Lumination LPL Series ISO5 Guide d'installation

Taper
Guide d'installation
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 1 of 4
(Rev 4/19/23)
IND674-LPL-Gen-C-ISO5-Series-Installation-Guide_R01
Installation Guide
IND674 | A-1027244
BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING / AVERTISSEMENT
RISK OF ELECTRIC SHOCK
• Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL approved wire for input/output connections.
Minimum size 18 AWG (0.75mm2).
• Do not install insulation within 3 inches (76 mm) of luminaire top.
Prepare Electrical Wiring
Electrical Requirements
• The LED luminaire must be connected to the mains
supply according to its ratings on the product label.
• Class 1 wiring should be in accordance with NEC.
Grounding Instructions
• The grounding and bonding of the overall system
shall be done in accordance to local electric code of
the country where the luminire is installed.
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des ls approuvés par UL pour les entrées/sorties de connexion.
Taille minimum 18 AWG (0.75mm2).
• Maintenir une distance de 76 mm (3 pouces) entre le luminaire et l’isolant.
Save These Instructions
Use only in the manner intended by the manufacturer.
If you have any questions, contact the manufacturer.
Lumination® LED Luminaire
LPL Gen C ISO5 Series
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
CAN ICES-005(A)/NMB-005(A)
Note: This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 2 of 4
(Rev 4/19/23)
IND674-LPL-Gen-C-ISO5-Series-Installation-Guide_R01
Lumination® LPL Gen C ISO5 Series Installation Guide
Carefully unpack unit from its packaging. Properly
inspect for defects before installing. Wear work
gloves to prevent dirt and oil from being
transferred to the luminaire.
Cut gasket to size from supplemental gasket kit. Install
appropriately sized pieces in the T grid (IMPORTANT NOTES:
Ensure tape pieces butt together, creating a complete seal
around the perimeter of the T grid. Ensure tape lines inner
edge of T grid, leaving little to no overhang of the tape over
the T grid).
1
L M H CCT
2BY2: 2360lm 3670lm 4290lm 3500k/4000k
2BY4: 3180lm 4190lm 4830lm 3500k/4000k
Luminaire Installation
Remove the xture from the package. Default lumen level
is H(high), default CCT is 4000K. If a lumen level other than
H(high) is desired, or CCT other than 4000K is preferred,
remove switch cover and set to the desired lumen level, or
preferred CCT by screwdriver, then re-attach cover.
2
3
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 3 of 4
(Rev 4/19/23)
IND674-LPL-Gen-C-ISO5-Series-Installation-Guide_R01
Lumination® LPL Gen C ISO5 Series Installation Guide
T-Bar
Bracket on
Safety cable hole
backplate
Insert luminaire into T-bar ceiling grid. Press down
on unit so that it is completely sealed with the T grid.
Unit should not move freely within the ceiling grid.
To ensure a consistent appearance, align xtures in the
same orientation throughout the ceiling pattern.
4
Bend the brackets on the back plate to make sure
they hook to T-Bar.
Secure safety cable to connection hole as needed to
meet local seismic requirements. Safety cable and
method of attachment to the building are provided
by contractor according to local building codes.
5
LPL22x SeriesLPL24x Series
LED.com
© 2023 Current Lighting Solutions, LLC. All rights reserved. Information and specifications subject to change
without notice. All values are design or typical values when measured under laboratory conditions.
Page 4 of 4
(Rev 4/19/23)
IND674-LPL-Gen-C-ISO5-Series-Installation-Guide_R01
Lumination® LPL Gen C Series Installation Guide
Electrical Connections
Remove electrical enclosure cover. Carefully
remove knockout for AC line input wires. Install
listed electrical ttings in the knockout holes for
wire protection.
1
Connect the AC line to the black (line) and white
(neutral) input wires of the LED driver using
18-14 AWG twist-on wire connectors. Connect the
ground wire to the green-yellow ground wire of the
LED driver. When connecting dimming controller,
wires must run through a separate knockout hole
equipped with an appropriate wire restraint or cable
gland. Then, re-attach and x enclosure cover with
screw by screw driver.
2
Option for Step 2: Follow diagram for 0-10V. Run wires from controller through a different knockout than the AC
input wire. At output side of xture, make appropriate connections using twist-on wire connectors. To combine
with LFAMBA0VQFAEL, LCAMBA0NRFAEL, LCAMBA0TSFAEL, LCAMBA0TQFAEL, LFAMBADVQFA, LCAMBA0NRFAB2,
LCAMBA0TSFAB2, LCAMBA0TQFAB2, LCAMBA0NRFA, LCAMBA0TSFA or LCAMBA0TQFA, please follow the install
instructions provided with those products.
NOTE: Please cover dimming leads with wire nuts if you will not connect with dimming leads.
3
Black To AC Main
White
Green/Yellow
Violet
Grey
Line
Neutral
Ground
1-10V(+)
1-10V(-)
Fixture
To 0-10V
Dimmer
Optional Installation: 0-10V Volt Dimming
Pink
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Lumination LPL Series ISO5 Guide d'installation

Taper
Guide d'installation

dans d''autres langues