800.879.8585
www.legrand.us/wattstopper
No. 24214 – 09/16 rev. 1
© Copyright 2016 Legrand All Rights Reserved.
© Copyright 2016 Tous droits réservés Legrand.
© Copyright 2016 Legrand Todos los derechos reservados.
Wattstopper warranties its products to be free
of defects in materials and workmanship for a
period of five (5) years. There are no obligations
or liabilities on the part of Wattstopper for
consequential damages arising out of, or in
connection with, the use or performance of this
product or other indirect damages with respect
to loss of property, revenue or profit, or cost of
removal, installation or reinstallation.
Wattstopper garantit que ses produits sont
exempts de défauts de matériaux et de fabrication
pour une période de cinq (5) ans. Wattstopper
ne peut être tenu responsable de tout dommage
consécutif causé par ou lié à l’utilisation ou
à la performance de ce produit ou tout autre
dommage indirect lié à la perte de propriété, de
revenus, ou de profits, ou aux coûts d’enlèvement,
d’installation ou de réinstallation.
Wattstopper garantiza que sus productos
están libres de defectos en materiales y mano
de obra por un período de cinco (5) años. No
existen obligaciones ni responsabilidades por
parte de Wattstopper por daños consecuentes
que se deriven o estén relacionados con el
uso o el rendimiento de este producto u otros
daños indirectos con respecto a la pérdida
de propiedad, renta o ganancias, o al costo
de extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
TROUBLESHOOTING
If the lights will not go OFF after the time out period, and the LED does not come on when moving in front of the sensor:
1. Disconnect the wire to the power pack, if lights do not go OFF, check Power Pack connection:
• voltage going in (120 or 277AC)
If there is no power, check the breaker has been turned back on.
• 24VDC coming out for the power pack (Red and Black).
If there is no power, check that the power pack has been wired correctly.
2. If lights still do not go off, call 800.879.8585 to talk to Technical Support.
Motion occurs in the room and the lights do not turn on:
1. Check the sensitivity setting and increase as needed.
2. Check connections between sensors and power packs.
3. If there is still a problem, check to see that there is 24VDC at the sensor (Red and Black).
• If 24VDC is present, replace sensor.
• If 24VDC is not present, check Power Pack.
4. If lights still do not turn on, call 800.879.8585 to talk to Technical Support.
Lights cycle on and off:
If the lights go off, and immediately turn back on, the sensor is picking up the infrared energy change from the lights. Adjusting the
sensitivity down slightly until the lights stay off will usually eliminate this problem. If not, use the masking tape provided to mask (block
out) the part of the lens window that views the lights.
ON OVERRIDE:
Next to the Sensitivity Adjustment dial is an opening that contains a jumper pin. Remove this jumper if you want to override the switching
circuit and have the lights and the LED remain on regardless of occupancy. Replacing the jumper in the same position, will reactivate
the switching circuit.
OVERLOAD PROTECTION
The occupancy sensor has a built in overload protection function that will automatically turn off the control output when the load current
exceeds 200mA. The LED will blink rapidly for 5 seconds to provide a visual indication of an overload condition. When the load current
is corrected or returns to normal, the control output will turn back on.
ORDERING INFORMATION
Catalog Description
WPIR PIR Occupancy Sensor
BZ-50 Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent
BZ-150 Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent, with Hold-On and Hold-Off capability
BZ-200 Power Pack: 120/277VAC, 50/60 Hz, 20A Ballast/ELV/MLV/Incandescent/LED, 16A, E-Ballast/CFL/Plug Load
BZ-250 Power Pack: 120/277VAC, 50/60 Hz, 20A, Ballast/ELV/MLV/Incandescent/LED, 16A E-Ballast/CFL/Plug Load,
with Hold-On/Hold-Off capability
BZ-250-347 Power Pack: 120/347VAC, 50/60 Hz, 16A Ballast/ELV/MLV/Incandescent/LED/ E-Ballast/CFL, 15A Plug Load,
with Hold-On/Hold-Off capability