• Attach the included strain relief to opposite side
of junction box. (The included strain relief is rated
for 0.225 to 0.612 inch diameter wiring. If a dif-
ferent form of wiring is used, please refer to all
electric codes and purchase a closed strain relief
to meet the requirements.)
• Without adjusting the terminal screws, insert
the wires properly in the terminal. Make sure
that the black wire connects with the black (L)
and the white connects with the white (N) and
the green or bare copper wire with the green (G
or ). (See box 2b)
• Do NOT insert wire underneath the screw clamp.
(see box 2a)
• Be certain the wire insulation is not trapped in
the terminal. 1-2 mm of wire must be visible (See
box 2b)
• After inserting wire, completely tighten the termi-
nal screws by turning clockwise. (See box 2c)
• After tightening the terminal screws, pull on each
wire to ensure that they are secure. Wire should
not be loose in the terminal after correct instal-
lation.
• Secure the wire in the junction box with the strain
relief.
Note: The arrow (shown in box 2d above) should
align with the power cord.
ab
1-2 mm
ADVERTENCIA
WARNING
AVERTISSEMENT
STRICTLY FOLLOW ALL INSTRUCTIONS IN THIS MANUAL.
USE ONLY 14 OR 12 AWG COPPER WIRE WITH A MIN. TEMP. RATING
OF 75°C (167°F).
PLACE ALL WIRING IN THE POWER SUPPLY BOX AND INSTALL COVER.
CONNECTION SCREWS ARE NOT REMOVABLE.
ESTRICTAMENTE SIGA TODAS LAS INSTRUCCIONES DE ESTE MANUAL.
UTILICE SÓLO EL 14 O 12 DE ALAMBRE DE COBRE AWG CON UN GRADO
DE LA TEMPERATURA MÍNIMA DE 75 ° C (167 ° F).
COLOQUE TODOS LOS CABLES EN LA CAJA DE LA FUENTE DE ALIMEN-
TACIÓN Y LA INSTALACIÓN DE LA CUBIERTA. TORNILLOS DE CONEXIÓN
NO SON EXTRAIBLES.
WIRE STRIP GAGE
1/2" (13 mm)
CALIBRE DE POUR DÉNUDER
INDICADOR DE CABLE PELADO
OBSERVER TOUTES LES INSTRUCTIONS DE CE GUIDE.
UTILISER SEULEMENT DU FIL DE CUIVRE 14 OU 12 AWG AVEC UNE
COTE DE TEMPÉRATURE MINIMALE DE 75°C (167°F).
PLACER TOUS LES FILS DANS LA BOÌTE D‘ALIMENTATION ET
REMETTRE LE COUVERCLE.
LES VIS DE CONNEXIONS NE SONT PAS AMOVIBLES.
view with cover installed
arrow
strain relief
black (L)
white (N) green (G)
2
2" - 3"
(51 mm - 76 mm)
3/8" - 1/2"
(10 mm - 13 mm)
1. Turn off any electricity to installation area.
2. Remove screws and cover from junction box and
set aside for later use.
3. Remove outer casing and insulation of the hardwir-
ing as shown in Fig. 1.
1
WARNING
To Reduce the Risk of Electrical Shock or Fire:
Carefully follow the installation instructions.
Do not remove, alter or bypass the terminal block.
Do not use an extension cord or adapter with this
part.
Do not cut or splice the cord.
Do not alter this part in any way.
Use the metal strain relief per instructions.
This kit is for hard-wired installations only. To plug
into an outlet, use the power cord supplied with the
unit.