Simplicity 076052-00 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation

Ce manuel convient également à

GE Generator Systems
Liquid-Cooled
Generator System
Installation and
Start-Up Manual
NOT
FOR REPRODUCTION
2
Thank you for purchasing this quality-built GE generator. We’re pleased that you’ve placed your confidence in the GE
brand. When operated and maintained according to the instructions in the operator’s manual, your generator will
provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with generator
systems and how to avoid them. This generator system is designed and intended only for use as an optional standby
system that provides an alternate source of electric power and to serve loads such as heating, refrigeration systems,
and communication systems that, when stopped during any power outage, could cause discomfort or inconvenience.
Save these original instructions for future reference.
This standby generator requires professional installation before use. The installer should follow the
instructions completely. Installations must strictly comply with all applicable codes, industry standards and regulations.
Where to Find Us
You never have to look far to find support and service for your generator. For quick service when you need it
most fill out the information below and keep your original receipt with this manual. You may contact Customer
Service, toll-free at 888‑575‑8226 between 8:00 AM and 5:00 PM CT., or click on SERVICE & SUPPORT at
www.homestandbygeneratorsystems.com, which provides a list of authorized dealers.
For Future Reference
Please fill out the information below and keep with your receipt to assist in unit identification for future purchase issues.
Date of Purchase: _____________________________
Generator
Model Number _____________________________
Model Revision _____________________________
Serial Number _____________________________
Engine
Serial Number _____________________________
NOT
FOR REPRODUCTION
3
Table of Contents
Safety Rules................................................4
Installation ................................................7
Owner Responsibilities ......................................
7
Installing Dealer/Contractor Responsibilities............................7
Unpacking Precautions................................................7
Shipment Contents ...................................................8
Installation Checklist..................................................8
Generator Placement .................................................9
Exhaust Side of Generator.............................................9
Placement of Standby Generator to
REDUCE THE RISK OF CARBON MONOXIDE POISONING ..................10
Placement of Standby Generator to REDUCE THE RISK OF FIRE...........12
Other General Location Guidelines ....................................16
Electrical and Fuel Inlet Locations.....................................17
The Gaseous Fuel System ............................................20
Fuel Pipe Sizing......................................................21
Fuel Conversion .....................................................21
Fuel Pressure........................................................21
Power Loss..........................................................21
Fuel Consumption ...................................................22
System Connectors ..................................................23
Grounding the Generator.............................................25
Final Installation Considerations ......................................27
Initial Start‑up (No Load) .............................................28
Operation.................................................29
Automatic Operation Sequence .......................................29
Setting Exercise Timer ...............................................29
Installation Inspection ...............................................30
Schematic Diagram..................................................31
Wiring Diagram .....................................................39
NOT
FOR REPRODUCTION
4
Safety Rules
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a degree
or level of hazard seriousness. A safety symbol may be used
to represent the type of hazard. The signal word NOTICE is
used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
Important Safety Instructions
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings
in this manual, and the tags and decals affixed to the unit
are, therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that it
is safe for you and others. You must also make sure that the
procedure, work method or operating technique that you
choose does not render the generator system unsafe.
Fire
Toxic Fumes
Explosive Pressure
Rotating Fan Blade
Lift Hazard Read Manual
Exploding BatteryRotating Belt/Pulley
Chemical BurnAuto Start
Hot SurfaceRotating Parts
Electrical ShockExplosion
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors, ventailation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
• Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
WARNING The engine exhaust from this product contains
chemicals known to the State of California to cause cancer, birth
defects, or other reproductive harm.
WARNING Certain components in this product and related
accessories contain chemicals known to the State of California
to cause cancer, birth defects, or other reproductive harm. Wash
hands after handling.
NOT
FOR REPRODUCTION
5
WARNING Storage batteries give off explosive hydrogen gas
during recharging.
Slightest spark will ignite hydrogen and
cause explosion, resulting in death, serious
injury and/or property damage.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents could cause severe chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette during
and for several minutes after charging a battery.
• DO NOT open or mutilate the battery.
• Wear protective goggles, rubber apron, rubber boots and
rubber gloves.
• Remove watches, rings, or other metal objects.
• Use tools having insulated handles.
WARNING Generator produces hazardous voltage.
Failure to properly ground generator could result
in electrocution.
Failure to isolate generator from power utility could result
in death or serious injury to electric utility workers due to
backfeed of electrical energy.
• DO NOT touch bare wires or bare receptacles.
• DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
• DO NOT handle generator or electrical cords while standing in
water, while barefoot, or while hands or feet are wet.
• If you must work around a unit while it is operating, stand on an
insulated dry surface to reduce the risk of a shock hazard.
• DO NOT allow unqualified persons or children to operate or
service generator.
• In case of an accident caused by electrical shock, immediately
shut down the source of electrical power and contact the local
authorities. Avoid direct contact with the victim.
• Despite the safe design of the residential generator, operating
this equipment imprudently, neglecting its maintenance or being
careless could cause possible injury or death.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• Before performing any maintenance on the generator, disconnect
the battery cable indicated by a NEGATIVE, NEG or () first. When
finished, reconnect that cable last.
• After your system is installed, the generator may crank and start
without warning any time there is a power failure. To prevent
possible injury, always set the generator’s system switch to OFF,
remove the service disconnect from the disconnect box AND
remove the 15 Amp fuse BEFORE working on the equipment.
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death, serious injury and/or
property damage.
• Install the fuel supply system according to NFPA 37 and other
applicable fuel-gas codes.
• Before placing the generator into service, the fuel system lines
must be properly purged and leak tested.
• After the generator is installed, you should inspect the fuel
system periodically.
• NO leakage is permitted.
• DO NOT operate engine if smell of fuel is present or other
explosive conditions exist.
• DO NOT smoke around the generator. Wipe up any oil spills
immediately. Ensure that no combustible materials are left in the
generator compartment. Keep the area near the generator clean
and free of debris.
WARNING Hazardous Voltage - Contact with power lines could
cause electric shock or burn, resulting in death or
serious injury.
Lifting Hazard / Heavy Object - Could result in
serious injury.
• If lifting or hoisting equipment is used, DO NOT contact any
power lines.
• DO NOT lift or move generator without assistance.
• Use lifting pipes as described in Lifting the Generator.
• DO NOT lift unit by roof as damage to generator will occur.
WARNING Moving parts could crush and cut.
Starter and other rotating parts
could entangle hands, hair, clothing,
or accessories resulting in serious injury.
• NEVER operate generator without protective housings, covers, or
guards in place.
• DO NOT wear loose clothing, jewelry or anything that could be
caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
• Before servicing, remove 15 Amp fuse from control panel and
disconnect Negative (NEG or ) battery cable.
NOT
FOR REPRODUCTION
6
CAUTION Excessively high operating speeds could result in
minor injury and/or equipment damage.
Excessively low speeds impose a heavy load on generator.
• DO NOT tamper with governed speed. Generator supplies correct
rated frequency and voltage when running at governed speed.
• DO NOT modify generator in any way.
WARNING Exhaust heat/gases could ignite combustibles
or structures resulting in death, serious injury and/or property
damage.
Contact with muffler area could cause burns resulting in
serious injury.
• DO NOT touch hot parts and AVOID hot
exhaust gases.
• Allow equipment to cool before touching.
• Exhaust outlet side of weatherproof enclosure must have at least
5 ft. (1.5m) minimum clearance from any structure, shrubs, trees
or any kind of vegetation.
• Standby generator weatherproof enclosure must be at least
5 ft. (1.5m) from windows, doors, any wall opening, shrubs or
vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a minimum
of 5 ft. (1.5 m) overhead clearance from any structure, overhang,
or trees.
• DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
• Use only flexible fuel line provided. Connect provided fuel line to
generator. DO NOT use with or substitute any other flexible
fuel line.
• Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/recommendations.
Carbon monoxide alarms cannot detect smoke.
• Keep at least minimum distances shown in General Location
Guidelines to insure for proper generator cooling and
maintenance clearances.
• Replacement parts must be the same and installed in the same
position as the original parts.
WARNING Hot pressurized coolant could cause serious injury
and/or property damage.
• DO NOT open radiator cap when hot.
• Before servicing, allow coolant to cool.
CAUTION Installing the 15A fuse could cause the engine
to start at any time without warning resulting in minor or
moderate injury.
• Observe that the 15 Amp fuse has been removed from the control
panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.
NOTICE Improper treatment of generator could damage it and
shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, contact your
authorized dealer.
• Operate generator only on level surfaces.
• Adequate, unobstructed flow of cooling and ventilating air is
critical to correct generator operation.
• The access panels/door must be installed whenever the unit
is running.
• DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• DO NOT start engine with air cleaner or air cleaner cover removed.
• DO NOT insert any objects through cooling slots.
• DO NOT use the generator or any of its parts as a step. Stepping
on the unit could cause stress and break parts. This may result in
dangerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
• If connected devices overheat, turn them off and disconnect them
from generator.
• Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively;
-unit makes unusual noises.
NOTICE Exceeding generators wattage/amperage capacity could
damage generator and/or electrical devices connected to it.
• Start generator and let engine stabilize before connecting
electrical loads.
NOT
FOR REPRODUCTION
7
• Readandfollowtheinstructionsgiveninthe
Operator’s Manual.
• Followaregularscheduleinmaintaining,caring
for and using your generator, as specified in the
Operator’s Manual.
Owner Responsibilities
The system is equipped with an optional water heater that is
activated when ambient temperature is less than 80°F AND
utility power is present at the transfer switch.
If you need more information on this matter, please call
888-575-8226, between 8:00 AM and 5:00 PM CT.
• Readandobservethesafetyrules.
• InstallonlyanULapprovedtransferswitchthatis
compatible with the generator.
• Readandfollowtheinstructionsgiveninthis
Installation and Start-up Manual.
• Installationmuststrictlycomplywithallapplicable
codes, industry standards, laws, and regulations.
• Allowsufficientroomonallsidesofgeneratorfor
maintenance and servicing.
Installing Dealer/Contractor Responsibilities
The unit is shipped ready for installation on a prepared
reinforced cement slab or engineered base. Avoid
damage from dropping, bumping, collision, etc. Store and
unpack carton with the proper side up, as noted on the
shipping carton.
Unpacking Precautions
Installation
This product is intended for use as an optional generator
system which provides an alternate source of electric power
and to serve loads such as heating, refrigeration systems,
and communication systems that, when stopped during any
power outage, could cause discomfort or inconvenience. This
product does not qualify for emergency standby as defined
by NFPA 70 (NEC).
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
Only current licensed electrical and plumbing
professionals should attempt generator system
installations. Installations must strictly comply with all
applicable codes, industry standards and regulations.
After removing the carton, carefully inspect the generator for
any damage that may have occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss or
damage. If loss or damage is noted after delivery, separate
the damaged materials and contact the carrier for claim
procedures. Missing or damaged parts are not warranted.
Delivery Inspection
NOT
FOR REPRODUCTION
8
The generator system is supplied with:
• Fully-servicedcoolantsystem
• Fully-servicedoil/lubricatingsystem
• Flexiblefuelhook-uphose
• Installationandstart-upmanual
• Operator’smanual
• Accessdoorkeys
• Spare15AmpATO-typefuse
• Ten-pincontrolpanelconnector
• Touchuppaint
• RemoteLEDindicatorkit(LED/plate/screws)
Not Supplied:
• Carbonmonoxidedetector(s)
• Smokedetector(s)
• Startingbattery
• Reinforcedconcretepad
• Connectingwireandconduit
• Fuelsupplyvalves/plumbing
• Two60”lengthsof2”Schedule40pipe(NOTconduit)
for lifting
• Crane,liftingstraps,chainsorcables
• Holepunchesfor7gasteel
• Torquescrewdriver,5to50inch-poundrange
• Voltage/frequencymeter
• Variouscommonandspecialtoolsandequipment
Shipment Contents
Proper installation of the generator requires the completion
of the following tasks:
Carbon Monoxide (CO) Detector
Carbon Monoxide (CO) detector in working order.
Smoke Detector in working order.
Placement
Required permits have been obtained.
Generator placed in a Carbon Monoxide (CO) safe zone.
See Placement of Standby Generator to Reduce the
Risk of Carbon Monoxide Poisoning.
Generator placed in a fire safe zone. See Placement of
Standby Generator to Reduce the Risk of Fire.
Generator placed in a water damage safe zone. See
Other General Location Guidelines.
Generator placed in a utility safe zone. See Other
General Location Guidelines.
Generator placed in a debris free zone. See Other
General Location Guidelines.
Fuel
Generator is connected to fuel source with flexible fuel
line, has no fuel leaks and conforms to local codes. See
The Gaseous Fuel System.
Proper fuel pressure has been measured with all gas
appliances operating. See The Gaseous Fuel System.
Electrical
Generator neutral is connected to Automatic
Transfer Switch. See Generator AC Connection
System.
Generator is grounded. See Grounding the
Generator.
Generator is connected to the transfer switch with
the specified wiring. See Utility Circuit Connection
and Transfer Switch Communication.
Generator is connected to the transfer switch with
the specified wiring. #18AWG twisted pair wiring
from the generator control panel to the transfer
switch is installed in a separate conduit from
high voltage wires unless the insulation rating on
all wiring is rated for 600V See Transfer Switch
Communication.
Dipswitches in most transfer switches must be set
to correspond to the wattage of the generator. See
Transfer Switch Operator/Installation Manual.
Operation
Correct battery type is installed and fully charged.
See Final Installation Considerations.
Generator engine oil level is at full mark. See Final
Installation Considerations.
Utility was shut off to test the operation of generator
and transfer switch. Note any fault codes and make
corrections as required.
Installation Checklist
NOT
FOR REPRODUCTION
9
Before installing the generator, consult with the owner and
convey the following requirements, which must be satisfied
before the installation is complete.
There are two equally important safety concerns in regards
to carbon monoxide poisoning and fire. There are also
several general location guidelines that must be met before
the installation is considered complete.
Generator Placement
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors, ventailation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
• Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
Exhaust Side of Generator
• Exhaustoutletsideofweatherproofenclosure
• Weatherproofenclosureoppositeexhaustside
A
A
B
B
A
NOT
FOR REPRODUCTION
10
Placement of Standby Generator to REDUCE THE RISK OF CARBON MONOXIDE POISONING
The arrows in the figure below point to POTENTIAL points of entry for Carbon Monoxide Gas.
All fossil fuel burning equipment, such as standby
generators, contains carbon monoxide (CO) gas in the engine
exhaust. CO gas is odorless, colorless and tasteless and is
unlikely to be noticed until a person is overcome. CO gas can
kill you so it is required that the following is included as part
of the installation:
• Installgeneratoroutdoorsinanareathatwillnot
accumulate deadly exhaust gas.
• DONOTinstallgeneratorwhereexhaustgascould
accumulate and enter inside or be drawn into a
potentially occupied building or structure.
• BylawitisrequiredinmanystatestohaveaCarbon
Monoxide (CO) detector in operating condition in
homes and other structures occupied by people.
Carbon monoxide detector(s) (A) MUST be
installed and maintained indoors according to the
manufacturer’s instructions / recommendations.
A CO monitor is an electric device that detects
hazardous levels of CO. When there is a buildup of
CO, the monitor will alert the occupants by flashing
visual indicator light and alarm. Smoke alarms cannot
detect CO gas.
• Nearbystructuresmaybeexposedtotheengine
exhaust from your standby generator and must be
considered when installing your standby generator.
• Ensureexhaustgasiskeptawayfrom:
B overhead doors
C doors
D windows (not shown)
E other openings that can allow exhaust gas to enter
inside or be drawn into a potenially occupied building
or structure.
A
A
B
C
D
E
B BC
NOT
FOR REPRODUCTION
11
• Directthestandbygeneratorexhaustawayfromor
parallel to the building or structure. DO NOT direct the
generator exhaust towards a potentially occupied
building, structure, windows, doors, ventilation
intakes, soffit vents, crawl spaces, open garage
doors or other openings where exhaust gas could
accumulate and enter inside or be drawn into a
potentially occupied building or structure.
• DONOTplacestandbygeneratorinanyareawhere
leaves or debris normally accumulates. Position
standby generator in an area where winds will carry
the exhaust gas away from any potentially occupied
building or structure.
NOT
FOR REPRODUCTION
12
Placement of Standby Generator to REDUCE THE RISK OF FIRE
The National Fire Protection Association (NFPA) standard
NFPA 37 establishes criteria for minimizing the hazard
of fire during the installation and operation of stationary
combustion engines. NFPA 37 limits the spacing of an
enclosed generator from openings in walls, structures and
combustible materials outside the enclosure.
The placement requirements provided are based on
compliance to NFPA 37 2010 section 4.1.4.
WARNING Exhaust heat/gases could ignite combustibles or
structures resulting in death, serious injury and/or
property damage.
• Exhaust outlet side of weatherproof enclosure must have at least
5 ft (1.5 m) minimum clearance from any structure, shrubs, trees
or any kind of vegetation.
• Standby generator weatherproof enclosure must be at least
5 ft (1.5 m) from windows, doors, any wall opening, shrubs or
vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a minimum
of 5 feet (1.5 m) overhead clearance from any structure, overhang
or trees.
• DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
• USE ONLY flexible steel fuel line provided. Connect provided fuel
line to generator, DO NOT use with or substitute any other flexible
fuel line.
• Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/ recommendations.
Carbon monoxide alarms cannot detect smoke.
• DO NOT place weatherproof enclosure in manner other than
shown in illustrations.
Examples of standby generator locations to reduce the
risk of fire:
Legend for Generator Locations to reduce the risk of fire.
A
Standby weatherproof enclosure must be at least 5 ft
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
B
Exhaust outlet side of weatherproof enclosure must
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
C
Standby weatherproof enclosure must have a
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
Vertical Clearances
A
A
A
A
C
NOT
FOR REPRODUCTION
13
Legend for Generator Locations to reduce the risk of fire.
A
Standby weatherproof enclosure must be at least 5 ft
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
B
Exhaust outlet side of weatherproof enclosure must
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
Typical Installations with Structure Without a Fire Rating
C
Standby weatherproof enclosure must have a
minimum of 5 feet (1.5 m) overhead clearance from
any structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
A
AA
A
A
5 ft (1.5 m) min.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
Standby
Standby
Standby
5 ft (1.5 m) min.
5 ft (1.5 m) min. 5 ft (1.5 m) min.
Exhaust
Exhaust
Exhaust
A
A
5 ft (1.5 m) min.
5 ft (1.5 m) min.
Standby
5 ft (1.5 m) min.
Exhaust
B
B
B
B
NOT
FOR REPRODUCTION
14
Typical Installation with Single Structure Having a Fire Resistance Rating of at Least 1 Hour
Legend for Generator Locations to reduce the risk of
fire:
- Standby weatherproof enclosure must be at
least 5 ft. (1.5 m) from windows, doors, any wall
opening, shrubs, or vegetation over 12 inches
(30.5 cm) in height.
- Exhaust oulet side of weatherproof enclosure
must have at least 5 ft. (1.5 m) minimum
clearance from any structure, overhang or trees.
- Standby weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from
any structure, overhang, or trees.
NOTICE DO NOT place weatherproof enclosure under
a deck or other type of coverend structure that may
confine airflow.
5 ft (1.5 m) min.
Standby
5 ft (1.5 m) min.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
Standby
Standby
A
A
A
A
A
B
3 ft (0.9 m) min.
2 ft (0.6 m) min.
2 ft (0.6 m) min.
Exhaust
Exhaust
B
Exhaust
B
A
B
C
NOT
FOR REPRODUCTION
15
Typical Installation with Dual Structure Having a Fire Resistance Rating of at Least 1 Hour
Legend for Generator Locations to reduce the risk of
fire:
- Standby weatherproof enclosure must be at
least 5 ft. (1.5 m) from windows, doors, any wall
opening, shrubs, or vegetation over 12 inches
(30.5 cm) in height.
- Exhaust oulet side of weatherproof enclosure
must have at least 5 ft. (1.5 m) minimum clearance
from any structure, overhang or trees.
- Standby weatherproof enclosure must have a
minimum of 5 ft. (1.5 m) overhead clearance from
any structure, overhang, or trees.
NOTICE DO NOT place weatherproof enclosure under
a deck or other type of coverend structure that may
confine airflow.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
5 ft (1.5 m) min.
Standby
Standby
Standby
A
A
A
A
A
A
3 ft (0.9 m) min.
2 ft (0.6 m) min.
2 ft (0.6 m) min.
2 ft (0.6 m) min.
2 ft (0.6 m) min.
2 ft (0.6 m) min.
B
Exhaust
Exhaust
B
B
Exhaust
A
B
C
NOT
FOR REPRODUCTION
16
Other General Location Guidelines
• Placethestandbygeneratorinapreparedlocation
that is flat and has provisions for water drainage.
• Installthestandbygeneratorinalocationwhere
sump pump discharge, rain gutter down spouts, roof
run-off, landscape irrigation, or water sprinklers will
not flood the unit or spray the enclosure and enter
any air inlet or outlet openings.
• Installthestandbygeneratorwhereitwillnotaffector
obstruct any services (including covered, concealed
and underground), such as telephone, electric, fuel
(natural gas / LPG vapor), irrigation, air conditioning,
cable, septic, sewer, well and so forth.
• Installthestandbygeneratorwhereleaves,grass,
snow, etc will not obstruct air inlet and outlet
openings. If prevailing winds will cause blowing or
drifting, you may need to construct a windbreak to
protect the unit.
NOT
FOR REPRODUCTION
17
Concrete Slab
At the appropriate location, construct a concrete slab:
• 28daycompressionstrengthof3000psi(200MPa)
• Minimum5”(13cm)thick
• Minimum6”(15cm)widerthanenclosureonallsides
(shown as D in figure)
• StrengthenslabwithNo.6reinforcingbars(on
12”(30.5cm)centers)or8ga.steelwirefabric(6”
(15cm) centers).
Avoid placing reinforcement in entrance stub-up area (shown
as (B ).
Attach unit to slab at four corner locations (A) with minimum
5/16”diameter(8mm)masonryanchorboltslongenoughto
secure the unit.
The fuel inlet location (C) ,the concrete slab, and the
exhaust outlet (E) are shown for reference.
34-1/4”
87cm
14-3/4”
37.5cm
92”
233.7cm
51”
129.5cm
6”
15.2cm
5”
12.7cm
7-1/2”
19cm
C
D
A
B
Electrical and Fuel Inlet Locations
A through-slab power cable stub-up is preferred (see
figure above). If stub-up’s are not used, (F) indicates the
recommended location for punching holes for attaching
power conduit. The 1 inch N.P.T. fuel inlet connector (C) is
shown for reference.
C
A Holes located in base to anchor to pad
B Stub up Area
C Fuel Inlet
D Concrete slab
D Exhaust Outlet
B
C
D
A
D
D
C
B
A
F
C
F
E
E
E
NOT
FOR REPRODUCTION
18
Remove circuit breaker box bottom plate prior to positioning
generator.Two60”lengthsof2”Schedule40pipe(A ,
supplied by the installer, are required to lift the generator
onto cement pad. Insert pipes through the lifting holes (B)
located near the unit’s base.
Use a spreader bar to ensure that the chains, straps or
cables DO NOT touch the generator’s roof. Retouch any
chipped paint with supplied touch-up paint.
Lifting the Generator
The generator weighs more than 1,700 pounds (771 kg).
Proper tools, equipment and qualified personnel should be
used in all phases of handling and moving the generator.
A B
WARNING Hazardous Voltage - Contact with power lines could
cause electric shock or burn, resulting in death or
serious injury.
Lifting Hazard / Heavy Object - Could result in
serious injury.
• If lifting or hoisting equipment is used, DO NOT contact any
power lines.
• DO NOT lift or move generator without assistance.
• Use lifting pipes as described in Lifting the Generator.
• DO NOT lift unit by roof as damage to generator will occur.
A
B
NOT
FOR REPRODUCTION
19
The generator is equipped with an enclosure that has
several access doors, as shown. The doors are named for a
significant component located behind them, as follows:
A - Fuel Inlet port (shown for reference)
B - Control Panel door (may be one door)
C - Exhaust opening (shown for reference)
D - Coolant/Oil Fill door
E - Battery door
F - Muffler door
The Coolant Fill, Battery and Control Panel doors must be
installed whenever the unit is running to assure proper
cooling, reduce noise and for added safety. The enclosure
also includes muffler and radiator access panels, used for
cleaning those components. Those panels should remain
closed at all other times.
Access Ports
Each generator is shipped with a set of identical keys. These
keys fit the locks that secure the access ports.
To open access door:
1. Insert key into lock of access door handle and turn
key one quarter turn counterclockwise.
2. Grasp door’s handle and turn one quarter turn
counterclockwise to open. Remove key.
3. Coolant Fill door is unlocked in the same manner. It
can be used for adding coolant or oil.
To close access door:
1. Close door and turn door’s handle one quarter
turn clockwise.
2. Insert key into lock of door handle and turn key one
quarter turn clockwise. Remove key.
Additional force may be required to fully close and lock
the doors because they create a pressurized seal for the
generator enclosure.
WARNING Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
C
E
D
A
B
F
A
B
C
D
E
F
NOT
FOR REPRODUCTION
20
• Aminimumofoneaccessible,approvedmanual
shutoff valve (F) shall be installed in the fuel supply
line within 6 ft (1.8 m) of the generator.
• Amanualfuelshut-offvalvelocatedintheinteriorof
the building.
• Wherelocalconditionsincludeearthquake,
tornado, unstable ground, or flood hazards, special
consideration shall be given to increase strength and
flexibility of piping supports and connections.
• Pipingmustbeofthecorrectsizetomaintainthe
required supply pressures and volume flow under
varying generator load conditions with all gas
appliances connected to the fuel system turned on
and operating.
• Useapipesealantorjointcompoundapprovedfor
use with NG/LPG on all threaded fittings to reduce the
possibility of leakage.
• Installedpipingmustbeproperlypurgedand
leak tested, in accordance with applicable codes
and standards.
The information below is provided to assist gaseous fuel
system technicians in planning installations. In no way
should this information be interpreted to conflict with
applicable fuel gas codes. Consult with your local fuel
supplier or Fire Marshall if questions or problems arise.
TO THE INSTALLER: Consult with the generator owner(s) and
convey any technical considerations that might affect their
installation plans before applying these general guidelines.
The following general rules apply to gaseous fuel
system piping:
• Thepipingshouldbeofamaterialthatconforms
to federal and local codes, rigidly mounted and
protected against vibration.
• Pipingshouldbeprotectedfromphysicaldamage
where it passes through flower beds, shrub beds, and
other cultivated areas where damage could occur.
• Installtheflexible,gaseoushose(B)(supplied)
between the generator Fuel Inlet port and rigid
piping to prevent thermal expansion or contraction
from causing excessive stress on the piping material.
• Aunion(C)orflangedconnectionshallbeprovided
downstream from this valve to permit removal
of controls.
• Amanometerportshouldbeprovided(D).Adigital
manometer, P/N 19495, is available at your Briggs &
Stratton service center. When the initial test runs are
complete, the manometer is removed and the port
is plugged. The manometer port permits temporary
installation of a manometer to ensure that the
engine receives the correct fuel pressure to operate
efficiently throughout its operating range.
• Wheretheformationofhydratesoriceisknownto
occur, piping should be protected against freezing.
The termination of hard piping should include a
sediment trap (E) where condensate is not likely
to freeze.
The Gaseous Fuel System
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death, serious injury and/or
property damage.
• LP gas is heavier than air and will settle in low areas.
• Natural gas is lighter than air and will collect in high areas.
• The slightest spark could ignite these fuels and cause an explosion.
• DO NOT light a cigarette or smoke.
NOTICE The supplied flexible gaseous pipe is not to be installed
underground or in contact with the ground.
• The entire flexible gaseous pipe must be visible for periodic
inspection and must not be concealed within nor contact nor run
through any wall, floor, or partition.
A
B
C
D
E
F
A Generator Fuel Inlet
B Flexible Fuel Hose
C Union Fitting
D Manometer Test Port
E Sediment Trap
F Manual Shut-off Valve
A
B
C
D
E
F
B
C
D
E
F
A
NOT
FOR REPRODUCTION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108

Simplicity 076052-00 Guide d'installation

Catégorie
Groupes électrogènes
Taper
Guide d'installation
Ce manuel convient également à