Big Ass Fans F-EV1-1001S75V60 Guide d'installation

Taper
Guide d'installation

Ce manuel convient également à

BIGASSFANS.COM
COLD FRONT 100
COLD FRONT 200
EXCEPTIONALLY
ENGINEERED
READ AND SAVE THESE INSTRUCTIONS
LISEZ ET CONSERVEZ CES INSTRUCTIONS
LEA Y GUARDE ESTAS INSTRUCCIONES
Operation and Maintenance Manual
Manuel de fonctionnement et d'entretien
Manual de operación y mantenimiento
F-EV1-1001S75
F-EV1-1001S75V60
READ AND SAVE THESE INSTRUCTIONS
DANGER
DANGER indicates an imminently hazardous
situation which, if not avoided, WILL result in
death or serious injury.
WARNING
WARNING indicates a potentially hazardous
situation which, if not avoided, COULD
result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous
situation which, if not avoided, MAY result in
minor or moderate injury.
IMPORTANT
IMPORTANT indicates a potentially
hazardous situation which, if not avoided,
MAY result in property damage.
Installation Guide
Rev. C
09/22/2020
Improper installation, delivery, or maintenance, including, but not limited to, any of the following actions by
the customer or agent of the customer will constitute a breach of and will void all warranties:
Failure to follow the required installation procedures specified in this Installation Guide and in
all other documentation supplied with the fans and related equipment including documentation
provided by the manufacturers of the individual fan and control components;
Failure to follow all relevant codes and ordinances, including, but not limited to, the National
Electrical Code (United States), applicable national and local electrical codes, and state and local
building codes;
Failure to follow electrical engineering industry standards regarding the approved method of
installing solid-state electrical equipment having the characteristics of the fans, the fan controls, and
their related components, even if such standards are not specifically referenced in any instructions or
literature supplied by Big Ass Fans or provided by manufacturers.
All trademarks used herein are the properties of their respective owners. No part of this document may
be reproduced or translated into a dierent language without the prior written consent of Big Ass Fans.
The information contained in this document is subject to change without notice. For the most up-to-date
information, see the online printable installation guide at www.bigassfans.com
Patent: www.bigassfans.com/patents • www.bigassfans.com/product-warranties
Original English Instructions www.bigassfans.com/support
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
1
CHECKLIST
DO
Read the Operation and Maintenance Manual.
Check all hose connections.
Use a 12 gauge cord if the cord is under 50 ft (15 m) or a 10 gauge
cord if the cord is over 50 ft (15 m).
Provide fresh air intake for the cooler and maintain a minimum
clearance of 3 ft (0.9m) behind the cooler.
Flush new cooling media.
1. Fill the cooler with water.
2. Switch on the pump.
3. Run the cooler without the fan running for 5 hours.
Make sure the cooling media is being evenly saturated.
Drain and clean the cooler weekly. Remove the cooling media and
wash with a garden hose.
Use Refresh™ tablets (algae killer) and/or CTT-EC™ cooler treatment
tablets (mineral treatment). One algae killer tablet is provided in the
cooler's reservoir. Additional water treatment tablets are available
at bigassfans.com.
DO NOT
Χ DO NOT forget to dry out the cooling media before shutting down
the cooler. Turn o the pump and leave the fan running for 10 to 15
minutes.
Χ DO NOT run the pump without filling the reservoir with water first.
Χ DO NOT use a water source with more than 120 PSI of water
pressure.
Χ DO NOT operate the cooler in a sealed room. Allow for fresh air
intake and exhaust.
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
2
ASSEMBLY
IMPORTANT
Carefully examine the carton for damage before opening. If the carton is
damaged, notify the shipping company immediately.
Install casters
1. Locate the package of four (4) casters and remove from box.
2. Lay box on its side and carefully open bottom of box. DO NOT STAND BOX
UPSIDE DOWN.
3. Install the four casters.
4. Stand cooler up on casters and remove box.
SETUP
The cooler has been factory tested and is ready to use. Place the cooler on level
ground with the casters locked to prevent inadvertent movement.
Connecting the water supply
The cooler comes equipped with a female garden hose water source connection.
Use a standard garden hose (not provided) to connect the water supply to the
cooler.
CAUTION
Do not connect to any water source where water pressure exceeds 120 PSI.
This will cause permanent damage to the cooler.
Connecting the electrical supply
IMPORTANT
The cooler should be plugged into a fused or breaker-protected circuit. Refer
to Table 1 for circuit size requirements.
Amperage and Circuit Requirements
Model Volts +/- 10% Frequency Min. Circuit Size
Running
Amps
Cold Front 100 120 V 60 Hz 15 A 1.5 A
Cold Front 200 120 V 60 Hz 15 A 2.7 A
Table 1: Electrical Requirements
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
3
CAUTION
Do not exceed the amperage ratings of the extension cord. Undersized
extension cords create excessive drops in voltage, causing the electric motor
to generate excess heat. This results in inecient motor operation and
premature motor failure and will void the warranty.
Three-Conductor Heavy Duty Extension Cord Requirements
Cord
Length
Cord Size
16 GA 14 GA 12 GA 10 GA
0–50 ft
(0–15 m)
13 A 18 A 25 A 30 A
50–100 ft
(15–30 m)
10 A 13 A 18 A 25 A
Table 2: Cord Size Requirements
OPERATION
The cooler must be placed on level ground to operate correctly. Evaporative
coolers create an oval-shaped air pattern. Obstacles such as racks and
workbenches may interfere with airflow. Position the cooler so that interruption
of the air pattern is minimized. Multiple coolers may be required to cover larger
areas.
There are three major factors to consider when determining where to place the
cooler.
1. Fresh Air Supply. The inlet (mesh sides) requires a constant, uninterrupted
supply of fresh air for maximum performance. A distance of 3 ft (0.9 m)
of clear space to any obstructions at the rear or inlet side of the cooler is
recommended.
2. Discharge Airflow. The cool air discharged from the cooler should be free from
obstruction to promote air circulation in order to maximize the cooling zone.
3. Ventilation. Adequate ventilation is needed to ensure the cooler does not
recirculate air that has already been through the evaporative cooling process.
Filling the cooler with water
Once the cooler has been connected to a water source, turn the water source on
to fill the cooler with water. The float valve will shut o the water flow when the
sump is full.
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
4
CAUTION
Prolonged use of hard water without proper water treatment will create
mineral deposit buildup. This will cause the pump to fail and is NOT
COVERED BY WARRANTY.
Starting the pump
On initial startup, the cooling media in your new cooler will take a few hours to
become fully saturated. During this time, the media may produce an odor. This
odor will dissipate over time. For best results, change the water in the reservoir a
few times.
Subsequent startups
On subsequent startups, turn on the pump, start the fan, and cool down.
Low water indicator
The cooler is equipped with a low water indicator light.
When the power is on and there is sucient water in the reservoir, the light will
be green and the pump will be running.
When the power is on and the water in the reservoir is low, the light will be red
and the pump will stop running.
Starting the fan
Turn the fan control knob clockwise to turn on the fan and adjust the speed to
your preferred setting.
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
5
MAINTENANCE AND STORAGE
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect the power supply before performing any service or maintenance.
Failure to do so may result in serious injury or death.
Removing the cooling media
Remove the cooling pads to access the inside of the cooler.
1. Remove pad grilles from support channel.
2. Tilt pads from the top and lift out of the cooler.
Daily maintenance
After each use, turn o the pump about 15 minutes before the fan is turned o to
allow the pads to drain and dry out. This controls mildew and bacteria growth for a
long and ecient pad life. Drain the water from the cooler if it will be unused for a
prolonged period of time.
Periodic maintenance
The cooling pads act as a filter to remove dust and other particles from the
incoming air stream. The collected particles and any water impurities will flow into
the sump and collect there. To keep the cooler operating at peak eciency, keep
the cooling media and sump clear of debris. Water treatment tablets are available
at bigassfans.com.
Draining the water sump
Depending on how often you operate the cooler, drain the sump anywhere from
every week for heavy use to monthly for light use.
1. Turn cooler o and disconnect the power supply.
2. Remove drain plug located at bottom of reservoir and let cooler drain.
3. Remove cooling pads.
4. Clean out reservoir with either a towel or wet/dry vacuum.
5. Reinstall pads and grille.
Cleaning the cooling media
Ensure the cooling pads are kept clean and dust-free. Dust and other particles
have an adverse eect on the pads’ ability to introduce water into the air stream. If
the pad surface is dirty, clean with a soft brush and water. Never use bleach.
Storage
1. Remove cooling pads and clean with a soft brush and water to remove dust
and debris.
2. Drain sump and wipe dry.
3. Store cooler in a dry area and cover to prevent dust buildup.
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
6
TROUBLESHOOTING AND REPAIR
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect the power supply before performing any service or maintenance.
Failure to do so may result in serious injury or death.
CAUTION
Please use caution when troubleshooting or repairing all electrical
components. Ensure all power is disconnected from the cooler before the
pads or fan guard are removed to gain access to the fan.
Tools needed
Screwdrivers
Pliers
Adjustable wrenches
Volt/Ohm meter (electrical troubleshooting)
Additional tools may be required.
General troubleshooting
The cooler consists of three systems:
Pump
Water distribution system
Fan system
Use the troubleshooting tables on the following pages to determine which
system(s) require servicing.
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
7
Pump troubleshooting
Issue Solution(s)
Pump motor will not run
when switch is turned on.
Turn fan on to check for power.
If fan does not start, check breaker and make
sure cord is plugged in.
If fan starts, check for power to and through
pump switch (when turned on).
Ensure water level is high enough to make the
low water cuto circuit.
Fill water reservoir.
Pump motor hums when
switch is turned on but does
not pump water.
Obstruction in impeller.
Remove object(s).
Pump motor failure.
Replace pump.
Breaker trips or fuse blows
when switch is turned on.
Check power cord length and breaker rating.
Refer to page 2 for cooler amperage draw and
to determine required cord gauge and circuit
size.
Check for locked up pump.
Replace pump.
Pump runs but does not
pump water.
Air lock in outlet side of pump.
Turn o and on to bleed.
Ensure the impeller is turning in pump.
If not, replace pump.
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
8
Pump repair procedures
CAUTION
Repairs should be performed by a qualified technician!
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect the power supply before performing any service or maintenance.
Failure to do so may result in serious injury or death.
Pump replacement
1. Remove cooling pads.
2. Remove switch plate and disconnect pump wire. Refer to wiring diagram on the
following page.
3. Remove hose and level switch from pump.
4. Remove pump from water sump and install new pump.
5. Perform the steps above in reverse to reconnect the wiring, level switch, and
hose. Secure wires to fan frame with wire ties so that wires are clear of fan
blades. Ensure plug is positioned correctly.
6. Reinstall cooling pads and guards.
7. Reconnect power and test pump.
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
9
Water distribution system troubleshooting
The water distribution system consists of two assemblies:
Water inlet assembly
Brass bulkhead fitting
Float valve assembly
Hose and valve assembly
Drip channel
Valve assembly
Connection hose
Issue Solution(s)
Floor at side of cooler is wet. Water inlet hose is loose at supply hose or inlet
hose is loose at bulkhead fitting.
Tighten connections and/or replace hose
washers.
Water overflows from
reservoir.
Float valve hose is loose at bulkhead fitting or
at float valve.
Tighten connections and/or replace hose
washers.
Water pressure is too high to allow float valve
to shut o (120 PSI max).
Reduce water pressure by adding an inline
reducer.
Float valve is not properly seated.
Check all hoses for leaks.
Water is spitting from the
cooler.
Check the hose and valve assembly.
Reduce flow control setting.
Replace cracked hose and valve assembly.
Tighten hose connections.
Water is leaking from the
drain plug.
Check that plug is tightly seated in hole.
Tighten drain plug.
Replace drain plug.
There are too many dry
streaks on the pads.
Check for blocked holes in the drip channel.
Remove and clean tube and holes.
Cooler will not fill. Check float screen.
Clean.
Float not functioning.
Replace.
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
10
Fan system troubleshooting
Issue Solution(s)
Fan will not run and makes
no sound.
Check power cord, extension cord, switches,
and circuit breaker.
Reconnect power or extension cord.
Reset breaker.
Fan will not run and makes
humming sound.
Check capacitor.
Re-center blade hub.
Motor stall (will not turn by hand).
Replace motor.
Breaker trips or fuse blows
when fan starts.
Motor stall.
Replace motor.
Check power source. Refer to page 2 for
electrical requirements.
Upgrade power supply.
Extension cord gauge is too small.
Replace with heavier cord.
Motor overheats, shuts o,
and restarts several minutes
later.
Extension cord gauge is too small.
Replace with heavier cord.
Inlet air is obstructed or too close to wall.
Provide minimum 3 ft (0.9 m) inlet clearance.
Faulty motor.
Replace motor.
Fan motor will not run and
switch makes soft clicking
sound.
Ensure switch is making good contact.
Replace switch if needed.
Fan blade does not turn
and cooler makes squealing
sound.
Motor stall (will not turn by hand).
Replace motor.
Fan will not reach speed but
turns and makes humming
sound.
Check capacitor (where visible) and motor
electrical connections.
Replace capacitor or motor.
Extension cord gauge is too small.
Replace with heavier cord.
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
11
Fan repair procedures
CAUTION
Repairs should be performed by a qualified technician!
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect the power supply before performing any service or maintenance.
Failure to do so may result in serious injury or death.
Fan motor replacement
1. Remove cooling pads.
2. Remove black motor wiring plate and disconnect motor wires. Mark each wire
with a marker or marker tape for easy matching when installing new motor.
3. Remove louver.
4. Remove the four (4) nuts and bolts securing the motor, fan, and support braces
(complete fan assembly).
5. Replace with new fan assembly.
6. Secure with four (4) nuts and bolts.
7. Replace any wire ties that were removed when uninstalling the old fan
assembly.
8. Replace black motor wiring plate.
9. Reinstall pads and connect power.
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
12
Wiring diagram
5
1
9
1314
FAN
120V
PUMP
LOW LEVEL
SWITCH
FAN
VARIABLE SPEED
SWITCH
PUMP SWITCH
INDICATOR LIGHT
GREEN
BLACK
BLACK
BLACK
BLACK
RED
BLACK
WHITE
WHITE
BLUE
BLACK
GREEN
WHITE
GREEN
WHITE
WHITE
WHITE
GREEN
GREEN
GREEN
GREEN
WHITE
BLACK
BLACK
BLACK
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
13
MAINTENANCE
Spring cleaning
Remove the cooling media and clean out any debris in the
water pan at the bottom of the cooler.
Remove the distribution tube from the mounting clips.
Remove the plug at the end of the tube and flush out.
Clean the distribution holes with a small brush and flush
with water to verify all holes are clear.
If the cooling media is heavily stained with minerals or is
damaged, replace the media. Replacement cooling media
is available at bigassfans.com. Verify the media is installed
correctly with the arrows on the side.
Connect the water line and turn on the water supply.
Check the float valve and make sure it is operating
properly. Verify that the float valve is shutting the water o
before walking away.
Switch on the fan motor and pump. Make sure the cooling
media is being evenly saturated with water. Small dry
streaks are acceptable.
Mid-summer checkup
Make sure the float valve is working properly. If the valve
sticks, the water will run continuously and flood the
reservoir. If this occurs, install a new float valve or contact
Customer Service.
Check all other working parts for cracks or damage,
including the pump, fan motor, and fan belt.
Check the condition of the cooling media. The cooler runs
most eciently when the media is clean. If the media has
a heavy accumulation of mineral deposits, replace it.
Use the drain valve to empty the reservoir. Remove any
debris.
WWW.BIGASSFANS.COM © 2020 DELTA T LLC ALL RIGHTS RESERVED.
14
Winterize
Clean the minerals from the reservoir. Vinegar can be
used to dissolve buildup. Flush out the reservoir through
the drain plug.
Inspect the water distribution tube for clogged holes.
Clean as necessary.
To prevent freezing in the cooler’s water line, disconnect
the water supply, and then open both valves on the side
of the cooler to dry out the reservoir.
Use a storage cover to protect your cooler and keep it
clean.
CONTACT US
Customer Service
2348 Innovation Drive
Lexington, KY 40511
USA
877-244-3267
bigassfans.com
www.bigassfans.com/support
Accessories and Replacement Parts
www.bigassfans.com
FRAAIS
LISEZ ET CONSERVEZ CES INSTRUCTIONS
DANGER
DANGER indique une situation
imminente dangereuse qui, si elle
n'est pas évitée, ENTRAÎNERA une
blessure grave ou mortelle.
AVERTISSEMENT
AVERTISSEMENT indique
une situation potentiellement
dangereuse qui, si elle n'est pas
évitée, PEUT entraîner une blessure
grave ou mortelle.
ATTENTION
ATTENTION indique une situation
potentiellement dangereuse qui, si
elle n'est pas évitée, PEUT entraîner
une blessure mineure ou modérée.
IMPORTANT
IMPORTANT indique une situation
potentiellement dangereuse qui, si
elle n'est pas évitée, PEUT entraîner
des dommages à la propriété.
Guide d'installation
Rév. C
09/22/2020
Une installation, une livraison ou un entretien non conforme, incluant, sans s'y limiter, l'une des actions
suivantes par le client ou son agent constitue une violation de toutes les garanties et les rendra nulles :
Le fait de ne pas suivre les procédures d'installation requises précisées dans ce guide d'installation
et dans toute autre documentation fournie avec les ventilateurs et l'équipement connexe incluant la
documentation fournie par le fabricant du ventilateur et des composants de commandes individuels;
Le fait de ne pas suivre tous les codes et règlements applicables incluant, sans toutefois s'y limiter, le
National Electrical Code (États-Unis), les codes de l'électricité nationaux ou locaux applicables et les
codes du bâtiment de l'État ou locaux;
Le fait de ne pas suivre les normes industrielles de l'électrotechnique sur la méthode approuvée de
l'installation de l'équipement électrique ayant les caractéristiques des ventilateurs, des commandes
du ventilateur et leurs composants connexes, même si ces normes ne sont pas mentionnées
spécifiquement dans toutes les instructions ou toute la documentation fournie par Big Ass Fans ou
par les fabricants.
Toutes les marques de commerce mentionnées ici appartiennent à leurs propriétaires respectifs.
Aucune partie de ce document ne peut être reproduite ou traduite dans une autre langue sans l'accord
préalable écrite de Big Ass Fans. Les renseignements contenus dans ce document peuvent être modifiés
sans préavis. Pour obtenir les informations les plus récentes, veuillez consultez le guide d'installation
imprimable au www.bigassfans.com
Brevet : www.bigassfans.com/patents • www.bigassfans.com/product-warranties
Instructions originales en anglais www.bigassfans.com/support
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56

Big Ass Fans F-EV1-1001S75V60 Guide d'installation

Taper
Guide d'installation
Ce manuel convient également à