© Copyright Danfoss | Commercial Compressors | 2014.11FRCC.PI.023.A2.61 - November 2014 - 8510264P01B
Discharge Gas Temperature sensor
replacement on PSH051-064-077
Instructions
Discharge Gas Temperature sensor
replacement on PSH compressors
Introduction
This procedure describes how to replace a
Discharge Gas Temperature sensor on PSH051
- 064 - 077 compressors. These operations
must be performed by qualied personnel in
compliance with all pertinent practises and
safety procedures.
DGT sensor replacement
• Unplug cable from DGT sensor. (g. 1 and 2)
• Disassemble the DGT sensor on the top shell
with an open end wrench. (g. 3)
• Remove thermal paste from the damaged
sensor and apply it on top of the new DGT
sensor. (g. 4)
• Mount the new DGT sensor with open end
torque wrench and tighten it with a 25N.m
torque. (g. 5)
• Plug the cable on DGT sensor. (g. 6)
• Check that the DGT sensor is operating
correctly. The alarm A42 “Discharge
temperature sensor error” must now be o.
Remplacement du capteur de température de
refoulement sur les compresseurs PSH
Introduction
Cette procédure décrit comment remplacer
un capteur de température de refoulement
sur des compresseurs PSH051 - 064 - 077.
Ces opérations doivent être réa-lisées par un
personnel qualié dans le respect des règles
en vigueur.
Remplacement du capteur
• Débrancher le câble du capteur de
température de refoulement. (g. 1 et 2)
• Démonter le capteur de température de
refoulement sur la cloche supérieure avec
une clé plate. (g. 3)
• Enlever la pâte contact du capteur de
température de refoulement endommagé et
mettre la pâte contact au bout du nouveau
capteur de température refoulement. (g. 4)
• Monter le nouveau capteur de température
et le serrer au couple 25N.m. (g. 5)
• Rebrancher le câble sur le capteur. (g. 6)
• Vérier le bon fonctionnement du capteur :
l’alarme A42 “Discharge temperature sensor
error” doit maintenant être désactivée.
La sostituzione del sensore di temperatura
del gas di scarico sui compressori PSH
Introduzione
Questa procedura descrive come sostituire un
sensore di temperatura del gas di scarico sui
compressori PSH051 - 064 - 077.
Queste operazioni devono essere eseguite da
personale qualicato in conformità con tutte le
pratiche pertinenti e le procedure di sicurezza.
Sostituzione del sensore DGT
• Scollegare il cavo dal sensore DGT. (g. 1 e 2)
• Smontare il sensore DGT sul coperchio del
compressore con una chiave ad estremità
aperta. (g. 3)
• Rimuovere la pasta termica dal sensore
danneggiato e applicarla sulla parte
superiore del sensore DGT nuovo. (g. 4)
• Montare il nuovo sensore DGT con una
chiave aperta e avvitare la vite con una
coppia di 25 Nm. (g. 5)
• Collegare il cavo sul sensore DGT. (g. 6)
• Controllare che il sensore DGT stia
funzionando correttamente. L’allarme A42
“Errore del sensore di temperatura di scarico
“ ora deve essere spento.