Simplicity 076003LP- Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation

Ce manuel convient également à

Questions?
Help is just a moment away!
Call: Residential Generator Helpline
(877) 369-9400 M-F 8-5 CT
45000 Watt
Residential Generator
System
Installation and Start-Up Manual
GEN42WN & GEN45WL
2
Thank you for purchasing this quality-built Rheem / Ruud residential generator. We are pleased that you’ve placed your
confidence in the Rheem or Ruud brand. When operated and maintained according to the instructions in the operator’s
manual, your residential generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with residential generator
systems and how to avoid them. This generator system is designed and intended only for use as an optional residential
standby system that provides an alternate source of electric power and to serve loads such as heating, refrigeration systems,
and communication systems that, when stopped during any power outage, could cause discomfort or inconvenience. Save
these instructions for future reference.
This generator system requires professional installation before use. Your installer should follow the instructions completely
Where to Find Us
You never have to look far to find support and service for your generator. Consult your Yellow Pages. There are many
Rheem and Ruud authorized service dealers who provide quality service. You can also contact customer service by phone at
(877) 369-9400 between 8:00 AM and 5:00 PM CT.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Date of Purchase
Generator
Model Number
Model Revision
Serial Number
Engine
Model Number
Serial Number
Rheem Sales Company
Randleman, NC 27317
(877) 369-9400
Copyright © 2009. All rights reserved. No part of this material
may be reproduced or transmitted in any form without the express
written permission of Rheem Sales Company.
3
Table of Contents
Important Safety Instructions........................4
Installation ....................................7
Home Owner Responsibilities ...................................7
Installing Dealer/Contractor Responsibilities ........................7
Delivery Inspection............................................7
Generator Location............................................8
Fuel Consumption ...........................................12
System Connectors ..........................................13
Grounding the Generator ......................................14
System Control Panel.........................................15
Final Installation Considerations ................................15
Initial Start-up (No Load)......................................16
Test Shutdown(s) Procedure ...................................17
Fuel Conversion .............................................18
Schematic Diagram ..........................................20
Wiring Diagram .............................................21
Operation .................................... 22
Automatic Operation Sequence .................................22
Setting Exercise Timer ........................................22
Installation Inspection ........................................22
4
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a
degree or level of hazard seriousness. A safety symbol may
be used to represent the type of hazard. The signal word
NOTICE is used to address practices not related to
personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
Save These Instructions
Fire
Toxic Fumes
Explosive Pressure
Rotating Fan Blade
Lift Hazard Read Manual
Exploding BatteryRotating Belt/Pulley
Chemical BurnAuto Start
Hot SurfaceRotating Parts
Electrical ShockExplosion
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that
it is safe for you and others. You must also make sure that
the procedure, work method or operating technique that you
choose does not render the generator system unsafe.
WARNING Running engine gives off carbon
monoxide, an odorless, colorless, poison gas.
Breathing carbon monoxide can cause headache,
fatigue, dizziness, vomiting, confusion, seizures,
nausea, fainting or death.
Operate generator ONLY outdoors.•
Install a battery operated carbon monoxide alarm near •
the bedrooms.
Keep exhaust gas from entering a confined area through •
windows, doors, ventilation intakes, or other openings.
WARNING The engine exhaust from this product
contains chemicals known to the State of California to
cause cancer, birth defects, or other reproductive harm.
WARNING Certain components in this product and
related accessories contain chemicals known to the State
of California to cause cancer, birth defects, or other
reproductive harm. Wash hands after handling.
WARNING Storage batteries give off explosive
hydrogen gas during recharging.
Slightest spark will ignite hydrogen
and cause explosion.
Battery electrolyte fluid contains
acid and is extremely caustic.
Contact with battery contents will cause severe
chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
DO NOT dispose of battery in a fire. Recycle battery.•
DO NOT allow any open flame, spark, heat, or lit cigarette •
during and for several minutes after charging a battery.
DO NOT open or mutilate the battery.•
Wear protective goggles, rubber apron, rubber boots and •
rubber gloves.
Remove watches, rings, or other metal objects.•
Use tools having insulated handles.•
5
WARNING Generator produces hazardous voltage.
Failure to properly ground generator can result in
electrocution.
Failure to isolate generator from power utility can
result in death or injury to electric utility workers
due to backfeed of electrical energy.
When using generator for backup power, notify •
utility company.
DO NOT touch bare wires or bare receptacles.•
DO NOT use generator with electrical cords which are •
worn, frayed, bare or otherwise damaged.
DO NOT handle generator or electrical cords while •
standing in water, while barefoot, or while hands or
feet are wet.
If you must work around a unit while it is operating, •
stand on an insulated dry surface to reduce the risk of
a shock hazard.
DO NOT allow unqualified persons or children to operate •
or service generator.
In case of an accident caused by electrical shock, •
immediately shut down the source of electrical power and
contact the local authorities. Avoid direct contact with
the victim.
Despite the safe design of the residential generator, •
operating this equipment imprudently, neglecting its
maintenance or being careless can cause possible
injury or death.
Remain alert at all times while working on this equipment. •
Never work on the equipment when you are physically
or mentally fatigued.
Before performing any maintenance on the generator, •
disconnect the battery cable indicated by a NEGATIVE,
NEG or (-) first. When finished, reconnect that cable last.
After your system is installed, the generator may crank •
and start without warning any time there is a power
failure. To prevent possible injury, always set the
generator’s system switch to OFF, remove the service
disconnect from the disconnect box AND remove the
15 Amp fuse BEFORE working on the equipment.
WARNING Propane and Natural Gas are extremely
flammable and explosive.
Fire or explosion can cause severe burns
or death.
Install the fuel supply system according to NFPA 37 and •
other applicable fuel-gas codes.
Before placing the generator into service, the fuel system •
lines must be properly purged and leak tested.
After the generator is installed, you should inspect the fuel •
system periodically.
NO leakage is permitted.•
DO NOT operate engine if smell of fuel is present or other •
explosive conditions exist.
DO NOT smoke around the generator. Wipe up any oil •
spills immediately. Ensure that no combustible materials
are left in the generator compartment. Keep the area near
the generator clean and free of debris.
WARNING Contact with muffler area can result in
serious burns.
Exhaust heat/gases can ignite combustibles
or structures causing a fire.
DO NOT touch hot parts and AVOID hot exhaust gases.•
Allow equipment to cool before touching.•
DO NOT install the generator closer than 5 feet (1.5m) •
from any combustibles or structures with combustible
walls having a fire resistance rating of less than 1 hour.
Keep at least minimum distances shown in • General
Location Guidelines to insure for proper generator cooling
and maintenance clearances.
It is a violation of California Public Resource Code, •
Section 4442, to use or operate the engine on any forest-
covered, brush-covered, or grass-covered land unless
the exhaust system is equipped with a spark arrester, as
defined in Section 4442, maintained in effective working
order. Other states or federal jurisdictions may have
similar laws.
Contact the original equipment manufacturer, retailer, or
dealer to obtain a spark arrester designed for the exhaust
system installed on this engine.
Replacement parts must be the same and installed in the •
same position as the original parts.
6
WARNING Moving parts can crush and cut.
Starter and other rotating parts
can entangle hands, hair, clothing,
or accessories.
NEVER operate generator without protective housings, •
covers, or guards in place.
DO NOT wear loose clothing, jewelry or anything that may •
be caught in the starter or other rotating parts.
Tie up long hair and remove jewelry.•
Before servicing, remove 15 Amp fuse from control panel •
and disconnect Negative (NEG or -) battery cable.
WARNING Hot pressurized coolant can cause severe
injury and/or property damage.
DO NOT open radiator cap when hot.•
Before servicing, allow coolant to cool.•
CAUTION Installing the 15A fuse could cause the
engine to start.
Observe that the 15 Amp fuse has been removed from the •
control panel for shipping.
DO NOT install this fuse until all plumbing and wiring has •
been completed and inspected.
CAUTION Excessively high operating speeds increase
risk of injury and damage to generator.
Excessively low speeds impose a heavy load on generator.
DO NOT tamper with governed speed. Generator supplies •
correct rated frequency and voltage when running at
governed speed.
DO NOT modify generator in any way.•
NOTICE Improper treatment of generator can damage it
and shorten its life.
Use generator only for intended uses.•
If you have questions about intended use, contact your •
authorized dealer.
Operate generator only on level surfaces.•
Adequate, unobstructed flow of cooling and ventilating air •
is critical to correct generator operation.
The access panels/doors must be installed whenever the •
unit is running.
DO NOT expose generator to excessive moisture, dust, •
dirt, or corrosive vapors.
Remain alert at all times while working on this equipment. •
Never work on the equipment when you are physically
or mentally fatigued.
DO NOT start engine with air cleaner or air cleaner •
cover removed.
DO NOT insert any objects through cooling slots.•
DO NOT use the generator or any of its parts as a step. •
Stepping on the unit can cause stress and break parts.
This may result in dangerous operating conditions from
leaking exhaust gases, fuel leakage, oil leakage, etc.
If connected devices overheat, turn them off and •
disconnect them from generator.
Shut off generator if: •
- electrical output is lost;
- equipment sparks, smokes, or emits flames;
- unit vibrates excessively.
NOTICE Exceeding generators wattage/amperage
capacity can damage generator and/or electrical devices
connected to it.
See • Essential Circuits in operator’s manual.
Start generator and let engine stabilize before connecting •
electrical loads.
WARNING Hazardous Voltage - Contact with power
lines can cause electric shock or burn.
Lifting Hazard / Heavy Object - Can cause
muscle strain or back injury.
If lifting or hoisting equipment is used, DO NOT contact •
any power lines.
DO NOT lift or move generator without assistance.•
Use lifting pipes as described in • Lifting the Generator.
The unit may shift on the lifting pipes during movement,
which can cause injury.
DO NOT lift unit by roof as damage to generator •
will occur.
7
Installation
Equipment Description
This product is intended for use as an optional residential
generator system which provides an alternate source
of electric power and to serve loads such as heating,
refrigeration systems, and communication systems that,
when stopped during any power outage, could cause
discomfort or inconvenience. This product does not qualify
for emergency standby as defined by NFPA 70 (NEC).
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
Home Owner Responsibilities
 • Readandfollowtheinstructionsgivenintheoperator’s
manual, especially the section regarding selecting
essential circuits.
 • Followaregularscheduleinmaintaining,caringfor
and using your residential generator, as specified in the
operator’s manual.
Installing Dealer/Contractor Responsibilities
 • Readandobservethesafetyrules.
 • InstallonlyanULapprovedtransferswitchthatis
compatible with the generator.
 • Readandfollowtheinstructionsgiveninthis
installation and start-up manual.
IMPORTANT: The system is equipped with a water heater
that is activated when ambient temperature is less than 80°F
AND utility power is present at the transfer switch.
If you need more information in this matter, please call
(877) 369-9400 between 8:00 AM and 5:00 PM CT.
Unpacking Precautions
The unit is shipped ready for installation on a prepared
reinforced cement slab or engineered base. Avoid
damage from dropping, bumping, collision, etc. Store and
unpack carton with the proper side up, as noted on the
shipping carton.
Delivery Inspection
After removing the carton, carefully inspect the generator for
any damage that may have occurred during shipment.
IMPORTANT: If loss or damage is noted at time of delivery,
have the person(s) making delivery note all damage on the
freight bill and affix his signature under the consignor’s
memo of loss or damage. If loss or damage is noted after
delivery, separate the damaged materials and contact the
carrier for claim procedures. Missing or damaged parts are
not warranted.
Shipment Contents
The generator system is supplied with:
 • Fully-servicedcoolantsystem
 • Fully-servicedoil/lubricatingsystem
 • Flexiblefuelhook-uphose
 • Installationandstart-upmanual
 • Operator’smanual
 • Engineoperator’smanual
 • Installationchecklist
 • Spareaccessdoorkeys
 • Spare15AmpATO-typefuse
 • Ten-polecontrolpanelconnector
 • Touchuppaint
 • RemoteLEDindicatorkit(LED/plate/screws)
Not Supplied:
 • Startingbattery(seepage16)
 • Reinforcedconcretepad
 • Connectingwireandconduit
 • Fuelsupplyvalves/plumbing
 • Variousspecialtoolsandequipment
 • Two60”lengthsof2”Schedule40pipe(NOTconduit)
 • Crane,liftingstraps,chainsorcables
 • Holepunchesfor7gasteel
 • Torquescrewdriver,5to50inch-poundrange
 • Voltage/frequencymeter
 • Ignitiontiminglight(ifconvertingfueltype)
 • AirFuelRatioMeter(O
2
Sensor and Analyzer, if
converting fuel type)
 • Dummyload(ifconvertingfueltype)
8
Generator Location
Before installing the generator, consult with the homeowner
and convey the following guidelines, which may affect the
desired location.
Install generator outdoors in an area which will not
accumulate deadly exhaust gas. DO NOT install generator
where exhaust gas could accumulate and enter inside or be
drawn into a potentially occupied building. Ensure exhaust
gas is kept away from windows, doors, ventilation intakes
or other openings that can allow exhaust gas to collect in a
confined area. Prevailing winds and air currents should be
taken into consideration when positioning generator.
General Location Guidelines
 • InstalltheunitoutdoorsONLY.
 • Placetheunitonapreparedconcreteslabthatisflat,
level, and has provisions for water drainage.
 • Installtheunitinalocationwheresumppump
discharge, rain gutter down spouts, roof run-off,
landscape irrigation, or water sprinklers will not flood
the unit or spray the enclosure and enter any air inlet or
outlet openings.
 • Installtheunitwhereitwillnotaffectorobstruct
any services (including covered, concealed and
underground), such as telephone, electric, fuel,
irrigation, air conditioning, and so forth.
 • Installtheunitwhereairinletandoutletopeningswill
not become obstructed by leaves, grass, snow, etc. If
prevailing winds will cause blowing or drifting, you may
need to construct a windbreak to protect the unit.
 • Installthegeneratorascloseaspossibletothetransfer
switch and fuel supply to reduce the length of wiring,
conduit, and piping.
IMPORTANT: Laws or local codes may regulate the distance
to the fuel supply.
The minimum (MIN) clearances from aerial view of generator
(B) to combustible (D), and non-combustible (A) materials is
shown below.
 • Thesedistancesareprovidedtogivegeneratorlocation
guidance relative ONLY to combustibles, generator
cooling, and maintenance.
 • Theminimumdistancesinthefigureareasshown.
All four sides of the generator cannot be enclosed
or restricted, even if the minimum distances are
maintained. DO NOT connect (A) and/or (D) to (E).
 • Aroofcannotbeused.
 • Exhaust(C) must not be allowed to accumulate.
A Non-Combustible material with Fire Resistant Rating of
1 hour or greater
B Residential Standby Generator
C Engine Exhaust
D Combustible Material or Structure with a Fire
Resistance Rating of less than 1 hour
E Any structure or material. DO NOT connect (A) and/or
(D) to (E)
WARNING Running engine gives off carbon
monoxide, an odorless, colorless, poison gas.
Breathing carbon monoxide can cause headache,
fatigue, dizziness, vomiting, confusion, seizures,
nausea, fainting or death.
Operate generator ONLY outdoors.•
Install a battery operated carbon monoxide alarm near •
the bedrooms.
Keep exhaust gas from entering a confined area through •
windows, doors, ventilation intakes, or other openings.
WARNING Exhaust heat/gases can ignite
combustibles or structures causing a fire.
DO NOT install the generator closer than 5 feet (1.5m) •
from any combustibles or structures with combustible
walls having a fire resistance rating of less than 1 hour.
A
B
E
D
E
C
2’
(.6m)
5’ (1.5m)
5’ (1.5m) 5’ (1.5m)
5’ (1.5m)
3’
(.9m)
2’
(.6m)
9
Concrete Slab
At the appropriate location, construct a concrete slab:
 • 28daycompressionstrengthof3000psi(200MPa)
 • Minimum5inchesthick
 • Minimum6incheswiderthanenclosureonallsides
(shown as D in figure)
 • StrengthenslabwithNo.6reinforcingbars(on
12”centers)or8ga.steelwirefabric(6”centers).
NOTE: Avoid placing reinforcement in entrance
stub-up area (B).
Attach unit to slab at four corner locations (A) with minimum
5/16”diameter(8mm)masonryanchorboltslongenoughto
secure the unit.
The fuel inlet location (C) and the exhaust opening (E) are
shown for reference.
Electrical and Fuel Inlet Locations
A through-slab power cable stub-up is preferred (see
(B) above). If stub-up’s are not used, (F) indicates the
recommended location for punching holes for attaching
power conduit. The 1 inch N.P.T. fuel inlet connector (C) is
shown for reference.
Lifting the Generator
The generator weighs more than 2,075 pounds (941 kg).
Proper tools, equipment and qualified personnel should be
used in all phases of handling and moving the generator.
Two60”lengthsof2”Schedule40pipe(G), supplied by the
installer, are required to lift the generator onto cement pad.
Insert pipes through the lifting holes (H) located near the
unit’s base.
Use a spreader bar to ensure that the chains, straps or
cables DO NOT touch the generator’s roof. Retouch any
chipped paint with supplied touch-up paint.
G
H
C
F
WARNING Hazardous Voltage - Contact with power
lines can cause electric shock or burn.
Lifting Hazard / Heavy Object - Can cause
muscle strain or back injury.
If lifting or hoisting equipment is used, DO NOT contact •
any power lines.
DO NOT lift or move generator without assistance.•
Use lifting pipes as described in • Lifting the Generator.
The unit may shift on the lifting pipes during movement,
which can cause injury.
DO NOT lift unit by roof as damage to generator •
will occur.
49”
19”
108”
92”
59”
9.5”
7”
7.38”
34.25”
10.13”
8”
Slab Top VIew
A
D
C
E
B
10
Access Ports
The residential generator is equipped with an enclosure that
has several access doors, as shown above. The doors are
named for a significant component located behind them,
as follows:
A. Fuel Inlet port (shown for reference)
B. Control Panel door (may be two doors)
C. Exhaust opening (shown for reference)
D. Coolant/Oil Fill door
E. Battery door
The Coolant Fill, Battery and Control Panel doors must be
installed whenever the unit is running to assure proper
cooling, reduce noise and for added safety.
Each residential generator is shipped with a set of identical
keys. These keys fit the locks that secure the access doors.
To open access door:
1. Insert key into lock of access door handle and turn key
one quarter turn counterclockwise.
2. Grasp door’s handle and turn one quarter turn
counterclockwise to open. Remove key.
3. Coolant Fill door is unlocked in the same manner. It can
be used for adding coolant or oil.
To close access door:
1. Close door and turn door’s handle one quarter
turn clockwise.
2. Insert key into lock of door handle and turn key one
quarter turn clockwise. Remove key.
The Gaseous Fuel System
The information below is provided to assist gaseous fuel
system technicians in planning installations. In no way
should this information be interpreted to conflict with
applicable fuel gas codes. Consult with your local fuel
supplier or Fire Marshall if questions or problems arise.
TO THE INSTALLER: Consult with the generator owner(s)
and convey any technical considerations that might
affect their installation plans before applying these
general guidelines.
The following general rules apply to gaseous fuel
system piping:
 • Thepipingshouldbeofamaterialthatconformsto
federal and local codes, rigidly mounted and protected
against vibration.
 • Pipingshouldbeprotectedfromphysicaldamage
where it passes through flower beds, shrub beds, and
other cultivated areas where damage could occur.
B
A
C
D
E
WARNING Contact with muffler and engine parts can
result in serious burns.
DO NOT touch hot parts and AVOID hot exhaust gases.•
Allow equipment to cool before touching.•
WARNING Propane and Natural Gas are extremely
flammable and explosive.
Fire or explosion can cause severe burns
or death.
LP gas is heavier than air and will settle in low areas.•
Natural gas is lighter than air and will collect in •
high areas.
The slightest spark can ignite these fuels and cause •
an explosion.
DO NOT light a cigarette or smoke.•
11
 • Installtheflexible,gaseoushose(supplied)between
the generator fuel inlet port and rigid piping to prevent
thermal expansion or contraction from causing
excessive stress on the piping material.
NOTE: Where local conditions include earthquake, tornado,
unstable ground, or flood hazards, special consideration
shall be given to increase strength and flexibility of piping
supports and connections.
 • Pipingmustbeofthecorrectsizetomaintainthe
required supply pressures and volume flow under
varying generator load conditions with all gas
appliances connected to the fuel system turned on
and operating.
 • Useapipesealantorjointcompoundapprovedfor
use with NG/LPG on all threaded fittings to reduce the
possibility of leakage.
 • Installedpipingmustbeproperlypurgedand
leak tested, in accordance with applicable codes
and standards.
Consider the following factors when planning to install the
fuel supply system:
 • Airdensityislessathighaltitudes,resultinginless
available engine power. See Power Decrease at High
Altitude or High Temperature in the operator’s manual.
 • Aminimumofoneaccessible,approvedmanualshutoff
valve shall be installed in the fuel supply line within 6 ft
(1.8 m) of the residential generator. A union or flanged
connection shall be provided downstream from this
valve to permit removal of controls.
 • BothLPvaporandnaturalgasfuelsupplypressure
at the generator’s fuel inlet port should be between
7 to 11 inches of water (in. W.C.) at full load with all
gas appliances turned on and operating.
The generator unit has been factory load tested to run on
either natural gas or LP vapor fuel. The unit can be converted
from natural gas to LP vapor or vice versa using two people
and special tools. See Fuel Conversion, later in this manual.
It is recommended that the fuel connection incorporate the
following components:
 • Aminimum10ft.(3m)sectionofgaspipebetween
the primary fuel regulator and the generator fuel inlet
connection (acts as accumulator for high block loads).
 • Amanualfuelshut-offvalvelocatedintheinteriorof
the building.
 • Amanualfuelshut-offvalvelocatedoutsidethe
building, just before the generator unit.
 • Wheretheformationofhydratesoriceisknownto
occur, piping should be protected against freezing. The
termination of hard piping should include a sediment
trap where condensate is not likely to freeze.
 • Amanometerportshouldbeprovided.
CAUTION The supplied flexible gaseous pipe is not to
be installed underground or in contact with the ground.
The entire flexible gaseous pipe must be visible for •
periodic inspection and must not be concealed within nor
contact nor run through any wall, floor, or partition.
WARNING Propane and Natural Gas are extremely
flammable and explosive.
Fire or explosion can cause severe
burns or death.
Before placing the generator into service, the fuel system •
lines must be properly purged and leak tested.
No leakage is permitted.•
12
The manometer port permits temporary installation of
a manometer to ensure that the engine receives the
correct fuel pressure to operate efficiently throughout its
operating range.
When the initial test runs are completed, the manometer
is removed and the port is plugged. A typical final fuel
connection assembly is shown here, where (A) is the fuel
supply and (B) goes to the generator.
Fuel Pipe Sizing
There are numerous on-line or otherwise-published
references for fuel pipe sizing. For example, NFPA 54 -
National Fuel Gas Code, 2006 (Item #: 320-6031-06) is a
common resource. The installer should consider the specific
gravity of gas and compensate for a nominal amount of
restriction from bends, fittings, etc. If an unusual number of
fittings, bends, or other restrictions are used, refer to federal
and local codes for guidance.
Fuel Consumption
Estimated fuel supply requirements at half and full load for
natural gas and LP vapor fuels are shown below.
Natural Gas LP Vapor
1/2 Load Full Load 1/2 Load Full Load
483 C 777 C 178 C 297 C
483,000 B 777,000 B 445,000 B 742,000 B
C = Cubic feet per hour
B = BTU’s per hour
Physical Properties LP Vapor Natural
Gas
Normal Atmospheric State Gas Gas
Boiling Point (in °F):
Initial
End
-44
-44
-259
-259
Heating Value:
BTU per gallon (Net LHV*)
BTU per gallon (gross**)
Cubic feet (gas)
83,340
91,547
2,500
63,310
1,000
Density*** 36.39 57.75
Weight† 4.24 2.65
Octane Number:
Research
Motor
110+
97
110+
* LHV (Low Heat Value) is the more realistic rating.
** Gross heat value does not consider heat lost in the form of water
during combustion.
*** Densityisgivenin“CubicFeetofGasperGallonofLiquid”.
† Weightisgivenin“PoundsperGallonofLiquid”.
B
A
13
System Connectors
Low voltage connections to signal fault contacts, transfer switch communication, remote LED and auxiliary 12VDC power are
made via a removable ten-pole connector plug. Compare this illustration with your generator to familiarize yourself with the
location of these connections. Count down to the proper pin location on the control board since visual alignment with the
decal can be misleading:
A - 10 Pole Connector Plug
B - Fault Contacts Use NO, COM and NC to hook up a
siren, light, etc. to alert you in case of a fault. Contacts
reverse state (NO goes to NC and vice versa) upon a
fault condition.
C - Transfer Switch Communication — Connect to transfer
switch control board for communication interface using
18AWG copper twisted pair wire.
D - Remote LED Output — Use this to hook up the remote
LED supplied with the generator. The remote LED will
turn on and off in a series of blinks if certain faults are
detected in the generator.
E - +12 Volt DC, .5 Amp Output — Internal auxiliary
power supply.
C
B
A
D
E
IMPORTANT:
•For45kWpoweroutputconnection,use#3/0AWGminimum300volt75°C-90°Ccopperwire,(ref.NECTable310.16,
100 ft. Use National Electric Code for correction factors and wire size calculations.)
•ForUtilityCircuitconnectionuse#14AWGminimum300volt75°C-90°Ccopperwire.
•Fortransferswitchcommunicationuse#18AWGtwistedpairconductors,nogreaterthan200ftinlength,300volt
75°C-90°C copper wire.
•Fastenonlyonewiretoeachconnectorscrew.
•Torqueconnectorplugscrewsto7in-lb(7.9Newtonmeter).
14
Generator AC Connection System
A single-phase, three-wire AC connection system is used
in the residential generator. The stator assembly consists
of a pair of stationary windings with two leads brought out
of each winding. The junction of leads T2 and T3 forms the
neutral lead, as shown schematically and as wiring diagram
below. A complete schematic and wiring diagram can be
found later in this manual.
NOTE: Neutral is not bonded to ground at generator.
Grounding the Generator
Ground the generator per applicable codes, standards and
regulations. There are two generator GND lug locations.
The one inside the alternator junction box next to the circuit
breaker is the primary lug and should suffice for most
applications. The second generator GND lug is located on the
frame below the generator circuit breaker cover and should
ONLY be used for a ground rod located at the generator, if
required by local codes. See Controls for location.
Utility Circuit Connection
“240VUtilityCircuit”leadsmustberoutedinconduit.The
“240VUtilityCircuit”leadsdeliverpowertothegenerator’s
circuit board and water heater. This power also charges
the starting battery. When power on these leads is lost, the
generator will start.
Using installer-supplied minimum 300V, 14 AWG copper
wire, connect each ten-amp fuse terminal in the alternator
junction box to the ten-amp fuse terminals in the automatic
transfer switch.
When making connections, obey wire type and torque
specifications printed on the circuit breaker and neutral/
ground connector.
Fault Detection System
The generator may have to run for long periods of time with
no operator present. For that reason, the system is equipped
with sensors that automatically shut down the generator
in the event of potentially damaging conditions, such as
low oil pressure, high temperature, over speed, and other
conditions. Refer to Fault Detection System in the Operator’s
Manual for more detailed information.
The owner will use the remote LED indicator to observe the
status of the residential generator system. The remote LED
will turn on and off in a series of blinks if certain faults are
detected in the generator system. Consult with the owner
for a convenient location. Locate the electrical box in an
area visible by the home owner such as near a garage door
opener or security control panel.
To install the remote LED indicator:
1. Push the LED through the mounting plate from the
front until it snaps in place.
IMPORTANT: The LED is polarity sensitive.
2. Using provided 10 pole connector and installer-supplied
minimum 18AWG wire, connect the remote LED to the
generator control board +LED and GND connection.
Use wire nuts to attach wire to LED leads.
3. Attach mounting plate to installer-supplied
electrical box.
10 A
10 A
240 VAC
T2
120 V
120 V
240 V
T4
T1
T3
N
G
T4
T1
Neutral
To Transfer Switch
Control
Board
Ground
Power Winding
Circuit
Breaker
Line 1
Water
Heater
Neutral
Neutral
To Transfer Switch
Utility Fuse
Connection
Line 2
Ground
15
System Control Panel
The residential generator control panel, located inside the
generator housing, is shown below.
Brief descriptions of the controls used during installation are:
A - Circuit Breaker Must be ON to supply power to the
transfer switch. Breaker enclosure includes removable
bottom panel to assist with conduit connections.
B - SET EXERCISE Used to set exercise cycle start time.
C - MANUAL OVER-RIDE Used to manually start and stop
the generator.
D - 15 Amp Fuse — Protects DC control circuits.
E - System Switch Switches modes to OFF or AUTO.
F - Digital Display Displays running time in hours or
fault codes.
See Controls in the operator’s manual for more information
System Switch
This two-position switch is the most important control on
the residential generator and is used as follows:
 • AUTO”positionisthenormaloperatingposition.If
a utility power outage is sensed, the system will start
the generator. When utility power is restored, lets the
engine stabilize internal temperatures, shuts off the
generator, and waits for the next utility power outage.
 • OFF”positionturnsoffrunninggenerator,prevents
unit from starting and resets any detected faults.
15 Amp Fuse
Protects the generator DC control circuits. If the fuse has
‘blown’ (melted open) or was removed, the engine cannot
crank or start. Replace the fuse using only an identical
ATO 15A fuse. One spare fuse is supplied with the unit.
If fuse was blown or removed, you will need to reset the
exercise timer (see Setting Exercise Timer).
Final Installation Considerations
Engine Oil
The engine is shipped from the factory pre-run and filled
with non-synthetic oil (API SL 10W-30). This allows for
system operation in a wide range of temperature and climate
conditions. Before starting the engine, check oil level and
ensure that engine is serviced as described in the engine
operator’s manual.
Coolant System
The engine is shipped from the factory filled with a
50-50 mix of automotive (Dex-Cool™ orange) anti-freeze
and water. This will provide optimum year round protection
against freezing, boiling and corrosion. The coolant system
incorporates a water heater that operates when ambient
temperature is below 80ºF AND utility power is present at the
transfer switch. Periodically check coolant level as described
in the engine manual.
A
B
C
E
D
F
NOTICE Any attempt to crank or start the engine before
it has been properly serviced with the recommended
coolant or oil will result in equipment failure.
Refer to • Maintenance in the operator’s manual and engine
manual for coolant and oil fill information.
Damage to equipment resulting from failure to follow this •
instruction will void engine and generator warranty.
16
Battery
The installer must supply and install a valve-regulated
rechargeable starting battery. The starting battery MUST
conform to the specifications shown in this chart.
Battery Specifications
Volts 12 Volt DC
Amps (MIN) 650 CCA (cold cranking amps)
Type Valve Regulated Lead Acid (VRLA)
Terminal Hardware Post
Dimensions (MAX):
Width 7.5 inches (191mm)
Length 11.25 inches (286mm)
Height 10.0 inches (254mm)
Install the battery as described in Servicing the Battery in
the Maintenance section of the operator’s manual. Always
make sure the NEGATIVE cable is connected last.
Fuel Supply System
Ensure that all fuel pipe connections are tight, secure and
without leaks.
Ensure that all gas line shutoff valves are OPEN and that
adequate fuel pressure is available whenever automatic
operation is desired.
Initial Start-up (No Load)
Before operating the generator or placing it into service,
inspect the entire installation carefully. Then begin testing the
system without any electrical loads connected, as follows:
NOTE: Unit has been set-up for NG or LP vapor operation at
the factory. Fuel conversion, if needed, must be completed
prior to performing these steps.
1. Connect an accurate AC voltmeter and a frequency
meter to check generator output at load side of
circuit breaker.
2. Set generator’s circuit breaker to its ON
(closed) position.
3. Confirm 15 Amp fuse is installed in system
control panel.
4. Set generator’s system switch to AUTO.
5. Push and hold MANUAL OVER-RIDE button on control
panel for about six seconds. Engine will start.
NOTE: When the generator is started for the very first time, it
will require that air in the gaseous fuel lines be purged. This
may take a few minutes.
6. Listen for unusual noises, vibration or other indications
of abnormal operation. Check for oil or coolant leaks
while engine runs.
7. Let engine warm up for about five minutes to allow
internal temperatures to stabilize.
8. No-load voltage should be 239 - 244 Volts, frequency
should be 59.8 - 60.2 Hz.
NOTE: If AC voltage is outside these ranges, perform the
generator adjustment, Steps 11 and 12 below.
9. Check generator output between one of the generator
connection lugs and the neutral lug, then between the
other generator connection lug and the neutral lug. In
both cases, voltage reading should be 117 - 123 Volts.
IMPORTANT: DO NOT proceed until you are certain that
generator AC voltage is correct and within the stated limits.
Generator frequency is fixed and not adjustable.
10. If voltage and frequency values are correct, proceed to
step 13.
11. Connect voltmeter as described in step 1 above.
12. While observing voltmeter, adjust alternator voltage
control (A) for 240 volts. DO NOT adjust either of the
other alternator controls.
13. Push and hold MANUAL OVER-RIDE button on control
panel until engine stops.
14. Install alternator circuit breaker enclosure cover.
UNDER-FREQ.
ADJUST
STABILITY
ADJUST
VOLTAGE
ADJUST
A
WARNING Battery posts, terminals and related
accessories contain lead and lead compounds - chemicals
known to the State of California to cause cancer and
reproductive harm. Wash hands after handling.
17
Test Shutdown(s) Procedure
The installer will test the system to verify that diagnostic
messages are correctly shown on the system control panel
digital display, as follows:
FC_1 - Low Battery
No test procedure required for this fault.
FC_2 - Low Oil Pressure
Locate wire #85 (A) connected to the oil pressure switch.
Connect an installer-supplied jumper wire to wire #85.
With the system switch in AUTO position, push and hold
MANUAL OVER-RIDE to start the generator. With the
generator running, connect other end of jumper to a good
ground location such as the engine block. The generator will
shut down and FC_2 will be displayed on the system control
panel. Remove the jumper wire. Turn the system switch to
OFF for 30 seconds to clear the fault.
FC_3 - Low Voltage
With the system switch in AUTO position, push and hold
MANUAL OVER-RIDE to start the generator. With the
generator running at no load, turn the generator circuit
breaker to OFF. The generator should shut down and
FC_3 will be displayed on the system control panel. Turn the
system switch to OFF for 30 seconds to clear the fault. Turn
the circuit breaker to ON position.
FC_4 - Engine Fails to Start
With the generator not running, turn the installer supplied
manual fuel valve to the OFF position. With the system
switch in AUTO, turn off utility power. The engine will crank,
attempting to start. After approximately a two-minute start
attempt (10 seconds of crank, 10 seconds of rest) the
generator should terminate the start attempt and FC_4 will
be displayed on the system control panel. Turn the system
switch to OFF for 30 seconds to clear the fault. Turn the
installer supplied fuel valve to the ON position.
FC_5 - Low Frequency
No test procedure required for this fault.
FC_6 - Engine Overspeed
No test procedure required for this fault.
FC_7 - High Temperature
Locate wire #95 (B) connected to the temperature switch.
Connect an installer-supplied jumper wire to wire #95.
With the system switch in AUTO position, push and hold
MANUAL OVER-RIDE to start the generator. With the
generator running, connect other end of jumper to a good
ground location such as the engine block. The generator
should shut down and display FC_7 on the system control
panel. Remove the jumper wire. Turn the system switch to
OFF for 30 seconds to clear the fault.
FC_8 - Transfer Switch Fault
(Units with ACCM II or later transfer switch only)
Verify that utility power is present at the automatic transfer
switch. With the system switch in AUTO position, carefully
remove one of the 2 Amp fuses from the transfer switch.
FC_8 will display on the system control panel. Carefully
reinstall the fuse in the transfer switch, then turn the system
switch to OFF for 30 seconds to clear the fault.
Analyze Test Results
If any test procedure above does not cause the generator
to shut down and display the indicated fault, repair the fault
condition before putting the unit into service.
A
B
18
Fuel Conversion
The unit is shipped from the factory calibrated for NG or LP
vapor operation. To convert the engine from NG to LP vapor
or from LP vapor to NG operation, follow these steps:
1. Set generator circuit breaker to OFF.
2. Set control panel system switch to OFF.
3. Remove 15 Amp fuse from system control panel.
4. Remove Zero Pressure Regulator (ZPR) tower cap (A).
The Main Adjust control is shown as (B).
5. Calibrate O
2
sensor per Analyzer manufacturer
specification. Install O
2
sensor into exhaust pipe.
NOTE: Technician supplies O
2
sensor and analyzer.
6. Attach timing light to #1 spark plug on engine (see
engine manual for diagram).
7, Re-install 15 Amp fuse in system control panel.
8. Set generator circuit breaker to ON.
9. Set control panel System switch to AUTO.
10. After purging fuel supply line, push and hold
MANUAL OVER-RIDE button on control panel for six
seconds. When engine starts, allow unit to warm up for
ten minutes under no load.
NOTE: If utility power is not connected, the generator
will start automatically.
11. Using technician-supplied timing light, locate timing
marks on crankshaft vibration dampener.
12. If timing is not within specification, loosen distributor
hold-down clamp. While observing timing indicator,
adjust distributor as listed below:
LP = 24 degrees before top dead center at no load
NG = 32 degrees before top dead center at no load
NOTE: Timing values are approved by PSI engineering.
13. Tighten distributor hold-down clamp.
14. While observing O
2
Analyzer readout, adjust zero
pressure regulator (A) and main adjustment (B) screws
to obtain stoichiometric value shown in table. Select
table value that corresponds to your O
2
Analyzer
display. The shaded line in table indicates optimum
target value.
Voltage Phi Lamda
2.40 1.000 1.000
2.45 1.012 0.988
2.50 1.024 0.977
2.55 1.036 0.966
2.60 1.048 0.955
2.65 1.060 0.944
2.70 1.071 0.933
15. Using technician-supplied load, add half load to
generator. Check and adjust (A) and (B) to achieve
target value.
16. Using technician-supplied load, add full load to
generator. Check and adjust (A) and (B) to achieve
target value.
17. Remove load and check if sensor value remained in
target area. If needed, adjust (A) and (B) to achieve
target value.
18. Add half, then full load to generator. Recheck and verify
sensor value remains in target area.
IMPORTANT: It may take several attempts to achieve the
target setting. Continue to test and adjust with engine
stabilized at no, half and full loads until target value is
achieved at all generator loads.
19. Remove load from generator. Allow generator to run
for ten minutes to stabilize internal temperatures. Turn
control panel system switch to OFF.
20. Remove 15 Amp fuse from system control panel.
21. Install the ZPR tower cap, remove O
2
sensor, and
timing light.
22. Re-install 15 Amp fuse in system control panel.
23. Set exercise timer.
24. Complete emissions statement and send with
installation checklist.
B A
WARNING Contact with muffler and engine parts can
result in serious burns.
DO NOT touch hot parts and AVOID hot exhaust gases.•
Allow equipment to cool before touching.•
19
Reserved
20
Schematic Diagram
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Simplicity 076003LP- Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation
Ce manuel convient également à