Eaton 5SC 750G Manuel utilisateur

Catégorie
Alimentations sans interruption (UPS)
Taper
Manuel utilisateur

Ce manuel convient également à

5SC 500G
5SC 500
5SC 750
5SC 1000
5SC 1500
User's guide
English - Français
Español - Português
5SC 750G
5SC 1500G
2
ENGLISH
5SC 500
5SC 750
5SC 1000
5SC 1500
5SC 500G
5SC 750G
5SC 1500G
Copyright © 2013 EATON
All rights reserved.
Service and support:
Call your local service representative
Installation
619-00470-02 -us (en)
619-00470-02-us (en)
Page 2
619-00470-02-us (en)
Page 3
ENGLISH
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
Important instructions that must always be followed.
Do not discard the UPS or the UPS batteries in the trash.
This product contains sealed lead acid batteries and must be disposed as it's explain in this manual.
For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE)
in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
Information, advice, help.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions
that should be followed during installation and maintenance of the UPS and batteries.
The 5SC models that are covered in this manual are intended for installation in an environment
within 0 to 35 °C / 32 to 95 °F, free of conductive contaminant.
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of
this equipment in a residential area is likely to cause harmful interference in which case the user will
be required to correct the interference at his own expense.
Certication Standards
• UPS directives: UL 1778 4
th
edition (UL listed).
• Performance: IEC 62040-3: 2001.
• Radiated emission: FCC CFR 47 part 15 subpart B, Class A, VCCI.
• Surges withstand ability: IEEE ANSI C62.41 Category A2 (UL Listed).
VCCI Notice
Page 4
Safety of Persons
• The system has its own power source (the battery). Consequently, the power outlets may be energized
even if the systems is disconnected from the AC power source.
• Dangerousvoltagelevelsarepresentwithinthesystem.Itshouldbeopenedexclusivelybyqualied
service personnel.
• The system must be properly grounded.
• The battery supplied with the system contains small amounts of toxic materials.
To avoid accidents, the directives listed below must be observed:
- servicing of batteries should be performed or supervised by personnel knowledgeable about betteries
and the required precautions.
- when replacing batteries, replace with the same type and number of batteries or battery packs.
-donotdisposeofbatteriesinare.Thebatteriesmayexplode.
- batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
Precautions must be taken for all handling:
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock
can be reduced if such grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply circuit).
Product Safety
• The UPS connection instructions and operation described in the manual must be followed in
the indicated order.
• A protection circuit breaker must be installed upstream and be easily accessible.
The system can be disconnected from the AC power source by opening this circuit breaker.
• Check that the indications on the rating plate correspond to your AC powered system and to
the actual electrical consumption of all the equipment to be connected to the system.
• For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall
be easily accessible
• Never install the system near liquids or in an excessively damp environment.
• Never let a foreign body penetrate inside the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The admissible storage temperature range is -15 to +40 ºC / 5 to 104 °F.
• The system is not for use in a computer room.
Special Precautions
• All handling operations will require at least two people (unpacking, installation in rack system).
• Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be
energized for a period of 24 hours, at least once every 6 months (for a normal storage temperature
less than 25 °C / 77 °F). This charges the battery, thus avoiding possible irreversible damage.
• During the replacement of the Battery Module, it is imperative to use the same type and number of
element as the original Battery Module provided with the UPS to maintain an identical level of
performance and safety. In case of doubt, don’t hesitate to contact your EATON representative.
619-00470-02-us (en)
619-00470-02-us (en)
Page 5
ENGLISH
Contents
1. Introduction ....................................................................................... 6
1.1 Environmental protection ...................................................................................................6
2. Presentation ...................................................................................... 7
2.1 Standard installation ..........................................................................................................7
2.2 Rear panels ........................................................................................................................ 7
2.3 Control panel .....................................................................................................................8
2.4 LCD description .................................................................................................................8
2.5 UPS setting through the LCD ............................................................................................9
3. Installation ...................................................................................... 10
3.1 Unpacking and contents check ........................................................................................ 10
3.2 Battery module connection ............................................................................................. 10
3.3 Communication ports ..................................................................................................... 11
4. Operation......................................................................................... 12
4.1 Start-up and Normal operation ......................................................................................... 12
4.2 Starting the UPS on Battery ............................................................................................12
4.3 UPS Shutdown ................................................................................................................12
4.4 Operation on Battery Power ............................................................................................12
4.5 Return of AC Input Power ................................................................................................ 12
5. Maintenance ................................................................................... 13
5.1 Troubleshooting ................................................................................................................ 13
5.2 Battery-module replacement ........................................................................................... 14
6. Appendices ...................................................................................... 15
6.1 Technical specications .................................................................................................... 15
Page 6
1. Introduction
Thank you for selecting an EATON product to protect your electrical equipment.
The 5SC range has been designed with the utmost care.
We recommend that you take the time to read this manual to take full advantage of the many features
of your UPS (Uninterruptible Power System).
Before installing your 5SC, please read the booklet presenting the safety instructions.
Then follow the instructions in this manual.
To discover the entire range of EATON products and the options available for the 5SC range,
we invite you to visit our web site at www.eaton.com/powerquality or contact your EATON representative.
1.1 Environmental protection
EATON has implemented an environmental-protection policy.
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
• The cardboard we use comprises over 50% of recycled cardboard.
• Sacks and bags are made of polyethylene.
• Packingmaterialsarerecyclableandbeartheappropriateidenticationsymbol
01
PET
Materials Abbreviations Number in
the symbols
Polyethylene terephthalat PET 01
High-density polyethylene HDPE 02
Polyvinyl chloride PVC 03
Low-density polyethylene LDPE 04
Polypropylene PP 05
Polystyrene PS 06
Follow all local regulations for the disposal of packing materials.
End of life
EATON will process products at the end of their service life in compliance with local regulations.
EATON works with companies in charge of collecting and eliminating our products at the end of
their service life.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing center for electrical and
electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations
concerning batteries.
The battery may be removed to comply with regulations and in view of correct disposal.
01
PET
619-00470-02-us (en)
619-00470-02-us (en)
Page 7
ENGLISH
2. Presentation
2.1 Standard installation
D
H
W
Description Weights
(lb/kg)
Dimensions (inch/mm)
D x W x H
5SC 500 15.0 / 6.8 9.4 x 5.9 x 8.3 / 240 x 150 x 210
5SC 750 23.6 / 10.7 13.4 x 5.9 x 8.3 / 340 x 150 x 210
5SC 1000 25.1 / 11. 4 13.4 x 5.9 x 8.3 / 340 x 150 x 210
5SC 1500 34.4 / 15.6 16.1 x 5.9 x 8.3 / 410 x 150 x 210
5SC 500G 14.6 / 6.6 9.4 x 5.9 x 8.3 / 240 x 150 x 210
5SC 750G 22.9 / 10.4 13.4 x 5.9 x 8.3 / 340 x 150 x 210
5SC 1500G 33.5 / 15.2 16.1 x 5.9 x 8.3 / 410 x 150 x 210
2.2 Rear panels
5SC 500 5SC 750
INPUT
OUTPUT
RS232 OR
5
3
4
1
2
Refer to the Bottom of
the unit for caution markings!
INPUT
OUTPUT
OUTPUT
RS232 OR
5
3
4
1
2
Refer to the Bottom of
the unit for caution markings!
5SC 1000 5SC 1500
INPUT
OUTPUT
OUTPUT
RS232 OR
Refer to the Bottom of
the unit for caution markings!
5
3
4
1
2
INPUT
OUTPUT
RS232 OR
Refer to the Bottom of
the unit for caution markings!
5
3
4
1
2
(1) USB communication port
(2) RS232 communication port
(3) Outlets for connection of critical equipment
(4) Attached 6 ft. input power cord for AC-power source
(5) Ground screw
Page 8
2. Presentation
2.2 Rear panels
5SC 500G 5SC 750G
INPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
RS232 OR
5
4
3
2
1
INPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
RS232 OR
5
4
3
2
1
5SC 1500G
INPUT
OUTPUT
Refer to the Bottom of
the unit for caution markings!
RS232 OR
5
4
3
2
1
(1) USB communication port
(2) RS232 communication port
(3) Outlets for connection of critical equipment
(4) Socket for connection to AC-power source
(5) Ground screw
2.3 Control panel
The UPS has a three-button LCD. It provides useful information about the UPS itself, load status, events,
measurements and settings.
AVR
%
Min
Hz
kVA
kW
6
7
8
6
ON/OFF button
7
Scroll down
8
Mute alarm
2.4 LCD description
16
15
14
17
11
10
9
12
13
9
UPS ON
10
AVR mode
11
Battery mode
12
Internal fault
13
Output load level
14
Battery level
15
Input measurements
16
Output measurements
17
Measuring unit
619-00470-02-us (en)
619-00470-02-us (en)
Page 9
ENGLISH
2.5 UPS setting through the LCD
5SC 500 / 750 / 1000 / 1500
Release scroll down button to select menu
5s
2s
2s
Alarm
Output voltage Sensitivity
(1)
2s
5SC 500G / 750G / 1500G
Release scroll down button to select menu
5s 2s
2s
2s
Output voltage Alarm
Sensitivity
(1)
(1) In low sensitivity mode (Lo) UPS will tolerate more uctuations in power and will go on battery power less
often. If the connected load is sensitive to power disturbances, keep the sensitivity as Standard (Std).
Example of setting
Save the new value
10s 5s 5s
• LCD shut off if no activity for 3 minutes.
2. Presentation
Page 10
3. Installation
3.1 Unpacking and contents check
(1) 5SC UPS
(2) Quick start and safety instructions
(3) User manual and IPSS (Intelligent Power Software Suite) CD-ROM
(4) RS232 communication cable
(5) USB communication cable
(6) 2 connection cables for the protected equipments (500G, 750G and 1500G models)
Packing materials must be disposed of in compliance with all local regulations concerning waste.
Recycling symbols are printed on the packing materials to facilitate sorting.
1
2
3
4
5
6
3.2 Battery module connection
Caution: Before starting the UPS, please connect the internal battery.
Note: A small amount of arcing may occur when connecting the batteries.
This is normal and does not damage the UPS or present any safety concern.
B
A
C
A - Remove front panel.
B - Connect the battery module
(never pull on the wires).
C - Attach the front panel.
619-00470-02-us (en)
619-00470-02-us (en)
Page 11
ENGLISH
3. Installation
3.3 Communication ports
Connection of RS232 or USB communication port
The RS232 and USB communication ports cannot operate simultaneously.
2
1
5
6
1. Connect the RS232 (5) or USB
(6) communication cable to
the serial or USB port on
the computer equipment.
2. Connect the other end of the
communication cable (5) or
(6) to the USB (2) or RS232 (1)
communication port on
the UPS.
The UPS can now communicate
with EATON power management
software.
Page 12
4. Operation
4.1 Start-up and Normal operation
To start the UPS:
1. Verify that the UPS power cord is plugged in.
2. Press the
button on the UPS front panel for at least 2 seconds.
3. Check the UPS front panel display for active alarms.
If the
indicator is on, do not proceed until all alarms are cleared.
Correct the alarms and restart if necessary.
4. Verify that the
indicator illuminates solid, indicating that the UPS is operating normally and any loads
are powered and protected.
4.2 Starting the UPS on Battery
Before using this feature, the UPS must have been powered by utility power with output enabled
at least once.
To start the UPS on battery:
1. Press the
button on the UPS front panel until the UPS front panel display illuminates.
The UPS cycles through Standby mode to Battery mode. The
indicator illuminates solid.
The UPS supplies power to your equipment.
2. Check the UPS front panel display for active alarms. Resolve any active alarms before continuing.
See "Troubleshooting" on page 21.
4.3 UPS Shutdown
To shut down the UPS:
Press the
button on the front panel for three seconds.
The UPS starts to beep. The UPS then transfers to Standby mode, and the
indicator turns off.
4.4 Operation on Battery Power
Transfer to battery power
• The connected devices continue to be supplied by the UPS when AC input power is no longer available.
The necessary energy is provided by the battery.
• The
indicator illuminates solid.
• The audio alarm beeps every ten seconds.
The connected devices are supplied by the battery.
Low-battery warning
• The indicator illuminates solid.
• The audio alarm beeps every three seconds.
The remaining battery power is low. Shut down all applications on the connected equipment because
automatic UPS shutdown is imminent.
End of battery backup time
• All the LEDs go OFF .
• The audio alarms stops.
4.5 Return of AC Input Power
Following an outage, the UPS restarts automatically when AC input power returns (unless the restart
function has been disabled) and the load is supplied again.
619-00470-02-us (en)
619-00470-02-us (en)
Page 13
ENGLISH
5. Maintenance
5.1 Troubleshooting
Operation status Possible cause Action
Overload
Power requirement exceeds the
UPS capacity (greater than 105 % of
nominal).
Remove some of the equipment
from the UPS. The UPS continues
to operate, but may shutdown
if the load increases.The alarm
resets when the condition becomes
inactive.
Site wiring fault A Site Wiring Fault has occurred.
The outlet that the UPS is plugged
into is not properly grounded or
properly wired.
Have a qualified electrician correct
the wiring.
Short-circuit fault
A short-circuit occurred. Check device connection or
integrity.
If error persists, note the alarm
message and the UPS serial
number, and then contact your
service representative.
Battery fault
The batteries in the UPS are
disconnected.
Verify that all batteries are properly
connected.
If error persists, note the alarm
message and the UPS serial
number, and then contact your
service representative.
The end of battery life is reached. Contact your service representative
for battery replacement.
Fan fault
The UPS has a fan fault. Check that no object is blocking the
fan.
If error persists, note the alarm
message and the UPS serial
number, and then contact your
service representative.
Charger fault
The UPS has a charger fault. The UPS does not charge the
battery anymore.
Note the alarm message and
the UPS serial number, and then
contact your service representative.
Page 14
5. Maintenance
5.2 Battery-module replacement
Safety recommendations
The battery can cause electrocution and high short-circuit currents. The following safety precautions
are required before servicing the battery components:
• remove watches, rings, bracelets and all other metal objects from the hands and arms,
• use tools with an insulated handle.
Battery tray removal on tower models
This operation must be performed when the UPS is switched OFF, and unplugged from AC source.
A
A - Remove the front panel.
B
B - Disconnect the battery-module by
separating the town connectors
(never pull on the wires).
C
C - Remove the plastique protection cover
in front of the battery (one screw).
D
D - Pull the plastic tab to remove
the battery block and replace it.
Mounting the new battery module
Carry out the above instructions in reverse order.
To ensure safety and high performance, use only batteries supplied by EATON.
Take care to firmly press together the two parts of the connector during remounting.
619-00470-02-us (en)
619-00470-02-us (en)
Adjustable to 100/110/120 V, must be set to the identical AC power source value.
Page 15
ENGLISH
6. Appendices
6.1 Technical specications
5SC 500 5SC 750 5SC 1000 5SC 1500
Output Power @ 120 V 500 VA
350 W
750 VA
525 W
1000 VA
700 W
1440 VA
1080 W
Output Power @ 110V 460 VA
325 W
690 VA
485 W
920 VA
645 W
1320 VA
990 W
Output Power @ 100 V 415 VA
290 W
620 VA
435 W
830 VA
580 W
1200 VA
900 W
AC Input power
•Rated input voltage Single phase 100-120 V
•Input voltage range 96 to 144 V
•Input frequency range 45 to 55 Hz (50 Hz system), 55 to 65 Hz (60 Hz system)
Output on battery power
•Voltage 100/110/120 V (-10/+6 %)
(1)
•Frequency 50/60 Hz ±0.1 Hz
Battery (sealed lead acid, maintenance free)
•Standard
1 x 12 V
9 Ah
2 x 12 V
7 Ah
2 x 12 V
9 Ah
3 x 12 V
9 Ah
Environment
• Operating temperature
range
0 to 35 °C / 32 to 95 °F
• Storage temperature
range
-15 to +40 °C / 5 to 104 °F
•Relative humidity
0 to 90 % (without condensation)
•Noise level
< 40 dBA in normal mode
(1)
For5SCModels-"CAUTION-Toreducetheriskofre,connectonlytoacircuitprovidedwith20amperes
maximum branch circuit overcurrent protection in accordance with the National Electric Code,
ANSI/NFPA 70".
Filter
Transformer
"AVR"
Charger Inverter
Battery
Page 16
6. Appendices
5SC 500G 5SC 750G 5SC 1500G
Output Power @ 230 V 500 VA
350 W
750 VA
525 W
1500 VA
1050 W
AC Input power
•Rated input voltage
Single phase 220-240 V
•Input voltage range 184 to 276 V
•Input frequency range 45 to 55 Hz (50 Hz system), 55 to 65 Hz (60 Hz system)
Output on battery power
•Voltage 220/230/240 V (-10/+6 %)
(1)
•Frequency 50/60 Hz ±0.1 Hz
Battery (sealed lead acid, maintenance free)
•Standard 1 x 12 V
9 Ah
2 x 12 V
7 Ah
3 x 12 V
9 Ah
Environment
• Operating temperature
range
0 to 35 °C / 32 to 95 °F
• Storage temperature
range
-15 to +40 °C / 5 to 104 °F
•Relative humidity 0 to 90 % (without condensation)
•Noise level < 40 dBA in normal mode
(1) Adjustable to 220/230/240 V, must be set to the identical AC power source value.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16 A,
250 V which is IEC/EN 60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20 A,
250 V.
This product is designed for IT power distribution system.
Filter
Transformer
"AVR"
Charger Inverter
Battery
619-00470-02-us (en)
619-00470-02-us (fr)
FRANÇAIS
Copyright © 2013 EATON
Tous droits réservés.
SAV et assistance :
Contacter votre représentant SAV local
Manuel d'installation
et d'utilisation
5SC 500
5SC 750
5SC 1000
5SC 1500
5SC 500G
5SC 750G
5SC 1500G
Page 2
619-00470-01-us (fr)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68

Eaton 5SC 750G Manuel utilisateur

Catégorie
Alimentations sans interruption (UPS)
Taper
Manuel utilisateur
Ce manuel convient également à