800.879.8585
www.legrand.us/wattstopper
No. 25225 – 11/16 rev. 1
© Copyright 2016 Legrand All Rights Reserved.
© Copyright 2016 Tous droits réservés Legrand.
© Copyright 2016 Legrand Todos los derechos reservados.
Wattstopper warranties its products to be free
of defects in materials and workmanship for a
period of five (5) years. There are no obligations
or liabilities on the part of Wattstopper for
consequential damages arising out of, or in
connection with, the use or performance of this
product or other indirect damages with respect
to loss of property, revenue or profit, or cost of
removal, installation or reinstallation.
Wattstopper garantit que ses produits sont
exempts de défauts de matériaux et de fabrication
pour une période de cinq (5) ans. Wattstopper
ne peut être tenu responsable de tout dommage
consécutif causé par ou lié à l’utilisation ou
à la performance de ce produit ou tout autre
dommage indirect lié à la perte de propriété, de
revenus, ou de profits, ou aux coûts d’enlèvement,
d’installation ou de réinstallation.
Wattstopper garantiza que sus productos
están libres de defectos en materiales y mano
de obra por un período de cinco (5) años. No
existen obligaciones ni responsabilidades por
parte de Wattstopper por daños consecuentes
que se deriven o estén relacionados con el
uso o el rendimiento de este producto u otros
daños indirectos con respecto a la pérdida
de propiedad, renta o ganancias, o al costo
de extracción, instalación o reinstalación.
WARRANTY INFORMATION INFORMATIONS RELATIVES À LA GARANTIE INFORMACIÓN DE LA GARANTÍA
Shield is Twisted & Heat Shrunk
(Not Connected to Terminal)
Connect to another
LMBC-300-H6
or to LM-MSTP
cable
Terminal
Female
Terminal Block
Male
Terminal Block
S
+
-
R
S
+
R
LMBC-300 LMBC-300
Connect to another
LMBC-300-H6
or to LM-MSTP cable
with Female Te
Block (in package)
If end of line, attach
120Ω resistor
S
+
R
S
+
R
-
-
-
18” DIN Rail
LMBC-300
If fewer than 6 LMBC-300s
are connected, place one at
each end to prevent slack
in cable
Shield connected to
Terminal Block at
each end of harness
Shield connected to
Terminal Block at
Example of LMBC-300-H6 Installed With LMBC-300s
1.25"
0.50"
Bare Wire
Insulation Strip Guide
*Legrand recommends using Ferrules,
but if not using, wire should be stripped to .25” only
Attaching a Ferrule
Crimp
Ferrule
Insulation
Jacket
LM-MSTP wire
Attaching Ferrules to LM-MSTP Wires
Wattstopper recommends attaching ferrules to the LM-MSTP wires to
help maintain signal integrity. Wires should be stripped as shown in the
diagram to the right. Insert the wire into a ferrule and crimp the end,
using a crimping tool designed to work with ferrules. Then insert the end
of the ferrule into the appropriate slot in the terminal block.
R
+
-
S
R
+
-
S
R
+
-
S
R
+
-
S
Room 1 Room 2 Room 3 Room 4 Room 5 Room 6Electrical Closet
Room 7 Room 8 Room 9 Room 10 Room 11 Room 12
Segment Manager
or
Segment Manager
with NB-Router
LM-MSTP cable (BACnet)
CAT-5e cable (DLM Network)
To
Room
Controller
LMBC-300-H6 with 6 LMBC-300s
Room
Controller
LMBC-300-H6 with 6 LMBC-300s
Example of hallway and rooms using networked LMBC-300-H6s