Raychem VIA-DU-20 Guide d'installation

Taper
Guide d'installation
CONTROL UNIT
REGELGERÄT
UNITÉ DE CONTRÔLE
UNITÁ DI CONTROLLO
VIA-DU-20
2 | nVent.com
CONTENTS:
1. Application ..............................................................................................................................................5
2. Function ...................................................................................................................................................5
3. Display and controls ..............................................................................................................................5
4. Operation .................................................................................................................................................6
5. Advice, fault messages and servicing ...............................................................................................9
6. Consignes de sécurité ........................................................................................................................12
7. Installation ............................................................................................................................................ 12
8. Technical data ..................................................................................................................................... 15
9. Circuit diagram .................................................................................................................................... 17
INHALT:
1. Anwendung ..........................................................................................................................................18
2. Funktion ................................................................................................................................................18
3. Anzeige und Bedienelemente ...........................................................................................................18
4. Bedienung .............................................................................................................................................19
5. Hinweise, Fehlermeldungen, Wartung ............................................................................................ 22
6. Sicherheitshinweise ...........................................................................................................................25
7. Montage ................................................................................................................................................25
8. Technische Daten ............................................................................................................................... 28
9. Anschlussbilder ................................................................................................................................... 30
SOMMAIRE:
1. Application ...........................................................................................................................................31
2. Fonctionnement ................................................................................................................................. 31
3. Affichage et touches de commande ..............................................................................................31
4. Commande ...........................................................................................................................................32
5. Consignes, codes d’erreur, entretien ...............................................................................................35
6. Consignes de sécurité .......................................................................................................................38
7. Montage ...............................................................................................................................................38
8. Caractéristiques techniques ............................................................................................................. 41
9. Schéma électrique .............................................................................................................................. 43
INDICE:
1. Impiego .................................................................................................................................................44
2. Funzioni ................................................................................................................................................44
3. Display e controlli ................................................................................................................................ 44
4. Funzionamento ...................................................................................................................................45
5. Consigli, messaggi errore e manutenzione ...................................................................................48
6. Istruzioni di sicurezza ....................................................................................................................... 51
7. Montaggio ............................................................................................................................................51
8. Dati tecnici ........................................................................................................................................... 54
9. Schemi elettrici .................................................................................................................................... 56
nVent.com | 3
1 2 3
4 5 6
(Dimensions in mm, Maße in mm, Dimensions en mm, Dimensioni in mm)
45
53
58
160
90
7,0C
9,0C
0T50
45
53
58
160
90
7,0C
9,0C
0T50
A
B
4 | nVent.com
(Dimensions in mm, Maße in mm, Dimensions en mm, Dimensioni in mm)
52
40
38
50
35
70
15 m ±150 mm
35
5,7
VIA-DU-S20
VIA-DU-A10
C
D
nVent.com | 5
1. APPLICATION
The VIA-DU-20 is a CE certified, electronic control device designed to regulate nVent
RAYCHEM ramp heating systems in garage driveways, staircases, inclines etc. The buried
heating cable is controlled by sensing both ground temperature and moisture. The heater
operates only when the temperature falls below the set value and there is moisture. Use of
this controller results in significant energy savings if compared to other devices that regulate
according to temperature only.
2. FUNCTION
The ground temperature and moisture are measured with the help of one sensor.
The sensor is heated so that it can also measure dry snow.
The control device evaluates the data from the sensor and switches the heating on, if the
ground temperature falls below a value set by menu and the ground moisture exceeds a value
set by menu.
In addition the device is capable of identifying a risk of freezing rain. This function serves to
switch the heating on when freezing rain is predicted.
The controller also has what is called an overruling entry. This can be configured using the
menu and serves to prevent over-loading or to allow the device to be controlled remotely via
the BMS.
3. DISPLAY AND CONTROLS
The device has a display which is lit when the device is being operated (see A). Under
normal operating conditions the device alternately shows the moisture, the ground and air
temperature and the status of the heating output (on/off). Only the values, which are relevant
for controlling, are shown. Air temperature e.g. is only shown, if “sleet precaution” is set to
“local detection”.
Testing the device / switch on the heating output
Selecting a language
Increasing the value selected, changing settings (forwards)
Reducing the value selected, changing settings (backwards)
Enter menu, exit menu
Confirm the value selected, select the next value and responding to fault
messages.
6 | nVent.com
4. OPERATION
4.1. Selecting a language
You can select a language by pressing the button once or more. The languages available
are German, English, French, Italian, Polish, Finnish, Hungarian. The language can be changed
regardless of the operating status.
After 2 seconds the device automatically returns to where it was when the language selection
procedure was called up (Normal display, test or parameter menu).
Example of display when selecting a language:
4.2. Testing mode
Pressing the once switches the heating timer on for 30 min. The display indicates the time
remaining, the software version number and the status of the heating output. The test mode
can be selected at any stage. It should however be remembered that any heating
periods underway will be interrupted. So for example, selecting the test mode will interrupt the
post-heating period.
The test finishes once the test time has elapsed, but can also be terminated by pressing the
button while the test is still underway. When the test mode has been terminated the device
will return to the standard display.
Display in test mode (example):
4.3. Operation of the parameter menu
The parameter menu can be called up by pressing the button. The parameter displayed
may be modified using the
and buttons.
If the buttons are pressed down for an extended period the value changes automatically
(autorepeat function). Pressing
and down at the same time will reset the parameter to
the default setting.
Now you can switch to the next parameter with the button
or you can leave the parameter
menu by pressing the
button.
If you have changed a parameter and want to switch to the next or leave the menu, there
appears “SAVE CHANGES” in the display. You can select “YES” or “NO” using the
and
buttons. Having confirmed this with the
button, device switches to the next parameter or
leaves the parameter menu with or without saving changes.
Confirming the final parameter, the device goes back to the standard display
nVent.com | 7
The following menu points can be set or called up:
Range of settings: +1.0 °C ... +6.0 °C
Interval: 1.0 K
Default setting: 3.0°C
The temperature threshold is used to set the value below which the ground temperature
must fall for the heating to come on, providing there is sufficient moisture. The temperature
threshold also is the set point for the sensor heating, i.e. there is the possibility to control the
sensor heating by this value.
Attention: If the temperature threshold is set to 1.0°C or 2.0°C, the sensor may freeze in. In
this case reliable detection of moisture can not be guaranteed.
The value of moisture is no longer indicated in the display.
Settings: OFF, 1 ... 10
Interval: 1
Default setting: 3
The moisture threshold determines the level of moisture which must be exceeded for the
heating to come on, providing the temperature is low enough. 1 is the most sensitive setting,
i.e. very little moisture is enough to reach this value.
If the moisture threshold is set to ‘OFF’, the control device will always switch the heating on,
as long as the temperature falls below the threshold value. No moisture is required. The value
of moisture is no longer indicated in the display.
Range of settings: 30 ... 120 min.
Interval: 10 min.
Default setting: 30 min.
The post-heating period is the time for which the device continues to heat after the threshold
conditions which set the heating on are no longer present.
Range of settings: OFF, –15°C, ...–1.0°C
Interval: 1.0 K
Default setting: OFF
If the temperature in the ground falls below the base value, the control device will keep on
heating (regardless of the moisture). This functions speeds up the time required to clear
the surface from snow and ice. If the ground temperature rises above the base temperature
again, the heating timer will remain switched on for the post-heating period.
Range of settings: LOCAL DETECTION,
WEATHER FORECAST, OFF
Default setting: LOCAL DETECTION
This function addresses the issue of freezing rain, the purpose is to preheat the surface to
prevent the associated problems.
* For the purpose of the use of VIA-DU-20 in the UK, ‘sleet’ is used to describe the condition
and effect of freezing rain.
8 | nVent.com
This can be done in two different ways:
1. Local detection freezing rain warning
If the device is set to LOCAL DETECTION, i.e. local detection of risk of freezing rain, the device
will heat the surface as soon as it notices a sharp rise in temperature after a lengthy period of
cold weather.
The rise in air temperature is performed by an air temperature sensor which is delivered
together with the device.
The device can recognise a lengthy period of cold weather by means of a ground temperature
sensor, if the ground temperature has been below a set value for 18 hours. See also the
sections on the rise in temperature and the low ground temperature for an
18 hour period in the paragraphs relating to the following parameters.
2. Freezing rain warning via the weather service
With this function, the device waits for a logic signal sent from an additional device to the
terminals of the air temperature sensor. The additional device, which is not part of the
standard package, evaluates information from the weather service and converts these into
the relevant logic status.
The control device expects the following logic status:
Logic status Input in control device Reaction of the control device
0 open Heating OFF (no risk of freezing rain)
1 short circuit Heating ON (risk of freezing rain)
Instructions for early recognition of freezing rain
If it has recognised the possibility of a fall of freezing rain, the device switches on for 5
hours. If the warning has come via the weather service, the five-hour period begins from
the moment the logic status signal changed from 0 to 1. The heating is switched off
as soon as the ground temperature reaches the threshold value or the five hours have
elapsed. If however, after five hours, the ground temperature and moist conditions are
present for heating to continue, the heating is not turned off, i.e. following the five-hour
period the device continues to operate under normal operating conditions.
If the device is set for the local detection freezing rain warning, you should ensure that the
base temperature is lower than the 18-hour ground temperature value, since otherwise the
temperature will never fall below the 18-hour value and the freezing rain warning will not
function.
The reliability of the early recognition function heavily depends on the correct setting of the
parameters. It is possible that ice may build up on the surface or the device may come on
unnecessarily.
Range of settings: 0.5K/h ... 4.0 K/h
Interval: 0.5 K/h
Default setting: 2.0 K/h
This parameter* is used for setting the minimum rise in the air temperature in order to
recognise the potential risk of freezing rain after a lengthy period of cold weather.
Range of settings: –15°C ... –1.0°C
Interval: 1.0 K
Default setting: – 1.0°C
* This parameter temperature is indicated only when “local detection” is selected.
nVent.com | 9
This parameter* is used to set the value below which the air temperature must fall for a
period of at least 18 hours. If this condition is fulfilled and the temperature rises sharply, there
is a risk of freezing rain. The heating will be switched on to prevent the risk of freezing rain.
Range of settings: OFF, ON, BMS
Default setting: OFF
The OVERRULING parameter is used to configure the relevant logic input. If the parameter is
set to ‘OFF’ the input is not evaluated by the control device. The control device is not affected.
In the ‘ON’ setting the control device cannot switch the heating on for 10 min. if the input is or
was short-circuited. This prevents peakloads in buildings. If the input is still short-
circuited or has short-circuited again after 10 minutes have elapsed, the device cannot turn
on the heating for another 10 minutes.
If the device is set to ‘BMS’ the heating output is remote controlled. If the input is short-
circuited, the control device switches the heating off. If the input is open, the device will
switch on the heating in any event.
The sensor values of the ice indicator are not displayed and not evaluated.
Range of settings: OFF, ON
Default setting: OFF
This parameter allows you to select what status the heating timer should assume in the
event of a fault. The ‘OFF’ setting is recommended for all energy sensitive applications,
whereas the ‘ON’ setting should be selected for safety applications.
This menu option indicates the heating time in hours (H) and minutes (M).
Using the and buttons the counter can be reset
5. ADVICE, FAULT MESSAGES AND SERVICING
5.1. What to do during set up
When the device is first put into operation it carries out an auto-test. During this test the
display indicates, “POWER-UP TESTS”. If the device finds a fault during this test, it displays
a number on the second line of the display. Otherwise the device goes into the standard
operating mode.
* This parameter is indicated only when “local detection” is selected.
10 | nVent.com
If a fault is identified, you should carry out another test by switching the device off and on
again. If the fault message is displayed again, the device is faulty and must be replaced.
If the fault message is displayed indicating the number ‘6’, perhaps one of the buttons is
stuck. In this case, the keyboard must be checked. Then switch the device off and on again
for another test.
5.2. What to do in the event of a loss of power
If there is a loss of power, all parameters will remain saved in the memory. Both relays
(heating and alarm) will stop working.
After the power failure, the device will continue to operate in its state when the power loss
occurred. The timers will remain constant during power loss (no reserve power supply).
5.3. Sensor monitoring
The ground temperature and moisture sensor and the air temperature sensor are monitored
for faults (breakage and short circuits) by the control device. If a fault occurs, the alarm relay
switches and the display indicates, “SENSOR FAULT” and a corresponding fault message is
emitted. The following fault messages are used:
Display Type of fault
SHORT GROUND TMP Ground sensor short circuit
OPEN GROUND TMP Ground sensor interrupted
MOISTURE General fault in the moisture measurement device. Possible
faults: there are conductive objects touching one or both
sensors or the control device input is faulty.
SHORT AIR TMP Short circuit in the air temperature sensor*
OPEN AIR TMP Interruption of air temperature sensor*
SHORT SENSHEATER Short circuit in the sensor heating (is recognised if the
temperature of the ground sensor remains below +2°C for
longer than 2 hours)
OPEN SENSHEATER Sensor heating interrupted
A failure will interrupt heating times, such as the post-heating period. The heating output will
be turned on or off as set under the parameter “IN THE CASE OF FAILURE HEATING...
* The monitoring of air temperature is only active when “local detection” is selected.
nVent.com | 11
5.4. Trouble shooting
Symptoms Probable Correction
Heating is on, but there
is no moisture
Setting overruling
BY BMS is selected
If necessary change settings
Setting moisture threshold
OFF is selected
If necessary change settings
The device has detected
a temperature drop and
heating is on for post
heating period
This is normal operation
The device shows
moisture 0, while
sensor is moist
The sensors surface it
soiled (oily)
Clean the surface of the ground
sensor with a flannel and water.
The surface of the sensor must
not be scratched with sharp
objects.
The moisture on the sensor
is frozen
Set the temperature threshold to
a higher value. This gives a higher
set point for sensor heating, too.
Heating is OFF although
there is moisture on
sensor
Moisture threshold too high Set the moisture threshold to a
lower value
Temperature threshold too
low
Set the temperature threshold to
a higher value
The device is set in over-
ruling ON and the logic
input is short-circuited
If necessary change settings
Heating is regularly OFF,
but area is not yet free of
ice and snow
The post-heating period is
too short
Set a longer post heating period
The sensor is dry, but there
is ice and snow on the
heated area
Set the temperature threshold to
a lower value. This gives a lower
set point for sensor heating, too.
Attention: Please change settings step by step to ensure reliable function. Also with careful
settings it can’t be guaranteed, that the heated area is always free of snow and ice.
5.5. Servicing
Neither control device nor any of the sensors require any servicing.
The surface of the ground sensor needs to be cleaned regularly, to ensure that it gives correct
moisture measurements. A flannel and tap water may be used. The surface of the sensor
must not be scratched with sharp objects. It is recommended that you check that the device
is working before the onset of winter.
12 | nVent.com
6. SAFETY INSTRUCTIONS
Only for electricians!
Attention: mistakes made when connecting up the device can cause damage to the control
unit. nVent is not liable for any damage caused by faulty connections and/or incorrect
handling.
Before working on the device, switch off the power supply.
The device may only be connected up and serviced by authorised, trained personnel.
The device is only designed to be connected to fixed cables.
When installing the device, make sure that high-voltage cables, such as the mains supply
and extensions do not come into contact with low-voltage cables such as sensor cables.
Moreover, you must ensure adequate protection against all the extension leads
disconnecting in compliance with the requirements of EN 60730, part I. This can be
achieved for example by fixing the cables with cable clips.
Local standards for electrical connection must be observed.
If the device does not work, please first check all connections and the mains power supply.
7. INSTALLATION
7.1. Installation of the control device
This device is installed in a housing to be snapped onto DIN rails (DIN EN 50022-35). It is
designed to be mounted in switchboxes and distribution boxes.
The housing has the following measurements: see
B
7.2. Installation of the ground temperature and moisture sensor
VIA-DU-S20
The sensor is yellow and can be recognised by its 5-core connection lead.
It has the following dimensions: see
C
The ground temperature and moisture sensor is to be installed within the heated area at least
2.5 cm and maximum 15 cm away from the heating cables (see diagram).
The sensor must be able to directly detect weather conditions (rain, snow, melted
snow and ice). The sensor may not be covered up (e.g. when clearing snow).
Take care that VIA-DU-S20 is not installed in an area which is continuously flooded with water
(e.g. drain line), neither in an area which is continuously under ice due to external parameters
(e.g. freezing of condensation water in cooling rooms).
The piece of wood is placed into the ground surface as a dummy for the sensor.
A metal protective pipe is to be installed up to the wooden piece. The pipe is to be secured
on the wooden piece to prevent concrete, asphalt, etc. from getting in. Once the material has
been put on and if necessary cooled, the piece of wood is removed and the sensor fitted into
the hole. The sensor must be mounted absolutely horizontal. The remaining space around
the sensor is to be filled with, for example, silicon, mortar or asphalt. The temperature of the
filling material must not exceed 80°C. Furthermore, it has to be ensured that there is a good
connection without hollow space between the sensor and the filling material. The sensor
connection lead may be extended from 15 m (standard length) to a maximum of 50 m with a
diameter of 1.5 mm² .
nVent.com | 13
* Optional, only needed when "local detection" is selected.
Sensor VIA-DU-S20 (within the
heated area, min. 2.5 cm and max.
15 cm from the heating cables)
Controller
(VIA-DU-20)
Air temperature
Sensor*
(VIA-DU-A10)
Picture 1
1.
5
To heating
cable
Controller
(VIA-DU-G20)
14 | nVent.com
7.3. Installation of air temperature sensor VIA-DU-A10
The sensor has the following dimensions: see
D
The air temperature sensor should be installed approx. 2-3 m above the ground in a protected
place (with a shelter). It must not be exposed to direct sunlight. It must also be protected
from external influences, i.e. it must not be installed above doors or windows or near lamps
or headlights.
The sensor connection lead may be up to 100 m long, given a diameter of 1.5mm².
metal protective tube Ø 16 mm
sub -
struc ture
sealing
filling material
e.g. concrete
sensor
max. 5
horizontal installation
sensor installation on slope
Picture 2
Picture 3
nVent.com | 15
8. TECHNICAL DATA
Operating voltage AC 230 V, ±10 %, 50/60 Hz
Power consumption 14 VA max.
Main relay (heating) I
max
4(1)A, 250 Vac
SPST, voltfree
Alarm relay I
max
2(1)A, 250 Vac
SPDT, voltfree
Switching accuracy ±1 K
Display Point matrix, 2 x 16 places
Assembly DIN rail
Housing material Noryl
Terminals 0.5 mm² to 2.5 mm²
Protection IP20/class II (Requirements of Class II are
only fulfilled after proper mounting)
Action type Type 1.C
Control pollution degree 2
Software class A
Rated impulse voltage 4 kV
Weight 750 g
Temperature resistance 0°C to +50°C
Main parameters
Temperature at which device comes on +1°C to +6°C
Moisture at which device switches on Off, 1 (moist) to 10 (very wet)
Post-heating period 30 to 120 min. (heating on)
Base temperature Off, –15°C to –1°C
Freezing rain warning Local detection, weather service, off
Overruling Off, on, by BMS
If there is a power failure, all parameters remain saved in the memory
Layout (see
A
)
Display, lit (parameter and fault display)
1. Test button
2. Increasing the value selected, changing settings (forwards)
3. Menu button
4. Selecting a language (D, GB, F, I, FIN, PL, H)
5. Reducing the value selected, changing settings (backwards)
6. Confirm button
16 | nVent.com
Ground temperature and moisture sensor VIA-DU-S20
Voltage DC 8 V (via control device)
Type of sensor PTC (see table below)
Protection IP67
Diameter of lead 5 x 0.5 mm², Ø 5.7 mm
Length of lead 15 m, can be extended to 50 m
(5 x 1.5 mm²)
Temperature resistance –30°C to +80°C
Sensor heating approx. 9.3 Ohm (green - brown wire)
Air temperature sensor* VIA-DU-A10
Type of sensor PTC (see table below)
Protection IP54
Terminals 1.5 to 2.5 mm²
Diameter of lead 2 x 1.5 mm², max. 100 m
(not part of standard package)
Temperature resistance –30°C to +80°C
Fitting Wallmounted
* Assembly not necessary if ‘Freezing rain warning’ is not set to ‘local detection
VIA-DU-A10 and VIA-DU-S20 (yellow- brown wire)
Temperature in °C Resistance in Ohm
-20 1335
-10
1459
0 1592
+10 1732
+20 1879
nVent.com | 17
L
N
PE
Alarm 2(1)A
Alarm 2(1)A
Connection of
an alarm lamp
(diagram) or horn
(rest position)
30 mA
**
*
L1
L2
L3
N
PE
VIA-DU-20
1
2
3
4
5
6
7
8
9
N
AC
DC
***
****
L
L
L’
Relais
4(1)A
Alarm
2(1)A
heating of
open space
Contactor
Air
temperature
sensor
Floor
temp. and
moisture
sensor
braun
yellow
white
grey
green
9. WIRING DIAGRAM
9.1. VIA-DU-20 with contactor
When using MI heating cables a 300 mA
RCD should be used.
* Local values, standards and rules
require two- or four-pole switching
using a electrical protection
** Depending on the application, both
one- and three-pole circuit breakers of
contactors are possible.
*** Optional and can be activated in a BMS.
**** Air temperature sensor will be needed
only if in menu freezing rain precaution
the parameter “local detection” has
been selected. When weather forecast
has been selected you have to connect
the voltfree contacts of additional
device to these terminals.
9.2. Alarm output
alarm lamp
current loop
Connection of
a current loop
(rest position)
Notice:
The alarm relay is always active
(switched on) as long as there
is no fault. The alarm relay is
potentialfree but not suitable for
the switching of safety low voltage
(SELV) as there is no double
insulation in the device.
18 | nVent.com
1. ANWENDUNG
Dieses CE-gekennzeichnete, elektronische Regelgerät dient zur Regelung von
Freiflächenheizungen in Garagenauffahrten, Treppenanlagen, Steigungen und Beckenkronen
in Kläranlagen. Abhängig von der Temperatur im Boden und der Feuchte auf dem Boden wird
das Heizband eingeschaltet, um die Fläche schnee- und eisfrei zu halten.
Dies ergibt gegenüber Anlagen, welche nur temperaturabhängig geregelt werden, eine
erhebliche Energieeinsparung, weil nur dann geheizt wird, wenn die voreingestellte Temperatur
unterschritten wird und zusätzlich auch Feuchte vorhanden ist.
2. FUNKTION
Mit Hilfe eines Sensors wird die Bodentemperatur und die Bodenfeuchte erfasst. Der Sensor
ist beheizt, um auch trockenen Schnee erfassen zu können.
Das Regelgerät wertet die Daten des Sensors aus und schaltet die Freiflächenbeheizung ein,
wenn die Bodentemperatur einen per Menü einstellbaren Wert unterschreitet und die Feuchte
auf der Bodenoberfläche einen per Menü einstellbaren Wert überschreitet.
Zusätzlich ist das Gerät in der Lage, die Gefahr von Eisregen zu erkennen. Diese Funktion
dient zum vorzeitigen Einschalten der Heizung bei Eisregengefahr, um das Gefrieren des
Niederschlages auf der Fläche zu vermeiden.
Außerdem besitzt das Gerät einen sogenannten Vorrangeingang. Er kann per Menü
konfiguriert werden und dient zur Vermeidung von Lastspitzen bzw. zur Fernsteuerung des
Gerätes durch die Gebäudeleittechnik (GLT).
3. ANZEIGE UND BEDIENELEMENTE
Das Gerät besitzt ein Display, das während der Bedienung beleuchtet ist (Siehe A).
Im Normalbetrieb zeigt das Gerät abwechselnd die Feuchte, die Boden- und die
Lufttemperatur sowie den Zustand des Heizungsausgangs (Ein/Aus) an. Es werden nur Werte
angezeigt, die tatsächlich in die Sensorauswertung eingehen. So wird z.B. die Lufttemperatur
nur angezeigt, wenn die Eisregenwarnung auf „Autark” steht.
Die Bedienung erfolgt über sechs Tasten, die folgende Funktionen haben:
Testen des Gerätes / Freiflächenbeheizung einschalten
Auswahl der Sprache
Erhöhen des ausgewählten Wertes, ändern der Einstellungen (vorwärts)
Senken des ausgewählten Wertes, ändern der Einstellungen (rückwärts)
Menü aufrufen, Menü verlassen
Bestätigen des ausgewählten Wertes, Anwahl des nächsten Wertes und
Quittieren von Fehlermeldungen.
nVent.com | 19
4. BEDIENUNG
4.1. Auswahl der Sprache
Durch ein- oder mehrmaliges Betätigen der Taste kann die gewünschte Sprache
ausgewählt werden. Angeboten werden die Sprachen Deutsch, Englisch, Französisch und
Italienisch. Die Sprache lässt sich in jedem Betriebszustand verändern.
Das Gerät kehrt nach 2 Sekunden selbständig wieder in den Betriebszustand zurück, aus dem
die Auswahl der Sprache aufgerufen wurde (Normalanzeige, Test oder Parametermenü).
Anzeige bei der Sprachauswahl (Beispiel):
4.2. Testmodus
Der erste Tastendruck auf die Taste führt zum Einschalten des Heizungsrelais für 30 min.
Angezeigt wird die verbleibende Testzeit, die Software-Versionsnummer und der Zustand
des Heizungsausgangs. Der Testmodus lässt sich in jedem Betriebszustand aufrufen. Dabei
ist allerdings zu beachten, dass laufende Heizperioden abgebrochen werden. So führt der
Testbetrieb z.B. dazu, dass die Nachheizzeit abgebrochen wird.
Der Testbetrieb endet nach Ablauf der Testzeit, kann jedoch auch beendet werden, indem im
laufenden Testmodus die Taste
gedrückt wird. Nach Beendigung des Testmodus kehrt das
Gerät zur Normalanzeige zurück.
Anzeige im Testmodus (Beispiel):
4.3. Bedienung des Parametermenüs
Das Parametermenü kann durch Drücken der Taste aufgerufen werden. Der angezeigte
Parameter wird mit Hilfe der Tasten
und verändert. Bei längerem Drücken dieser Tasten
wechselt der Wert automatisch (Autorepeat-Funktion).
Durch gleichzeitiges Betätigen der Tasten
und kann der entsprechende Menüpunkt auf
die Werkeinstellung zurückgestellt werden. Mit der Taste
kann zum nächsten Parameter
gewechselt werden oder es kann durch Drücken der Taste
das Parametermenü verlassen
werden. Wurde ein Parameter verändert, erscheint beim Wechsel zum nächsten bzw. beim
Verlassen des Menüs im Display die Abfrage „AEND. SPEICHERN“ (=Änderung speichern). Mit
den Tasten
und kann „JA“ oder „NEIN“ ausgewählt werden. Nach dem Bestätigen mit
der Taste
wird zum nächsten Parameter gewechselt bzw. das Menü verlassen und der
Parameter gespeichert bzw. verworfen. Mit der Bestätigung des letzten Parameters kehrt das
Gerät wieder zur Normalanzeige zurück.
20 | nVent.com
Es können folgende Menüpunkte eingestellt bzw. abgefragt werden:
Einstellbereich: +1,0°C ... +6,0°C
Schrittweite: 1,0 K
Werkseinstellung: 3,0°C
Die Temperaturschwelle dient zum Einstellen der Bodentemperatur, die unterschritten werden
muss, damit die Heizung bei genügender Feuchte eingeschaltet wird. Die Temperaturschwelle
ist gleichzeitig der Sollwert für die Heizung im Sensor, d.h. über diesen Wert ist es möglich, die
Sensorheizung zu beeinflussen.
Achtung: Wenn die Temperaturschwelle auf 1,0 bzw. 2,0°C eingestellt wird kann im Extremfall
der Sensor zufrieren. Eine zuverlässige Feuchteerkennung ist dann nicht mehr
gewährleistet.
Einstellbereich: AUS, 1...10
Schrittweite: 1
Werkseinstellung: 3
Die Feuchteschwelle dient zum Einstellen des Feuchtegrades, der überschritten werden muss,
damit die Heizung bei niedriger Temperatur eingeschaltet wird. Dabei ist 1 der empfindlichste
Wert, d.h. es genügt sehr wenig Feuchte, um den Wert 1 zu erreichen.
Wenn die Feuchteschwelle auf den Wert „AUS” gestellt wird, schaltet das Regelgerät die
Freiflächenbeheizung immer ein, sobald die Temperaturschwelle unterschritten wird. Es
braucht keine Feuchte vorhanden sein. Der Wert der Feuchte wird dabei nicht mehr angezeigt.
Einstellbereich: 30...120 min
Schrittweite: 10 min
Werkseinstellung: 30 min
Die Nachheizzeit ist die Zeit, in der das Gerät nach dem Wegfall der Heizungs-Einschalt-
bedingungen noch weiterheizt.
Einstellbereich: AUS ,–15,0°C...–1,0°C
Schrittweite: 1,0 K
Werkseinstellung: AUS
Bei Unterschreitung der Sockeltemperatur im Boden heizt das Regelgerät immer (unabhängig
von der Feuchte). Diese Funktion dient dazu, die Fläche bei sicherheitsrelevanten
Anwendungen schneller schnee- und eisfrei zu bekommen. Steigt die Bodentemperatur
wieder über die Sockeltemperatur, bleibt das Heizungsrelais noch für die Nachheizzeit
eingeschaltet.
Einstellbereich: AUTARK,
WETTERDIENST, AUS
Werkseinstellung: AUTARK
Diese Funktion hat die Aufgabe bei drohendem Eisregen die Fläche soweit vorzuheizen, dass
bei einsetzendem Eisregen kein Niederschlag mehr auf der Fläche gefriert.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

Raychem VIA-DU-20 Guide d'installation

Taper
Guide d'installation