting Plate, one DIN rail with barrier for up to 4 ELCU-100s
DMP-3EM Mounting Plate, three DIN rails with barrier for up to 12 ELCU-100s
LENC MODELS AND ACCESSORIES
WARNING: MAKE SURE ALL POWER
IS OFF BEFORE WIRING. DO NOT
ENERGIZE WIRING UNTIL THE UNIT
IS FULLY ASSEMBLED. CONFORM TO ALL
APPLICABLE BUILDING AND ELECTRICAL
CODES WHEN MOUNTING THE ENCLOSURE.
2
MOUNTING AND INSTALLATION
Dimensions are shown on the following page. Be sure to allow adequate surface spacing for the covers.
Step 1 Mount the Enclosure
1. The enclosure should be level, plumb and rigidly installed with hardware sufficient to hold 100 lbs. (46 kg) minimum. The product
label should be in an upright, readable position.
2. Determine the appropriate wire entry locations. Make sure that all line and low voltage wiring entry locations are confined to the
appropriate compartments as shown in the diagram below.
3. Drill or knock out openings to bring wiring conduit into the enclosure. See the drawing below for details on 0-10V and network
wiring.
Multiple panels:
For surface mounting: Allow a minimum of 0.25” between adjacent enclosures for shoebox cover clearance.
For ush mounting: The front flange should be flush with the finished wall surface. Allow a minimum of 1.75” between adjacent
enclosures for butt alignment of flush covers.
Step 2 Install the Interior
Do not install the interior assembly until after the LMCP enclosure has been securely mounted to the wall and the conduit/wiring holes
have been drilled or knocked out.
NOTE: If this enclosure includes the optional DMP-1 Din Rail Mounting Plate (to allow for installation of EM-IN Emergency Interior
contactors), place DMP Plate over lower studs before installing the interior.
1. Place the interior in the enclosure and align the interior with the studs provided in the enclosure.
2. Attach the interior assembly to the back of the enclosure using the four sets of nuts and washers provided.
Step 3 Cover Installation
1. Drive the supplied cover mounting screws into the threaded holes until
approximately 3/8” of the thread is still exposed.
2. Hang the cover on the screws by aligning the screw heads with the
keyholes.
3. Tighten the screws to complete the installation.
4. Insert completed relay and circuit schedules and the Lighting Control Panel Interior Instructions in the plastic sleeve affixed to the
inside of the cover to complete the panel installation.
See the LMCP Installation Instructions for details on connecting the power supply and connecting the loads and line voltage to the
relays.
010V AND NETWORK WIRING
The Class 2 wire-way at the top of the LMCP panel is designed to provide separation between Class 1 wiring and BACnet/IRB network
wiring. All 0–10V wires must originate as Class 2 or be reclassified. The 0–10V wires are routed through multiple 1.5” openings with
grommets in the top of the Class 1/Class 2 barrier. The BACnet/IRB wires are routed through the wire-way.
0–10V
LMRJ Cable
LM-MSTP Cable
Line
Voltage
Wire-way
DIN-rail for
NB-ROUTER
mounting
WARNING: DO NOT INSTALL OR
REMOVE COVER WITH POWER
APPLIED TO THE LIGHTING CONTROL
PANEL. DANGER OF ELECTRIC SHOCK.
3
LENC8-24S
LENC8S
LENC8F
LENC24S
LENC24F
8.08"
35.8"
40.5"
Low voltage
section
Line voltage section
Line voltage section
16"
LENC48S
LENC48F
14"
4.94"4.94"
43.88"
(44.5” w/cover)
LENC24-48S
40.5"
Low voltage
section
Line voltage section
Line voltage section
16"
14"
4.94"
4.94"
23.34"
20.54"
43.88"
(44.5” w/cover)
8.08"
23.34"
Low voltage
section
Line voltage section
Line voltage section
16"
14"
26"
4.94"4.94"
23.88" (24” w/ cover)
31.42"
(32” w/cover)
Low
voltage
section
Line voltage section
14.5"
15.08"
(15.75” w/ cover)
13.58"
11.68"
4.82"
16.5" (16.62” w/cover)
15.08"
Line voltage section
16"
12.2" 11.68"
26"
16.34”
Low
voltage
section
23.88" (24” w/ cover)
23.88" (24” w/ cover)
23.88" (24” w/ cover)
31.42"
(32” w/cover)
3.5"
2.5”
22”21”
10”
14”
14”
14”
4.375”
6.5”
DMP2
DMP3EM
8.5”
12”
DMP1EM
DMP1
4"
5”
4.375”
18”
DIMENSIONS
Depth for all models 4.5“, with cover attached 4.67”.
NOTE: For flush mount enclosures, add 1.35” to height and 1.85” to width.
DIN RAIL MOUNTING OPTIONS
800.879.8585
www.legrand.us/wattstopper
No. 31198 – 03/21 rev. 1
© Copyright 2021 Legrand All Rights Reserved.
© Copyright 2021 Tous droits réservés Legrand.
© Copyright 2021 Legrand Todos los derechos reservados.
Wattstopper warranties its products to be free
of defects in materials and workmanship for a
period of five (5) years. There are no obligations
or liabilities on the part of Wattstopper for
consequential damages arising out of, or in
connection with, the use or performance of this
product or other indirect damages with respect
to loss of property, revenue or profit, or cost of
removal, installation or reinstallation.
Wattstopper garantit que ses produits sont
exempts de défauts de matériaux et de fabrication
pour une période de cinq (5) ans. Wattstopper
ne peut être tenu responsable de tout dommage
consécutif causé par ou lié à l’utilisation ou
à la performance de ce produit ou tout autre
dommage indirect lié à la perte de propriété, de
revenus, ou de profits, ou aux coûts d’enlèvement,
d’installation ou de réinstallation.
Wattstopper garantiza que sus productos
están libres de defectos en materiales y mano
de obra por un período de cinco (5) años. No
existen obligaciones ni responsabilidades por
parte de Wattstopper por daños consecuentes
que se deriven o estén relacionados con el
uso o el rendimiento de este producto u otros
daños indirectos con respecto a la pérdida
de propiedad, renta o ganancias, o al costo
de extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

wattstopper LENC Series Lighting Integrator Panel Enclosures Guide d'installation

Taper
Guide d'installation
Ce manuel convient également à