WHAT TO DO IF YOU SMELL GAS
Open Windows
DO NOT try to light any appliance.
DO NOT use electrical switches.
DO NOT use any telephone in your house. Immediately call your local gas supplier from a location remote from
the leak. Follow the gas supplier’s instructions.
Do not touch any electrical switch; do not use any phone in your building.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
If you cannot reach your gas supplier, call the Fire Department.
FOR YOUR SAFETY:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
ENERCO Group, Inc., 4560 W. 160TH ST., CLEVELAND, OHIO 44135 • 866-447-2194
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause
property damage, injury, or death. Read the installation, operating and maintenance instructions
thoroughly before installing or servicing this equipment
OPERATING INSTRUCTIONS
AND OWNER’S MANUAL
READ INSTRUCTIONS CAREFULLY: Read and follow all instructions.
Place instructions in a safe place for future reference. Do not allow anyone who has
not read these instructions to assemble, light, adjust or operate the heater.
Model #
2STG
ER
LANGUAGES INCLUDED
•ENGLISH
•FRENCH
•SPANISH
Heatstar ER2STG
Gas-Fired Low-Intensity Infrared Heaters Approved
For Commercial Applications
ER2STG 60-100
ER2STG 80-125
ER2STG 125-175
2
Enerco | Heatstar ER2STG Tube Series Heater Operating Instructions and Owner’s Manual
Installer Responsibility
All heaters and associated gas piping should be installed in
accordance with applicable specifications and this installation
made only by firms (or individuals) well qualified in this type of
work. Consult local building inspectors, Fire Marshals or your
local Enerco Group, Inc Factory Representative for guidance.
Heatstar ER2STG heaters are installed on the basis of
information given in a layout drawing, which together with the
cited codes and regulations, comprise the basic information
needed to complete the installation. The installer must
furnish all needed material that is not furnished as standard
equipment, and it is his responsibility to see that such materials,
as well as the installation methods he uses result in a job that is
workmanlike and in compliance with all applicable codes.
Enerco Group, Inc Factory Representatives have had training
and experience in the application of this equipment and can
be called on for suggestions about installation which can save
material and money.
WARNING:
FIRE, BURN, INHALATION, AND EXPLOSION HAZARD.
KEEP SOLID COMBUSTIBLES, SUCH AS BUILDING MATERI-
ALS, PAPER OR CARDBOARD, A SAFE DISTANCE AWAY
FROM THE HEATER AS RECOMMENDED BY THE INSTRUC-
TIONS. NEVER USE THE HEATER IN SPACES WHICH DO OR
MAY CONTAIN VOLATILE OR AIRBORNE COMBUSTIBLES,
OR PRODUCTS SUCH AS GASOLINE, SOLVENTS, PAINT
THINNER, DUST PARTICLES OR UNKNOWN CHEMICALS.
GENERAL HAZARD WARNING:
FAILURE TO COMPLY WITH THE PRECAUTIONS AND
INSTRUCTIONS PROVIDED WITH THIS HEATER, CAN
RESULT IN DEATH, SERIOUS BODILY INJURY AND
PROPERTY LOSS OR DAMAGE FROM HAZARDS OF
FIRE, EXPLOSION, BURN, ASPHYXIATION, CARBON
MONOXIDE POISONING, AND/OR ELECTRICAL SHOCK.
ONLY PERSONS WHO CAN UNDERSTAND AND FOL-
LOW THE INSTRUCTIONS SHOULD USE OR SERVICE
THIS HEATER.
IF YOU NEED ASSISTANCE OR HEATER INFORMATION
SUCH AS AN INSTRUCTIONS MANUAL, LABELS, ETC.
CONTACT THE MANUFACTURER.
WARNING:
YOUR SAFETY IS IMPORTANT TO YOU AND TO OTHERS,
SO PLEASE READ THESE INSTRUCTIONS BEFORE YOU
OPERATE THIS HEATER.
CONTENTS
Section 1 INTRODUCTION.........................................................2
Section 2 PLANNING.................................................................3
Section 3 INSTALLATION & ASSEMBLY.....................................6
Section 4 ENGINEERING SPECIFICATIONS ..............................12
Section 5 VENTING/DUCTING………………………………………… 13
Section 6 GAS PIPING..............................................................16
Section 7 WIRING....................................................................17
Section 8 OPERATION MAINTENANCE....................................18
Section 8 TROUBLESHOOTING................................................20
Section 9 REPLACEMENT PARTS..............................................23
WARRANTY INFORMATION....................................................24
WARNING:
THIS PRODUCT CAN EXPOSE YOU TO CHEMICALS INCLUDING
LEAD AND LEAD COMPOUNDS, WHICH ARE KNOWN TO THE
STATE OF CALIFORNIA TO CAUSE CANCER AND BIRTH DEFECTS
OR OTHER REPRODUCTIVE HARM. FOR MORE INFORMATION
VISIT WWW.P65WARNINGS.CA.GOV
SECTION 1:Introduction
Heatstar ER2STG models are low-cost, field assembled infrared
heaters that are easy to install and require only minimal
maintenance. They are designed to provide years of economical
operation and trouble-free service.
Checking Shipment
Check the shipment against the Bill of Lading for shortages.
Also, check for external damage to cartons. Note any
shortages, and/or external damage to cartons on the Bill of
Lading in the presence of the delivery trucker. The delivery
trucker should acknowledge any shortages or damage by
initializing this “noted” Bill of Lading. Immediately report any
claims for damaged material, or shortages that were not
evident at the time of shipment, to the carrier and your Enerco
Group, Inc Factory Representative.
WARNING:
Fuels used in liquefied propange gas appliances, and the products
of combustion of such fuel, can expose you to chemicals including
benzene, which is known to the state of California to cause can-
cer and cause birth defects or other reproductive harm, for more
information go to www.P65Warnings.ca.gov
3Operating Instructions and Owner’s ManualEnerco | Heatstar ER2STG Tube Series Heater
SECTION 2: Planning
The following codes and instructions should be followed when
planning the installation of the Heatstar ER2STG heater. In
addition to these instructions, the warnings in (Section 1) must
be carefully adhered to since improper installation may lead to
property damage, injury, or death.
National Standards and Applicable
Codes
Gas Codes:
The type of gas appearing on the nameplate must be
the type of gas used. Installation must comply with local
codes and recommendations of the local gas company,
and the National Fuel Gas Code, ANSI Z223.1 – latest
revision, (same as NFPA Bulletin 54) or the Natural Gas
and Propane Installation Code, CSA B149.1.
Clearance between the heater and its vent and adjacent
combustible material (which is part of the building or its
contents) shall be maintained to conform with the Stan-
dard for Installation of Gas Appliances and Gas Piping,
NFPA-54 /ANSI Z223.1 – latest revision, National Fuel
Gas Code or the Natural Gas and Propane Installation
Code, CSA B149.1.
Aircraft Hangers:
Installation in aircraft hangers must be in accordance
with the Standard for Aircraft Hangers, ANSI / NFPA-
409 – latest revision.
Heaters in aircraft storage or service areas shall be in-
stalled at a height of 10 feet above the upper surface of
wings or engine enclosures of the highest aircraft which
may be housed in the hanger. (This should be measured
from the bottom of the heater to the wing or engine
enclosure, whichever is highest from the floor.)
In other sections of aircraft hangers, such as shops or
offices, heaters must not be installed less than 8 feet
above the floor.
Heaters installed in aircraft hangers shall be located
so as not to be subject to damage by aircraft, cranes,
moveable scaffolding or other objects.
Public Garages:
Installations in garages must be made in accordance
with the Standard for Parking Structures, NFPA-88A –
latest revision or the Standard for Repair Garages, NFPA-
88B – latest revision.
Heaters must not be installed less than 8 feet above
the floor. Minimum clearances to combustibles must be
maintained from vehicles parked below the heater.
When installed over hoists, minimum clearances to com-
bustibles must be maintained from the uppermost point
on the hoist.
Venting:
The venting must be installed in accordance to the latest
revision of ANSI Z223.1 or CSA 149.1. Partial informa-
tion with regard to this code is provided in (Section 5) of
this installation manual with regard to size and configu-
rations for venting arrangements.
Any portion of flue pipe passing through a combus-
tible wall must be dual insulated or have an approved
thimble. Refer to to the latest revision of ANSI Z223.1 or
CSA 149.1
Hazardous Locations:
Where there is the possibility of exposure to combustible
airborne material or vapor, consult the local Fire
Marshal, the fire insurance carrier or other authorities
for approval of the proposed installation.
Critical Considerations
Heatstar ER2STG is a suspended heater. Therefore, its
stability, flexibility, and safety are very important. Before
starting installation, be sure the system can meet the
following requirements.
For use in indoor or outdoor installation. Not for use in
residential dwellings.
Maintain specified clearances to combustibles, and safe
distance from the heat-sensitive material, equipment
and work stations.
The stated clearances to combustibles represent a sur-
face temperature of 90°F (30°C) above room
temperature. Building materials with low heat tolerance(
such as plastic, vinyl siding, canvas, etc.) may be subject
to degradation at lower temperatures. It is the install-
ers responsibility to assure that adjacent materials are
protected from degradation.
Provide a suspension with vertical length of chain or
swinging rod which has at least 2 inches of horizontal
travel for each burner in a straight run. Be sure the sus-
pension system is sufficiently flexible to accommodate
thermal expansion which occurs as the system heats up
(see Figure 6 on page 11).
Provide access to burners for servicing, preferable on
both sides, above and behind the burner for removal.
Provide a minimum of 18 inches of clearance between
burners and building walls. (Always observe minimum
clearances to combustibles.)
Be sure the heater has a downward pitch of one-half
inch per 20 feet away from the burner.
Provide signs in storage areas to specify maximum stack-
ing height to maintain required clearances to combus-
tibles.
Plan location supports (see Figure 2A-D on page 8).
Locate a support near all elbows.
The installation must conform with local building codes
or in the absence of local codes, with the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 or the Natural Gas
and Propane Installation Code, CSA B149.1.
If an external electrical source is utilized, the heater,
when installed, must be electrically grounded in accor-
dance with the National Electical Code, ANSI/ NFPA 70
or current Canadian Electrical Code, CSA C22.1.
Available Venting Kits
F102848 Category I 4" Vertical Vent Kit
F102849 Category I 6" Vertical Vent Kit
F102860 Category III 4" Stainless Steel Horizontal Vent
Kit
4
Enerco | Heatstar ER2STG Tube Series Heater Operating Instructions and Owner’s Manual
TABLE 1: Minimum Clearances to Combustibles (Use Figure 1 on page 5 as a Guide)
Reflector Type Position ER2STG-100 ER2STG-125 ER2STG-175
Standard
Reflector
(Horizontal)
A
B
C
D
6”
36”
74”
36”
6”
36”
87”
36”
8”
36”
87”
36”
45° Reflector Tilt
A
B
C
E
F
18”
36”
74”
36”
60”
18”
36”
87”
36”
60”
18”
36”
87”
36”
60”
U-Tube Standard
(Horizontal)
A
B
C
D
18”
36”
74”
36”
18”
36”
87”
36”
18”
36”
87”
36”
U-Tube Opposite
45°
A
B
C
F
18”
36”
74”
60”
18”
36”
87”
60”
18”
36”
87”
60”
U-Tube Full 45°
A
B
C
E
F
18”
36”
74”
36”
60”
18”
36”
87”
36”
60”
18”
36”
87”
36”
60”
Unvented Above A 36” 36” 36”
WARNING:
FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY OR DEATH.
In all situations, clearances to combustibles must be maintained. Failure to observe clearances to combustibles may result in property
damage, severe injury, or death.
Minimum clearances must be maintained from vehicles parked below the heater. Signs should be posted in storage areas to specify
maximum stacking height to maintain required clearances to combustibles.
Caution should be used when running the system near combustible materials such as wood, paper, rubber, etc. Consideration should be
given to partitions, storage racks, hoists, building construction, etc.
TABLE 1 gives minimum acceptable clearances to combustibles. Clearances as shown in TABLE 1 are not for use in four-sided enclosures.
Clearances To Combustibles
5Operating Instructions and Owner’s ManualEnerco | Heatstar ER2STG Tube Series Heater
D
A
C
STANDARD REFLECTOR
A
E
C
E
45 DEGREE REFLECTOR TILT
C
A
EF
U-TUBE OPPOSITE 45 DEGREE
A
CD
U-TUBE STANDARD
C
E
A
E
U-TUBE FULL 45
BE
FRONT AND BACK CLEARANCE
Clearances To Combustibles
Figure 1: Clearances To Combustibles (Refer to TABLE 1 on page 4)
A
C
EF
STANDARD REFLECTOR
D
A
C
A
C
D
“U”-Tube, Standard
A
C
D
F
“U”-Tube, Opposite 45°
F
C C
AA
E
A
F
“U”-Tube, Full 45°
C
AC
B
B
Front and Back Clearance
6
Enerco | Heatstar ER2STG Tube Series Heater Operating Instructions and Owner’s Manual
SECTION 3: Installation & Assembly
TUBE
KEY FOR TUBE COUPLING
(14616)
TUBE HANGER
(14585P)
HEAT EXCHANGER TUBE 10'
(06413)
TURBULATOR BAFFLE 5' (03447)
**NOT INCLUDED WITH ALL MODELS**
REFLECTOR 10'
(00418A)
VENT ADAPTER
(19021)
BURNER BOX
7Operating Instructions and Owner’s ManualEnerco | Heatstar ER2STG Tube Series Heater
Vent Adapter
Used to attach the heat
exchanger tubing to vent pipe.
Installation Procedure
Take maximum advantage of the building upper structure, beams, joists, purlins, etc., from which to suspend the heater.
There is no unique sequence for installation of the tubing. On-site observation will usually reveal a logical sequence. Begin
the installation at the most critical dimension. This could save time. Watch for swinging doors, overhead cranes, car lifts etc.
Reflectors and tubing can be installed as you move along. Carefully adjust system pitch at each position to level the heater.
Pitch down one-half inch in 20 feet (away from burner).
DON’T Pressure test the gas line using high pressure (greater than ½ PSIG) without closing the high-pressure shutoff
cocks. Failure to do so will result in damage to the burners.
DO Familiarize yourself with local and national
codes.
Develop a planned procedure which will conserve material and labor on the job.
Check to see that all material and equipment is on the job before starting installation.
Allow for thermal expansion of the hot tube.
Install the gas connector only as shown in instructions (see Figure 14 on page 16).
Have slip joints where required between reflectors to keep them from buckling or coming apart.
Provide 1 sq. inch of free air opening to each 1,000 BTU/hr. of heater input (but not less than 100 sq. inches) in enclosed
spaces. One opening should be within 12 inches of the top and one within 12 inches of the bottom of the enclosure.
Burner Housing
Must always be
installed horizontally.
Tube and Reflector Hanger
Install immediately after first
coupling.
Turbulator
Enerco Group, Inc. normally ships Ener-Radiant heaters with
turbulators assembled into appropriate tubes.
Tube and Reflector Hanger
Suspend system from these hangers.
Minimum two (2) required per tube.
Reflectors
Alternate overlap as shown
on overview. Length of
reflector and amount of
overlap is indicated.
10' 2=1/2" ALUMINIZED
Heat Exchange Tubes
Supplied in 10 ft. lengths.
Tube Coupling Assembly
Coupling should be oriented with
slide bar on top, and all couplings
should “point” in the same direction.
Assemble the heater components as shown in Figures 2a, 2b, 2c, 2d, Optional reflector configurations are shown in (Figure 1). Install
appropriated suspension hardware, beam clamps, chain or rod at predetermined locations. Adjustment of chain length will provide uniform
FIGURE 2: Heatstar ER2STG Overview
8
Enerco | Heatstar ER2STG Tube Series Heater Operating Instructions and Owner’s Manual
FIGURE 2A: Heatstar Model ER2STG 60-100 Assembly Overview
30 ft. Exchanger length. 31 ft. - 4 in. Total Heater length. 6 Suspension points as indicated.
FIGURE 2B: Heatstar Model ER2STG 80-125 or ER2STG 60-100
40 ft. Exchanger length. 41 ft. - 4 in. Total Heater length. 8 Suspension points as indicated.
FIGURE 2C: Heatstar Model ER2STG 80-125 or ER2STG 125-175
50 ft. Exchanger length. 51 ft. - 4 in. Total Heater length. 10 Suspension points as indicated.
FIGURE 2D: Heatstar Model ER2STG 125-175
60 ft. Exchanger length. 61 ft. - 4 in. Total Heater length. 12 Suspension points as indicated.
ALUMINIZED ALUMINIZED ALUMINIZED ALUMINIZED
18”
Typ.
18” 18” 18”
10’ 2-1/2” 10’ 2-1/2” 10’ 2-1/2” 10’ 2-1/2”
10’ 2-1/2” 10’ 2-1/2” 10’ 2-1/2”
10’ 2-1/2”
10’ 2-1/2”
18”
Typ.
ALUMINIZED ALUMINIZED ALUMINIZED ALUMINIZED ALUMINIZED
18” 18” 18” 18” 18” 18” 18” 18” 18”
10’ 2-1/2” 10’ 2-1/2” 10’ 2-1/2”
10’ 2-1/2” 10’ 2-1/2” 10’ 2-1/2”
18”
Typ.
ALUMINIZED ALUMINIZED ALUMINIZED ALUMINIZED ALUMINIZEDALUMINIZED
18” 18” 18” 18” 18” 18” 18” 18” 18” 18” 18”
(1) TURBULATOR SECTION (5')
9Operating Instructions and Owner’s ManualEnerco | Heatstar ER2STG Tube Series Heater
FIGURE 3: Heatstar ER2STG Dimensions & Suggested Mounting Heights
Turbulator
Heat Exchanger Tubing
Turbulator
Heat Exchanger Tubing
Minimum Total Length (see chart below)
Burner Side View
Burner Ratings and Heat Exchanger Lengths: (NG and LP) Suggested Mounting Heights
Model # Rate (BTU/Hr.)
Low-High
Heat Exchanger
Length Turbulator Minimum
Total Length
Suggested
Min. Space
Typical
Mounting
Height
ER2STG
60-100
60 - 100,000 30 ft. 5 ft. 31' - 4' 12’ - 15’ 12’ - 15’
60 - 100,000 40 ft. None 41' - 4' 15’ - 18’ 12" - 15'
ER2STG
80 - 125
80 -125,000 40 ft. None 41' - 4' 15’ - 20’ 14’ - 19'
80 - 125,000 50 ft. None 51' - 4' 15’ - 18’ 14’ - 19'
ER2STG
125-175
125 - 175,000 50 ft. None 51' - 4' 20’ - 23’ 15’ - 25'
125 - 175,000 60 ft. None 61' - 4' 20’ - 25’ 15’ - 25'
Burner Rear View
9.25"
(23.49cm)
9.25"(23.49cm)
17.75"(45.08)
( IF NECESSARY
10
Enerco | Heatstar ER2STG Tube Series Heater Operating Instructions and Owner’s Manual
Couplings: Tube and tube fittings are connected by wrap-
around couplings which clamp by means of
a tapered, hammer-driven lock member. The
starting ends of the coupling and lock member
are identified by 1/4” holes which are put
together when starting assembly. Be sure the
tube ends are in line and tube ends butt against
stop pin(s) inside coupling. The slide bar is to be
hammer-driven to a point of securing the coupling
snugly to the tubes. Over-driving will result in
distortion of the coupling or slide bar lip to a
point decreasing the holding the capability of the
coupling. (See Figure 4)
90° Elbow
Elbow Fitting Dimensions
FIGURE 5: Installation of Elbow & Coupling
Elbow Package: Stk. # F106415 Elbow Package includes:
(1) elbow, (1) coupling and (1) refelctor.
Install elbow into radiant tube sequence
where plans indicate a 90° bend
U-Tube Fitting Dimensions 180° U-Tube
Stk. # i ncludes:
F106414 U-Tube Package
(1)U -tube, (1) coupling and (2)
radiant tube sequence where plans
indicate a 180° bend
COUPLING ASSEMBLY
Coupling (Less Key) - 14612
Key for Coupling - 14616
Tighten
Loosen
Hole 1
Coupling
Assembly
Impact
Block
Hole 2
When assembling coupling note
the location of Hole 1 and Hole 2
Orient coupling so that
the impact block is above
tube centerline.
TUBE COUPLING
KEY for COUPLING
FIGURE 4:
(38.73 CM)
(15.24 CM)
18" (45cm)
10"
(25cm)
(10cm)
(43cm)
9" (22cm) Radius
11 Operating Instructions and Owner’s ManualEnerco | Heatstar ER2STG Tube Series Heater
Chain kit - Stk. #17370
One chain kit will suspend one 10 ft. section of tube and one 10 ft.
section of reflector.
FIGURE 7A: Tube and Reflector Hanger
FIGURE 7B: Mounting Flange / Tube Detail
1) Insert tube 06413 into front casting to point (A).
2) Tighten set screws marked (B) until snug.
3) After all (3) set screws are snug, turn each
additional 1/4 turn to secure tube in place.
FIGURE 8: Burner Box / Transition Tube Detail
FIGURE 6: Typical Suspension Details
Screw Hook
I-Beam
Beam
S-Hook
Bar Joist
Truss
Concrete
Beam
Mounting Flange
Cap Screw
Stk. 98012
Split Lock Washer
Stk. #98527
Gasket
Stk. #12397
Burner Box
(flame observation
window facing down)
horizontal reflector position (standard)
side 45° reflector position (optional)
FIGURE 9: Reflector End Cap
Parts list
1 00419 Reflector End Cap (Qty 1)
2 09369 Spring Clip (Qty 4)
Flange Kit #06428XL
Kit Includes: Flange,Screws(4), Lock Washers(4), Gasket(1)
12
Enerco | Heatstar ER2STG Tube Series Heater Operating Instructions and Owner’s Manual
SECTION 4
Engineering Specifications
The total heating system supplied shall be design certified by CSA
under the latest revision of ANSI Z83.20 and CSA 2.34.
A. Burner & Burner Controls
1. Burners shall be capable of firing with one of the fuel options as
specified on the purchase documents: Natural Gas or LP.
2. Burners shall be supplied to fire at any one of the input rates as
specified.
ER2STG 60 - 100 60,000 - 100,000 BTU/Hr.
ER2STG 80 - 125 80,000 - 125,000 BTU/Hr.
ER2STG 125 -175 125,000 -175, 000 BTU/Hr.
3. Burner shall be equipped with a direct sense silicon-carbide hot
surface ignition control system with 100% shut-off ignition device.
Power supplied to each heater shall be 120V, 60Hz, single phase.
Burners shall be rated for 1.0 Amp (run) and 5.0 Amp (start.)
4. Burner shall be equipped with thermal overload motor protec-
tion, balanced air rotor, combustion air proving safety pressure
switch, and viewing window for flame observation.
5. When specified, in contaminated environments, the burner shall
be capable of supplying outside air to each burner for the sup-
port of combustion.
6. All burners shall be pre-wired with a grounded electrical
cord and plug.
7. Low voltage 2-stage thermostat required for correct 2-stage
burner operation.
B. Heat Exchanger
1. Radiant tubing shall be 4” diameter aluminized steel supplied in
10 ft. sections. Sections shall be joined with stainless steel wrap-
around couplings.
2. Reflector to be of aluminum material and designed to direct all
radiant output below horizontal center line of radiant tube.
3. Heaters shall be vented according to manufacturer’s
recommendations.
Gas INLET pressure:
Natural Gas: 4.6” W.C. Min
11.0” W.C. Max
LP Gas: 11.0” W.C. Min
14.0” W.C. Max
1/2” NPT Gas Connector Size
Electrical Rating: (All Models)
120V - 60Hz
1.0 AMP (Run) 5.0 AMP (Start)
Dimensions:
Flue Connection Size…………………4”
Outside Air Connection Size………4”
MANIFOLD PRESSURE
ER2STG 60-100
LOW FIRE
( MIN. RATE)
HIGH FIRE
(MAX RATE)
NATURAL GAS - INCHES
W.C.
1.3" 3.5"
PROPANE - INCHES W.C. 3.5" 10.5"
MANIFOLD PRESSURE
ER2STG 80-125
LOW FIRE
( MIN. RATE)
HIGH FIRE
(MAX RATE)
NATURAL GAS - INCHES
W.C.
1.7" 3.5"
PROPANE - INCHES W.C. 4.2" 10.5"
MANIFOLD PRESSURE
ER2STG 125-175
LOW FIRE
( MIN. RATE)
HIGH FIRE
(MAX RATE)
NATURAL GAS - INCHES
W.C.
2.2" 3.5"
PROPANE - INCHES W.C. 5.8" 10.5"
Gas pressure at MANIFOLD:
1/2” NPT Gas Connector Size
13 Operating Instructions and Owner’s ManualEnerco | Heatstar ER2STG Tube Series Heater
SECTION 5
Venting / Ducting
General Requirements
This heater must be vented in accordance with the
specifications
contained in this manual and with the following national codes
and any state, provincial or local codes which may apply:
• Refer to National Fuel Gas Code NFPA 54/ANSI Z223.1- latest
revision.
• CANADA: Refer to Natural Gas and Propane Installation Code
CSA B149.1- latest revision.
The heater may be vented to the outdoors either vertically or
horizontally.
Optional outside air supply may be directed to the heater
horizontally or vertically.
Be sure that the method selected for venting heater complies
with all codes as required for each particular location
The use of single-wall vent pipe (26 gauge) is recommended. A
section of double-wall vent pipe is recommended when passing
through the roof or wall.
Exhaust end of heater will accept a 4'(10 cm) vent pipe using
the vent adapter. Install the vent adapter with the seam on
top, secure all vent joints with a minimum of 3 #8 x 3/8" sheet
metal screws and seal all joints using a high temperature
silicone sealant.
If condensation in the flue is a problem, the flue length should
be shortened or insulated.
Vent pipe must be sloped downward away from the burner
1/4"(.6 cm) for ever 10'(3m).
VENT LENGTHS:
Maximum total vent length allowed in thirty (30’) feet.
Maximum outside air supply duct allowed thirty (30’) feet.
Maximum total vent length plus outside air supply length
shall not exceed fifty (50’) feet.
NOTE:
A total of two (2) elbows are allowed for vent and
outside air supply combination. Subtract 5' feet per additional
elbow from maximum length allowed if 3 or more elbows are
used.
Install a minimum 18" (30 cm) straight length of duct for air
intake or vent before any Tee or elbow.
Alternative Arrangements / Optional Equipment for Venting
Unvented Operation
a) Sufficient ventilation must be provided in the amount of 4
CFM per 1,000 BTU/hr. firing rate.
b) Refer to ANSI Z223.1 - latest revision, NFPA-54 and local
codes for additional information.
c) Use of optional outside combustion air is not recommended
with unvented heaters due to pressure considerations. Refer
to page 16
Horizontal Venting
This heater, when horizontally vented, must be installed
with approved venting system. For horizontal venting
installations these tube heaters are certified as a Category III
appliance
a) Four (4”) inch O.D. flue pipe is required. Thirty (30’) feet
maximum length is recommended.
b) All flue joints should be sealed using suitable product such
as General Electric RTV106 or Permatex Form-A-Gasket Red
High Temperature Silicone Adhesive Sealant.
c) Do not install any elbow or 45 fitting to bring vent lower
than the horizontal tube system.
d) Vent terminal should be installed at a height sufficient to
prevent blockage by snow.
1) Vent must exit building not less than seven (7’) feet
above grade when located adjacent to public walkways.
2) Vent must terminate at least three (3’) feet above any
forced air inlet located within ten feet (10’).
3) Vent must terminate at least four (4’) feet below, four
(4’) feet horizontally from, or one (1’) foot above any
door, window, or gravity inlet into any building.
4) Vent terminal shall be located at least twelve (12”)
inches from any opening through which vent gases
could enter the building.
5) Vent terminal must be beyond any combustible over
hang
Vertical Venting
This heater, when vertically vented, must be installed with
the approved venting system. For vertical vent installations,
ER2STG 60-100 model and ER2STG 80-125 model are category
I appliances. The ER2STG 125-175 model is only Category I
when vented vertically with 6" (15.25cm) diameter vent pipe.
a) Four (4”) inch O.D. flue pipe, maximum thirty (30’) feet
in length may be used as shown with approved vent cap.
(See General Requirements on this page for additional
information.)
b) An insulated thimble may be required to pass through
combustible structures (check local codes).
c) All flue joints should be sealed using suitable products (see
recommendation for horizontal venting.)
Common Venting
a) Horizontal run to vent must never exceed 75% of the
vertical height of the vent. Refer to ANSI Z223.1 - latest
revision, NFA-54 for proper vent sizes and installation.
b) Open area of common vent must equal the sum of the
open area of individual vents connected to it. (See chart
below and diagrams - page 14.)
c) Use double wall vent as required (check codes.)
d) All joints must be sealed using suitable products.
e) Connections to common stack must be positioned to avoid
direct opposition between streams of combustion gases.
COMMON VENTING - (2) Heaters (Horizontal and Vertical)
Model # H = 6 ft. H = 8 ft. H = 15 ft.
ER2STG 60-100 D = 8" D = 8" D = 7"
ER2STG 80-125 D = 10" D = 10" D = 8"
14
Enerco | Heatstar ER2STG Tube Series Heater Operating Instructions and Owner’s Manual
FIGURE 12: Common Roof Venting
Type "B" Vent required outdoors.
Vent Adapter Stk. #19021
Outside Wall
Secure all joints with 3 (minimum) #8 x 3/8"
sheet metal screws and seal all joints.
H
Vent Cap
Wall Thimble
(If Applicable)
Burner Box
Burner Box
HORIZONTAL COMMON VENTING
VERTICAL COMMON VENTING
SIDE VIEW
TOP VIEW
Type "B" Vent required outdoors.
Vent Adapter Stk. #19021
At least 1/4" per foot rise or pitch
must be maintained on horizontal
runs from heater to vent.
Roof
Secure all joints with 3 (minimum) #8 x 3/8"
sheet metal screws and seal all joints.
H
Approved Vent Cap
Type "B" Vent required outdoors.
Vent Adapter Stk. #19021
Outside Wall
H
Vent Cap
Flashing
Wall Thimble
(If Applicable)
Burner Box Burner Box
Burner Box
Burner Box
Burner Box
Burner Box
D
Burner Box Burner Box
D
4” Aluminized steel Heat Exchange Tube
4” Aluminized steel Heat Exchange Tube
D
15 Operating Instructions and Owner’s ManualEnerco | Heatstar ER2STG Tube Series Heater
FIGURE 10: Unvented Operation
36”
36”
A
1. Ventilation equal to 4 CFM per 1,000 BTU/HR firing rate must
be provided in unvented heater installations
2. For dimensions A "unvented" refer to ( Figure 1- Minimum
Clearances to Combustibles.)
3. This heater requires ventilation in the building to dilute the
products of combustion and provide fresh air for efficient
combustion.
FIGURE 10b: Double Wall
Double wall vent run
Double wall terminal end
FIGURE 11: Vertical Venting
18"(45cm)
18" (45cm) Min. 3'-0" (91cm) Min.
8"(20cm) to 10"(25cm) Max.
6' (182cm) Min.
FIGURE 10A: Single Wall
Single wall vent run
Single wall terminal end
18" (45cm) Min. 3'-0" (91cm) Min.
6' (182cm) Min.
2"(5cm) Clearance thimble
2"(5cm) Clearance thimble
required when u pipe
extends through
combustible materials
(91cm)
(91cm)
Vent Adapter
16
Enerco | Heatstar ER2STG Tube Series Heater Operating Instructions and Owner’s Manual
Outside Combustion Air Supply
The Heatstar ER2STG heater is approved for installation
with an outside air supply system. Some compounds such as
halogenated hydrocarbons or other corrosive chemicals in the
air can be drawn into the equipment and cause an accelerated
rate of corrosion of some of the heater components. The use
of such chemical compounds near the enclosure should be
avoided.
IMPORTANT: If the building has a slight negative
pressure or contaminants are present in the air, an
outside combustion air supply to the heaters is strongly
recommended.
For an outside air supply, a four (4”) inch O.D. single wall pipe
may be attached to the heater. The duct may be up to thirty
(30’) ft. maximum length or two (2’) ft. minimum length with
no more than two (2) elbows. (See General Requirements on
page 15 for additional information.)
The air supply duct may have to be insulated to prevent
condensation on the outer surface. The outside air terminal
should be securely fastened to the outside wall by drilling four
(4) 1/4” diameter holes in the outside flange; wood screws or
bolts and expansion sleeves may be used to fasten terminal.
PVC Pipe, “Dryer Hose”, or equivalent may be used instead of
standard vent pipe.
FIGURE 13: Non-Pressurized Outside Air Supply Duct
SECTION 6
Gas Piping
Read applicable warnings in (Section 1) before proceeding with
Gas Pipe installation. Improper installation may result in property
damage, severe injury, or death.
Meter and service must be large enough to handle all the burners
being installed plus any other connected load. The gas line which
feed the system must be large enough to supply the required gas
with a maximum pressure drop of 1/2” water column. When gas
piping is not included in the layout drawing, the local gas supplier
will usually help in planning the gas piping.
A 1/2” tapping at each burner location must be located and
oriented as shown in (Figure 14). To check system pressure, put a
plugged 1/8” NPT tapping in the gas line at the connection to the
burner farthest from the supply. Before connecting the burners to
the supply system, verify that all high pressure testing of the gas
piping has been completed. Do not high pressure test the gas piping
with the burners connected.
Follow these instructions to ensure a professional gas supply
installation:
Support all gas piping with suitable pipe hanging
materials.
Use wrought iron or wrought steel pipe and malleable
iron fitting. All pipe fittings should be new and free
from defects. Carefully ream the pipe and tubing ends
to remove obstructions and burrs.
Use L.P. gas-resistant joint compound on all pipe
threads.
Check the pipe and tubing ends for leaks before
placing heating equipment into service. When
checking for gas leaks, use soap and water solution:
NEVER USE AN OPEN FLAME.
Install the flex gas connector as shown. The flex gas connector
accommodates expansion of the heating system and allows for easy
installation and service of the burner.
FIGURE 14: Gas Line Connection with Stainless Steel Flex Gas
Connector
Shut-Off Valve must be parallel
to burner gas inlet. The 2”
displacement shown is for the cold
condition. This displacement may
reduce when the system is fired.
12"
1/2" Stainless Steel Flex Gas Connector
Stk. #16401
4" (10 cm)
Seal All Joints
Heater Movement
Heater Movement
Heater Movement
Heater Movement
Outside Air
Terminal
Flex Pipe
6" (15 cm) to
12" (30 cm) Long
Flex Pipe
6" (15 cm) to
12" (30 cm) Long
Flex Pipe
6" (15 cm) to
12" (30 cm) Long
Outside Air
Terminal
NOTE:
Flue pipe requires additional
support. Flex pipe will not
support riser and outside
air terminal
Vertical Outside Air
Horizontal Outside Air
FIGURE 14A: Incorrect Gas Line Connection with Stainless
Steel Flex Gas Connector
17 Operating Instructions and Owner’s ManualEnerco | Heatstar ER2STG Tube Series Heater
THERMOSTAT CONNECTION
24V
W1
W2
LOW HEAT
HIGH HEAT
R
W1
W2
TUBE BURNER CONNECTIONS INTERNAL THERMOSTAT WIRING
SECTION 7
Wiring
Heaters are normally controlled by thermostats. Heaters must be
electrically grounded in accordance with the National Electrical
Code, ANSI/NFPA 70 or current Canadian Electrical Code, CSA
C22.1.
If any of the original wire as supplied with the appliance must
be replaced, it must be replaced with wiring material having a
temperature rating of at least 105 °C and rated for 600V
Each burner must be electrically grounded in accordance with
the National Electric code ANSI/NFPA-70- latest version NOTE:
• Connecting the top two terminals of the bushing
located at the bottom left of the back of the
burner box will give you low fire
• Connect all three of the terminals for high heat
L1
N
Earth Ground
GV
M
T1
PCB1
S1/240
S1/120
N
L1
S2/FS
PSW
W
MV1
GRND
blk
wh
blk
grn
Pressure Switch
24 V
SW1
C1
blk
wh
grn
Primary
Secondary
FC+ FC-
LED
R
F2/IND
F1/120
red
To Thermostat
24V
W1 W2
grn
red
wh
grn
brn
wh
red
red
Flame Sense
Burner
HSI
wh
wh
blk
wh
wh
yellow
SW1 - Panel Interlock Switch
C1 - 1.5 ufd @ 450 volts
Wire is AWG18 Stranded @ 600 volts - 105 degrees C
Crimp Caps are # CE5 - 105 degrees C
(Neutral Connection Not Needed in this Configuration)
blue
24 VAC
blk
grn
WIRING DIAGRAM
BURNER BOX CONNECTION INTERNAL THERMOSTAT WIRING
FIGURE 18A
FIGURE 18B
18
Enerco | Heatstar ER2STG Tube Series Heater Operating Instructions and Owner’s Manual
Sequence of Operation
1. Turn the thermostat up. When the thermostat calls for heat,
blower motor will energize.
2. When the motor approaches nominal running RPM, the air
proving switch closes and activates the ignition module.
3. The ignition module then energizes the hot surface igniter
for a timed warm-up period (approximately 45 to 60
seconds.)
4. After the warm-up period, the gas valve is energized.
5. If a flame is detected, the gas valve remains open. When the
call for heat is satisfied, and the system control mechanism
de-energizes the burner line voltage supply, the gas valves
are turned off.
6. If no flame is detected on a three-trial module, the gas
valve is closed, and a purge period begins. After the purge,
the module acts to power the igniter for a second warm-
up period, and a second trial for ignition period. If flame is
still not established, a third and final purge, warm-up, and
trial cycle begins. After three trials, the module will lockout
until reset. Reset is accomplished by removing power from
the module for at least five (5) seconds (thermostat cycle
required.)
7. If flame is established and lost on the first or second trial,
the gas valve is turned off, a purge, warm-up, and trial for
ignition will occur on a three-trial module, only three trials
for ignition are allowed per thermostat cycle.
Maintenance
For best performance, the following maintenance procedures
should be performed before each heating season:
1. Be sure gas and electrical supply to heater are off before
performing any service or maintenance.
2. Check condition of blower scroll and motor. Dirt and dust may
be blown out with compressed air, or a vacuum cleaner may be
used. When using compressed air, do not exceed 30 psi in order
to not damage fragile hot surface igniter.
3. Check condition of burner. Carefully remove any dust or
debris from inside the burner box or burner cup.
4. Inspect the igniter. Replace igniter if there is excessive
carbon residue, erosion, breakage or other defects.
5. Check the inside of the firing tube with a flashlight. If carbon
or scale are present, scrape out the deposits with a wire
brush or rod, or metal plate attached to a wooden pole.
6. Check to see that the burner observation window is clean
and free of cracks or holes. Clean or replace as necessary.
7. Check the flue pipe for dirt. After cleaning as necessary, re-
attach the flue pipe to the heater.
8. Outside surfaces of heater may be cleaned by wiping with a
damp cloth.
9. A qualified service agency should be contacted for service
other than routine maintenance.
10. Check vent terminal and fresh air inlet to see that they have
not been blocked during the non-heating season. If either
pipe is restricted, the air switch won’t close, resulting in a no-
heat situation.
SECTION 8
Operation & Maintenance
Basic Operation of 2-Stage Tube Heater
Unit fires at rates designated as Low and High
Fire rate is determined by thermostat
Initial Start:
If thermostat is more than 2 degrees above the room/
space temperature, the heater will start and go into high fire
range. The unit will stay in the high range until the space air
temperature reaches the thermostat set-point. The heater will
shut off.
As the room/space air temperature decreases below the
thermostat set point (approximately 1 degree) the heater will
come on and fire until the thermostat set point is reached.
If the room/space air temperature experiences a rapid
decrease in air temperature (below 3 degrees from set point)
the heater will come on and fire at the high rate until the set
point is reached.
LADDER DIAGRAM
L
N
24V
M
C1
Panel Interlock
F2/IND
F1/120
(Control PCB)
HSI
L1 S1/120
(Control PCB)
PCB
L1
PCB
S2/FSL1
Burner
Flame Sense
T1
115V
PCB
R
PCB
PSW
Pressure Switch
W1
W2
T'Stat
W
MV1
(Control PCB)
Gas
Valve
Earth &
Chassis Ground
FIGURE 18C
HIGH ALTITUDE
Heaters may be fired at full input up to 2000 ft. (610m) above sea level. Above 2000 ft. (610m) a high altitude conversion kit may be required
to ensure proper burner performance, please consult the manufacturer. Be prepared to answer factory questions regarding: type of fuel for the
proposed appliance conversion, gas pressure available at site, and specific altitude at site. The conversion shall be carried out by a manufactur-
er's authorized representative, in accordance with the requirements of the manufacturer, provincial, or territorial authorities having jurisdiction
and in accordance with the requirements of the CSA B149.1 or CSA 149.2 installation codes.
19 Operating Instructions and Owner’s ManualEnerco | Heatstar ER2STG Tube Series Heater
Burner Does Not 1. Check ground wire continuity.
Stay Lit: 2. Check burner internal wiring for reversed
leads.
3. Check insulation on the igniter leads.
4. Clean or replace flame sensor.
5. Replace module if necessary.
IGNITION MODULE LED Status
The Heatstar ER2STG series Tube Heater is equipped with a Ignition
module. This ignition module has a built-in diagnostic program,
which will assist in troubleshooting in the event of a valve-related
problem. The LED or (Light Emitting Diode) is located on the ignition
module as shown in diagram below. The LED status indications are
listed below to help with the troubleshooting.
FIGURE 19:
Off No power to the control
ON Control Fault
1-Flashes Airflow Fault
2--Flashes Flame Sense Fault
3-Flashes Ignition Lockout.
Troubleshooting
CAUTION: Before opening the Heatstar
ER2STG burner door for any type of service, be
sure the gas supply has been shut off at the
heater and the electrical cord from the burner
box has been unplugged.
Blower Motor 1. Is the thermostat calling for heat? Is there
Fails to Run: 120V at the burner receptacle?
2. Check blower side door for seal. Check door
switch. Replace if necessary.
3. Check blower for obstructions. Replace
blower if necessary.
Igniter 1. Check igniter for damage. Replace if
Does Not Glow: necessary.
2. Check voltage and resistance at igniter.
(Voltage should be 120V. Resistance should be
40-75 ohms.)
3. Check for obstructions to the air inlet and
outlet.
4. Check wiring and hose connections to the
air switch. Replace if necessary.
5. Check voltages at transformer primary and
secondary. Replace transformer or module if
necessary.
Valve Does Not Gas pressure downstream of gas control can
Come On: be measure by using a manometer and
connecting to pressure tap on control/
1. Check to see if manual valve heater is ON.
2. Check to see if manual valve knob on heater
gas control in ON.
3. Supply gas pressure can be checked at
1/8” NPT pressure tapping on heater external
manual valve.
4. Check to see if gas control is opening: no
manifold pressure indicates valve is closed.
If the valve is closed, either the gas valve or
the ignition module is faulty.
WARNING: Do not disconnect ground leads
inside heater. Do not interchange grounded
and ungrounded leads on transformer or
ignition module.
Burner Does Not 1. Check to see if gas lines were properly
Light: purged of air.
2. Check inlet and outlet gas pressure during
ignition period.
Natural inlet pressure should be 4.6”
Natural outlet pressure should be set
according to chart on page 12.
LP inlet pressure should be 11.0”
LP outlet pressure should be set according to
chart on page 12.
3. Check for proper orifice and air plate.
IGNITION MODULE
LED
20
Enerco | Heatstar ER2STG Tube Series Heater Operating Instructions and Owner’s Manual
SECTION 8: Troubleshooting Guide. Heatstar ER2STG
START
Turn on thermostat
Does blower turn
on?
Yes
Does the igniter
warm up and glow
red?
Yes
No
Check Thermostat
and Wiring. Is the
power supply to unit
120V?
No
Find the source
of the electrical
problem
Check LED indicator on Ignition Control for
indication of fault. Refer to Ignition Module
testing on page 19 to determine problem.
No Is the air intake or
exhaust blocked?
Yes
Remove Obstruction
Check wiring and
connections
No Is the ignitor
damaged?
No
Check voltage at
ignitor. Is it 120V
during ignition
cycle?
Yes Is blower side door
in place?
No
Replace door
No
Check wiring and
hose connection to
air switch. Are they
OK?
Yes
Is the voltage at
the transformer
secondary 24V?
No
Is the voltage at the
transformer primary
120V
Replace ignitor.
Yes
No
Is the resistance
through igniter 40
to 75 ohms?
Remove door. Is
voltage at door
switch 120?
Yes
No
Check voltage at
Ignition Control
Replace wiring and/
or hose connection.
No
Jumper wires at
pressure switch.
Does the ignitor
glow red?
Yes
Replace transformerYes
Check wire
connections.
Yes
Depress switch.
Does blower come
on?
Yes Yes
No
Check voltage to
motor. Is it 120V?
Yes
Is the blower fan
obstructed?
No
Replace blower
motor.
Replace pressure
switch.
Yes
Replace Ignition
No
Check LED indicator on Ignition Module for
indication of fault. Refer to Ignition Control
testing on page 19 to determine problem.
Check door fit. If
damaged, replace
door.
Replace switch.
No
Remove obstruction
Yes
After ignitor warm-
up period, does the
valve click?
Yes
Does the burner
light?
Yes
Does the burner
stay on?
Yes
Does the burner
run until the call
for heat ends?
If a problem still exists, contact Enerco Group, Inc Technical Products
Customer Service 1-866-447-2194
No
The Ignition Module checks the status of the blower proving switch contacts must see a change in the
contact with every firing cycle. Placing a jumper at the switch out of sequence will result in a fault with
the LED indicator flashing two times.
Were the gas lines purged of air?
No No
Yes
Check inlet gas pressure. Is pressure correct?
Refer to page 12 for correct pressure for unit.
Yes
Check inlet gas shutoff. Adjust regulator.
Contact gas supplier
Is the continuity of
the ground wire
OK?
No
The switch on the gas valve must be in the on
position and the line purged of air.
No
Repair wiring.
No
Check the continuity of the ground wire.
Check the thermostat.
Check outlet gas pressure during ignition cycle.
Refer to page 12 for correct pressure
Yes
Adjust to proper pressure.
No
Are L1 and L2
reversed?
Yes
Yes
Repair wiring
Is the wiring at the
Ignition Module
No
Repair wiring
Is the insulation on
the sensor lead OK?
No
Repair wiring
No Yes Yes
Are the wires to
the Ignition Control
OK?
Yes
Replace Ignition
No Replace/repair wires.
Yes
Check for proper
burner orifice and
air plate.
Is the sensor
positioned
properly?
Yes
Is the sensor dirty?
No
Replace Sensor
No Repair/Replace
Yes
Clean sensor.
A fault indication of three flashes may indicate
that the flame sensing circuit is not functioning
properly. Perform the following series of checks
to correct the problem.
No
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

HeatStar ER2STG100-LP Le manuel du propriétaire

Catégorie
Chauffe-eau
Taper
Le manuel du propriétaire