Generac 7 kW 0058880 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur
7kW Air-cooled,
Automatic Standby Generators
Owner's Manual
L
I
S
T
E
D
C
U
S
Introduction .............................................. 1
Read This Manual Thoroughly ................................................1
Safety Rules ............................................. 1
Contents ...............................................................................1
Operation and Maintenance....................................................1
How to Obtain Service ...........................................................1
Standards Index .....................................................................3
General Information ................................. 4
1.1 Unpacking/Inspection .....................................................4
1.2 Protection Systems ........................................................4
1.3 NEC Requirements .........................................................4
1.4 Emission Information......................................................4
1.5 The Generator ................................................................5
1.6 Specifications ................................................................5
1.7 System Ready LED .........................................................6
1.8 Fuel Requirements and Recommendations ......................6
1.9 Fuel Consumption ..........................................................6
1.10 Reconfiguring the Fuel System ........................................6
1.11 High Altitude Operation ...................................................7
1.12 Location .........................................................................8
1.13 Battery Requirements ...................................................10
1.14 Battery Installation ........................................................10
1.15 The Battery ..................................................................10
1.16 Battery Charger ............................................................11
Post Installation Start-up and
Adjustments ........................................... 11
2.1 Before Initial Startup .....................................................11
2.2 Check Transfer Switch Operation ..................................11
2.3 Electrical Checks ..........................................................11
2.4 Generator Tests Under Load ..........................................12
2.5 Checking Automatic Operation ......................................12
2.6 Engine Governor Adjustment ........................................13
Operation ................................................ 13
3.1 Control Panel Interface .................................................13
3.2 Automatic Transfer Operation ........................................14
3.3 Sequence of Automatic Operation .................................14
3.4 Manual Operation .........................................................15
3.5 Side Compartment .......................................................15
3.6 Protection Systems ......................................................16
3.7 Shutting the Generator Down While Under Load ............17
Maintenance ........................................... 17
4.1 Performing Scheduled Maintenance ..............................17
4.2 Fuse .............................................................................18
4.3 Checking the Engine Oil Level .......................................18
4.4 Changing the Engine Oil ................................................18
4.5 Changing the Engine Air Cleaner ...................................19
4.6 Spark Plug ...................................................................19
4.7 Battery Maintenance .....................................................19
4.8 Adjusting OHV-432 Valve Clearance ..............................20
4.9 Cooling System ............................................................20
4.10 Attention After Submersion ...........................................21
4.11 Corrosion Protection.....................................................21
4.12 Out of Service Procedure ..............................................21
4.13 Service Schedule .........................................................22
Troubleshooting ..................................... 23
5.1 Troubleshooting Guide ..................................................23
Installation Diagrams ............................ 24
Warranty ................................................. 28
MANUAL DEL PROPIETARIO .........31
MANUEL D'ENTRETIEN...................59
Table of Contents
WARNING!
California Proposition 65
Engine exhaust and some of its constituents are known to the state of California to cause cancer,
birth defects, and other reproductive harm.
WARNING!
California Proposition 65
This product contains or emits chemicals known to the state of California to cause cancer,
birth defects, and other reproductive harm.
1
INTRODUCTION
Thank you for purchasing this compact, high performance, air-cooled,
engine-driven generator. It is designed to automatically supply electrical
power to operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, composite enclosure and is
intended exclusively for outdoor installation. This generator will operate
using either vapor withdrawn liquid propane (LP) or natural gas (NG).
NOTE:
This generator is suitable for supplying typical residential loads such
as Induction Motors (sump pumps, refrigerators, air conditioners,
furnaces, etc.), Electronic Components (computer, monitor, TV, etc.),
Lighting Loads and Microwave ovens.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact the nearest Dealer
for starting, operating and servicing procedures.
The information contained herein was based on machines in production
at the time of publication. The manufacturer reserves the right to modify
this manual at any time.
SAFETY RULES
Throughout this publication, and on tags and decals affixed to the genera-
tor, DANGER, WARNING, CAUTION and NOTE blocks are used to alert
personnel to special instructions about a particular operation that may be
hazardous if performed incorrectly or carelessly. Observe them carefully.
Their definitions are as follows:
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF
NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.
Indicates a hazardous situation or action which, if not
avoided, could result in death or serious injury.
Indicates a hazardous situation or action which, if not
avoided, could result in minor or moderate injury.
NOTE:
Notes contain additional information important to a procedure
and will be found within the regular text body of this manual.
These safety warnings cannot eliminate the hazards that they
indicate. Common sense and strict compliance with the special
instructions while performing the action or service are essential to
preventing accidents.
Four commonly used safety symbols accompany the DANGER,
WARNING and CAUTION blocks. The type of information each
indicates is as follows:
This symbol points out important safety information that,
if not followed, could endanger personal safety and/or
property of others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
The operator is responsible for proper and safe use of the equipment. The
manufacturer strongly recommends that the operator read this Owner's
Manual and thoroughly understand all instructions before using this
equipment. The manufacturer also strongly recommends instructing other
users to properly start and operate the unit. This prepares them if they
need to operate the equipment in an emergency.
CONTENTS
This manual contains important instructions that should be followed
during installation and maintenance of the generator and batteries for the
model: 6 kW NG, 7 kW LP, single-cylinder OHV 432 Engine.
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to make sure
that all maintenance for safe operation is performed promptly, and to have
the equipment checked periodically by a Dealer. Normal maintenance ser-
vice and replacement of parts are the responsibility of the owner/operator
and, as such, are not considered defects in materials or workmanship
within the terms of the warranty. Individual operating habits and usage
contribute to the need for maintenance service.
Proper maintenance and care of the generator ensures a minimum number
of problems and keep operating expenses at a minimum. See a Dealer for
service aids and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, contact a Dealer for
assistance. Service technicians are factory-trained and are capable of
handling all service needs.
When contacting a Dealer about parts and service, always supply the
complete model number and serial number of the unit as given on its data
decal, which is located on the generator. See section "The Generator" for
decal sample and location.
Model No. _________________ Serial No. ______________
Introduction
AUTHORIZED SERVICE DEALER LOCATION
To locate the nearest AUTHORIZED
SERVICE DEALER, please call this number:
1-800-333-1322
or locate us on the web at:
www.generac.com
2
Study these SAFETY RULES carefully before installing, operating
or servicing this equipment. Become familiar with this Owner’s
Manual and with the unit. The generator can operate safely, effi-
ciently and reliably only if it is properly installed, operated and
maintained. Many accidents are caused by failing to follow simple
and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance
that might involve a hazard. The warnings in this manual, and on
tags and decals affixed to the unit are, therefore, not all-inclusive. If
using a procedure, work method or operating technique the manu-
facturer does not specifically recommend, ensure that it is safe for
others. Also make sure the procedure, work method or operating
technique utilized does not render the generator unsafe.
Despite the safe design of this generator,
operating this equipment imprudently,
neglecting its maintenance or being careless
can cause possible injury or death. Permit
only responsible and capable persons to
install, operate and maintain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
Parts of the generator are rotating and/or
hot during and immediately after operation.
Exercise care near running generators.
Installation must always comply with appli-
cable codes, standards, laws and regula-
tions.
A running generator gives off carbon mon-
oxide, and odorless, colorless poison gas.
Breathing in carbon monoxide can cause
headaches, fatigue, diziness, nausea, vomit-
ting, confusion, fainting, siezures or death.
GENERAL HAZARDS
For safety reasons, the manufacturer recommends that this equip-
ment be installed, serviced and repaired by a Service Dealer or other
competent, qualified electrician or installation technician who is
familiar with applicable codes, standards and regulations. The opera-
tor also must comply with all such codes, standards and regulations.
The engine exhaust fumes contain carbon monoxide, which
can be DEADLY. This dangerous gas, if breathed in sufficient
concentrations, can cause unconsciousness or even death.
Do NOT alter or add to the exhaust system or do anything that
might render the system unsafe or in noncompliance with appli-
cable codes and standards.
Install a battery operated carbon monoxide alarm indoors,
according to manufacturer's instructions/recommendations.
Adequate, unobstructed flow of cooling and ventilating air is
critical to correct generator operation. Do not alter the instal-
lation or permit even partial blockage of ventilation provisions,
as this can seriously affect safe operation of the generator. The
generator MUST be installed and operated outdoors only.
Keep hands, feet, clothing, etc., away from drive belts, fans,
and other moving or hot parts. Never remove any drive belt or
fan guard while the unit is operating.
When working on this equipment, remain alert at all times.
Never work on the equipment when physically or mentally
fatigued.
Inspect the generator regularly, and contact the nearest Dealer
for parts needing repair or replacement.
Before performing any maintenance on the generator, discon-
nect its battery cables to prevent accidental start up. Disconnect
the cable from the battery post indicated by a NEGATIVE, NEG
or (–) first, then remove the POSITIVE, POS or (+) cable. When
reconnecting the cables, connect the POSITIVE cable first, the
NEGATIVE cable last.
Never use the generator or any of its parts as a step. Stepping
on the unit can stress and break parts, and may result in dan-
gerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
EXHAUST HAZARDS
• Generator engine exhaust contains DEADLY carbon monox-
ide, an odorless, colorless poisonous gas. Breathing carbon
monoxide can cause: dizziness, throbbing temples, nausea,
muscular twitching, headache, vomiting, weakness and sleepi-
ness, inability to think clearly, fainting, unconsciousness or
even death. If you experience any carbon monoxide poisoning
symptoms, move into fresh air and immediately seek medical
attention.
Never operate the generator set inside any garage or other
enclosed area.
ELECTRICAL HAZARDS
• All generators covered by this manual produce dangerous elec-
trical voltages and can cause fatal electrical shock. Utility power
delivers extremely high and dangerous voltages to the transfer
switch as does the standby generator when it is in operation.
Avoid contact with bare wires, terminals, connections, etc.,
while the unit is running. Ensure all appropriate covers, guards
and barriers are in place, secured and/or locked before operat-
ing the generator. If work must be done around an operating
unit, stand on an insulated, dry surface to reduce shock hazard.
Do not handle any kind of electrical device while stand-
ing in water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
IMPORTANT SAFETY INSTRUCTIONS: SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation
be copied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this
equipment.
Safety Rules
3
The National Electrical Code (NEC) requires the frame and external
electrically conductive parts of the generator to be connected to
an approved earth ground. Local electrical codes also may require
proper grounding of the generator electrical system.
After installing this home standby electrical system, the genera-
tor may crank and start at any time without warning. When this
occurs, load circuits are transferred to the STANDBY (genera-
tor) power source. To prevent possible injury if such a start and
transfer occur, always set the generator’s AUTO/OFF/MANUAL
switch to its OFF position before working on equipment and
remove the 7.5A fuse from the generator control panel.
In case of accident caused by electric shock, immediately shut
down the source of electrical power. If this is not possible,
attempt to free the victim from the live conductor. AVOID DIRECT
CONTACT WITH THE VICTIM. Use a nonconducting implement,
such as a dry rope or board, to free the victim from the live
conductor. If the victim is unconscious, apply first aid and get
immediate medical help.
Never wear jewelry when working on this equipment. Jewelry
can conduct electricity resulting in electric shock, or may get
caught in moving components causing injury.
FIRE HAZARDS
For fire safety, the generator must be installed and maintained
properly. Installation must always comply with applicable
codes, standards, laws and regulations. Adhere strictly
to local, state and national electrical and building codes.
Comply with regulations the Occupational Safety and Health
Administration (OSHA) has established. Also, ensure that the
generator is installed in accordance with the manufacturer’s
instructions and recommendations. Following proper installa-
tion, do nothing that might alter a safe installation and render
the unit in noncompliance with the aforementioned codes,
standards, laws and regulations.
Keep a fire extinguisher near the generator at all times.
Extinguishers rated “ABC” by the National Fire Protection
Association are appropriate for use on the standby electric
system. Keep the extinguisher properly charged and be familiar
with its use. Consult the local fire department with any ques-
tions pertaining to fire extinguishers.
EXPLOSION HAZARDS
Do not smoke around the generator. Wipe up any fuel or oil
spills immediately. Ensure that no combustible materials are left
in the generator compartment, or on or near the generator, as
FIRE or EXPLOSION may result. Keep the area surrounding the
generator clean and free from debris.
Gaseous fluids such as natural gas and liquid propane (LP)
gas are extremely EXPLOSIVE. Install the fuel supply system
according to applicable fuel-gas codes. Before placing the
home standby electric system into service, fuel system lines
must be properly purged and leak tested according to applica-
ble code. After installation, inspect the fuel system periodically
for leaks. No leakage is permitted.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and
laws, the published information listed below may be used for
installation guidance for this equipment.
1. NFPA No. 37, STATIONARY COMBUSTION ENGINES AND
GAS TURBINES, available from the National Fire Protection
Association, 470 Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR
HEALTH CARE FACILITIES, available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE, available same as
Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD FOR
STORAGE AND HANDLING OF LIQUEFIED PETROLEUM GAS,
available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELECTRIC
CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available from the
American Insurance Association, 85 John Street, New York,
N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, available from the Food
and Energy Council, 909 University Avenue, Columbia, MO
65201.
8. ASAE EP-3634, INSTALLATION AND MAINTENANCE OF
FARM STANDBY ELECTRICAL SYSTEMS, available from the
American Society of Agricultural Engineers, 2950 Niles Road,
St. Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS
CODE, available same as Item 1.
Safety Rules
Only qualified electricians or contractors
should attempt such installations, which must
comply strictly with applicable codes, stan-
dards and regulations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for damage.
This standby generator set is ready for installation with a factory
supplied and pre-mounted base pad and has a weather protec-
tive enclosure that is intended for outdoor installation only.
This UL listed standby generator set may be packaged with
an automatic transfer switch with built in load center. Circuit
breakers for emergency circuit connections are included (if
equipped).
This UL listed, 2-pole switch is rated at 50 AC amperes at 250
volts maximum. The 50 Amp transfer switch is for indoor use
only.
If this generator is used to power electrical load
circuits normally powered by a utility power
source, it is required by code to install a trans-
fer switch. The transfer switch must effectively
isolate the electrical system from the utility
distribution system when the generator is oper-
ating (NEC 700, 701 & 702). Failure to isolate an
electrical system by such means will result in
damage to the generator and also may result in
injury or death to utility power workers due to
backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have the
person(s) making the delivery note all damage on the freight bill
or affix their signature under the consignor's memo of loss or
damage.
If a loss or damage is noted after delivery, separate the damaged
materials and contact the carrier for claim procedures.
“Concealed damage” is understood to mean damage to the con-
tents of a package that is not in evidence at the time of delivery,
but is discovered later.
To properly open the roof, press down on the center top lip and
release the latch. If pressure is not applied from the top, the roof
may appear stuck. Always verify that the side lock is unlocked
before attempting to lift the roof.
1.2 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have to run for
long periods of time with no operator present to monitor engine
conditions. For that reason, the engine is equipped with the follow-
ing systems that protect it against potentially damaging conditions:
1. Low Oil Pressure Sensor 4. Overspeed
2. High Temperature Sensor 5. RPM Sensor
3. Overcrank 6. Low Battery
There are LED's on the control panel to notify personnel that one of
these failures has occurred. There is a Status LED that illuminates
when all of the conditions described in the "Ready to Run" section
are true.
1.3 NEC REQUIREMENTS
Local code enforcement may require that AFCI’s be incorporated
into the transfer switch distribution panel. The Transfer Switch pro-
vided with this generator has a distribution panel that will accept
AFCI’s.
Siemens Part No. Q115AF - 15A or Q120AF - 20A can be obtained
from a local electrical wholesaler and will simply replace any of
the single pole circuit breakers supplied in the Transfer Switch
distribution panel.
1.4 EMISSION INFORMATION
The Environmental Protection Agency requires that this generator
complies with exhaust emission standards. This generator is certi-
fied to meet the applicable EPA emission levels. Additional infor-
mation regarding the requirements set by the EPA is as follows:
The generator is certified for use as a stationary engine for standby
power generation. Any other use may be a violation of federal and/
or local laws. It is important to follow the maintenance specifica-
tions in the "Maintenance" section to ensure that the engine com-
plies with the applicable emission standards for the duration of the
engine’s life. This engine is certified to operate on Liquid Propane
fuel and pipeline Natural Gas. The emission control system on the
generator consists of the following:
Fuel Metering System
• Carburetor/mixer assembly
• Fuel regulator
Air Induction System
• Intake pipe/manifold
• Air cleaner
• Ignition System
• Spark plug
• Ignition module
4
General Information
5
1.5 THE GENERATOR
Figure 1.1 – 7kW, Single Cylinder, LV-432 Engine (door
removed)
Exhaust
Enclosure
Base
Fuel Regulator
Battery
Fuel Inlet
Ground Lug
Oil Filter
Data Label
(see sample)
Air Filter
Circuit Breaker
Control Panel
Data label Sample
1.6 SPECIFICATIONS
1.6.1 GENERATOR
Rated Voltage ........................................................................240
Rated Maximum Load Current (Amps) at 240 Volts (LP)* .....29.2
Main Circuit Breaker ........................................................30 Amp
Transfer Switch Load Center Circuits
30A, 240V ................................................................................1
20A, 120V ..................................................................................1
15A, 120V ................................................................................5
Phase .......................................................................................1
Number of Rotor Poles ..............................................................2
Rated AC Frequency ...........................................................60 Hz
Battery Requirement ...............................Group 26R, 12 Volts and
525 CCA Minimum
Weight (unit only in lbs.) .......................................................225
Enclosure ................................................................... Composite
Normal Operating Range: This unit is tested in accordance to UL
2200 standards with an operating temperature of -20 °F (-29 °C)
to 122 °F. (50 °C). For areas where temperatures fall below 32
°F (0 °C), a cold weather kit and synthetic oil is required. When
operated above 77º F (25º C) there may be a decrease in engine
power. (Please reference the engine specifications section).
These generators are rated in accordance with UL2200, Safety
Standard for Stationary Engine Generator Assemblies; and CSA-
C22.2 No. 100-04 Standard for Motors and Generators.
* Natural Gas ratings will depend on specific fuel Btu content. Typical derates are
between 10-20% off the LP gas rating.
** Circuits to be moved must be protected by same size breaker. For example,
a 15 amp circuit in the main panel must be a 15 amp circuit in the transfer
switch.
1.6.2 ENGINE
Type of Engine ..............................................................OHV-432
Number of Cylinders .................................................................1
Rated Horsepower @ 3,600 rpm* .......................................14.8
Displacement ....................................................................432cc
Cylinder Block ................................Aluminum w/Cast Iron Sleeve
Valve Arrangement .............................................Overhead Valves
Ignition System .........................................Solid-state w/Magneto
Recommended Spark Plug .............................................RC12YC
Spark Plug Gap .........................................0.76 mm (0.030 inch)
Compression Ratio ..............................................................8.2:1
Starter ............................................................................12 VDC
Oil Capacity Including Filter........................Approx. 1.1 Qts (1.0L)
Recommended Oil Filter ......................................Part # 0H9039
Recommended Air Filter ......................................Part # 0H6104
Operating RPM ...................................................................3,600
* Engine power is subject to and limited by such factors as fuel Btu content,
ambient temperature and altitude. Engine power decreases about 3.5 percent
for each 1,000 feet above sea level; and also will decrease about 1 percent for
each 6 C (10 F) above 16 C (60 F) ambient temperature.
General Information
1.7 SYSTEM READY LED
The "System Ready LED" is illuminated when all of the following
conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the AUTO position.
2. The utility voltage supplied to the unit is sensed by the control-
ler.
3. No alarms are present, for example, low oil pressure, high
temperature, etc.
1.8 FUEL REQUIREMENTS AND
RECOMMENDATIONS
With LP gas, use only the vapor withdrawal system. This type of
system uses the vapors formed above the liquid fuel in the storage
tank.
The engine has been fitted with a field convertible fuel system. The
unit will run on natural gas or LP gas, but it has been factory set to
run on natural gas. Should the primary fuel need to be changed to
LP gas, the fuel system needs to be reconfigured. See the recon-
figuring the Fuel System section for instructions on reconfiguration
of the fuel system.
Recommended fuels should have a Btu content of at least 1,000
Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic
foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is five (5) inches to seven
(7) inches water column (0.18 to 0.25 psi); and for liquid pro-
pane, 10 inches to 12 inches of water column (0.36 to 0.43 psi).
The primary regulator for the propane supply is NOT INCLUDED
with the generator.
NOTE:
All pipe sizing, construction and layout must comply with NFPA
54 for natural gas applications and NFPA 58 for liquid propane
applications. Once the generator is installed, verify that the fuel
pressure NEVER drops below five (5) inches water column for
natural gas or 10 inches water column for liquid propane.
Prior to installation of the generator, the installer should consult
local fuel suppliers or the fire marshal to check codes and regula-
tions for proper installation. Local codes will mandate correct rout-
ing of gaseous fuel line piping around gardens, shrubs and other
landscaping to prevent any damage.
Special considerations should be given when installing the unit
where local conditions include flooding, tornados, hurricanes,
earthquakes and unstable ground for the flexibility and strength of
piping and their connections.
Use an approved pipe sealant or joint compound on all threaded
fittings.
All installed gaseous fuel piping must be purged and leak tested
prior to initial start-up in accordance with local codes, standards
and regulations.
1.9 FUEL CONSUMPTION
Unit
Nat. Gas* LP Vapor**
1/2 Load Full Load 1/2 Load Full Load
6/7 kW 85/2.41 148/4.19 0.99/3.75 1.26/4.79
Values given are approximate.
* Natural gas is in cubic feet per hour / cubic meters per hour.
** LP is in gallons per hour / liters per hour.
Verify that gas meter is capable of providing enough fuel flow to
include household appliances.
1.9.1 BTU FLOW REQUIREMENTS - NATURAL GAS
BTU flow required for each unit based on 1000 BTU per cubic foot.
6kW — 148,000 BTU/Hour
Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even
the slightest spark can ignite such fuels and
cause an explosion. No leakage of fuel is
permitted. Natural gas, which is lighter than
air, tends to collect in high areas. LP gas is
heavier than air and tends to settle in low
areas.
NOTE:
A minimum of one approved manual shut-off valve must be
installed in the gaseous fuel supply line. The valve must be
easily accessible. Local codes determine the proper location.
1.10 RECONFIGURING THE FUEL
SYSTEM
1.10.1 7 KW, 432CC ENGINE
1. Remove the generator enclosure roof by turning the four
quarter turn latches on the roof top. Push down slightly on the
latch then turn 90 degrees to release. The latch should pop up
as shown in Figure 1.2.
6
General Information
7
Figure 1.2 — Turn Latch
2. Remove the two side panels of the enclosure by lifting the
panels straight up until they are clear (Figure 1.3).
Figure 1.3 — Remove Side Panels
3. Carefully place the roof and side panels to one side.
4. Locate the fuel throttle assembly mounted to the engine
intake.
5. To change the fuel selection, remove the hose clamp and hose
from the throttle assembly (Figure 1.4).
Figure 1.4 — Remove Hose Clamp & Hose
6. Remove the Natural Gas (Larger ID) fuel jet from the fuel inlet
(Figure 1.5).
7. Obtain the fuel jet for Propane (Smaller ID that has been sup-
plied loose with the owners manual).
8. Verify that the O-ring, supplied loose with the owners manual
is installed, into the groove of the fuel jet.
9. Insert the Propane fuel jet into the end of the fuel inlet.
10. Reinstall the hose and clamp onto the fuel inlet and secure.
11. Verify the hose has not been kinked in any way.
12. The generator is now ready to run on LP Vapor fuel.
Figure 1.5 — Remove Fuel Jet
Throttle
Assembly
Fuel Jet
Fuel Inlet
O-Ring (installed)
Hose Clamp
Regulator
Hose
1.11 HIGH ALTITUDE OPERATION
The fuel system on this generator may be influenced by operation
at higher altitudes. Proper operation can be ensured by installing
an altitude kit when required. See the table below to determine
when an altitude kit is required. Operating this generator without
the proper altitude kit installed may increase the engine’s emis-
sions and decrease fuel economy and performance. Kits may be
obtained from any Dealer, and should be installed by a qualified
individual.
Unit Fuel Altitude Range* Kit Part Number
6/7 kW
LP Vapor 0- 6500 ft** Not Required
Nat. Gas
0- 2000 ft Not Required
2000 - 6500 ft** OJ7057
" Elevation above sea level
** At elevations above 6500 ft. the engine may experience
decreased performance.
General Information
Remove Clamp
and Hose
8
1.12 LOCATION
The engine exhaust fumes contain carbon
monoxide, which can be DEADLY. This dan-
gerous gas, if breathed in sufficient con-
centrations, can cause unconsciousness or
even death. This generator must be installed
properly, in strict compliance with applicable
codes and standards. Following installation,
do nothing that might render the system
unsafe or in noncompliance with such codes
and standards.
Operate the generator outdoors ONLY.
Keep exhaust gases from entering a confined
area through windows, doors, ventilation, crawl
spaces or other openings (Figure 1.9).
It is highly recommended that carbon monox-
ide detector(s) be installed indoors according
to the manufacturer's instructions/recommen-
dations.
The generator must be mounted safely per
applicable codes and the manufacturer's speci-
fications. Do NOT alter or add to the exhaust
system, or do anything that might render the
exhaust system unsafe or in noncompliance
with applicable codes and standards.
1.12.1 GENERATOR
Install the generator set, in its protective enclosure, outdoors,
where adequate cooling and ventilating air is always available
(Figure 1.6). Consider these factors:
• The installation of the generator must comply strictly with
NFPA 37, NFPA 54, NFPA 58, and NFPA 70 standards.
• Install the unit where air inlet and outlet openings will not
become obstructed by leaves, grass, snow, etc. If prevailing
winds will cause blowing or drifting, consider using a wind-
break to protect the unit.
Install the generator on high ground where water levels will not
rise and endanger it.
Allow sufficient room on all sides of the generator for mainte-
nance and servicing. This unit must be installed in accordance
with current applicable NFPA 37 and NFPA 70 standards; as
well as any other federal, state and local codes for minimum
distances from other structures. DO NOT install under wooden
decks or structures.
Install the unit where rain gutter down spouts, roof run-off,
landscape irrigation, water sprinklers or sump pump discharge
does not flood the unit or spray the enclosure, including any air
inlet or outlet openings.
Install the unit where services will not be affected or obstructed,
including concealed, underground or covered services such as
electrical, fuel, phone, air conditioning or irrigation.
Where strong prevailing winds blow from one direction, face the
generator air inlet openings to the prevailing winds.
Install the generator as close as possible to the fuel supply, to
reduce the length of piping.
• Install the generator as close as possible to the transfer switch.
REMEMBER THAT LAWS OR CODES MAY REGULATE THE
DISTANCE AND LOCATION.
The genset must be installed on a level surface. The base frame
must be level within two (2) inches all around.
Figure 1.6 – Generator Clearances
The generator is typically placed on pea gravel or crushed
stone. Check local codes if a concrete slab is required. If a
concrete base slab is required, all federal, state and local codes
should be followed. Special attention should be given to the
concrete base slab which should exceed the length and width
of the generator by a minimum of six (6) inches (0.152 meters)
on all sides.
1.12.2 NEW INSTALLATION GUIDELINES FOR
STATIONARY AIR-COOLED 7KW GENERATORS.
The National Fire Protection Association has a standard for the
installation and use of stationary combustion engines. That
standard is NFPA 37 and its requirements limit the spacing of an
enclosed generator set from a structure or wall (Figure 1.7).
NFPA 37, Section 4.1.4, Engines Located Outdoors. Engines, and
their weatherproof housings if provided, that are installed outdoors
shall be located at least 5 ft. from openings in walls and at least 5
ft. from structures having combustible walls.
Generator exhaust contains DEADLY carbon monoxide gas. This
dangerous gas can cause unconsciousness or death. Do not place
the unit near windows, doors, fresh air intakes (furnaces, etc.) or
any openings in the building or structure, including windows and
doors of an attached garage.
General Information
9
General Information
Figure 1.7 – Installation Guidelines
60 inches Minimum Distance All Around
36” if the surface has a fire resistant rating of at least one hour per NFPA 37
Existing Wall
No operable windows or openings in the wall permitted
within 5 feet from any point of the generator.
60” Minimum
60” Recommended
Minimum From Ends
Clearance from the ends and front of the generator
must be 36” minimum per NFPA 37. This would
include shrubs, trees and any kind of vegetation.
Clearance at the top should be a minimum of 60
inches from any structure, overhang or projections
from the wall. The generator should not be placed
under a deck or other structure that is closed in and
would limit or constrain air flow.
These guidelines are based upon the
requirements of NFPA 37 and the
manufacturer’s requirement for air flow
for proper operation. Local codes may
be different and more restrictive than
what is described here.
Top of Generator
Generator
NOTE:
Failure to follow these minimum clearance guidelines may result in the generator failing inspection by the local building, electrical or fire
inspector requiring the generator be reinstalled in the correct location.
10
General Information
1.12.3 TRANSFER SWITCH
The transfer switch that shipped inside the carton with the genera-
tor is enclosed in a NEMA 1 (indoor rated only) enclosure.
Install the transfer switch indoors on a firm, sturdy supporting
structure.
To prevent switch distortion, level the switch if necessary. This
can be done by placing washers between the switch enclosure
and mounting surface.
Never install the switch where water or any corrosive substance
might drip onto the enclosure.
• Protect the switch at all times against excessive moisture, dust,
dirt, lint, construction grit and corrosive vapors.
If the AUTO/OFF/MANUAL switch is not set
to its OFF position, the generator can crank
and start as soon as the battery cables are
connected. Sparking can occur at the battery
posts and cause an explosion.
1.13 BATTERY REQUIREMENTS
See the Specifications section for correct battery size and rating.
1.14 BATTERY INSTALLATION
Fill the battery with the proper electrolyte fluid if necessary and
have the battery fully charged before installing it.
Before installing and connecting the battery, complete the follow-
ing steps:
1. Set the generator's AUTO/OFF/MANUAL switch to OFF.
2. Turn off utility power supply to the transfer switch.
3. Remove the 7.5A fuse from the generator control panel.
Battery cables were factory connected at the generator (Figure
1.8). Connect cables to battery posts as follows:
4. Connect the red battery cable (from starter contactor) to the
battery post indicated by a positive, POS or (+).
5. Connect the black battery cable (from frame ground) to the
battery post indicated by a negative, NEG or (—).
6. Install the battery post covers (included).
7. Install fuse.
Figure 1.8 – Battery Cable Connections
NOTE:
Dielectric grease should be used on battery posts to aid in the
prevention of corrosion.
NOTE:
Damage will result if battery connections are made in reverse.
NOTE:
In areas where temperatures fall below 32° F (0° C) it is
required that a pad type battery heater be installed to aid in
cold weather starting.
1.15 THE BATTERY
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following
precautions are to be observed when work-
ing on batteries:
Remove the 7.5A fuse from the generator con-
trol panel.
• Remove watches, rings or other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
Do not lay tools or metal parts on top of the
battery.
Disconnect charging source prior to connecting
or disconnecting battery terminals.
Do not open or mutilate the battery.
Released electrolyte has been known to
be harmful to the skin and eyes, and to be
toxic.
The electrolyte is a dilute sulfuric acid that
is harmful to the skin and eyes. It is electri-
cally conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing.
If electrolyte contacts the skin, wash it off
immediately with water.
If electrolyte contacts the eyes, flush thorough-
ly and immediately with water and seek medical
attention.
Spilled electrolyte is to be washed down with
an acid neutralizing agent. A common practice
is to use a solution of 1 pound (500 grams)
bicarbonate of soda to 1 gallon (4 liters) of
water. The bicarbonate of soda (baking soda)
solution is to be added until the evidence of
reaction (foaming) has ceased. The resulting
liquid is to be flushed with water and the area
dried.
Lead-acid batteries present a risk of fire
because they generate hydrogen gas. The fol-
lowing procedures are to be followed:
11
• DO NOT SMOKE when near the battery.
DO NOT cause flame or spark in battery area.
Discharge static electricity from body before
touching the battery by first touching a ground-
ed metal surface.
Be sure the AUTO/OFF/MANUAL switch is
set to the OFF position before connecting
the battery cables. If the switch is set to
AUTO or MANUAL, the generator can crank
and start as soon as the battery cables are
connected.
Be sure the utility power supply is turned off
and the 7.5A fuse is removed from the gener-
ator control panel, or sparking may occur at
the battery posts as the cables are attached
and cause an explosion.
Servicing of the battery is to be performed or supervised by per-
sonnel knowledgeable of batteries and the required precautions.
Keep unauthorized personnel away from batteries.
See the Specifications section for the correct size and rating when
replacing the battery. Have these procedures performed at the
intervals specified in the “Service Schedule.” A negative ground
system is used. Battery connections are shown on the wiring dia-
grams. Make sure the battery is correctly connected and terminals
are tight. Observe battery polarity when connecting the battery to
the generator set.
1.16 BATTERY CHARGER
It operates as a trickle charger which ensures output is continually
optimized to promote maximum battery life and charging levels are
at safe conditions.
2.1 BEFORE INITIAL START-UP
NOTE:
These units have been run and tested at the factory prior to
being shipped and do not require any type of break-in.
NOTE:
This unit comes filled with oil from the factory. Check the oil
level and add the appropriate amount if necessary.
Before starting, complete the following:
1. Set the generator’s main circuit breaker to its OFF (or OPEN)
position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF
position.
3. Turn OFF all breakers on the load center of the transfer box (T1
and T2).
4. Turn OFF all loads connected to the transfer switch terminals
T1 and T2.
5. Check the engine crankcase oil level and, if necessary, fill to
the dipstick FULL mark with the recommended oil. Do not fill
above the FULL mark.
6. Check the fuel supply. Gaseous fuel lines must have been
properly purged and leak tested in accordance with applicable
fuel-gas codes. All fuel shutoff valves in the fuel supply lines
must be open.
During initial start up only, the generator may exceed the normal
number of start attempts and experience an “over crank” fault (See
the "Overcrank" section). This is due to accumulated air in the fuel
system during installation. Reset the control board and retry up to
two more times, if necessary. If unit fails to start, contact the local
dealer for assistance.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
so could damage the engine.
2.2 CHECK TRANSFER SWITCH
OPERATION
Refer to the "Manual Transfer Operation" section, of the owner’s
manual for procedures.
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned
off. Failure to turn off all power voltage sup-
plies will result in extremely hazardous and
possibly fatal electrical shock.
2.3 ELECTRICAL CHECKS
Complete electrical checks as follows:
1. Set the generator's main circuit breaker to its OFF (or OPEN)
position.
2. Set the generator's AUTO/OFF/MANUAL switch to the OFF
position.
3. Turn OFF all breakers on the load center of the transfer box (T1
and T2).
4. Turn ON the utility power supply to the transfer switch using
the means provided (such as a utility main line circuit break-
er).
The transfer switch is now electrically ener-
gized or “live.” Contact with electrically “hot”
parts will result in extremely hazardous and
possibly fatal electrical shock. Proceed with
caution.
5. Use an accurate AC voltmeter to check utility power source
voltage across transfer switch terminals N1 and N2. Nominal
line-to-line voltage should be 240 volts AC.
6. Check utility power source voltage across terminals N1 and
the transfer switch neutral lug; then across terminal N2 and
neutral. Nominal line-to-neutral voltage should be 120 volts
AC.
7. When certain that utility supply voltage is compatible with
transfer switch and load circuit ratings, turn OFF the utility
power supply to the transfer switch.
8. On the generator panel, set the Auto/Off/ Manual switch to
MANUAL. The engine should crank and start.
Post Installation Start-up and Adjustments
12
9. Let the engine warm up for about five minutes to allow inter-
nal temperatures to stabilize. Then, set the generator’s main
circuit breaker to its ON (or closed) position.
Proceed with caution! Generator power volt-
age is now supplied to the transfer switch.
Contact with live transfer switch parts will
result in dangerous and possibly fatal electri-
cal shock.
10. Connect an accurate AC voltmeter and a frequency meter
across transfer switch terminal lugs E1 and E2. Voltage
should be 240-245 at a frequency of 62-63 Hertz.
11. Connect the AC voltmeter test leads across terminal lugs E1
and neutral; then across E2 and neutral. In both cases, voltage
reading should be 120-125 volts AC.
12. Set the generator’s main circuit breaker to its OFF (or OPEN)
position. Let the engine run at no-load for a few minutes to
stabilize internal engine generator temperatures.
13. Set the generator's AUTO/OFF/MANUAL switch to OFF. The
engine should shut down.
NOTE:
It is important not to proceed until certain that generator AC
voltage and frequency are correct and within the stated limits.
2.4 GENERATOR TESTS UNDER
LOAD
To test the generator set with electrical loads applied, proceed as
follows:
1. Set generator’s main circuit breaker to its OFF (or OPEN) posi-
tion.
2. Turn OFF all breakers on the load center of the transfer box (T1
and T2).
3. Set the generator's AUTO/OFF/MANUAL switch to OFF.
4. Turn OFF the utility power supply to the transfer switch,
using the means provided (such as a utility main line circuit
breaker).
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned
off. Failure to turn off all power voltage sup-
plies will result in extremely hazardous and
possibly fatal electrical shock.
5. Manually set the transfer switch to the STANDBY position, i.e.,
load terminals connected to the generator's E1/E2 terminals.
The transfer switch operating lever should be down.
6. Set the generator's AUTO/OFF/MANUAL switch to MANUAL.
The engine should crank and start immediately.
7. Let the engine stabilize and warm up for a few minutes.
8. Set the generator’s main circuit breaker to its ON (or CLOSED)
position. Loads are now powered by the standby generator.
9. Turn ON the load center of the transfer switch (T1 and T2).
10. Connect an accurate AC voltmeter and a frequency meter
across terminal lugs E1 and E2. Voltage should be greater
than 230 volts, and frequency should be greater than 58 Hz.
11. Let the generator run at full rated load for 20-30 minutes.
Listen for unusual noises, vibration or other indications of
abnormal operation. Check for oil leaks, evidence of overheat-
ing, etc.
12. When testing under load is complete, turn OFF electrical
loads.
13. Set the generator's main circuit breaker to its OFF (or OPEN)
position.
14. Let the engine run at no-load for a few minutes.
15. Set the AUTO/OFF/MANUAL switch to OFF. The engine should
shut down.
2.5 CHECKING AUTOMATIC
OPERATION
To check the system for proper automatic operation, proceed as
follows:
1. Set generator’s main circuit breaker to its OFF (or OPEN) posi-
tion.
2. Check that the AUTO/OFF/MANUAL switch is set to OFF.
3. Turn OFF the utility power supply to the transfer switch, using
means provided (such as a utility main line circuit breaker).
4. Manually set the transfer switch to the UTILITY position, i.e.,
load terminals connected to the utility power source side.
5. Turn ON the utility power supply to the transfer switch,
using the means provided (such as a utility main line circuit
breaker).
6. Set the generator's main circuit breaker to its ON (or CLOSED)
position.
7. Set the AUTO/OFF/MANUAL switch to AUTO. The system is
now ready for automatic operation.
8. Turn OFF the utility power supply to the transfer switch.
With the AUTO/OFF/MANUAL switch at AUTO, the engine should
crank and start when the utility source power is turned OFF after a
10 second delay. After starting, the transfer switch should connect
load circuits to the standby side after a five (5) second delay. Let
the system go through its entire automatic sequence of operation.
With the generator running and loads powered by generator AC
output, turn ON the utility power supply to the transfer switch. The
following should occur:
After about 15 seconds, the switch should transfer loads back
to the utility power source.
• About one minute after re-transfer, the engine should shut
down.
Post Installation Start-up and Adjustments
13
Operation
2.6 ENGINE GOVERNOR
ADJUSTMENT
If both AC frequency and voltage are correspondingly high or low,
adjust the engine governor as follows:
The engine must be OFF to perform steps 1
and 2.
1. Loosen the governor clamp bolt (Figure 2.1).
2. Hold the governor lever at its wide open throttle position
(clockwise), and rotate the governor shaft clockwise as far
as it will go. Then, tighten the governor lever clamp bolt to 70
inch-pounds (8 N-m).
3. Start the generator; let it stabilize and warm up at no-load.
4. Connect a frequency meter across the generators AC output
leads.
5. Turn the adjust screw to obtain a frequency reading of 62.5
Hz.
Figure 2.1 — Engine Governor Adjustment Single
Cylinder Engines
3.1 CONTROL PANEL INTERFACE
3.1.1 USING THE AUTO/OFF/MANUAL SWITCH
(FIGURE 3.1)
With the switch set to AUTO, the engine may
crank and start at any time without warning.
Such automatic starting occurs when utility
power source voltage droops below a preset
level or during the normal exercise cycle. To
prevent possible injury that might be caused
by such sudden starts, always set the switch
to OFF and remove the fuses before work-
ing on or around the generator or transfer
switch. Then, place a “DO NOT OPERATE”
tag on the generator panel and on the trans-
fer switch.
1. AUTO” Position – Selecting this switch activates fully auto-
matic system operation. It also allows the unit to automatically
start and exercise the engine every seven days with the setting
of the exercise timer (see the Setting the Exercise Timer sec-
tion).
2. “OFF” Position – This switch position shuts down the engine.
This position also prevents automatic operation.
3. “MANUAL” Position – Set the switch to MANUAL to crank
and start the engine. Transfer to standby power will not occur
unless there is a utility failure.
3.1.2 SETTING THE EXERCISE TIMER
This generator is equipped with an exercise timer. Once it is set,
the generator will start and exercise every seven days, on the day
of the week and at the time of day specified. During this exercise
period, the unit runs for approximately 12 minutes and then shuts
down. Transfer of loads to the generator output does not occur
during the exercise cycle unless utility power is lost.
A switch on the control panel (see Figure 3.1) permits selection of
the day and time for the system to exercise. At the chosen time,
perform the following sequence to select the desired day and time
of day the system will exercise. Remember seasonal time changes
affect the exercise settings.
1. Verify that the AUTO/OFF/MANUAL switch is set to AUTO.
2. Press and hold the “Set Exercise” switch for several seconds.
All the red LED’s will stop flashing immediately and the gen-
erator will start.
3. The generator will start and run for approximately 12 minutes
and then shut down. The exerciser is now set to run at this
time of day each week.
Example: If the “Set Exercise” pressed on Saturday afternoon at
2:00 p.m., the generator will start and exercise for approximately
12 minutes every Saturday at 2:00 p.m.
Figure 3.1 – Generator Control Panel
SET
EXERCISE
SYSTEM READY
LOW BATTERY
LOW OIL PRESSURE
HIGH OIL TEMPERATURE
OVERSPEED
RPM SENSOR LOSS
OVERCRANK
14
Set-up Procedure
1. Ensure Utility power is supplied to the Transfer Switch.
2. Remove the 7.5A Fuse from the Control Panel.
3. Wait ten (10) seconds.
4. Install the 7.5A Fuse.
5. Set the AUTO/OFF/MANUAL switch to AUTO.
6. All the LEDs on the Control Panel will begin to flash.
7. Press and hold the SET EXERCISE button for five (5) seconds.
8. Only the System Ready LED will remain on, the rest will stop
flashing.
9. The Generator will crank, start and run for twelve (12) min-
utes. It will NOT transfer during this time unless Utility is lost.
10. At the end of the Exercise period the Generator will shut down.
NOTE:
The exerciser will only work in the AUTO mode and will not work
unless this procedure is performed. The excercise time will
need to be reset every time the 12 volt battery is disconnected
and then reconnected, and/or when the fuse is removed.
3.2 AUTOMATIC TRANSFER
OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are set to their
UTILITY position, i.e., loads connected to the utility power
source (Figure 3.1).
2. Be sure that normal UTILITY power source voltage is avail-
able to transfer switch terminal lugs N1 and N2 (Refer to the
Electrical Data section).
3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO.
4. Set the generator’s main circuit breaker to its ON (or CLOSED)
position.
With the preceding steps complete, the generator will start auto-
matically when utility source voltage drops below a preset level.
After the unit starts, loads are transferred to the standby power
source. Refer to the Sequence of Automatic Operation section.
3.3 SEQUENCE OF AUTOMATIC
OPERATION
3.3.1 UTILITY FAILURE
Initial Conditions: Generator in Auto, ready to run, load being sup-
plied by utility source. When utility fails (below 65% of nominal),
a 10 second line interrupt delay time is started. If the utility is still
not present when the timer expires, the engine will crank and start.
Once started, a five (5) second engine warm-up timer will be initi-
ated. When the warm-up timer expires, the control will transfer the
load to the generator. If the utility power is restored (above 75% of
nominal) at any time from the initiation of the engine start until the
generator is ready to accept load (5 second warm-up time has not
elapsed), the controller will complete the start cycle and run the
generator through its normal cool down cycle; however, the load
will remain on the utility source.
3.3.2 CRANKING
The system will control the cyclic cranking as follows: 16 second
crank, seven (7) second rest, 16 second crank, seven (7) second
rest followed by three (3) additional cycles of seven (7) second
cranks followed by three (3) second rests.
Choke Operation
The 432cc engines have a choke behind the air box that is auto-
matically controlled by the electronic control board.
Failure to Start
This is defined as any of the following occurrences during crank-
ing:
1. Not reaching starter dropout within the specified crank cycle.
Starter dropout is defined as four (4) cycles at 1,000 RPM.
2. Reaching starter dropout, but then not reaching 2200 RPM
within 15 seconds. In this case the control board will go into
a rest cycle for seven (7) seconds, then continue the rest of
the crank cycle.
During a rest cycle the start and fuel outputs are de-energized and
the magneto output is shorted to ground.
Cranking Conditions
The following notes apply during cranking cycle.
1. Starter motor will not engage within five (5) seconds of the
engine shutting down.
2. The fuel output will not be energized with the starter.
3. The starter and magneto outputs will be energized together.
4. Once the starter is energized the control board will begin look-
ing for engine rotation. If it does not see an RPM signal within
three (3) seconds it will shut down and latch out on RPM
sensor loss.
5. Once the control board sees an RPM signal, it will energize the
fuel solenoid and continue the crank sequence.
6. Starter motor will disengage when speed reaches starter
dropout.
7. If the generator does not reach 2200 RPM within 15 seconds,
re-crank cycle will occur.
8. If engine stops turning between starter dropout and 2200
RPM, the board will go into a rest cycle for seven (7) seconds
then re-crank (if additional crank cycles exist).
9. Once started, the generator will wait for a hold-off period
before starting to monitor oil pressure and oil temperature
(refer to the Alarm Messages section for hold-off times).
10. During Manual start cranking, if the Mode switch is moved
from the Manual position, the cranking stops immediately.
11. During Auto mode cranking, if the Utility returns, the cranking
cycle does NOT abort but continues until complete. Once the
engine starts, it will run for one (1) minute, then shut down.
Operation
15
3.3.3 LOAD TRANSFER
The transfer of load when the generator is running is dependent
upon the operating mode as follows:
1. Manual
Will not transfer to generator if utility is present.
Will transfer to generator if utility fails (below 65% of nominal for
10 consecutive seconds.
Will transfer back when utility returns for 15 consecutive sec-
onds. The engine will continue to run until removed from the
Manual mode.
2. Auto
Will start and run if Utility fails for 10 consecutive seconds.
Will start a five (5) second engine warm-up timer.
Will not transfer if utility subsequently returns.
Will transfer to generator if utility is still not present.
• Will transfer back to utility once utility returns (above 75% of
nominal) for 15 seconds.
Will transfer back to utility if the generator is shut down for any
reason (such as the switch is in the OFF position or a shutdown
alarm.
After transfer, will shut down engine after one (1) minute cool-
down time.
3. Exercise
Will not exercise if generator is already running in either Auto or
Manual mode.
During exercise, the controller will only transfer if utility fails
during exercise for 10 seconds, and will switch to Auto mode.
3.3.4 UTILITY RESTORED
Initial Condition: Generator supplying power to customer load.
When the utility returns (above 75% of nominal), a 15 second
return to utility timer will start. At the completion of this timer, if
the utility supply is still present and acceptable, the control will
transfer the load back to the utility and run the engine through a
one (1) minute cool down period and then shut down. If utility fails
for three (3) seconds during this cool down period, the control
will transfer load back to the generator and continue to run while
monitoring for utility to return.
3.4 MANUAL OPERATION
This transfer switch is suitable for manual transfer under load
providing the dead front cover is in place.
Manual operation must be checked BEFORE the transfer switch
is operated electrically. To check manual operation, proceed as
follows:
1. Turn the generator’s AUTO/OFF/MANUAL switch to OFF.
2. Turn OFF both UTILITY (service disconnect breaker) and the
main line circuit breaker on the generator.
3. Note position of the 2 switches below the transfer switch
operator.
Utility supply switch (left side) ON and Generator supply
switch (right side) OFF – LOAD terminals are connected to
the Utility.
Utility supply switch (left side) OFF and Generator supply
switch (right side) ON – LOAD terminals are connected to the
Generator.
3.4.1 CLOSE TO UTILITY SOURCE SIDE
Before proceeding, verify the position of the transfer mechanism
by observing the position of 50A, 2-pole switches.
If the Utility Supply switch (left side) is ON, no further action is
required.
If not, move the Utility Supply switch handle to the ON position.
Note: the Generator Supply switch handle should move to the OFF
position.
The customer load is now connected to the Utility supply.
3.4.2 CLOSE TO GENERATOR SOURCE SIDE
Before proceeding, verify the position of the transfer mechanism
by observing the position of 50A, 2-pole switches.
If the Generator Supply switch (right side) is ON, no further action
is required.
If not, move the Generator Supply switch handle to the ON posi-
tion. Note: the Utility Supply switch handle should move to the OFF
position.
The customer load is now connected to the Generator supply.
3.4.3 RETURN TO UTILITY SOURCE SIDE
Move the Utility Supply switch handle to the ON position. Note: the
Generator Supply switch handle should move to the OFF position.
The customer load is now connected to the Utility supply.
3.5 SIDE COMPARTMENT
(FIGURES 3.2 & 3.3)
Local codes may require this compartment to be locked. A hasp is
provided so the owner can secure the compartment with their own
padlock. Check local codes in the area.
3.5.1 MAIN CIRCUIT BREAKER
This is a 2-pole breaker rated according to the Specifications sec-
tion.
Figure 3.2 – Side Compartment
Operation
16
Figure 3.3 – Open Side Compartment
3.6 PROTECTION SYSTEMS
3.6.1 ALARMS
Low Oil Pressure (Shutdown Alarm)
A five (5) second delay on start-up and eight (8) second delay
once the engine is running.
This switch (Figure 3.4) has normally closed contacts that are
held open by engine oil pressure during operation. Should the oil
pressure drop below the five (5) PSI range, switch contacts close
and the engine shuts down. The unit should not be restarted until
oil level is verified.
High Oil Temperature (Shutdown Alarm – Auto Reset)
A 10 second delay on start-up and one (1) second delay before
shutdown. Auto reset when the condition clears and restart the
engine if a valid start signal is still present.
This switch’s contacts (Figure 3.4) close if the temperature should
exceed approximately 124° C (255° F), initiating an engine shut-
down. Once the oil temperature drops to a safe level the switch’s
contacts open again.
Over Crank (Shutdown Alarm)
This occurs if the engine has not started within the specified crank
cycle. (See "Cranking" section.)
Over Speed (Shutdown Alarm)
4320 RPM for three (3) seconds or 4500 RPM immediately. This
feature protects the generator from damage by shutting it down
if it happens to run faster than the preset limit. This protection
also prevents the generator from supplying an output that could
potentially damage appliances connected to the generator circuit.
Contact the nearest Dealer if this failure occurs.
Figure 3.4 – Low Oil Pressure and
High Temperature Switches
RPM Sensor Loss (Shutdown Alarm)
During cranking, if the Control Board does not see a valid RPM
signal within three (3) seconds, it will shut down and lock out on
RPM sensor loss. While engine is running, if RPM signal is lost for
two (2) seconds the Control Board will shut the engine down, wait
15 seconds, then re-crank the engine. If no RPM signal is detected
within the first three (3) seconds of cranking, the Control Board
will shut the engine down and latch out on RPM sensor loss. If the
RPM signal is detected, the engine will start and run normally. If
the RPM signal is subsequently lost again, the Control Board will
try one more re-crank attempt before latching out and displaying
the RPM sensor failure message.
Clear Alarms
Clear alarms by setting the AUTO/OFF/MANUAL switch to the OFF
position.
3.6.2 WARNINGS
Second Priority (Non-latching) Displayed on the control panel.
Warnings automatically clear when the monitored condition goes
away. Warnings cannot cause shutdowns.
Low Battery
The Control Board monitors battery voltage and illuminates an
LED warning if the battery voltage falls below 11.9 volts for one
(1) minute. Warning is automatically cleared if the battery voltage
rises above 12.4 volts. Battery voltage is not monitored during the
crank cycle.
3.6.3 PANEL ORIENTATION
When replacing the panels after installation or maintenance, the
orientation of each panel is critical to proper cooling and operation
of the generator. Slide each panel into the corner post as identified
in Figure 3.5. Note the decals on each panel for the correct place-
ment, including the roof.
Operation
17
Figure 3.5 — Panel Location
BACKTOP
TOP
BACK
BACK
BACK
BA
C
K
TO
P
TO
P
B
A
CK
3.7 SHUTTING THE GENERATOR
DOWN WHILE UNDER LOAD
To safely stop and start a loaded generator follow these steps.
ISOLATE THE MAIN SERVICE DISTRIBUTION PANEL
1. At the main service distribution panel, open (turn off) the main
service entrance breaker.
STOPPING THE GENERATOR
1. Turn the Main Circuit Breaker off (Figure 3.6).
2. Allow the generator to run for 1 minute without load to cool
down.
Figure 3.6 – Open Side Compartment
3. Turn the Auto/Off/Manual switch to the Off position (Figure
3.7).
4. If the generator will be left off for longer than 1 hour without
utility present remove the 7.5 Amp Main Fuse from the control
panel (Figure 3.7). This will prevent the control panel from
running down the battery.
STARTING THE GENERATOR
1. If the Main Fuse was removed, replace the fuse.
2. Turn the Auto/Off/Manual switch to the Auto position. After a
short delay the generator will start.
3. Allow the generator to run for 15 seconds to allow the engine
to warm up.
4. Turn on the Main Circuit Breaker.
Figure 3.7 – Generator Control Panel
SET
EXERCISE
SYSTEM READY
LOW BATTERY
LOW OIL PRESSURE
HIGH OIL TEMPERATURE
OVERSPEED
RPM SENSOR LOSS
OVERCRANK
REPOWER THE MAIN SERVICE DISTRIBUTION PANEL
1. At the main service distribution panel, close (turn on) the main
service entrance breaker.
This method will ensure proper transfer between generator and
utility in the event that utility returns while the generator is shut
off.
4.1 PERFORMING SCHEDULED
MAINTENANCE
It is important to perform service as specified in the Maintenance
Schedule for proper generator operation, and to ensure that the
generator complies with the applicable emission standards for the
duration of its useful life. Service and repairs may be performed
by any capable person or repair shop. Additionally, emissions criti-
cal maintenance must be performed as scheduled in order for the
Emissions Warranty to be valid. Emissions critical maintenance
consists of servicing the air filter and spark plugs in accordance
with the Maintenance Schedule.
Maintenance
18
4.2 FUSE
The 7.5 amp fuse on the control panel protects the DC control
circuit against overload (Figures 3.1 and 3.2). This fuse is wired
in series with the battery output lead to the panel. If this fuse ele-
ment has melted open, the engine will not be able to crank or start.
Replace this fuse using only an identical 7.5 amp replacement
fuse. Whenever the fuse is removed or replaced, the exercise timer
needs to be reset.
4.3 CHECKING THE ENGINE OIL
LEVEL
For oil capacities, see the Specifications section. For engine oil
recommendations, see the Engine Oil Recommendations section.
When power outages necessitate running the generator for extend-
ed periods of time, the oil level should be checked daily.
To check the engine oil level, proceed as follows (Figures 4.1):
1. If the generator is running during a utility outage, first turn OFF
all associated loads running in the residence. Second, turn the
generator's main circuit breaker to the OFF position.
2. Move the AUTO/OFF/MANUAL switch to the OFF position.
3. Remove the dipstick and wipe it dry with a clean cloth.
4. Completely insert the dipstick; then, remove it again. The oil
level should be at the dipstick “Full” mark. If necessary, add
oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL
MARK.
5. Install the dipstick.
6. Reset the AUTO/OFF/MANUAL switch to its original position.
7. If the generator was running during a utility outage, first turn
the generator's main circuit breaker back to the ON position.
Second, turn ON needed loads in the residence.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
Figure 4.1 — Oil Dipstick and Fill
4.4 CHANGING THE ENGINE OIL
Hot oil may cause burns. Allow engine to
cool before draining oil. Avoid prolonged
or repeated skin exposure with used oil.
Thoroughly wash exposed areas with soap.
4.4.1 OIL CHANGE INTERVALS
See the "Service Schedule" section.
4.4.2 ENGINE OIL RECOMMENDATIONS
All oil should meet minimum American Petroleum Institute (API)
Service Class SJ, SL or better. Use no special additives. Select
the oil's viscosity grade according to the expected operating tem-
perature.
• SAE 30 Above 32° F
• 10W-30 Between 40° F and -10° F
• Synthetic 5W-30 10° F and below
SAE 30
SA E 3 0
Synthetic 5W-30
Sy nth et ic 5W- 30
10W-30
10 W-3 0
Any attempt to crank or start the engine
before it has been properly serviced with the
recommended oil may result in an engine
failure.
4.4.3 OIL & OIL FILTER CHANGE PROCEDURE
To change the oil, proceed as follows:
1. Start the engine by moving the AUTO/OFF/MANUAL switch to
MANUAL and run until it is thoroughly warmed up. Then shut
OFF the engine by moving the switch to the OFF position.
2. Immediately after the engine shuts OFF, pull the oil drain hose
(Figure 4.1) free of its zip-tie. Remove the cap from the hose
and drain the oil into a suitable container.
3. After the oil has drained, replace the cap onto the end of the
oil drain hose. Retain the hose in the zip-tie when finished.
Change the engine oil filter as follows:
1. With the oil drained, remove the old oil filter by turning it
counterclockwise.
2. Apply a light coating of clean engine oil to the gasket of the
new filter. See the Specifications section for recommended
filter.
Maintenance
Oil Dipstick
and Fill
Oil Drain
Hose
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88

Generac 7 kW 0058880 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur