Danfoss AKS 41U ver.4.0 Guide d'installation

Taper
Guide d'installation
DIR RI5KB55M © Danfoss A/S (RC-CMS / MWA), 01-2005 1
Assembly
Montage
Montaje
Remember clearance required for
replacement of level transmitter, if
applicable
Ne pas oublier le dégagement en hauteur
nécessaire pour un remplacement éventuel
du transmetteur de niveau.
No olvidar dejar el espacio suficiente por si
es necesario cambiar el transductor de nivel.
–13°F < t < 131°F
(–25°C < t < 55°C)
Insulate
Isoler !
Aislar
Max. 870 psig (60 bar) (operating range)
870 psig (60 bar) max. (pression de service)
Max 870 psig (60 bar) (presión de trabajo)
Plug - can be mounted in 4 different positions
Prise - peut être montée dans 4 directions
Clavija - puede montarse en 4 direcciones
Instruction
Type AKS 41U ver. 4.0
084R9761
084R9761
AKS 41U
–76°F < t < 212°F
(–60°C < t < 100°C)
Type
Insertion
length
AKS 41U-6” 6” (152 mm)
AKS 41U-8” 8” (203 mm)
AKS 41U-12” 12” (305 mm)
AKS 41U-15.3” 15.3” (389 mm)
AKS 41U-19.2” 19.2” (488 mm)
AKS 41U-23.1” 23.1” (587 mm)
AKS 41U-30” 30” (762 mm)
AKS 41U-35” 35” (889 mm)
AKS 41U-45” 45” (1143 mm)
AKS 41U-55” 55” (1397 mm)
AKS 41U-65” 65” (1651 mm)
AKS 41U-85” 85” (2159 mm)
AKS 41U-105” 105” (2667 mm)
AKS 41U-120” 120” (3048 mm)
Electronic head (top part) can be removed
from the sensor tube without taking the
sensor tube out of the system.
Il est possible d’enlever la tête
électronique (partie supérieure) du tube
de capteur sans sortir ce tube du système.
El cabezal electrónico (parte superior) se
puede retirar del tubo del sensor sin tener
que retirar el tubo del sensor del sistema.
2 RI5KB55M © Danfoss A/S (RC-CMS / MWA), 01-2005 DIR
Electrical connection
Connexion électrique
Conexion eléctrica
Controller,
Régulateurs,
Controlador
24 V d.c.
or
24 V a.c.
50/60 Hz
24 V a.c.
Measuring range
Plage de mesure
Rango de medida
R717 (NH
3
)
It is not necessary to change the settings.
The factory setting can be used.
Le réglage en usine peut être utilisé et il n'est
donc pas nécessaire de modifier les réglages.
No es necesario cambiar los parámetros.
Se puede utilizar el ajuste de fábrica.
R22 / R404A / R134a/R744 (CO
2
)
Setting the required refrigerant must be made
by following the procedure described in the
next section.
Suivre la procédure décrite dans le chapitre
suivant pour modifier les réglages selon le fluide
frigorigène utilisé.
La calibración para el refrigerante requerido
debe efectuarse siguiendo las instrucciones
mostradas más adelante.
R_ _ _ _
If an alternative refrigerant is used to those
listed, revised calibration of the level transmitter
is required. Please contract Danfoss.
Si vous utilisez un fluide frigorigène qui ne figure
pas sur la liste, une modification du calibrage du
transmetteur de niveau est nécessaire. Veuillez
contacter Danfoss.
Si se utilizan otros refrigerantes no relacio-
nados aquí, se requiere una nueva calibración
del transmisor de nivel. Consultar a Danfoss.
Factory setting:
The rod comes factory calibrated for R717
(NH
3
), so that it will cover 4 to 20 mA
throughout the rod’s whole measuring range.
Any disturbances in connection with the level
measurement will be damped internally.
Réglages en usine :
La tige est calibrée en usine pour le fluide
frigorigène R 717 (NH
3
) de façon à transmettre
un signal d'intensité comprise entre 4 et 20
mA sur la plage de mesure complète de la tige.
Toute perturbation dans le cadre de la mesure
de niveau sera amortie intérieurement.
Ajuste de fábrica:
La varilla está calibrada de fábrica para R 717
(NH
3
) con una señal de salida de 4-20 mA, que se
distribuye a lo largo de la longitud de la varilla.
Cualquier perturbación del control de nivel será
amortiguada interiormente.
EKC 347
1.69”
(43 mm)
1.18”
(30 mm)
DIR RI5KB55M © Danfoss A/S (RC-CMS / MWA), 01-2005 3
3 DIN connection
Connexion DIN
Conexión DIN
4 Green LED
DEL verte
LED verde
5 Calibration cover
Couvercle de calibrage
Tapa de calibración
6 Calibration pushbutton
Bouton-poussoir de calibrage
Botón de calibración
7 OPTION: LED Bargraph for indication of
liquid level.
OPTION : bargraph à DEL pour indication de
niveau liquide
OPCIÓN: bargraph LED para la indicación de
nivel de líquido
English
Changing Refrigerant setting
The setting may be carried out before the level
transmitter is mounted in the plant.
1. Before electrically connecting the liquid level
sensor press the calibration pushbotton and
keep it pressed while connecting 24V a.c./ 24 V
d.c. to the sensor and then releasing the
pushbotton.
NOTE!
The setting of the sensor for the actual
refrigerant may be carried out before
the liquid level sensor is installed.
The default setting is R717
2. After releasing the calibration pushbotton
observe the present refrigerant setting and
measure the 4-20 mA output signal on
terminals 2(+) and 3(-).
1 flash of Green LED - output signal is
~ 5 mA = R717 (factory setting)
2 flashes of Green LED - output signal is
~ 6 mA = R22
3 flashes of Green LED - output signal is
~ 7 mA = R404A
4 flashes of Green LED - output signal is
~ 8 mA = R134a
5 flashes of Green LED - output signal is
~ 9 mA = R744
3. Activate the calibration pushbutton to select
required refrigerant. Each activation will cause
AKS 41U to step to next refrigerant according to
below sequence:
~ 5 mA = R717 (factory setting)
~ 6 mA = R22
~ 7 mA = R404A
~ 8 mA = R134a
~ 9 mA = R744
4. When the current corresponds to the required
refrigerant, wait 10 seconds until the green LED
is constant ON (not flashing). This indicates that
the required refrigerant has been selected.
5. To leave the setting mode isolate the voltage
supply to the level transmitter.
Go through step 1, 2 and 5 if you wish to check
the setting.
Signal damping
Signal damping is factory-set at 15 seconds. This
setting can be altered by activating the calibration
pushbutton, while the level probe is in normal
operation. The setting range is 1 to 120 seconds.
Procedure:
1. Connect the supply voltage.
2. Push the calibration pushbutton once for each
second by which you want to increase the
damping. Anytime a calibration is started it will
begin with 1 second signal damping.
Example:
1. push 1 sec.
2. pushes 2 sec.
etc.
120. pushes 120 sec.
121. pushes 120 sec.
Réglage de l'AKS 41
Les réglages peuvent être effectués avant
l’installation du transmetteur de niveau.
1. Avant de mettre sous tension la sonde de
niveau liquide, appuyer sur le bouton-poussoir
de calibrage et le tenir enfoncé tout en
connectant l’alimentation 24 V c.a. / 24 V c.d. à
la sonde ; relâcher ensuite le bouton-poussoir.
Attention !
Respecter impérativement cette
séquence. Si vous mettez le
transmetteur sous tension avant
d’appuyer sur le bouton-poussoir de
calibrage, l’amortissement du signal sera
modifié. Le réglage par défaut est celui du R717.
2. Relâcher le bouton-poussoir de calibrage, puis
noter le réglage actuel du fluide frigorigène et
mesurer l’intensité du signal de sortie 4 - 20 mA
aux bornes 2(+) et 3(-).
1 clignotement de la DEL verte - l'intensité
du signal de sortie est ~ 5 mA = R 717
(réglage en usine)
2 clignotements de la DEL verte - l'intensité
du signal de sortie est ~ 6 mA = R 22
3 clignotements de la DEL verte - l'intensité
du signal de sortie est ~ 7 mA = R 404a
4 clignotements de la DEL verte - l'intensité
du signal de sortie est ~ 8 mA = R 134a
5 clignotements de la DEL verte - l'intensitét
du signal de sortie est ~ 9 mA = R744
3. Activer le bouton-poussoir de calibrage pour
sélectionner le fluide frigorigène choisi. Chaque
pression permet à l’AKS de passer au fluide
frigorigène suivant selon la séquence suivante :
~ 5 mA = R 717 (réglage en usine)
~ 6 mA = R 22
~ 7 mA = R 404a
~ 8 mA = R 134a
~ 9 mA = R744
4. Lorsque l’intensité du courant correspond au
fluide frigorigène choisi, attendre 10 secondes
jusqu’à ce que la DEL verte soit allumée en
permanence (ne clignote plus), ce qui signifie
que le fluide frigorigène choisi a été sélectionné.
5. Pour quitter le mode réglage, mettre hors
tension le transmetteur de niveau. Pour
contrôler les réglages, suivre les étapes 1, 2 et 5.
Amortissement de signal
L’amortissement de signal est réglé en usine à 15
secondes. Ce réglage peut être modifié en activant
le bouton-poussoir de calibrage pendant que la
sonde de niveau est en mode d’exploitation
normale. La plage de réglage sétend de 1 à 120
secondes.
Procédure :
1. Mettre sous tension.
2. Appuyer sur le bouton-poussoir de calibrage
autant de fois que vous souhaitez augmenter la
durée d’amortissement. Tout nouveau calibrage
commencera toujours par une durée
d’amortissement de signal de 1 seconde.
Exemple :
1 x pression 1 seconde
2 x pressions 2 secondes
etc.
120 x pressions 120 secondes
121 x pressions 120 secondes
10 secondes après la dernière pression, la valeur est
enregistrée dans la mémoire et la DEL verte se
remet à clignoter.
Au bout de 10 secondes, une nouvelle pression
fait passer l’amortissement de signal à 1 seconde
(si le réglage de l’amortissement est trop élevé,
redémarrer la procédure à partir de l’étape 1).
Réglage des points de calibrage minimum et
maximum :
Calibrage du minimum :
1. Amener le niveau du liquide frigorigène au
niveau minimal souhaité.
2. Appuyer sur le bouton-poussoir de calibrage et
le tenir enfoncé pendant 5 secondes environ,
jusqu’à ce que la DEL verte s’arrête de clignoter.
3. Appuyer une fois sur le bouton-poussoir
de calibrage dans un délai de 10 secondes (si
le bouton-poussoir de calibrage nest pas activé
dans ce délai, l’appareil quitte automatiquement
le mode étalonnage et revient au mode
d’exploitation normale).
La DEL verte s’allume pendant quelques secondes,
puis se met à clignoter.
La sortie est désormais de 4 mA et lAKS 41 ou 41U
est en mode d’exploitation normale.
Français
10 seconds after the last push, the value will be
saved in the memory and the green LED will start
flashing again.
After 10 seconds, a further push will change the
signal damping to 1-second. (If the damping
setting is set too high, restart the procedure from
step 1).
Adjusting the min. /max. calibration points:
Min. calibration:
1. Bring the refrigerant liquid level to desired
minimum level.
2. Press the calibration pushbutton and keep it
activated in approx. 5 seconds, until green LED
stopps flashing.
3. Activate, within the next 10 seconds, the
calibration pushbutton once (If calibration
pushbutton is not activated within 10 seconds, it
will automatically leave calibration mode and
return to normal operation)
Green LED is ON in a few seconds, and then flashing.
Output is now 4 mA and AKS 41 / 41U is in normal
operation
Max. calibration:
1. Bring the refrigerant liquid level to desired
maximum level.
2. Press the calibration pushbutton and keep it
activated in approx. 5 seconds, until green LED
stopps flashing.
3. Activate, within the next 10 seconds, the
calibration pushbutton twice (If calibration
pushbutton is not activated within 10 seconds, it
will automatically leave calibration mode and
return to normal operation)
Green LED is ON in a few seconds, and then flashing.
Output is now 20 mA and AKS 41 / 41U is in normal
operation
Min. calibration when minimum refrigerant
level must be different from 4 mA:
1. Bring the refrigerant liquid level to desired
minimum level.
2. Press the calibration pushbutton and keep it
activated in approx. 5 seconds, until green LED
stopps flashing.
3. Activate, within the next 10 seconds, the
calibration pushbutton once and keep it
activated. (If calibration pushbutton is not
activated within 10 seconds, it will automatically
leave calibration mode and return to normal
operation)
4. Observe the output mA signal increasing fast
starting at 4 mA.
5. Release the calibration pushbutton when the
output signal is approx. 0.5 mA from the desired
point.
6. All the next activations will increase the output
signal by approx. 0.05 mA
7. Approx. 10 seconds after the latest activation the
LED starts flashing
8. Output now corresponds to the value measured
at the latest activation.
Max. calibration when maximum refrigerant
level must be different from 20 mA:
1. Bring the refrigerant liquid level to desired
maximum level.
2. Press the calibration pushbutton and keep it
activated in approx. 5 seconds, until green LED
stopps flashing.
3. Activate, within the next 10 seconds, the
calibration pushbutton twice and keep it
activated. (If calibration pushbutton is not
activated within 10 seconds, it will automatically
leave calibration mode and return to normal
operation)
4. Observe the output mA signal decreasing fast
starting at 20 mA.
5. Release the calibration pushbutton when the
output signal is approx. 0.5 mA from the desired
point.
6. All the next activations will decrease the output
signal by approx. 0.05 mA
7. Approx. 10 seconds after the latest activation the
LED starts flashing
8. Output now corresponds to the value measured
at the latest activation.
Reset to factory setting
AKS 41 can always be reset to factory setting
regardless of any revised calibration values
1. Press the calibtation pushbutton and keep it
activated in min. 20 sec, until green LED starts
flashing
2. Release calibtation pushbutton
3. When LED starts flashing, reset to factory setting
is completed.
For furter calibration information please see
technical leaflet RD8AA.
4 RI5KB55M © Danfoss A/S (RC-CMS / MWA), 01-2005 DIR
Espanol
Ajuste del AKS 41
El ajuste del sensor para el refrigerante que va a ser
utilizado se debe realizar antes de instalar el sensor
de nivel de líquido.
1. Antes de realizar la conexión eléctrica del sensor
de nivel de líquido presionar el botón de
calibración y mantenerlo pulsado durante la
conexión de 24 V c.a./24 V c.c. al sensor y luego
soltarlo.
Calibrage du maximum :
1. Amener le niveau du liquide frigorigène au
niveau maximal souhaité.
2. Appuyer sur le bouton-poussoir de calibrage et
le tenir enfoncé pendant 5 secondes environ,
jusqu’à ce que la DEL verte s’arrête de clignoter.
3. Appuyer deux fois sur le bouton-poussoir
de calibrage dans un délai de 10 secondes (si
le bouton-poussoir de calibrage nest pas activé
dans ce délai, l’appareil quitte automatiquement
le mode étalonnage et revient au mode
d’exploitation normale).
La DEL verte s’allume pendant quelques secondes,
puis se met à clignoter.
La sortie est désormais de 20 mA et lAKS 41 ou 41U
est en mode d’exploitation normale.
Calibrage du minimum lorsque le niveau
minimum de fluide frigorigène doit être
différent de 4 mA :
1. Amener le niveau du liquide frigorigène au
niveau minimal souhaité.
2. Appuyer sur le bouton-poussoir de calibrage et
le tenir enfoncé pendant 5 secondes environ,
jusqu’à ce que la DEL verte s’arrête de clignoter.
3. Appuyer une fois sur le bouton-poussoir
de calibrage dans un délai de 10 secondes et
le tenir enfoncé (si le bouton-poussoir de
calibrage nest pas activé dans ce délai, l’appareil
quitte automatiquement le mode étalonnage et
revient au mode d’exploitation normale).
4. Noter la hausse rapide du signal de sortie à partir
de 4 mA.
5. Relâcher le bouton-poussoir de calibrage lorsque
le signal de sortie est à 0,5 mA environ du point
souhaité.
6. Chaque nouvelle activation permet d’augmenter
le signal de sortie de 0,05 mA environ.
7. La DEL se met à clignoter 10 secondes environ
après la dernière activation.
8. La sortie correspond désormais à la valeur
mesurée lors de la dernière activation.
Calibrage du maximum lorsque le niveau
maximum de fluide frigorigène doit être
différent de 20 mA :
1. Amener le niveau du liquide frigorigène au
niveau maximal souhaité.
2. Appuyer sur le bouton-poussoir de calibrage et
le tenir enfoncé pendant 5 secondes environ,
jusqu’à ce que la DEL verte s’arrête de clignoter.
3. Appuyer deux fois sur le bouton-poussoir
de calibrage dans un délai de 10 secondes et
le tenir enfoncé (si le bouton-poussoir de
calibrage nest pas activé dans ce délai, l’appareil
quitte automatiquement le mode étalonnage et
revient au mode d’exploitation normale).
4. Noter la baisse rapide du signal de sortie à partir
de 20 mA.
5. Relâcher le bouton-poussoir de calibrage lorsque
le signal de sortie est à 0,5 mA environ du point
souhaité.
6. Chaque nouvelle activation permet de diminuer
le signal de sortie de 0,05 mA environ.
7. La DEL se met à clignoter 10 secondes environ
après la dernière activation.
8. La sortie correspond désormais à la valeur
mesurée lors de la dernière activation.
Réinitialisation aux réglages en usine
LAKS 41 peut toujours être réinitialisé aux réglages
en usine indépendamment des modifications
apportées aux valeurs de calibrage.
1. Appuyer sur le bouton-poussoir de calibrage et
le tenir enfoncé pendant au moins 20 secondes,
jusqu’à ce que la DEL verte se mette à clignoter
2. Relâcher le bouton-poussoir de calibrage
3. Lorsque la DEL se met à clignoter, la
réinitialisation aux réglages en usine est achevée.
Si vous souhaitez obtenir des informations
complémentaires sur le calibrage, veuillez vous
reporter à la brochure technique RD8AA.
¡Precaución!
La secuencia se debe de cumplir. Si se
conecta la tensión antes de activar el
botón, la señal de amortiguación
cambiará. El ajuste por defecto es R717.
2. Soltar el botón de calibración, comprobar el
ajuste del refrigerante utilizado y medir la señal
de salida de 4-20 mA a los terminales 2(+) y 3(-).
El LED verde parpadea 1 vez - la señal de
salida es de 5 mA = R 717 (ajuste de fábrica)
El LED verde parpadea 2 veces - la señal de
salida es de 6 mA = R 22
El LED verde parpadea 3 veces - la señal de
salida es de 7 mA = R 404A
El LED verde parpadea 4 veces - la señal de
salida es de 8 mA = R 134a
El LED verde parpadea 4 veces - la señal de
salida es de 9 mA = R744
3. Activar el botón de calibración para seleccionar
el refrigerante requerido. Cada pulsación del
botón hará que el AKS 41U seleccione
escalonadamente el siguiente refrigerante de la
lista, de acuerdo con la siguiente secuencia:
~ 5 mA = R 717 (ajuste de fábrica)
~ 6 mA = R 22
~ 7 mA = R 404A
~ 8 mA = R 134a
~ 9 mA = R744
4. Cuando la intensidad corresponde al refrigerante
requerido, esperar 10 segundos hasta que el LED
verde permanezca encendido (sin parpadear).
Esto indica que el refrigerante requerido ha sido
seleccionado.
5. Para salir de la sección de ajustes, cortar el
suministro de corriente al transductor de nivel. Si
se desea comprobar el ajuste, seguir los puntos 1,
2 y 5.
Amortiguación de señal
El ajuste de fábrica de la amortiguación de señal
es de 15 segundos. Se puede modificar este ajuste
mediante la activación del botón de calibración,
mientras la sonda de nivel se encuentra en
funcionamiento normal. El intervalo de ajuste es de
1 a 120 segundos.
Procedimiento:
1. Conectar la alimentación.
2. Pulsar el botón de calibración una vez para cada
segundo que se quiere aumentar el tiempo de
amortiguación. El inicio de una calibración
siempre comenzará con una señal de
amortiguación de 1 segundo.
Ejemplo:
1 x pulsación
1 seg.
2 x pulsaciones
2 seg.
etc.
120 x pulsaciones
120 seg.
121 x pulsaciones
120 seg.
10 segundos después de la última pulsa-ción, el valor
se grabará en la memoria, y el LED verde comenzará
a parpadear de nuevo.
Después de 10 segundos, una pulsación adicional
cambiará la amortiguación de señal a 1 segundo. (Si
el ajuste de amortiguación se ha establecido muy
alto, reinicie el procedimiento desde el paso 1).
Ajuste de los puntos máx. y mín de calibración:
Punto mín. de calibración:
1. Ajustar el nivel del líquido refrigerante al nivel
mínimo deseado.
2. Pulsar el botón de calibración y mantenerlo
activado durante 5 seg. aprox., hasta que deje de
parpadear el LED verde.
3. Activar una vez el botón pulsador de calibración
en los próximos 10 segundos (Si no se activa
el botón pulsador antes de transcurridos 10
segundos, el sistema saldrá automáticamente del
modo de calibración y regresará al modo normal
de funcionamiento)
El LED verde se enciende unos pocos segundos, y
después parpadea.
La salida es ahora 4 mA y el AKS 41 / 41U ya se
encuentra en modo de funcionamiento normal.
Punto máx. de calibración:
1. Ajustar el nivel del líquido refrigerante al nivel
máximo deseado.
2. Pulsar el botón de calibración y mantenerlo
activado durante 5 seg. aprox., hasta que deje
de parpadear el LED verde.
3. Activar dos veces el botón pulsador de
calibración en los próximos 10 segundos (Si no
se activa el botón pulsador antes de
transcurridos 10 segundos, el sistema saldrá
automáticamente del modo de calibración y
regresará al modo normal de funcionamiento)
El LED verde se enciende unos pocos segundos, y
después parpadea.
La salida es ahora 20 mA y el AKS 41 / 41U ya se
encuentra en modo de funcionamiento normal.
Calibración mínima cuando el nivel del
refrigerante debe ser distinto de 4 mA:
1. Ajustar el nivel del líquido refrigerante al nivel
mínimo deseado.
2. Pulsar el botón de calibración y mantenerlo
activado durante 5 seg. aprox., hasta que deje
de parpadear el LED verde.
3. Activar, antes de transcurridos 10 segundos, el
botón pulsador de calibración una vez y
mantenerlo activado. (Si no se activa el botón
pulsador antes de transcurridos 10 segundos,
el sistema automáticamente saldrá del modo de
calibración y regresará al modo de funciona-
miento normal).
4. Observar la señal de salida de mA aumentar
rápidamente desde 4 mA.
5. Soltar el botón de calibración cuando la señal
de salida se encuentre aprox. a 0.5 mA del punto
deseado.
6. Todas las nuevas activaciones aumentarán la
señal de salida en aproximadamente 0.05 mA.
7. Aprox. 10 segundos después de la última
activación el LED comenzará a parpadear.
8. La salida ahora corresponde al valor medido en
la última activación.
Calibración máxima cuando el nivel del
refrigerante debe ser distinto de 20 mA:
1. Ajustar el nivel del líquido refrigerante al nivel
máximo deseado.
2. Pulsar el botón de calibración y mantenerlo
activado durante 5 seg. aprox., hasta que deje
de parpadear el LED verde.
3. Activar, antes de transcurridos 10 segundos,
el botón pulsador de calibración dos veces
y mantenerlo activado. (Si no se activa el botón
pulsador antes de transcurridos 10 segundos,
el sistema automáticamente saldrá del modo de
calibración y regresará al modo de funciona-
miento normal).
4. Observar la señal de salida de mA al reducirse
rápidamente desde 20 mA.
5. Soltar el botón de calibración cuando la señal
de salida se encuentre aprox. a 0.5 mA del punto
deseado.
6. Todas las nuevas activaciones reducirán la señal
de salida en aprox. 0.05 mA.
7. Aprox. 10 segundos después de la última
activación el LED comenzará a parpadear.
8. La salida ahora corresponde al valor medido en
la última activación.
Reajuste al ajuste de fábrica
No obstante los valores de calibración revisados,
siempre es posible reajustar el AKS 41 al ajuste de
fábrica.
1. Pulsar el botón de calibración y mantenerlo
activado durante 20 seg. como mínimo, hasta
que comience a parpadear el LED verde.
2. Soltar el botón de calibración.
3. Cuando el LED comienza a parpadear, el
reajuste al ajuste de fábrica está terminado.
Para obtener informaciones de calibración
adicionales, véase el folleto técnico RD8AA.