Legrand FS-705 PIR Low Voltage Wide-Angle Occupancy Sensor Guide d'installation

Taper
Guide d'installation
Wattstopper
®
Wide-Angle Occupancy Sensor Passive Infrared Low Voltage (V3)
Installation Instructions • Instructions d’Installation • Instrucciones de Instalación
No: 24732 – 09/16 rev. 1
Catalog Number • Numéro de Catalogue • Número de Catálogo: FS-705
Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China
SPECIFICATIONS
Power Supply ...... 24VDC from Wattstopper Class 2 Power Pack only
Current Consumption ................................................... 7mA@24VDC
Dimensions .............................. 3.15” front to back x 2.68” W x 1.77” H
............................ (80mm front to back x 68mm W x 45mm H)
Weight ..................................................................2.17 oz. (60 grams)
Temperature ranges:
Operating ....................................... 32° to 131°F (0° to +55°C)
Storage .......................................-22° to 176°F (-30° to +80°C)
Detection indicator ..................................................................Red LED
DESCRIPTION AND OPERATION
The FS-705 is a low-voltage passive infrared (PIR) occupancy sensor designed to contol lighting where wide-angle 180° coverage is
desired. It is ideally suited for use in aisleways with refrigeration systems, and in freezer cases, vending machines, and display areas.
It is designed to turn on cabinet lights when it detects people in the aisle, then turn the lights off when the aisle is vacant, after a time
delay expires. To connect to a dimming system, contact Technical Support.
It is a low voltage device used in conjunction with a Wattstopper 24VDC Class 2 power pack.
COVERAGE PATTERN
The sensor contains dual pyros and a lens providing 40 detection zones, ensuring dense coverage within the detection area. The sensor
provides true 180° horizontal and 70° vertical coverage.
13’
1’
3’
5’
(1.52m)
7’
9’
11
(3.35m)
2’4’
(1.22m)
6’8’
(2.43m)
10’12’
(3.66m)
14’
15’
(4.57m)
0
3’
13’
9’
7’
5’
(1.52m)
1’
30’ x 15’ Maximum Sensitivity
24’ x 12’ Minimum Sensitivity
Sensor
15’
(4.57m)
11
(3.35m)
15’
(4.57m)
47mm
68mm
45mm
22mm
1.77”
1.85”
2.68”
33mm
0.86”1.30”
1’
7’
6’
5’
4’
3’
2’
1’2’3’
(0.91m)
4’5’6’
(1.82m)
7’8’9’
(2.74m)
10’1112’
(3.66m)
13’14’15’
(4.57m)
M
ax im u m Se n si t iv it
y
Mi ni m um S e ns i ti vi t y
Sensor Mounting Height
Distance
0
Sensor at
7.5’ (2.286m)
Top View
Side View
2
INSTALLATION
Determine an appropriate mounting location for the FS-705. Mount the FS-705 on top of the cabinet in the center for equal coverage
on either side. Place the front edge of the sensor at the front edge of the cabinet. Secure the sensor to the top of the cabinet with self
tapping screws.
BZ‑SERIES Power Packs
Attach a BZ-SERIES power pack to a junction box through a ½ inch knock-out. Install the power pack according to instructions provided
with the unit.
Power Pack mounted inside or attached
to j-box or other suitable enclosure
protecting line voltage connections
FS-C5 RJ45 coupler if needed
FS-C1 (10’) or FS-C3 (3’) cable
FS-705 at front
edge of cabinet
Figure 1: Installing on a freezer unit
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
WIRING
For custom configurations, including connections to dimming controls and building automation systems, contact Technical Support at
1-866-588-5473.
Low Voltage Connections
Connect the low voltage wiring to the power pack as shown in the wiring diagram for the power pack you are using.
BZ‑50RC Power Pack
See Figure 2
BZ‑50 Power Pack
See Figure 3
BZ‑150 Power Pack
See Figure 4
Line Voltage Connections
1. Connect the black wire and one of the red wires to the non-switched hot.
2. Connect the white wire to the neutral.
3. Connect the other red to the switch leg.
FS-705 Sensor
Use FS-C1 (shown)
or FS-C3 cable.
120/230/277VAC, 50/60Hz, 225mA output
20A ballast or incandescent load
Motor load: 1HP@120/240VAC
Class 2 power supply
Model #:
BZ-50RC Power Pack
UL 2043 Plenum Rated
APPLIANCE
CONTROL
88T9
Line
Neutral
Load
Local OFF Switch
Feed-through
10' (3m)
White
Red
Red
Black
Figure 2: BZ‑50RC Power Pack connected to
FS‑705 using an FS‑C1 or FS‑C3 cable
3
ADJUSTMENTS
The Time Delay and PIR Sensitivity adjustments are located on the back of the FS-705 under a removable cover.
The sensors are factory preset for maximum sensitivity and a 30-second time delay.
+
=ON
,
=OFF
234
Time Delay
30 second
,,,
1 minute
+, ,
2 minutes
,+,
8 minutes
+
,,
1
Sensitivity
Minimum
Maximum
+
,
Switch Settings
TEST OCCUPANCY SENSOR
IMPORTANT: There is an initial warm-up period:
It may take up to a minute for the sensor to warm up during the initial power-up. The sensor has an “instant on” feature. This occurs
during installation or after a lengthy power failure only. As soon as power is supplied to the power pack, the lights will come ON and stay
ON for approximately 1 minute. If no movement is detected within that time, the lights will turn OFF until detection occurs. If movement
is detected during the initial 1 minute, then the lights will stay ON for whatever time has been set on the time delay.
1. Turn the time delay to minimum.
2. Move out of the sensor’s view. Lights should turn OFF after 30 seconds.
3. Walk down the aisle. When the first sensor detects motion the red LED in the sensor will flash and the first coolers lights should
turn on.
4. Proceed down the aisle, the second cooler’s sensor should detect you, the red LED in the sensor will flash and the second
cooler’s lights should turn ON.
5. This process should continue down the rest of the aisle. As you walk down the aisle, the cooler lights should progressively turn ON
prior to you walking in front of that cooler, turning on one at a time as you proceed down the aisle.
6. Repeat this process from the opposite end of the aisle. No matter which direction you approach, the system should function in this
way.
FS-705 Sensor
Blue
Red
Black
FS-C2 shielded 6” (152mm) cable with 3 flying leads at one end and a shielded RJ45 male
connector at the other. Add an FS-C5 coupler and FS-C1 or FS-C3 to extend cable.
Line
Neutral
Load
Local OFF Switch
Feed-through
Yellow
08618r1
120/230/277VAC, 50/60Hz, 225mA output
20A ballast or incandescent load
Motor load: 1HP@120/240VAC
Class 2 power supply
Model #:
BZ-50 Power Pack
UL 2043 Plenum Rated
APPLIANCE
CONTROL
88T9
Red
White
Neut.
Power Pack
Switch
Lighting
Load
Black
Hot
Red
RJ45 connection
24VDC
Sensor
White
Red
Red
Black
Figure 3: BZ‑50 Power Pack connected
to FS‑705 using an FS‑C2 adaptor
Figure 4: BZ‑150 Power Pack connected
to FS‑705 using an FS‑C2 adaptor
FS-705 Sensor
Blue
Red
Black
FS-C2 shielded 6” (152mm) cable with 3 flying leads at one end and a shielded RJ45
male connector at the other. Use FS-C5 coupler with FS-C1 or FS-C3 to extend cable.
Line
Neutral
Load
Local OFF Switch
Feed-through
Brown
Grey
Yellow
Yellow
UL 2043 Plenum Rated
APPLIANCE
CONTROL
88T9
Auto
ON
Manual
ON
120/230/277VAC, 50/60Hz, 225mA output
20A ballast or incandescent load
Motor load: 1HP@120/240VAC
Class 2 power supply
Model #:
BZ-150 Power Pack
08405r1
+24VDC
Common
Red
White
Neut.
Power Pack
Blue
Black
Red
Dry
Contact
Lighting
Load
277VAC
Black
120VAC
+12-24VDC In
Hold OFF
+12-24VDC In
Hold ON
Any 3-Wire
24VDC
Sensor
Hot
Red
Brown
Orange
Grey
Control
Momentary Switch (optional)
Low Voltage Wires
Set BZ-150
to
Auto-ON
White
Red
Red
Black
800.879.8585
www.legrand.us/wattstopper
No. 24732 – 09/16 rev. 1
© Copyright 2016 Legrand All Rights Reserved.
© Copyright 2016 Tous droits réservés Legrand.
© Copyright 2016 Legrand Todos los derechos reservados.
Wattstopper warranties its products to be free
of defects in materials and workmanship for a
period of five (5) years. There are no obligations
or liabilities on the part of Wattstopper for
consequential damages arising out of, or in
connection with, the use or performance of this
product or other indirect damages with respect
to loss of property, revenue or profit, or cost of
removal, installation or reinstallation.
Wattstopper garantit que ses produits sont
exempts de défauts de matériaux et de fabrication
pour une période de cinq (5) ans. Wattstopper
ne peut être tenu responsable de tout dommage
consécutif causé par ou lié à l’utilisation ou
à la performance de ce produit ou tout autre
dommage indirect lié à la perte de propriété, de
revenus, ou de profits, ou aux coûts d’enlèvement,
d’installation ou de réinstallation.
Wattstopper garantiza que sus productos
están libres de defectos en materiales y mano
de obra por un período de cinco (5) años. No
existen obligaciones ni responsabilidades por
parte de Wattstopper por daños consecuentes
que se deriven o estén relacionados con el
uso o el rendimiento de este producto u otros
daños indirectos con respecto a la pérdida
de propiedad, renta o ganancias, o al costo
de extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
TROUBLESHOOTING
Lights will not turn on:
Sensor LED does not ash when motion is within the coverage zone of the detector:
Is the Red LED on the power pack flashing?
If no, check circuit breaker. Check all wiring to power pack and all RJ45 connections between sensors and power pack. Test a
different sensor connected directly to the power pack.
If yes, check wiring to power pack and all RJ45 connections between sensors and power pack. The power pack LED will
continuously blink to indicate that the Over Current Mode has been activated. During an over current event, the +24VDC output
is turned off and the relay opens. Upon removal of the Over Current condition, the BZ will not attempt to restore the power for 10
seconds after an over-current event.
Sensor LED does ash when motion is within the coverage zone of the detector:
Check all wire connections and verify the load wires are tightly secured at the power pack. The power pack LED will blink once
every 5 seconds to indicate when the relay is closed.
Check the light switch.
If lights still do not turn on, call 866-588-5473 for technical support.
Lights will not turn off:
The time delay on the sensor can be set from 30 seconds to 8 minutes. Ensure that the time delay is set to the desired delay and that
there is no movement within the sensor’s view for that time period. To quickly test the unit for proper operation, set the time delay to
minimum and move out of the sensor’s view. Lights should turn off after 30 seconds.
If lights still do not turn off, disconnect the sensors from the power pack. The lights should turn off.
If the lights remain on even with nothing connected to the power pack, check the high voltage wiring of the power pack. If all of
the wiring is correct and the lights are still on, replace the power pack.
If the lights turn off with nothing connected to the power pack, check the low voltage wiring and connections.
If lights still do not turn off, call 866-588-5473 for technical support.
ORDERING INFORMATION
Catalog Number Description
FS-705 Wide-Angle PIR Sensor, 24VDC
BZ-50 Power Pack with flying leads for connecting low voltage wires
BZ-50RC Power Pack with RJ45 jack for connecting low voltage wires
BZ-150 Power Pack with flying leads for connecting low voltage wires, hold-on/hold-off inputs, plus manual or auto mode
option
FS-C1 One 10’ cable with a shielded RJ45 male connector at each end
FS-C2 One 6” (152mm) cable with 3 flying leads at one end and a shielded RJ45 male connector at the other or use
with BZ-50 or BZ-150 power packs.
FS-C3 One 3’ cable with a shielded 90° RJ45 male connector at one end and a shielded straight male RJ4 connector at
the other end, for space-limited areas
FS-C4 Shielded RJ45 splitter with female to dual female receptacles
FS-C5 Shielded RJ45 male-to-male coupler
  • Page 1 1