48"(121.9cm)models:42"(106.7cm)minimumclearance
betweenthetopofthecookingplatformandthebottomofan
uncoveredwoodormetalcabinet.
***NOTE:Ifbackwallisconstructedofacombustiblematerial
andabackguardisnotinstalled,a6"(15.2cm)minimum
clearanceisrequiredforallmodels.
Ifcodespermitandaseparategroundwireisused,itis
recommendedthataqualifiedelectricalinstallerdeterminethat
thegroundpathandwiregaugeareinaccordancewithlocal
codes.
Ifcodespermitandaseparategroundwireisused,itis
recommendedthataqualifiedelectriciandeterminethatthe
groundpathisadequate.
Donotuseanextensioncord.
Besurethattheelectricalconnectionandwiresizeareadequate
andinconformancewiththeNationalElectricalCode,ANSI/
NFPA70-latesteditionandalllocalcodesandordinances.
Acopyoftheabovecodestandardscanbeobtainedfrom:
NationalFireProtectionAssociation
OneBatterymarchPark
Quincy,MA02269.
WARNING:Improperconnectionoftheequipment-grounding
conductorcanresultinariskofelectricshock.Checkwitha
qualifiedelectricianorservicetechnicianifyouareindoubtasto
whethertheapplianceisproperlygrounded.Donotmodifythe
powersupplycordplug.Ifitwillnotfittheoutlet,haveaproper
outletinstalledbyaqualifiedelectrician.
Electrical Connection
To properly install your range, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
• Range must be connected to the proper electrical voltage
and frequency as specified on the model/serial number rating
plate. The model/serial number rating plate is located under
the console on the right-hand side. Refer to the figures in the
"Product Dimensions" section of the "Location
Requirements" section.
• This range may be manufactured with a 4-wire power supply
cord or may not include a power supply cord. If your range
does not include a power supply cord, use a 4-wire power
supply cord rated at 250 volts, 40 or 50 amps and
investigated for use with ranges.
Range Rating* Specified Rating of Power
Supply Cord Kit and
Circuit Protection
120/240 Volts 120/208 Volts Amps Range Size
8.8 - 16.5 kW 7.8 - 12.5 kW 40 or 50"* 30" (76.2 cm),
36" (91.4 cm)
16.6 - 22.5 kW 12.6 - 18.5 kW 50 48" (121.9 cm)
*The NEC calculated load is less than the total connected load
listed on the model/serial rating plate.
**If connecting to a 50-amp circuit, use a 50-amp rated cord with
kit. For 50-amp rated cord kits, use kits that specify use with a
nominal 13/8"(34.9 mm) diameter connection opening.
A circuit breaker is recommended.
Wire sizes and connections must conform with the rating of
the range.
The Tech Sheet is located behind the kick plate in a clear
plastic bag.
If connecting to a 4-wire system:
This range is manufactured with the ground connected to the
cabinet. The ground must be revised so the green ground wire of
the 4-wire power supply cord is connected to the cabinet. See
"Electrical Connection."
Grounding through the neutral conductor is prohibited for new
branch-circuit installations (1996 NEC); mobile homes; and
recreational vehicles, or an area where local codes prohibit
grounding through the neutral conductor.
When a 4-wire receptacle of NEMA Type 14-50R is used, a
matching UL listed, 4-wire, 250-volt, 40- or 50-amp, range power
supply cord must be used. This cord contains 4 copper
conductors with ring terminals or open-end spade terminals with
upturned ends, terminating in a NEMA Type 14-50R plug on the
supply end.
The fourth (grounding) conductor must be identified by a green or
green/yellow cover and the neutral conductor by a white cover.
Cord should be Type SRD or SRDT with a UL listed strain relief
and be at least 4 ft (1.22 m) long.
4-wire receptacle (14-50R)
The minimum conductor sized for the copper 4-wire power
cord are:
40-amp circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-8 green grounding
If connecting to a 3-wire system:
Local codes may permit the use of a UL listed, 3-wire, 250-volt,
40- or 50-amp range power supply cord (pigtail). This cord
contains 3 copper conductors with ring terminals or open-end
spade terminals with upturned ends, terminating in a NEMA Type
10-50P plug on the supply end. Connectors on the appliance end
must be provided at the point the power supply cord enters the
appliance. This uses a 3-wire receptacle of NEMA Type 10-50R.
3-wire receptacle (10-50R)
6