Wiremold 1500 & 2600 Series Steel Pancake Overfloor Raceway Guide d'installation

Taper
Guide d'installation
Wiremold Electrical Systems conform to and should be installed and properly grounded in compliance with
requirements of the current National Electrical Code, Canadian Electrical Code or codes administered by local
authorities.
All electrical products may represent possible shock or fire hazard if improperly installed or used. Wiremold
electrical products are UL Listed, made for interior use only, and should be installed in conformance with current
local and/or the National Electrical Code.
Los Sistemas Eléctricos Wiremold cumplen con los requisitos del Código Nacional Eléctrico, el Código Canadiense
Eléctrico o los códigos vigentes administrados por autoridades locales, así mismo deben instalarse y conectarse a
tierra en la forma debida siguiendo los requisitos de los códigos antes mencionados.
Todos los productos eléctricos pueden provocar posibles choques o peligros de incendio si se instalan o usan de
manera indebida. Los productos eléctricos Wiremold están registrados bajo el cUL, se fabrican sólo para uso en
interiores y deben instalarse de acuerdo con el Código Nacional Eléctrico y cualquier otro código vigente.
Les Systèmes électriques Wiremold se conforment aux versions actuelles du Code national de l’électricité, du Code
canadien de l’électricité ou des règlementés par les autorités locales, et doivent être installés et correctement mis à
la terre les exigences du code approprié.
Tout produit électrique peut présenter un danger de choc électrique ou d’incendie s’il n’est pas installé ou utilisé
correctement. Les produits électriques de Wiremold sont répertoriés par les Laboratoires des Assureurs du
Canada (LAC), ne sont destinés qu’à l’usage intérieur et doivent être installés conformemént aux versions
actuelles des règlements locaux et/ou du Code national de l’électricité.
2400 SERIES RACEWAY
1500 & 2600 SERIES
PANCAKE RACEWAY
656, 1500R, 1542D,
2642D, 2686FO
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 42428 – January 2003
2400
7/8"
[22.2mm]
1 29/32"
[48mm]
1.39in
2
[897mm
2
]
2600
22/32"
[18.3mm]
2 7/32"
[56.6mm]
0.72in
2
[465mm
2
]
1500
11/32"
[8.8mm]
1 9/16"
[39mm]
0.22in
2
[142mm
2
]
CABLE/WIRE O.D. (Approx. Dia)
SIZE Inches [mm] 20% FILL* 40% FILL**
UNSHIELDED Cat 3 0.190 [4.8] 9 19
TWISTED PAIR Cat 5e 0.210 [5.3] 8 16
Cat 6 0.250 [6.3] 5 11
TELEPHONE 2-pair, 0.140 [3.6] 18 36
3-pair, 0.150 [3.8] 15 31
4-pair, 0.190 [4.8] 9 19
25-pair, 0.410 [10.4] 2 4
COAXIAL RG58/U 0.195 [5.0] 9 18
RG59/U 0.242 [6.1] 6 12
RG62/U 0.242 [6.1] 6 12
RG6/U 0.270 [6.9] 4 9
TWINAXIAL 100 Ohm 0.330 [8.4] 3 6
SHIELDED TYPE 1 0.390 [9.9] 2 4
TWISTED PAIR TYPE 2 0.465 [11.8] 1 3
TYPE 3 0.245 [6.2] 5 11
FIBER Mini ZipCord 0.079 x 0.157 [2 x 4] 22 44
ZipCord 0.118 x 0.236 [3 x 6] 10 20
Round 4 Strand Fiber 0.187 [4.8] 10 20
Round 6 Strand Fiber 0.256 [6.5] 5 10
NUMBER OF CONDUCTORS (40% FILL)
WIRE SIZE O.D.
WITHOUT DEVICES WITH 2427
THHN/THWN Inches [mm]
RECEPTACLE
14 AWG 0.111 [2.8] 57 12
12 AWG 0.130 [3.3] 41 9
10 AWG 0.164 [4.2] 26
2400 RACEWAY WIRE FILL CAPACITIES FOR POWER
2400 RACEWAY WIRE FILL CAPACITIES FOR COMMUNICATIONS
CABLE/WIRE O.D. (Approx. Dia)
SIZE Inches [mm] 20% FILL* 40% FILL**
UNSHIELDED Cat 3 0.190 [4.8] 1 3
TWISTED PAIR Cat 5e 0.210 [5.3] 1 2
Cat 6 0.250 [6.3] 0 1
TELEPHONE 2-pair, 0.140 [3.6] 2 5
3-pair, 0.150 [3.8] 2 4
4-pair, 0.190 [4.8] 1 3
25-pair, 0.410 [10.4] 0 0
COAXIAL RG58/U 0.195 [5.0] 1 2
RG59/U 0.242 [6.1] 0 1
RG62/U 0.242 [6.1] 0 1
RG6/U 0.270 [6.9] 0 1
TWINAXIAL 100 Ohm 0.330 [8.4] 0 1
SHIELDED TYPE 1 0.390 [9.9] 0 0
TWISTED PAIR TYPE 2 0.465 [11.8] 0 0
TYPE 3 0.245 [6.2] 0 1
FIBER Mini ZipCord 0.079 x 0.157 [2 x 4] 3 7
ZipCord 0.118 x 0.236 [3 x 6] 1 3
Round 4 Strand Fiber
0.187 [4.8] 1 3
Round 6 Strand Fiber
0.256 [6.5] 0 1
1500 RACEWAY WIRE FILL CAPACITIES FOR COMMUNICATIONS
NUMBER OF
WIRE SIZE O.D. CONDUCTORS
THHN/THWN Inches [mm] (40% FILL)
14 AWG 0.111 [2.8] 29
12 AWG 0.130 [3.3] 21
10 AWG 0.164 [4.2] 13
2600 RACEWAY WIRE FILL CAPACITIES FOR POWER
NUMBER OF
WIRE SIZE O.D. CONDUCTORS
THHN/THWN Inches [mm] (40% FILL)
14 AWG 0.111 [2.8] 9
12 AWG 0.130 [3.3] 6
10 AWG 0.164 [4.2] 3
1500 RACEWAY WIRE FILL CAPACITIES FOR POWER
CABLE/WIRE O.D. (Approx. Dia)
SIZE Inches [mm] 20% FILL* 40% FILL**
UNSHIELDED Cat 3 0.190 [4.8] 5 10
TWISTED PAIR Cat 5e 0.210 [5.3] 4 8
Cat 6 0.250 [6.3] 2 5
TELEPHONE 2-pair, 0.140 [3.6] 9 18
3-pair, 0.150 [3.8] 8 16
4-pair, 0.190 [4.8] 5 10
25-pair, 0.410 [10.4] 1 2
COAXIAL RG58/U 0.195 [5.0] 4 9
RG59/U 0.242 [6.1] 3 6
RG62/U 0.242 [6.1] 3 6
RG6/U 0.270 [6.9] 2 5
TWINAXIAL 100 Ohm 0.330 [8.4] 1 3
SHIELDED TYPE 1 0.390 [9.9] 1 2
TWISTED PAIR TYPE 2 0.465 [11.8] 0 1
TYPE 3 0.245 [6.2] 3 6
FIBER Mini ZipCord 0.079 x 0.157 [2 x 4] 11 23
ZipCord 0.118 x 0.236 [3 x 6] 5 10
Round 4 Strand Fiber
0.187 [4.8] 5 10
Round 6 Strand Fiber
0.256 [6.5] 2 5
2600 RACEWAY WIRE FILL CAPACITIES FOR COMMUNICATIONS
The Wiremold Company
U.S. and International:
60 Woodlawn Street • West Hartford, CT 06110
1-800-621-0049 • FAX 860-232-2062 • Outside U.S. 860-233-6251
Canada:
850 Gartshore Street • Fergus, Ontario N1M 2W8
1-800-741-7957 • FAX 519-843-5980
42428 – January 2003 – For latest specs visit www.wiremold.com
© Copyright 2003 The Wiremold Company All Rights Reserved
2686FO
SIZE TYPE FEEDING 2400
14 AWG THHN 35
12 AWG THHN 26
10 AWG THHN 16
WIRE FILL CAPACITY FOR POWER
2400
1500, 2600
656
2686FO
1500R 1542D, 2642D
2400B
24"
[600mm]
Max
2400C
1
2
1500R
1500
2600
1
2
24"
[600mm]
Max
656
1500
2600
1500
2600
2400
2400
1500
2600
1500
2600
2400
NOTE: Use a #8 [5/16", 7.9mm Head Size] Pan Head Screw or equivalent.
Use un tornillo de cabeza redonda N° 8 (con cabeza de 7.9mm [5/16"] o equivalente.
Utilisez une vis BER n°8 (tête do 7,9mm [5/16 po]) ou équivalent.