Echoflex Installation Guide
LED Fixture Controller 240–377 VAC
LED Fixture Controller 240–377 VAC Page 6 of 8 Echoflex
Controller Interface
The controller interface has two LEDs and two buttons.
LEDs
The Power LED (red) and Learn LED (green) indicate whether the controller is
providing information via blink codes or is in an operational mode. See
Blink Codes and Operations on page 7.
Learn Button
The [Learn] button initiates Link mode for linking switches or sensors to the
controller. See the relevant switch or sensor documentation for information
on linking. Link mode times out after 30 seconds of inactivity.
Repeating the linking process for a device that is already linked to a
controller will unlink it from that controller.
Clear Button
The [Clear] button resets the controller either to its pre-commissioned state
or to its factory default state.
To reset to pre-commissioned state:
1. Press the [Clear] button until the Power and Learn LEDs start blinking.
2. Release the [Clear] button. The Power LED blink codes indicate the
type and count of devices linked at pre-commissioning.
To reset to factory default state:
1. Press and hold the [Clear] button until the Power and Learn LEDs start
blinking and continue to hold for 15 seconds until the LEDs turn solid.
2. Release the [Clear] button. The Power LED displays solid red to
indicates factory default state. All links are removed.
Test the Controller
Echoflex provides the controller in either a pre-commissioned state or a
factory default state.
• Pre-commissioned devices are linked, configured, and labelled
according to customer specifications. When powered up, the Power
LED repeats a blink code to indicate the type and number of devices
currently linked to the controller. See Blink Codes and Operations
on page 7. To test the relay(s), press the [Learn] button or use a
linked switch.