Initiating Device Circuit (IDC)
Wiring Styles Supervised power limited Class A and Class B
Voltage 3.3 V DC (<200 µA)
Line Impedance 100 Ω max
End-of-Line resistors* 47k Ω
Note: *A UL listed end-of-line resistor is available at Apollo, Part no. 44251-146
Remarque: * Une résistance de fin de ligne répertoriée UL est disponible chez Apollo, réf. 44251-146
2
WIRING INSTRUCTION
INSTALLATION
This product must be installed in accordance with the applicable NFPA standards, local codes and
jurisdictional authorities. Failure to follow these instructions may result in failure of devices to report
an alarm condition. Apollo America Inc. is not responsible for devices which are improperly installed,
maintained and tested.
Before installing this product, check the continuity, polarity and insulation resistance of all wiring. Check
that wiring is in accordance with the fire system drawings and conforms to all applicable local codes
such as NFPA 72.
1. Mount the electrical box as required and install all cables for termination.
2. Terminate all cables in compliance with local codes and regulation. Ensure that cable shield/
earth continuity is maintained and no short occurs with the back box (see Fig. 3 and 4 for
wiring instructions)
3. Set the address on dip switch of the unit as shown on page 4.
4. Install the wire separator provided.
5. Gently push the completed assembly towards the mounting box and verify wiring and
address. Align the fixing holes.
6. Secure the module to the electrical box with provided screws. Do not over tighten screws.
7. Place the face plate over the module and secure with provided screws.
8. Commission the module.
TECHNICAL INFORMATION COUNT.
3
OUTPUT CIRCUIT
Realy Output - Non Supervised 30 V DC 4 A-resistive
Programmable - Dry Contact 240 V AC 4 A-resistive
Analogue Values (XP95/Discovery Protocol)
Without Ground Fault With Ground Fault*
Normal 16 19
Alarm 64 69
Trouble 4 4
Analogue Values (COREProtocol)
Without Ground Fault With Ground Fault
Normal 16 19
Alarm 65 70
Trouble 4 4
Note: * Ground fault values need to be enabled by the dip switch (by Default no ground Fault values will
show up).
Remarque: * Les valeurs de défaut à la terre doivent être activées par le commutateur DIP (par défaut,
aucune valeur de défaut à la terre ne s'affiche).
Note: Analogue Values need to be tested with each individual compatible UL listed panel for compatibility.
Separate incoming and outgoing wire at every terminal
Do not loop Ne pas boucler
Remarque: les valeurs analogiques doivent être testées avec chaque panneau homologué UL compatible
individuel pour la compatibilité.
WARNING: DISCONNECT POWER BEFORE OPENING
AVERTISSEMENT: COUPER LE COURANT AVANT D'OUVRIR
Class A | Fig. 3
Fig. 1 Fig. 2
Remarque: "X" désigne les terminaux inutilisés.
Note: ‘X’ denotes unused terminals.
CAUTION –
•
•
When Making Installation, Route Field Wiring Away From Sharp Projections, Corners, and Internal
Components
A minimum of 1/4 inch space is required between Power Limited and Non-Power Limited circuits
while wiring.
MISE EN GARDE –
•
Lors de la pose, acheminer le câblage extérieur de manière à éviter les arêtes vives, les coins et les
composants internes
•
Un espace minimum de 1/4 pouce est requis entre les circuits à puissance limitée et non limitée
lors du câblage.