Operator’s Manual
Generator Systems
60000* Watt
Generator System
Series 60000
*This generator is rated in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards
Association) standard C22.2 No. 100-4 (motors and generators).
NOT
for
REPRODUCTION
2
Thank you for purchasing this quality-built GE generator. We’re pleased that you’ve placed your confidence in the GE
brand. When operated and maintained according to the instructions in this manual, your generator will provide many
years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with standby
generators and how to avoid them. Because we do not necessarily know all the applications this equipment could
be used for, it is important that you read and understand these instructions thoroughly before attempting to start or
operate this equipment. Save these instructions for future reference.
This generator requires professional installation before use. Refer to the separate installation manual for full
information. Your installer should follow the instructions completely.
Where to Find Us
You never have to look far to find support and service for your generator. For quick service when you need
it most fill out the information below and keep your original receipt with this manual. You may contact
Customer Service at 888-575-8226 between 8:00 AM and 5:00 PM CT., or click on SERVICE & SUPPORT at
www.standbygeneratorsystems.com, which provides a list of authorized dealers.
Generator and engine model and serial numbers should be recorded in the installation manual.
NOT
for
REPRODUCTION
3
Table of Contents
Safety Rules..........................................................4
Installation ..........................................................7
For the Owner........................................................7
For the Installing Dealer/Contractor....................................7
Owner Orientation....................................................8
Fuel Factors..........................................................8
Generator Location ...................................................9
Delivery Inspection ...................................................9
Controls ............................................................10
Operation...........................................................14
Automatic Operation ................................................15
Setting Exercise Timer ...............................................15
Maintenance ........................................................16
Shutdown alarm Detection System....................................16
Generator Maintenance..............................................18
Engine Oil...........................................................18
Synthetic Oils .......................................................18
Oil Recommendation.................................................19
Checking Engine Oil Level ............................................19
Engine V-Belts.......................................................20
Engine Coolant System...............................................21
Engine Air Cleaner ..................................................21
Generator Electrical System Maintenance .............................22
Battery .............................................................22
Fuel System Inspection and Maintenance ..............................23
Storage.............................................................24
Troubleshooting .....................................................26
Warranty ...........................................................28
Product Specifications ...............................................30
NOT
for
REPRODUCTION
4
Safety Rules
SAVE THESE INSTRUCTIONS - This manual contains
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a degree
or level of hazard seriousness. A safety symbol may be used
to represent the type of hazard. The signal word NOTICE is
used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
Important Safety Instructions
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings
in this manual, and the tags and decals affixed to the unit
are, therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that it
is safe for you and others. You must also make sure that the
procedure, work method or operating technique that you
choose does not render the generator system unsafe.
Fire
Toxic Fumes
Explosive Pressure
Rotating Fan Blade
Lift Hazard Read Manual
Exploding BatteryRotating Belt/Pulley
Chemical BurnAuto Start
Hot SurfaceRotating Parts
Electrical ShockExplosion
WARNING The engine exhaust from this product contains
chemicals known to the State of California to cause cancer, birth
defects, or other reproductive harm.
WARNING Certain components in this product and related
accessories contain chemicals known to the State of California
to cause cancer, birth defects, or other reproductive harm. Wash
hands after handling.
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
Keep exhaust gas away from any windows, doors, ventailation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
NOT
for
REPRODUCTION
5
WARNING Storage batteries give off explosive hydrogen gas
during recharging.
Slightest spark will ignite hydrogen and
cause explosion, resulting in death or
serious injury.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents could cause severe chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
DO NOT dispose of battery in a fire. Recycle battery.
DO NOT allow any open flame, spark, heat, or lit cigarette during
and for several minutes after charging a battery.
DO NOT open or mutilate the battery.
Wear protective goggles, rubber apron, rubber boots and
rubber gloves.
Remove watches, rings, or other metal objects.
Use tools having insulated handles.
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death or serious injury.
Install the fuel supply system according to NFPA 37 and other
applicable fuel-gas codes.
Before placing the generator into service, the fuel system lines
must be properly purged and leak tested.
After the generator is installed, you should inspect the fuel
system periodically.
NO leakage is permitted.
DO NOT operate engine if smell of fuel is present or other
explosive conditions exist.
DO NOT smoke around the generator. Wipe up any oil spills
immediately. Ensure that no combustible materials are left in the
generator compartment. Keep the area near the generator clean
and free of debris.
WARNING Generator produces hazardous voltage.
Failure to properly ground generator could result
in electrocution.
Failure to isolate generator from utility power could result
in death or serious injury to electric utility workers due to
backfeed of electrical energy.
DO NOT touch bare wires or bare receptacles.
DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
DO NOT handle generator or electrical cords while standing in
water, while barefoot, or while hands or feet are wet.
If you must work around a unit while it is operating, stand on an
insulated dry surface to reduce the risk of a shock hazard.
DO NOT allow unqualified persons or children to operate or
service generator.
In case of an accident caused by electrical shock, immediately
shut down the source of electrical power and contact the local
authorities. Avoid direct contact with the victim.
Despite the safe design of the generator, operating this
equipment imprudently, neglecting its maintenance or being
careless could cause possible injury or death.
Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
Before performing any maintenance on the generator, disconnect
the battery cable indicated by a NEGATIVE, NEG or (-) first. When
finished, reconnect that cable last.
After your system is installed, the generator may crank and start
without warning any time there is a power failure. To prevent
possible injury, always set the generator’s system switch to OFF,
open the service disconnect switch AND remove the 15 Amp fuse
BEFORE working on the equipment.
NOT
for
REPRODUCTION
6
WARNING Moving parts could crush and cut.
Starter and other rotating parts
could entangle hands, hair, clothing,
or accessories resulting in serious injury.
NEVER operate generator without protective housings, covers, or
guards in place.
DO NOT wear loose clothing, jewelry or anything that could be
caught in the starter or other rotating parts.
Tie up long hair and remove jewelry.
Before servicing, remove control board fuse from control panel
and disconnect Negative (NEG or -) battery cable.
WARNING Hot pressurized coolant could cause serious injury.
DO NOT open radiator cap when hot.
Before servicing, allow coolant to cool.
CAUTION Installing the 15A fuse could cause the engine
to start at any time without warning resulting in minor or
moderate injury.
Observe that the control board fuse has been removed from the
control panel for shipping.
DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.
CAUTION Excessively high operating speeds could result in
minor injury and/or equipment damage.
Excessively low speeds impose a heavy load on generator.
DO NOT tamper with governed speed. Generator supplies correct
rated frequency and voltage when running at governed speed.
DO NOT modify generator in any way.
NOTICE Exceeding generators wattage/amperage capacity could
damage generator and/or electrical devices connected to it.
Start generator and let engine stabilize before connecting
electrical loads.
NOTICE Improper treatment of generator could damage it and
shorten its life.
Use generator only for intended uses.
If you have questions about intended use, contact your
authorized dealer.
Operate generator only on level surfaces.
Adequate, unobstructed flow of cooling and ventilating air is
critical to correct generator operation.
The access panels/door must be installed whenever the unit
is running.
DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
DO NOT start engine with air cleaner or air cleaner cover removed.
DO NOT insert any objects through cooling slots.
DO NOT use the generator or any of its parts as a step. Stepping
on the unit could cause stress and break parts. This may result in
dangerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
If connected devices overheat, turn them off and disconnect them
from generator.
Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
-unit makes unusual noises.
WARNING Exhaust heat/gases could ignite combustibles or
structures resulting in death or serious injury.
Contact with muffler area could cause burns
resulting in serious injury.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
Exhaust outlet side of weatherproof enclosure must have at least
5 ft. (1.5m) minimum clearance from any structure, shrubs, trees
or any kind of vegetation.
Standby generator weatherproof enclosure must be at least
5 ft. (1.5m) from windows, doors, any wall opening, shrubs or
vegetation over 12 inches (30.5 cm) in height.
Standby generator weatherproof enclosure must have a minimum
of 5 ft. (1.5 m) overhead clearance from any structure, overhang,
or trees.
DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
Use only flexible fuel line provided. Connect provided fuel line to
generator. DO NOT use with or substitute any other flexible
fuel line.
Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/recommendations.
Carbon monoxide alarms cannot detect smoke.
Keep at least minimum distances shown in General Location
Guidelines to insure for proper generator cooling and
maintenance clearances.
Replacement parts must be the same and installed in the same
position as the original parts.
NOT
for
REPRODUCTION
7
To help you make informed choices and communicate
effectively with your installation contractor(s),
Read and understand Owner Orientation in this manual
before contracting or starting your generator installation.
To arrange for proper installation, contact the store at
which you purchased your generator, your dealer, a licensed
electrician or your utility power provider.
The generator warranty is VOID unless the system is
installed by licensed electrical and plumbing professionals.
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
The Emission Control System for this generator is warranted
for standards set by the U.S. Environmental Protection
Agency and by the California Air Resources Board (CARB).
For the Owner
If you need more information in this matter, please call
888 575‑8226 between 8:00 AM and 5:00 PM CT..
For most applications, the Installation manual contains
all the information required to properly install and start
the generator. This Operator’s Manual describes routine
operation and owner maintenance procedures.
For the Installing Dealer/Contractor
Installation
We sincerely appreciate your patronage. For this reason, we
have made every effort to provide for a safe, streamlined
and cost-effective installation. Because each installation is
unique, it is impossible to know of and advise the trade of all
conceivable procedures and methods by which installation
might be achieved. Neither could we know of possible
hazards and/or the results of each method or procedure. For
these reasons,
Only current licensed electrical and plumbing
professionals should attempt generator system
installations. Installations must strictly comply with all
applicable codes, industry standards and regulations.
Your generator is supplied with this “Operator’s Manual”
and a separate “Installation Manual”. These are important
documents and should be retained by the owner after the
installation has been completed.
NOT
for
REPRODUCTION
8
Power Decrease at High Altitude or
High Temperature
Air density is less at high altitudes, resulting in less available
engine power. Specifically, engine power will decrease 3.5%
for each 1,000 feet (300 meters) above sea level and 1%
for each 10° F (5.6°C) above 77°F (25°C). Make sure you and
your installer consider these factors when determining total
generator load.
An important consideration affecting the entire installation
is the type of fuel used by your generator. The system was
factory tested and adjusted using either natural gas or
liquid propane (LP vapor). For proper engine function, factors
that are inherent to each of these fuels, your location and
the duration of possible utility interruptions are important
considerations in the following fuel guidelines:
Use clean, dry fuel, free of moisture or any
particulate material. Using fuels outside the
following recommended values may cause
performance problems.
In engines set up to run on propane (LP), use
commercial grade HD5 propane with a minimum fuel
energy of 2500 BTUs/ft
3
with maximum propylene
content of 5% and butane and heavier gas content of
2.5% and minimum propane content of 90%.
Natural gas rating will depend on specific fuel but typical
derates are between 10 to 20% off the LP gas rating.
Fuel Factors
gaseous fuel supply increases, and the number of 90 degree
bends in the fuel supply increases, compensations in piping
and wiring materials must be made. This is necessary to
comply with local codes and overcome electrical voltage
drops and gaseous fuel pressure drops.
The factors mentioned above will have a direct effect on
the overall price of your generator installation.
In some areas you may need to acquire electrical permits
for installing the generator, building permits for installing
gas lines, and permits for noise allowances. Your installer
should check your local codes AND obtain the permits before
installing the system.
This section provides generator owners with the information
necessary to achieve the most satisfactory and cost effective
installation possible.
The illustrations are for typical circumstances and are meant
to familiarize you with the installation options available
with your generator. A thorough understanding of these
options will provide fundamental control over the cost of
your installation, as well as ensure your final satisfaction
and security.
Federal and local codes, appearance, noise levels, fuel types,
and distances are the factors that must be considered when
negotiating with an installation professional. Remember
that as the distance from the existing electrical service and
Owner Orientation
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death or serious injury.
The residential generator is equipped with an
automatic safety gas “fuel shut-off” valve.
DO NOT operate the equipment if the “fuel shut-off” valve is
missing or inoperative.
NOT
for
REPRODUCTION
9
Delivery Inspection
Carefully inspect the generator for any damage that may
have occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss or
damage. If loss or damage is noted after delivery, separate
the damaged materials and contact the carrier and your
installer for claim procedures. Missing or damaged parts are
not warranted.
The generator system is supplied with:
Fully-serviced coolant system
Fully-serviced oil/lubricating system
Flexible fuel hook-up
Installation and start-up manual
Operator’s manual
Spare access door keys
Spare 15 Amp ATO-type fuse
Two-pin control panel connector
Touch up paint
To be supplied by Installer:
Starting battery
Reinforced concrete mounting pad
Connecting wire and conduit
Fuel supply valves/plumbing
Various specialty tools/equipment
The actual physical location of your generator has a direct
affect on:
1. The amount of plumbing required to fuel
your generator.
2. The amount of wiring required to control and connect
your generator.
Specific location guidelines are discussed in the installation
manual. Acquaint yourself with that information and confer
with your installer. Be sure to ask how your site might
affect installation costs and compliance with local codes
and standards.
The generator must be installed outdoors. DO NOT install
generator where exhaust gas could accumulate and enter
inside or be drawn into a potentially occupied building.
Ensure exhaust gas is kept away from any windows, doors,
ventilation intakes or other openings that can allow exhaust
gas to collect in a confined area. Prevailing winds and air
currents should be taken into consideration when positioning
generator. See the installation manual for full details on safe
generator location.
Generator Location
WARNING Exhaust heat/gases could ignite combustibles or
structures resulting in death or serious injury.
DO NOT install the generator closer than 5 feet (1.5m) from any
combustibles or structures with combustible walls having a fire
resistance rating of less than 1 hour.
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
Operate this product ONLY outdoors.
Install a battery operated carbon monoxide alarm near
the bedrooms.
Keep exhaust gas from entering a confined area through
windows, doors, ventilation intakes, or other openings.
NOT
for
REPRODUCTION
10
Read this operator’s manual and Important Safety Instructions before operating your generator.
Compare the illustrations of this model with your generator to familiarize yourself with the locations of various controls
and adjustments. Save this manual for future reference.
60 kW Generator
Generator is pictured with access doors removed for clarity
and screen guard open for clarity.
A - Exhaust Port — High-performance muffler lowers engine
sound level to comply with most residential codes.
B - Coolant Fill Door — Provides access for servicing engine
with coolant.
C - Air Cleaner — Protects engine by filtering dust and debris
out of intake air.
D - Battery Door opening — Provides access to starting
battery and air cleaner.
E - Engine Label — Identifies engine model and type.
F - Oil Dip Stick — Used to check the engine oil level.
G - Oil Fill Cap — Remove to service the engine with
recommended oil.
H - Screen Guard — Prevents fingers from touching radiator
fan and houses the coolant recovery bottle. Must stay
closed while generator is in use.
J - Coolant Recovery Bottle — Located on inside of screen
guard. Provides visual indicator of engine coolant level.
K - Oil Filter — Filters engine oil to prolong system life.
L - Fuel Inlet — Fuel supply is connected here.
M - Oil Drain Hose — Provided to facilitate oil changing.
N - ID Label (located on base) — Identifies unit by
serial number.
P - Circuit Breaker Enclosure - Equipped with removable
bottom to assist with conduit connection.
R - Control Panel Door opening — Provides access to control
panel, oil filter, etc.
S - Control Panel — Used for various test, operation and
maintenance functions. See System Control Panel.
Controls
J
L
MN
P
R
A
B
H
S
C
D
F
GE
H
K
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
NOT
for
REPRODUCTION
11
System Control Panel
The system control panel is a printed circuit board that is
integrated with the control panel of the generator. It contains
all the logic circuits, operator controls, and system displays
necessary to operate, program, and protect the generator.
The system control panel interprets and monitors electrical
inputs from related circuits throughout the unit.
Please refer to the supplied Control Panel Application Guide
for detailed information about the control panel.
NOT
for
REPRODUCTION
12
The generator is equipped with an enclosure that has
several access doors. The doors are named for a significant
component located behind them, as follows:
A - Fuel Inlet port (shown for reference)
B - Control Panel door
C - Exhaust opening (shown for reference)
D - Coolant Fill door
E - Battery door
F - Muffler door
The enclosure also includes muffler and radiator access
panels, used for cleaning those components. All panels
should remain closed at all other times to assure proper
cooling, reduce noise, and for added safety.
NOTE: Doors shown in picture may differ from those on unit.
Access Ports
Each generator is equipped with a set of identical keys. These
keys fit the locks that secure the access doors.
NOTICE Before opening and/or removing doors, remove
power to the unit by using the following procedures:
1. Turn the generator off.
2. Remove control board fuse from control board.
To open access door:
1. Insert key into lock of access door handle and turn
key one quarter turn counterclockwise.
2. Grasp door’s handle and turn one quarter turn
counterclockwise to open. Remove key.
3. Coolant Fill door is unlocked in the same manner. It
can be used for adding coolant or oil.
To close access door:
1. Close door and turn door’s handle one quarter
turn clockwise.
2. Insert key into lock of door handle and turn key one
quarter turn clockwise. Remove key.
Additional force may be required to fully close and lock
the doors because they create a pressurized seal for the
generator enclosure.
WARNING Contact with muffler area could cause burns
resulting in serious injury.
DO NOT touch hot parts and AVOID hot exhaust gases.
Allow equipment to cool before touching.
A
D
B
E
C
F
A
B
C
D
E
F
NOT
for
REPRODUCTION
13
Screen Guard
To gain access to the engine and cooling system
components:
1. Remove two screws (A) and washers at top and
bottom of screen guard.
2. The screen guard will swing open to allow access to
the engine and cooling system components.
A
A
NOT
for
REPRODUCTION
14
Operation
Battery
The installer must supply a valve-regulated, rechargeable
12 volt DC starting battery. See Battery in Final Installation
Considerations in the installation manual.
With the battery installed, all wiring to transfer switch and
generator completed, utility power supplied to the automatic
transfer switch, and the unit in AUTO mode, the battery
receives a trickle charge while the engine is not running. The
trickle charge cannot be used to recharge a battery that is
completely discharged.
Control Board Fuse
The generator’s 15 Amp fuse is critical to correct system
operation. Your installer will ensure the fuse is properly
installed upon completion of the installation.
Engine Oil
The engine is shipped from the factory pre-run and filled
with non-synthetic oil (API SL 10W-30). This allows for
system operation in a wide range of temperature and
climate conditions. Before starting the engine, check oil
level and ensure that engine is serviced as described in the
Maintenance section.
Coolant System
This engine is shipped from the factory filled with a 50-50 mix
of automotive (Ethylene glycol) anti-freeze and water. This
will provide optimum year round protection against freezing,
boiling and corrosion. The coolant system incorporates an
optional water heater that operates with a fixed thermostat
set at 100°F - 120°F (39°C - 49°C) AND utility power is present
at the transfer switch. Before starting the engine, check
coolant level as described in the Maintenance section
Important Owner’s Considerations
WARNING Battery posts, terminals and related accessories
contain lead and lead compounds, chemicals known to the State
of California to cause cancer and reproductive harm. Wash
hands after handling.
NOTICE Any attempt to crank or start the engine before it has
been properly serviced with the recommended oil will result in
equipment failure.
Refer to Maintenance section for coolant and oil fill information.
Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
NOT
for
REPRODUCTION
15
The transfer switch monitors utility voltage. Should utility
voltage drop below a preset level, the transfer switch will
signal the engine to crank and start.
When utility voltage is restored above a preset voltage level,
the engine is signaled to shut down.
The actual system operation is not adjustable and is
sequenced by sensors and timers on the transfer switch,
as follows:
Utility Voltage Dropout Sensor
This sensor monitors utility source voltage.
If utility source voltage drops below about 70 percent
of the nominal supply voltage, the sensor energizes
a 3 second timer. The timer is used to ‘sense’
brown-outs.
Once the timer has expired, the engine will crank
and start.
Automatic Operation
Setting Exercise Timer
Utility Voltage Pickup Sensor
This sensor monitors utility voltage. When utility voltage is
restored above 80 percent of the nominal source voltage,
a time delay starts timing and the engine will go to engine
cool-down.
Engine Cool-down Timer
When utility power is sensed and the load transfers back to
the utility source, the engine will go into a cool down period
as described below:
If the generator has run for MORE than 5 minutes,
once the utility transfer occurs, the engine will
continue to run for about 1 minute before shutting
down.
If the generator has run for LESS than 5 minutes, once
the utility transfer occurs, the engine will continue to
run until 5 minutes has elapsed before shutting down.
It is recommended to have the generator go through an
excercise cycle once every seven days. During this exercise
period, the unit runs for approximately 20 minutes and then
shuts down.
Refer to the Control Panel Application Guide supplied with
this generator for more detailed information on the exercise
timer.
OR, refer to the Automatic Transfer Switch Application Guide
for more detailed information on the exercise timer.
NOT
for
REPRODUCTION
16
Maintenance
Before performing any generator maintenance, always
perform the following steps:
1. Set generator circuit breaker to its OFF position.
2. Turn the generator off.
3. Remove control board fuse from control board.
4. Utility voltage is present at generator control board.
Disconnect power before servicing control board by
removing the fuses from the transfer switch.
5. After all servicing has been completed, replace fuses
in transfer switch, replace control board fuse in
control board, set circuit breaker ON and turn the
generator on.
Servicing the System
The generator may have to run for long periods of time
with no operator present. For that reason, the system is
equipped with sensors that automatically shut down the
generator in the event of potentially damaging conditions,
such as low oil pressure, high temperature, over speed, and
other conditions.
The generator’s control board shows possible shutdown
alarms descriptions on the digital display.
The possible shutdown alarms are listed below:
• Overspeed
• Underspeed
Low Oil Pressure
High Coolant Temperature
External Shutdown 1
External Shutdown 2
External Shutdown 3
GCB (Generator Circuit Breaker) Fail
Generator Overvoltage
Generator Undervoltage
Generator Overfrequency
Generator Underfrequency
Generator CCW Rotation
Start Fail
Stop Fail
Battery Flat
Voltage Autodetect
Reset Shutdown Alarm Detection System
The operator must reset the shutdown alarm detection
system each time it activates.
Refer to the Control Panel Application Guide supplied with
this generator for more detailed information on resetting the
Shutdown Alarm Detection System.
Overspeed
This shutdown alarm is indicated by Overspeed showing
on the digital display. This condition occurs if the engine
speed in greater than 115% of nominal engine RPM, which is
derived from generator frequency.
To remedy the problem, contact your installer or an
authorized dealer.
Underspeed
This shutdown alarm is indicated by Underspeed showing on
the digital display. This condition occurs if the engine speed
drops under the nominal engine RPM.
To remedy the problem, contact your installer or an
authorized dealer.
Low Oil Pressure
This shutdown alarm is indicated by Low Oil Pressure on
the digital display. The unit is equipped with an oil pressure
switch that uses normally closed contacts held open by
engine oil pressure during operation. Should oil pressure drop
below the 8 psi range, switch contacts close and the engine
will shut down.
To remedy the low oil pressure condition, add the
recommended oil to the FULL mark on the dipstick or contact
your installer or an authorized dealer.
Shutdown Alarm Detection System
NOT
for
REPRODUCTION
17
High Coolant Temperature
This shutdown alarm is indicated by High Coolant
Temperature on the digital display. This condition occurs
when the temperature of the coolant exceeds the shutdown
threshold.
To remedy the problem, contact your installer or an
authorized dealer.
External Shutdown 1,2 or 3
This shutdown alarm is indicated by External Shutdown on
the digital display.
To remedy the problem, contact your installer or an
authorized dealer.
Generator Circuit Breaker (GCB) Fail
This shutdown alarm is indicated by GCB Fail on the digital
display. This condition occurs when the generator circuit
breaker trips or becomes non-functional.
To remedy the problem, contact your installer or an
authorized dealer.
Generator Overvoltage
This shutdown alarm is indicated by Generator Overvoltage
on the digital display. This condition occurs when the output
voltage exceeds the preset threshold.
To remedy the problem, contact your installer or an
authorized dealer.
Generator Undervoltage
This shutdown alarm is indicated by Generator Undervoltage
on the digital display. This condition occurs when the output
voltage drops below the preset threshold.
To remedy the problem, contact your installer or an
authorized dealer.
Generator Overfrequency
This shutdown alarm is indicated by Generator
Overfrequency on the digital display. This condition occurs
when the generator frequency is out of limits given by
setpoints.
To remedy the problem, contact your installer or an
authorized dealer.
Generator Underfrequency
This shutdown alarm is indicated by Generator
Underfrequency on the digital display. This condition occurs
when the generator frequency is out of limits given by
setpoints.
To remedy the problem, contact your installer or an
authorized dealer.
Generator CCW Rotation
This shutdown alarm is indicated by Generator CCW on the
digital display. This condition occurs when the generator
phase is out of sequence.
To remedy the problem, contact your installer or an
authorized dealer.
Start Fail
This shutdown alarm is indicated by Start Fail on the digital
display. This condition occurs when the generator does not
start.
To remedy the problem, contact your installer or an
authorized dealer.
Stop Fail
This shutdown alarm is indicated by Stop Fail on the digital
display. This condition occurs when the generator fails to
stop.
To remedy the problem, contact your installer or an
authorized dealer.
Battery Flat
This shutdown alarm is indicated by Battery Flat on the
digital display. This condition occurs if the controller loses
power during starting sequence due to a bad battery
condition. It will not try to start again until the battery is
functioning properly.
To remedy the problem, contact your installer or an
authorized dealer.
Voltage Autodetect
This shutdown alarm is indicated by Voltage Autodetect on
the digital display. This condition occurs if the controller
loses power during starting sequence due to a bad battery
condition. It will not try to start again until the battery is
functioning properly.
To remedy the problem, contact your installer or an
authorized dealer.
NOT
for
REPRODUCTION
18
Generator maintenance consists of keeping the unit clean.
Operate the unit in an environment where it will not be
exposed to excessive dust, moisture or any corrosive vapors.
Cooling air louvers on the enclosure must not become
clogged with snow, leaves, or any other foreign material. To
prevent generator damage caused by overheating, keep the
enclosure cooling inlets and outlets clean and unobstructed
at all times.
Check the cleanliness of the unit frequently and clean when
dust, dirt, oil, moisture or other foreign substances are visible
on its exterior/interior surface. Inspect the air inlet and outlet
openings inside and outside the enclosure to ensure air flow
is not blocked.
DO NOT use direct spray from a garden hose to clean
generator. Water can enter the engine and generator and
cause problems.
Generator Maintenance
Cleaning the Generator
1. Turn the generator off.
2. Remove control board fuse from control board.
3. Clean generator as desired.
Use a damp cloth to wipe exterior surfaces clean.
Use a soft, bristle brush to loosen caked on dirt, etc.
Use a vacuum cleaner to pick up loose dirt and debris.
Use low pressure air (not to exceed 25 psi) to blow
away dirt. Inspect cooling air slots and openings on
the generator. These openings must be kept clean
and unobstructed.
4. Reinstall control board fuse in control board.
5. Turn the generator on and place in AUTO mode.
NOTICE Improper treatment of generator can damage it and
shorten its life.
DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
DO NOT insert any objects through cooling slots.
Engine Maintenance
The maintenance of an engine and related components are
critical to its operating performance and lifespan. Industrial
engines operate in an environment that often include hot
and cold temperatures and extreme dust. The recommended
maintenance schedule is listed in this section, however,
environmental operating conditions and additional installed
equipment may require more frequent inspection and
servicing.
The owner and/or authorized service technician should
review the operating conditions of the equipment to
determine the inspection and maintenance intervals. Proper
engine cooling and lubrication are very important, so pay
particular attention to these matters.
The engine is shipped from the factory pre-run and filled
with non-synthetic oil (API SL 10W-30). This allows for
system operation in a wide range of temperature and
climate conditions.
Engine Oil
Synthetic Oils
Synthetic oils have been available for use in industrial
engines for a relatively long period of time and may offer
advantages in cold and hot temperatures. However, it is not
known if synthetic oils provided operational or economic
benefits over conventional petroleum-based oils in industrial
engines.
Use of synthetic oils does not permit the extension of oil
change intervals.
NOT
for
REPRODUCTION
19
Oil Recommendation
HOT WEATHER
COLD WEATHER
SAE 10W-30
PREFERRED
SAE 15W-40
FOR THE BEST FUEL ECONOMY AND COLD STARTING, SELECT THE LOWEST
SAE VISCOSITY GRADE OIL FOR THE EXPECTED TEMPERATURE RANGE
IF NEITHER SAE 10W-30
NOR SAE 15W-40 GRADE
OILS ARE AVAILABLE, SAE
30 GRADE MAY BE USED AT
TEMPERATURES ABOVE 4
DEGREES C (40F), SAE 40
GRADE AY BE USED AT
TEMPERATURES ABOVE 27
DEGREES C (80F).
DO NOT USE SAE 10W-40
GRADE OIL OR ANY OTHER
GRADE NOT RECOMMENDED
RECOMMENDED SAE VISCOSITY GRADE ENGINE OILS
40°F (4°C)
Select an engine oil viscosity that will best match the
prevailing daytime temperature.
The oil must meet GM specification 9986231. Motor oils
meeting this specification receive the API (American
Petroleum Institute) starburst symbol.
It is noted that the GF-4 oils are also “backwards compatible”
and are equal or better that previous grades of oil in all
aspects.
Checking Engine Oil Level
NOTICE It is important to be careful when checking engine oil
level. Oil must be maintained between “ADD” and the “FULL”
mark on the dipstick. To ensure that you are not getting a
false reading, make sure the following steps are taken before
checking the oil level.
1. Stop engine.
1. Turn the generator off.
3. Remove control board fuse from control panel.
4. Allow approximately five minutes for the oil to drain
back into the oil pan.
5. Remove the dipstick. Wipe with a clean cloth or paper
towel and reinstall. Push the dipstick all the way into
the dipstick tube.
6. Remove the dipstick and note the amount of oil on the
dipstick. The oil level must be between the “ADD” and
“FULL” marks.
7. If the oil level is below the “ADD” mark, reinstall the
dipstick and proceed to step 8.
8. Remove the oil filler cap from the valve cover.
9. Add the required amount of oil to bring the level up to,
but not over the “FULL” mark on the dipstick. Reinstall
the oil filler cap to valve rocker arm cover and wipe
any excess oil clean.
NOT
for
REPRODUCTION
20
Changing Engine Oil
KEEP OUT OF REACH OF CHILDREN. DON’T POLLUTE.
CONSERVE RESOURCES. RETURN USED OIL TO
COLLECTION CENTERS.
Change oil while the engine is still warm from running.
1. Turn the generator off.
2. Remove control board fuse from control board.
3. Place oil drain hose (B) into an approved container.
4. Open valve (A) located on bottom of oil pan.
C
B
Shown here is the oil drain hose (B) and the oil filter location
(C) for the 60kW generator:
To make the task of adding oil more convenient, we
recommend use of a funnel attached to a length of tubing long
enough to reach from the Coolant Fill door to the oil fill opening
on the engine valve cover.
5. When oil has drained, replace brass fitting on hose.
6. Add the required amount of oil to bring the level up to,
but not over the “FULL” mark on the dipstick. Reinstall
the oil filler cap to valve rocker arm cover and wipe
any excess oil clean.
7. Reinstall control board fuse in control board.
8. Turn the generator on and place in AUTO mode.
CAUTION Avoid prolonged or repeated skin contact with used
motor oil.
Used motor oil has been shown to cause skin cancer in certain
laboratory animals.
Thoroughly wash exposed areas with soap and water.
A
Engine V-Belts
The engine installed in this equipment uses drive belt(s) that
drive the water pump and alternator. The drive belt(s) are an
integral part of the cooling and charging system and should be
inspected according to the maintenance schedule.
When inspecting the belts, check for:
• Cracks
Chunking of the belt
• Splits
Material hanging loose from the belt
Glazing, hardening
If any of these conditions exist, the belt should be replaced.
C
B
B
A
NOT
for
REPRODUCTION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124

Simplicity 076266-00 Manuel utilisateur

Catégorie
Groupes électrogènes
Taper
Manuel utilisateur