Cornwell Tools RAC34788 Le manuel du propriétaire

Taper
Le manuel du propriétaire
Operating Manual for
Model 34788
Recovery, Recycling, Recharging Unit
OO
OO
O
PP
PP
P
EE
EE
E
RR
RR
R
AA
AA
A
TT
TT
T
II
II
I
NN
NN
N
GG
GG
G
MM
MM
M
AA
AA
A
NN
NN
N
UU
UU
U
AA
AA
A
LL
LL
L
®
SAFETY DEFINITIONS: Follow all WARNING, CAUTION, IMPORTANT, and NOTE messages in this manual. These messages
are defined as follows: WARNING means you may risk serious personal injury or death; CAUTION means you may risk personal
injury, property damage, or unit damage; IMPORTANT means you may risk unit damage; and NOTEs and OPERATING TIPS provide
clarity and helpful information. These safety messages cover situations ROBINAIR is aware of. ROBINAIR cannot know, evaluate,
and advise you as to all possible hazards. You must verify that conditions and procedures do not jeopardize your personal safety.
DISCLAIMER: Information, illustrations, and specifications contained in this manual are based on the latest information available at
the time of publication. The right is reserved to make changes at any time without obligation to notify any person or organization of
such revisions or changes. Further, ROBINAIR shall not be liable for errors contained herein or for incidental or consequential damages
(including lost profits) in connection with the furnishing, performance, or use of this material. If necessary, obtain additional health
and safety information from the appropriate government agencies and the vehicle, refrigerant, and lubricant manufacturers.
ALLOW ONLY QUALIFIED PERSONNEL TO OPERATE THE UNIT. Before operating the unit, read and follow
the instructions and warnings in this manual. The operator must be familiar with air conditioning and refrigeration
systems, refrigerants, and the dangers of pressurized components. If the operator cannot read this manual,
operating instructions and safety precautions must be read and discussed in the operator’s native language.
– Si el operador no puede leer las instrucciones, las instrucciones de operación y las precauciones de seguridad
deberán leerse y comentarse en el idioma nativo del operador.
– Si l’utilisateur ne peut lire les instructions, les instructions et les consignes de sécurité doivent lui être expliquées
dans sa langue maternelle.
PRESSURIZED TANK CONTAINS LIQUID REFRIGERANT. Do not overfill the internal storage vessel, because
overfilling may cause explosion and personal injury or death. Do not recover refrigerants into nonrefillable
containers; use only federally authorized refillable containers (DOT spec. 4BW or 4BA).
HOSES MAY CONTAIN LIQUID REFRIGERANT UNDER PRESSURE. Contact with refrigerant may cause
personal injury. Wear protective equipment, including safety goggles. Disconnect hoses using extreme caution.
DO NOT BREATHE REFRIGERANT AND LUBRICANT VAPOR OR MIST. Exposure may cause personal
injury, especially to the eyes, nose, throat, and lungs. Use the unit in locations with mechanical ventilation that
provides at least four air changes per hour. If accidental system discharge occurs, ventilate the work area before
resuming service.
DO NOT USE AN EXTENSION CORD. An extension cord may overheat and cause fire. If you must use an
extension cord, use the shortest possible cord with a minimum size of 14 AWG.
TO REDUCE THE RISK OF FIRE, do not use the unit in the vicinity of spilled or open containers of gasoline or
other flammable substances.
DO NOT USE COMPRESSED AIR TO PRESSURE TEST OR LEAK TEST THE UNIT OR VEHICLE AIR
CONDITIONING SYSTEM. Some mixtures of air and R-134a refrigerant are combustible at elevated pressures.
These mixtures are potentially dangerous and may result in fire or explosion causing personal injury or property
damage.
USE THIS UNIT WITH R-134a REFRIGERANT ONLY. The unit is designed to recover, recycle, and recharge
only R-134a refrigerant. Do not attempt to adapt the unit for another refrigerant. Do not mix refrigerant types
through a system or in the same container; mixing of refrigerants will cause severe damage to the unit and the
vehicle air conditioning system.
HIGH VOLTAGE ELECTRICITY INSIDE THE UNIT HAS A RISK OF ELECTRICAL SHOCK. Exposure may
cause personal injury. Disconnect the power before servicing the unit.
WARNINGS
Model 34788
Recovery, Recycling, & Recharging Unit
OPERATING NOTE: At temperatures exceeding 120° F / 49° C, wait 10 minutes between recovery jobs.
1
539602 Rev. B, September 20, 2007
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Keypad Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Menu Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unpack the Accessory Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Power Up the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Select a Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Select Operating Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Set Tank Fill Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Add Oil to the Vacuum Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fill the Internal Storage Vessel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Recover Refrigerant from a Vehicle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Evacuate the A/C System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Replenish A/C System Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Recharge the A/C System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Operating Instructions — Automatic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electrical Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Manually Fill the Internal Storage Vessel (ISV) . . . . . . . . . . . . . . . . . . . . . . . . 15
Replace the Filter-Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Check Remaining Filter Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Change the Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Adjust Tank Fill Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Change Vacuum Pump Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Scale Calibration Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Check for Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Spanish Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
French Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inside Front Cover
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Inside Back Cover
IMPORTANT: To comply with federal law governing A/C system service, you must complete and
mail the MVAC Certification Form included in the accessory kit. Technicians using this equipment
must be certified under EPA Section 609 (Environmental Protection Agency). For more information,
read the MACS information included in the accessory kit, or visit the MACS website at www.macsw.org.
To validate the warranty provided by SPX Robinair, complete the warranty card included in the
accessory kit, and mail it within ten days from the purchase date of the unit.
2
Introduction
Robinair No. 34788 is used on R-134a vehicles and is designed to be compatible with existing service
equipment and standard service procedures. Model No. 34788 is a UL-listed, single-pass system that
meets SAE specifications for recycled refrigerant. Follow the SAE-J2211 recommended service
procedure for the containment of R-134a.
The unit includes a 3 cfm (85 l/m) Robinair high vacuum pump for fast, thorough evacuation. The
compressor pulls the A/C system to 0 psig, then works in series with the vacuum pump to achieve highly
efficient recovery and immediate recharge. If the system is not opened for service, there is no need to pull
additional vacuum. If the system is opened for service, use the unit’s vacuum cycle to remove air and
moisture from the A/C system. (We recommend a minimum 15-minute vacuum, or follow the vehicle
manufacturer’s specs.) Note: R-134a systems require special oils. Refer to the A/C system manufacturer’s
service manual for oil specifications.
Technical Specifications
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . 115V, 60 Hz
Operating Range . . . . 50° to 120° F (11° to 49° C)
Filter-Drier . . . . . . . . . . . . . . .43 cu. in. spin-on type
Pump Free-Air Displacement
. . . . . 3 cfm (85 l/m)
Dimensions . . . . . . . . . . . . . 49" H x 34" W x 23" D
. . . . . . . . . . . . . . . . . (124.5 cm x 86.4 cm x 58.4 cm)
Digital Display: visual
interface between operator
and machine.
Main Power Switch: supplies
electrical power to unit.
Manifold Gauges:
connect to vehicle A/C
system; show system’s
low-side and high-side
pressure.
Flow Indicators: red light indicates
high-side flow from vehicle A/C system
through unit; blue light indicates low-
side flow from vehicle A/C system
through unit.
Control Panel:
folds flat for storage.
Database Expansion Slot: an
optional vehicle database will
supply information regarding
charge capacity by vehicle model.
Tool Storage Areas
(additional storage
on back side for
extra filter-driers and
oil bottles).
3
539602 Rev. B, September 20, 2007
Introduction
Keypad Functions
START
YES START / YES begins or resumes a
function, or answers a query.
STOP / NO terminates or pauses a
function, or answers a query.
MENU displays the selection menu.
ARROWS are used for scrolling
through menu items.
AUTOMATIC activates a menu that
helps the user set up an automatic recover
/ vacuum / leak test / charge sequence.
RECOVER activates the recovery
sequence.
VACUUM activates the vacuum
sequence, followed by an option to
activate a leak test.
INJECT OIL injects oil into the vehicle
A/C system.
CHARGE charges the vehicle A/C
system with a programmed amount of
refrigerant.
REFRIGERANT DATABASE (optional)
offers access to system oil and refrigerant
specifications by vehicle model and year.
Purchase Robinair part no. 34411.
RECOVER
STOP
NO
VACUUM
CHARGE
MENU
INJECT OIL
AUTOMATIC
Keypad
Glossary
A/C System : The vehicle air conditioning system being serviced.
Internal Storage Vessel : The refillable refrigerant storage vessel
designed specifically for this unit; 30 lb. (14 kg).
Source Tank : A disposable tank of new refrigerant used to refill
the internal storage vessel; not included.
Unit : Model No. 34788.
REFRIGERANT
DATABASE
When the unit is not performing a function,
pressing the UP or DOWN arrow key
adjusts contrast on the digital display.
4
Menu Functions
1. Press the MENU button on the keypad.
2. Press the UP or DOWN arrow key to scroll
through the menu choices shown on the second
line of the display :
SELECT LANGUAGE
SERVICE MENU
CALIBRATION CHECK
ADJUST TANK FILL LVL
MANUAL REFILL
REFRIG MANAGEMENT
MAINTAIN FILTER
MAINTAIN VACUUM OIL
SELECT UNITS
VERSION X.XX
3. Press START / YES to make a choice from
the menu. Press STOP / NO to pause during
any process, and STOP / NO a second time to
exit a process.
Introduction
Menu Choice: Select Language
Operator may choose to have prompts displayed in one of
three languages: English, Spanish, or French.
Menu Choice: Service Menu
For Robinair service center use only.
Menu Choice: Calibration Check
Use to verify internal scale calibration. Refer to instructions
in Maintenance section under Scale Calibration Check.
Menu Choice: Adjust Tank Fill Lvl
When connected to a refrigerant source, the unit maintains
a pre-set amount of refrigerant in the internal storage vessel
(default is 15 lbs.). This value may be adjusted up or down
to suit the user’s needs. Refer to instructions outlined in the
Maintenance section under Adjust Tank Fill Level.
Menu Choice: Manual Refill
Use to transfer refrigerant from the source tank to the
internal storage vessel (ISV). Refer to instructions outlined
in the Maintenance section under Manually Fill the ISV.
Menu Choice: Refrig Management
Displays the amount of refrigerant recovered, charged,
and replenished (for the life of the unit), and filtered
(since the last filter change).
Menu Choice: Maintain Filter
The filter-drier removes acid, particulates, and moisture
from the refrigerant. To meet SAE J-2788 requirements,
it is mandatory to replace the filter-drier after 150 lbs.
(68 kg) of refrigerant has been filtered. This menu item
shows how much refrigerant has been filtered since the
last filter change, and allows the user to reset the value
once a filter change is complete. A code, which appears on
the filter, must be entered into the unit to ensure compliance
with SAE J-2788. Refer to the instructions outlined in the
Maintenance section under Replace the Filter-Drier.
Menu Choice: Maintain Vacuum Oil
For maximum vacuum pump performance, change
vacuum pump oil after every 10 hours of operation. This
menu item displays how long the vacuum pump has
operated since the last oil change, and allows the user to
reset the value once an oil change is complete. Refer to
the instructions outlined in the Maintenance section
under Change Vacuum Pump Oil.
Menu Choice: Select Units
The operator may choose to have test results displayed in
Imperial (lb.), Imperial (lb. and oz.), or Metric (kg).
Menu Choice: Version X.XX
Displays the revision level of the software in the unit.
Arrow
Keys
Start / Yes
Button Stop / No
Button
Menu
Button
5
539602 Rev. B, September 20, 2007
Setup
Unpack the Accessory Kit
Unpack the accessory kit from the bag, and remove the
plastic packaging. The kit consists of
A calibration weight.
Vacuum pump oil, oil filler cap, and tube.
Plastic pouch containing a warranty card (to be
completed and mailed), applicable MSDS sheets, a
service center listing, and an envelope of Mobile Air
Conditioning Society (MACS) information.
Important: You must complete and mail the
MVAC Certification Form and your technicians
must be certified with the Environmental
Protection Agency (EPA) to operate this
equipment.
Power Up the Unit
1. Unwind the power cord from the handle, and plug it
into a correct voltage outlet. See Figure 1.
2. Turn on the main power switch. The first time the
unit is powered up, it displays the initial setup mode.
Select a Language – English
Seleccionar Idioma – Espanol
Selection Langue – Francais
The operator may choose to have prompts displayed in
one of three languages: English, Spanish, or French.
1.
Use the UP or DOWN arrow key to toggle through
the choices for English, Spanish, or French. Refer to
Figure 2.
2.
Press START / YES to select the displayed language.
Select Operating Units
The operator may choose to have test results displayed
in Imperial (lb., or lb. and oz.) or Metric (kg) units.
1. Use the UP or DOWN arrow key to toggle through
choices for IMPERIAL UNITS or METRIC UNITS.
2. Press START / YES to select the displayed
operating unit choice.
IMPORTANT :
R-134a systems have
special fittings (per SAE specifications)
to avoid cross-contamination with R-12
systems. DO NOT adapt your unit for a
different refrigerant — system failure
will result.
Arrow
Keys
Start / Yes
Button
Figure 2
Stop / No
Button
Power
Cord
Main
Power Switch
Figure 1
6
Set Tank Fill Level
The operator may either accept the unit’s pre-set default
weight of 15 lbs. (6.8 kg) of refrigerant stored in the
internal storage vessel (ISV), or change the amount to
accommodate the application.
The unit displays
LEVEL: 15.00 LBS.
ENTER TANK FILL LVL
LIMIT: 4 TO 20 LBS.
PRESS START / YES TO SAVE
1. Press START / YES to accept the default amount,
or use the keypad to enter a desired amount and
press START / YES.
Add Oil to the Vacuum Pump
IMPORTANT: The vacuum pump is shipped
without oil in the reservoir. Failure to add oil to
the vacuum pump will damage the pump.
The unit displays
ADD 5 OZ OF NEW OIL
TO VACUUM PUMP
START TO CONTINUE
1. Remove the brass plug from the vacuum pump oil
fill port. See Figure 3.
2.
Attach the flexible tube/cap to the oil bottle; pour
only five (5) ounces of vacuum pump oil into the fill
port. Note: You will top off the oil in the next step as
the vacuum pump is running.
3. Press and release the START / YES key. While the
vacuum pump is running, slowly add oil until the
level rises to the center of the reservoir’s sight glass.
4. Press the STOP / NO key to stop the vacuum pump,
and install the brass plug in the fill port.
5. Press START / YES to continue.
Setup
Figure 3
Sight
Glass
Fill Port
Vacuum Pump
Sight Glass
ss
ss
s
CAUTION: The unit is programmed
to run the setup procedure as outlined
here. To prevent personal injury, do
NOT operate the unit at any other time
without the brass plug installed,
because the vacuum pump is
pressurized during normal operation
.
Fill Port
7
539602 Rev. B, September 20, 2007
Setup
Fill the Internal Storage Vessel (ISV)
1.
Press START / YES, and the unit automatically
runs a 5-minute vacuum to clear all internal air.
Note: The “burping” noise heard during this
process indicates air is being purged from the
system—this is normal.
2. After the vacuum pump shuts off, connect the
fill hose to the liquid connector on a full
source tank.
3. Open the source tank valve.
4. Install the source tank, and secure it to the
unit (using the tank strap) in such a way that
liquid refrigerant is supplied to the
connection.
5. Press START / YES to begin filling the
internal storage vessel. Add at least 8 lbs.
(3.6 kg) of refrigerant to ensure enough
refrigerant is available for charging.
This process takes 15–20 minutes. The unit
stops when a sufficient amount of refrigerant
has been transferred to the internal tank, or
when the source tank is empty.
Press STOP / NO to pause. Press STOP /
NO again to exit, or START / YES to
resume.
6. When the fill process is complete, press
STOP / NO to exit. The unit is ready for
operation.
Note: There is no need to calibrate the scale; it
is calibrated at the factory.
Figure 4
Side View
Fill Hose
(connect to
liquid line)
Power
Cord
Source
Tank
Strap
Low- and
High-Side
Hoses
8
Notes
9
539602 Rev. B, September 20, 2007
Operating Instructions
Recover Refrigerant from a Vehicle
1. Empty the oil drain bottle located on the right-hand
side of the unit, if necessary, or make note of the
current oil level. See Figure 5.
2. Connect the high- and low-side hoses to the vehicle
A/C system.
3. Open the coupler valves on the hoses.
4. Press the RECOVER button.
Note: The clicking noise heard during the recovery
process indicates the solenoid is opening and closing —
this is normal.
5. When the system has recovered to 0 psi, the vacuum
pump starts and runs until recovery is complete. The
unit then goes into an automatic oil drain—this may
require 90 seconds to complete.
6. After the oil drain is complete, the display shows
RECOVER COMPLETE
RECOVERED XX.XX LBS. (X.XX KG)
CHECK OIL BOTTLE
Note: The displayed recovered weight can vary,
depending on ambient conditions, and should not be
used as an indicator of scale accuracy.
7. Check the oil drain bottle, and note the amount of oil
that was removed from the A/C system. This is the
amount of new oil that must be charged into the A/C
system after evacuation is complete.
Dispose of used oil according to local, state, and
federal regulations.
Recovery is complete. You are now ready to either
advance to the charge process, or to make repairs to the
A/C system followed by the evacuation process.
Oil Drain
Bottle
Figure 5
Operating Tips
After the RECOVER function is selected :
If system pressure is below 10 psi, the display
readsLOW RECOVER PRESSURE
CHECK CONNECTIONS
until pressure increases, or the START / YES
button is pressed. Verify the high- and low-side
hoses are connected and coupler valves are
open. Press STOP / NO to exit.
If 100 lbs. (45 kg) or more of refrigerant has
been recovered since the last filter-drier change,
the display reads
FILTER WEIGHT XXX LB (XX KG)
To meet SAE J-2788 requirements, it is
mandatory to replace the filter-drier after
150 lbs. (68 kg) of refrigerant has been
filtered. The unit gives a warning to replace the
filter when filter weight reaches 100 lbs.; when
filter weight reaches 150 lbs., the unit locks
out and ceases to operate. Refer to
instructions outlined in the Maintenance section
under Replace the Filter-Drier.
If the unit has refrigerant in its low-side plumbing,
it begins a clearing process and displays
RECOVER IN PROGRESS
CLEARING
If you wish to skip the clearing operation,
or stop the clearing prematurely, press
START / YES.
10
Evacuate the A/C System
1. Ensure service hoses are connected, and coupler
valves are OPEN.
2. Press VACUUM.
3.
Press START / YES to accept the default evacuation
time of 10 minutes, or enter the desired vacuum time
using the number keys, and press START / YES.
IMPORTANT: The unit pulls a vacuum on the
vehicle A/C system to remove air and boil off
moisture that may be present in the system.
Evacuate the system for at least 10 minutes,
or follow the A/C system manufacturer’s
specifications, to ensure adequate moisture
and contaminant removal.
4. The unit gives you the option of doing a leak test
after evacuation.
Press START / YES to perform the leak test.
Press STOP / NO to skip the leak test and begin
evacuation.
5. The unit evacuates the A/C system and stops when
the specified amount of time has elapsed.
Press STOP / NO to pause the process. Press
START / YES to resume, or STOP / NO again
to exit.
You are now ready to replenish the A/C system with
new oil, if necessary, or to recharge the system with
refrigerant.
Operating Instructions
Operating Tips
If the vacuum pump has run for 10 or more
hours without an oil change, the unit displays
VACUUM OIL TIME XX:XX
CHANGE OIL NOW?
Refer to instructions outlined in the
Maintenance section under Change Vacuum
Pump Oil.
Before the unit begins evacuating the A/C
system, it checks for any pressure in the
system that might damage the vacuum pump.
If pressure is detected, the unit displays
PRESSURE EXISTS
PRESS ANY KEY TO EXIT
Press any key to exit, and recover refrigerant
before proceeding.
If a leak test was selected at the end of
vacuum, and a leak is detected, the unit
displays
LEAK TEST FAILED
PRESS ANY KEY TO EXIT
Press any key to exit the evacuation, perform
needed repairs, and repeat the evacuation.
To ensure an accurate leak test, it is
imperative that a thorough recovery and
evacuation of the system be performed.
During the recovery process, cold spots can
develop in the automotive system. Pockets of
refrigerant in desiccant and in system oil will
continue to vaporize as the A/C system
temperature equalizes toward ambient. As
this occurs, A/C system pressure will
increase, which may be interpreted by the
unit as a leak.
This will vary somewhat with ambient
temperature conditions.
11
539602 Rev. B, September 20, 2007
Replenish A/C System Oil
Oil may be replenished through the high side after the
vacuum function, or with an oil inject tool after
charging the vehicle.
IMPORTANT : To prevent damage to
equipment, charge only the amount of oil that
was removed from the A/C system during the
recovery process. If no oil was removed from
the A/C system during recovery, DO NOT
charge any oil into the A/C system.
Empty the oil drain bottle before recovering an A/C
system to prevent an inaccurate oil charge.
1. Refer to the vehicle service manual, or the optional
vehicle reference database card, to determine the
correct oil for the A/C system being serviced.
2. Check the oil drain bottle to determine the amount of
oil that was removed. See Figure 6.
3. Adjust the o-ring around the oil injector bottle to the
required oil charge level.
For example, if the bottle’s oil level is at 4 ounces,
and you need 1/2 ounce of oil to replenish the A/C
system, place the o-ring at the 3-1/2 ounce level.
4. Attach the oil injector bottle to the unit.
5. Press the INJECT OIL button. The unit looks for
pressure in the hoses, and temporarily displays
EQUALIZING PRESSURE.
6.
When prompted, press and hold the INJECT OIL
button until the oil level in the oil injector bottle
reaches the o-ring.
7. Press STOP / NO after the oil inject is complete to
recharge the system with refrigerant. The display
will prompt into the charge mode. (Charge mode
after injecting oil will allow only a high-side charge.)
Note: You must recharge the A/C system with
refrigerant at this time to ensure all the oil is delivered.
Operating Instructions
Figure 6
Oil Injector
Bottle
Oil Drain Bottle
O-ring
12
Recharge the A/C System
1.
Press CHARGE. Press CHARGE again to toggle
between a high-side charge, a low-side charge, or both.
Note:
Charge mode after injecting oil will allow only a
high-side charge.
The blue light on the control panel indicates a low-
side charge; the red light indicates a high-side charge.
See Figure 7.
2. Accept the default weight by pressing START /
YES, or type in a weight using the number keys, and
press START / YES.
3. Select START / YES to perform an oil inject; select
STOP / NO to skip the oil inject.
4.
After a valid charge weight is entered, the display reads
CHARGE IN PROGRESS / DO NOT DISTURB
X.XX LBS. (X.XX KG)
Moving or bumping the unit at this point may result
in an incorrect reading.
Note:
During a charge cycle, if the unit fails to transfer
refrigerant due to low tank pressure, the charge
process is automatically interrupted and the unit
operates in a mode to build tank pressure. Once tank
pressure is sufficient, the unit automatically
completes the charge.
When the charge cycle gets close to the weight
entered in Step 2, the unit slows down. It’ll charge,
settle, charge again, settle, etc., with the blue/red
lights illuminating accordingly.
5. When the charge is complete, the display reads
CHARGED XXX LBS (KG)
PRESS START TO EQUALIZE HOSES
The user must equalize pressure in the service hoses
to ensure all liquid refrigerant trapped in the hoses is
transferred to the vehicle A/C system for an accurate
charge. Press START / YES to equalize hoses.
Operating Instructions
Operating Tips
After selecting the CHARGE function and
entering a desired weight, if the weight entered
will leave less than 3 lbs. (1.36 kg) of
refrigerant in the internal tank after charge, the
charge function will not start. The display reads
INSUFFICIENT REFRIG.
PRESS ANY KEY TO EXIT
Refer to the Maintenance section of this manual
for instructions to Manually Refill the Internal
Storage Vessel (ISV).
Red Light indicates
High-Side Charge
Blue Light indicates
Low-Side Charge
Figure 7
13
539602 Rev. B, September 20, 2007
Operating Instructions
Recharge the A/C System contd.
6. Close the high-side coupler valve. The display reads
DISCONNECT HS HOSE
AND START A/C MAX
START TO CONTINUE
The high-side hose may be removed from the vehicle,
but the low-side hose must stay connected to
the vehicle with the low-side coupler open.
7. Place the vehicle gear selector in park or neutral,
with the emergency brake ON.
8.
Start the vehicle. The A/C system should be set at
maximum.
9. Press START / YES. The display reads
EQUALIZING HOSES
PLEASE WAIT
The unit internally connects the low- and high-side
hoses, allowing the vehicle’s compressor to pull
refrigerant into the A/C system. When the charge is
complete, the display shows
DISCONNECT LOW SIDE HOSE
START TO CONTINUE
10
.
Close the low-side coupler valve. Remove the service
hoses from the A/C system.
IMPORTANT: If the low-side or high-side
coupler valves are left open, the system will
pull the refrigerant back out of the vehicle.
11.
Shut OFF the vehicle.
12.
Press
START / YES to begin clearing the hoses.
CLEARING HOSES
PLEASE WAIT
When the hoses are cleared, the display reads
CHARGE COMPLETE
CHARGED XX.XX LBS
ANY KEY EXITS
The A/C system is now ready for use.
WARNING: To prevent personal injury,
Verify the vehicle is in park or neutral
with the emergency brake ON before
starting the engine.
Never run a vehicle without adequate
ventilation in the work area.
14
Operating Instructions – Automatic
The automatic function allows a user to program an
automatic recovery, vacuum, leak test, and / or charge
sequence. The user may choose to skip any step in the
automatic operation during the programming. A total
automatic sequence may take an hour to complete.
Note: Oil recovered during the recovery cycle can be
injected by the user before the charge cycle, or can be
manually injected into the vehicle after charge using a
separate oil injection tool.
1.
Connect the high- and low-side service hoses to the
A/C system, and open the coupler valves on the hoses.
2. Press the AUTOMATIC button. See Figure 8.
3. The unit asks if a recovery is needed. Press STOP /
NO to skip the recovery cycle; press START / YES
to accept.
4.
The unit asks if a leak test is needed. Press STOP / NO
to skip the leak test; press START / YES to accept.
5. The unit asks if a charge is needed. Press STOP /
NO to skip the charge cycle; press START / YES to
accept. Press CHARGE to toggle between high- or
low-side charge, or both.
Accept the default weight by pressing START /
YES, or type in a desired weight using the number
keys and press START / YES.
6. The display shows an overview of all the tests that
were selected. Press START / YES to begin the
automatic sequence.
Note : If a high-side charge has been selected, before
charging, the automatic sequence will pause and
“beep” for 30 seconds to allow the user to inject oil, if
desired. See Replenish the A/C System Oil instructions
in this manual.
7.
When the sequence is complete, the display shows the
amount of refrigerant that was recovered and charged.
8. Close the high- and low-side coupler valves, and
remove the service hoses from the A/C system.
9
.
If any oil was recovered during the recovery cycle,
and oil was not injected before the charge cycle, use
an oil injection tool at this time to manually inject oil
into the A/C system.
Operating Tips
If the weight entered is more than the refrigerant
available in the internal tank, the charge function
will not start. The display reads
INSUFFICIENT REFRIG.
PRESS ANY KEY TO EXIT
Refer to the Maintenance section of this manual for
instructions to Manually Fill the ISV.
If problems are encountered during the automatic
sequence, the unit will “beep” three times and the
control panel readout will pinpoint the problem
encountered. The sequence remains paused until the
user enters a decision regarding how to proceed.
Before the unit begins evacuating the A/C system
during the automatic sequence, it checks for any
pressure in the system that may damage the vacuum
pump. If pressure is detected, the unit displays
PRESSURE EXISTS
PRESS ANY KEY TO EXIT
Press any key to exit the automatic sequence.
If a leak test was programmed, and a leak is
detected, the unit displays
LEAK TEST FAILED
PRESS STOP TO EXIT
PRESS START TO CONTINUE
Press STOP to exit the automatic sequence and
perform needed repairs. Press START to continue
the automatic sequence despite the failed leak test.
To ensure an accurate leak test, it is imperative
that a thorough recovery and evacuation of the
system is performed. During the recovery process,
cold spots can develop in the automotive system.
Pockets of refrigerant in desiccant and in system
oil will continue to vaporize as the A/C system
temperature equalizes toward ambient. As this
occurs, A/C system pressure increases, which may
be interpreted by the unit as a leak. This varies
somewhat with ambient temperature conditions.
Automatic
Function
Figure 8
15
539602 Rev. B, September 20, 2007
Maintenance
General Maintenance
1. On a regular basis, wipe off the unit using a clean
cloth to remove grease and dirt.
2.
Periodically check internal components for leaks; over
time, fittings can loosen as the unit is moved. Open the
door panel, and trace lines using a leak detector.
Check connections on the back of the unit. Tighten
any loose fittings or connections you may find.
Electrical Protection
The unit is equipped with a 15 amp circuit breaker on
the back panel. See Figure 9. If the breaker trips, its
button will pop out. A tripped circuit breaker will cause
the unit to lose all power.
Press the circuit breaker button to reset.
Manually Fill the
Internal Storage Vessel (ISV)
This menu item is used to transfer refrigerant from a
source tank to the internal storage vessel.
Note: If a refrigerant source tank remains connected to
the unit during normal operation, the correct amount of
refrigerant will automatically be maintained in the ISV.
The ISV may be manually refilled, if necessary.
1. Press Menu, and use arrow keys to select MANUAL
REFILL. Press START / YES. The unit displays
CONNECT SOURCE TANK
START TO BEGIN
2. Connect the fill hose to a full source tank, and open
the source tank valve.
3. Install the source tank, and secure it to the unit with
the source tank strap in such a way that liquid
refrigerant is supplied to the connection.
4. Press START / YES to begin. The display shows
TANK FILL IN PROGRESS
TRANSFER XX LBS
5. The unit automatically stops when the preset tank fill
level is reached, or press STOP / NO to exit. Figure 10
Side View
Fill Hose
Power
Cord
Source
Tank
Strap
Low- and
High-Side
Hoses
Circuit
Breaker
Figure 9
Back View
16
Replace the Filter-Drier
The filter-drier is designed to trap acid and particulates,
and to remove water from refrigerant. To meet the
SAE J-2788 mandate for adequate moisture and
contaminant removal, the filter-drier must be replaced
after 150 lbs. (68 kg) of refrigerant has been filtered.
Therefore, you no longer have a choice—the
filter-drier must be replaced. The unit gives a
warning when 100 lbs. of the filter capacity has been
used; the unit locks down when the 150 lb. filter
capacity has been reached and will no longer
function. For this reason, always have a spare Robinair
No. 34724 filter-drier on hand.
Check Remaining Filter Capacity
1. Press MENU.
2. Use the arrow keys to scroll through the menu to
MAINTAIN FILTER, and press START / YES.
The unit displays
XXX LBS FILTERED
RECOVER LOCKOUT IN XXX LBS
REPLACE FILTER NOW?
PRESS STOP TO EXIT
3. Press STOP / NO to exit.
Change the Filter
1. Press MENU.
2. Use the arrow keys to scroll through the menu to
MAINTAIN FILTER, and press START / YES.
The unit displays
XXX LBS FILTERED
RECOVER LOCKOUT IN XXX LBS
REPLACE FILTER NOW?
PRESS STOP TO EXIT
3. Press START / YES to proceed.
4. If there is pressure in the filter, the unit begins a
clearing process. When complete, the display reads
ENTER 10 DIGIT SERIAL NUMBER. Use the
keypad to enter the serial number that appears on the
new filter-drier, and press START / YES.
Maintenance
IMPORTANT: Use only authentic Robinair
No. 34724 filter-driers in this machine.
All performance tests and claims are
based on using this specific filter-drier.
And only the Robinair No. 34724 filter-
drier includes the code necessary to
make the unit operable again.
Enter the Serial No. for a New Filter-Drier
The numerical keys on the keypad include an
alphabet that is used to enter the serial number
code for the new filter-drier. The procedure is
similar to text messaging. For example,
To enter an “A”:
Press the 2 key once to
see the “2 on the
digital display; press
the 2 key again to
display the “A.
To enter aC”:
Press the 2 key once to
see the “2 on the
digital display; press
the 2 key three more
times to see the “Con
the display.
After the appropriate letter is shown on the
display, pause for a moment until the cursor
moves to the next position.
Operating Tips
17
539602 Rev. B, September 20, 2007
5. The display reads PLEASE REPLACE FILTER.
Open the rear door of the unit and unscrew the old
filter. See Figure 11.
6.
Look at the new filter—verify both o-rings are
lubricated and correctly located in the grooves. See
Figure 12. Thread the new filter into place. Press
START / YES.
Note: If the display shows SERIAL NUMBER ERROR,
the serial number is invalid or the filter-drier has
already been used in this unit.
7. Close the door. Press STOP / NO to exit. The filter-
drier replacement is now complete.
Replace the Filter-Drier contd.
Maintenance
Filter-
Drier
Rear View
(without shroud)
Adjust Tank Fill Level
When connected to a refrigerant source, the unit
maintains a default value of 15 lbs. of refrigerant in the
internal storage vessel. This value may be adjusted up
or down to suit the application.
1. Press MENU.
2. Use the arrow keys to scroll through the menu to
ADJUST TANK FILL LVL, and press START /
YES. The unit displays
LEVEL: 15.00 LBS.
ENTER TANK FILL LVL
LIMIT: 4 TO 20 LBS.
PRESS START / YES TO SAVE
3. Use the keypad to enter a value between 4 lbs. and
20 lbs., and press START / YES.
Figure 11
O-rings
Figure 12
18
Change Vacuum Pump Oil
For maximum vacuum pump performance, change the
vacuum pump oil after every 10 hours of operation. (The
unit will display a prompt after 10 hours of operation.)
1. Press MENU. Use the arrow keys to select
MAINTAIN VACUUM OIL, and press START /
YES. The display shows how long the vacuum pump
has operated since the last oil change:
PUMP OIL TIME X:XX
TIME REMAINING X:XX
CHANGE OIL?
2. Press START / YES. The display shows VACUUM
OIL CHANGE TIME 2:00, and counts down to zero.
Allow the vacuum pump to run until it automatically
stops. The display then shows DRAIN OLD OIL
AND ADD 5 OZ NEW OIL.
3. Refer to Figure 13, and remove the brass plug from
the vacuum pump’s oil fill port. (The pump drains
faster when vented.)
4.
Remove the oil drain fitting cap, and drain the oil into
a suitable container for disposal. Replace the cap.
5.
Attach the flexible tube and cap to the oil bottle; pour
five (5) ounces of vacuum pump oil into the fill port.
6. Press START / YES. The display shows FILL
PUMP TO CENTER OF SIGHT GLASS, and the
vacuum pump starts. While the vacuum pump is
running, slowly add oil until the level rises to the
center of the reservoir’s sight glass.
7. Press STOP / NO. The counter resets to zero after a
vacuum pump oil change has been completed.
8. Replace the brass plug on the fill port. Press STOP /
NO to exit to the Main Menu.
CAUTION: To prevent personal injury, do
NOT operate the unit at any time without the
brass plug installed, because the vacuum
pump is pressurized during normal operation.
Review the laws in your jurisdiction to
determine the correct disposal
procedure for pump oil. It is the
responsibility of the user to determine
if a material is a hazardous waste at
the time of disposal. Ensure you are in
compliance with all applicable laws
and regulations.
Oil Drain Fitting
Oil Fill Port
Sight Glass
Maintenance
Figure 13
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Cornwell Tools RAC34788 Le manuel du propriétaire

Taper
Le manuel du propriétaire

dans d''autres langues